BRAZILIAN NAVY
DIRECTORATE OF PORTS AND COASTS
MARINE SAFETY SUPERINTENDENCE
DEPARTMENT OF INQUIRIES AND INVESTIGATIONS OF NAVIGATION ACCIDENTS
“FPSO CIDADE DE SAO MATEUS”
EXPLOSION WITH VICTIMS
11TH FEBRUARY 2015
MARITIME SAFETY INVESTIGATION REPORT
Platform FPSO CIDADE DE SAO MATEUS on the investigation day
Reference: Casualty Investigation Code, of the International Maritime Organization (IMO) -
MSCMEPC.3 / Circ.2 13 June 2008 / Resolution MSC.255 (84)
7/23/2019 Fpso Cidade Smateus En
http://slidepdf.com/reader/full/fpso-cidade-smateus-en 2/44
BRAZILIAN NAVY
Directorate of Ports and CoastsMarine Safety Superintendence
Department of Inquiries and Investigations of Navigation Accidents
Explosion with victims on “FPSO CIDADE DE SAO MATEUS”
Maritime Safety Investigation Report
2
INDEX
LIST OF ABBREVIATIONS ....................................................................................... 3
I INTRODUCTION....................................................................................................... 4
II SYNOPSIS ................................................................................................................ 4
III GENERAL INFORMATION .................................................................................. 4
IV ACCIDENT LOCAL DATA…………………........................................................ 8
V HUMAN FACTORS AND CREW........................................................................... 9
VI CHRONOLOGICAL SEQUENCE OF EVENTS ................................................. 10
VII PROCEDURES AFTER THE ACCIDENT ......................................................... 12
VIII CONSEQUENCES OF THE ACCIDENT ......................................................... 12
IX EXPERT EXAMINATIONS.................................................................................. 23
X ANALYSIS AND CAUSAL FACTORS................................................................ 23
XI LESSONS LEARNED AND PRELIMINARY CONCLUSIONS ....................... 43
XII SAFETY RECOMMENDATIONS...................................................................... 45
XIII ANNEX .............................................................................................................. 46
7/23/2019 Fpso Cidade Smateus En
http://slidepdf.com/reader/full/fpso-cidade-smateus-en 3/44
BRAZILIAN NAVY
Directorate of Ports and CoastsMarine Safety Superintendence
Department of Inquiries and Investigations of Navigation Accidents
Explosion with victims on “FPSO CIDADE DE SAO MATEUS”
Maritime Safety Investigation Report
3
LIST OF ABBREVIATIONS
ABS - Classification Society, American Bureau of Shipping
ANP - National Petroleum Agency
AJB - Brazilian Jurisdictional Waters
CCM - Engine Control Center
CPES - the Port Authority of Espirito Santo
DHN - Directorate of Hydrography and Navigation
DNV-GL - Det Norske Veritas / Germanischer Lloyd Classication Society
DPEM - Damage Compulsory Insurance of Personal Injury Caused by Ships or its load
FISPQ – Chemical Material Safety Data Sheet
FPSO - stationary production unit, Storage and Transfer Oil and Gas Export
GIO - Offshore Installation Manager
IMO - the International Maritime Organization
ISAIM – Safety Investigation of Maritime Casualties and Incidents
ISM Code - International Safety Management Code
MCA - Auxiliary Combustion Engine
NR 33 - Regulatory Standard No. 33 - Health and Safety at Work in Confined Spaces
SMQS - Health, Environment, Safety and Quality
STCW 78 - International Convention on Education Standards, Certification and Watchkeeping
for Seafarers, 1978
VHF - Very High Frequency (frequency of 30 MHz to 300 MHz)
7/23/2019 Fpso Cidade Smateus En
http://slidepdf.com/reader/full/fpso-cidade-smateus-en 4/44
BRAZILIAN NAVY
Directorate of Ports and CoastsMarine Safety Superintendence
Department of Inquiries and Investigations of Navigation Accidents
Explosion with victims on “FPSO CIDADE DE SAO MATEUS”
Maritime Safety Investigation Report
4
I – INTRODUCTION
For the purpose of accomplishing the collection and the analysis of evidences, the
identification of the causal factors and the elaboration of the recommendations of safety that are
necessary, in order to avoid that in the future occur similar maritime accidents and/or incidents,
the Directorate of Ports and Coasts (DPC) carried out the present Safety Investigation of
Maritime Accidents and Incidents (ISAIM) in compliance with that laid down in the Casualty
Investigation Code of the International Maritime Organization (IMO), adopted by Resolution
MSC.255(84).
This Final Report is a technical document that reflects the result obtained by the DPC in
relation to the circumstances that contributed or may have contributed to unleash the occurrence
and does not resort to any procedures of proof for verification of civil or criminal responsibility.
Furthermore, it should be emphasized the importance of protecting the persons responsible
for the supplying of information related to the occurrence of the accident, for the use of
information included in this report for ends other than the prevention of future similar accidents
may lead to erroneous interpretations and conclusions.
II – SYNOPSIS
On February 11, 2015 in the morning aboard the FPSO Platform CIDADE DE SAO
MATEUS, was performed the transfer of the mixture of water and condensate from the central
cargo tank 6C to port waste tank, in order to empty the cargo tank, submit it to inspection and
test the valves contained therein. This operation began at 8h53m with the use of the drain pump,
installed in the pump room. At 11h30m the images of the closed circuit television (CCTV)
showed condensate leak in a section of the pump discharge line and then a gas alarm was
activated automatically. From this occurrence, decisions were made, actions were developed and
the crisis culminated with the explosion inside the pump room, producing severe damage to the
platform, the deaths of nine crew members and injuries to others twenty six persons. The
chronology of this accident will be detailed later.
III - GENERAL INFORMATION
(A) Platform FPSO CIDADE DE SAO MATEUS
The FPSO CIDADE DE SAO MATEUS (Photo # 1) is a stationary production unit, storage,
oil and gas export and transfer, with capacity to produce 4.000m³ / day of oil and 10.000.000m³ /day of gas. Flying the Panama flag, she is registered at the Port of Panama, on the property of
7/23/2019 Fpso Cidade Smateus En
http://slidepdf.com/reader/full/fpso-cidade-smateus-en 5/44
BRAZILIAN NAVY
Directorate of Ports and CoastsMarine Safety Superintendence
Department of Inquiries and Investigations of Navigation Accidents
Explosion with victims on “FPSO CIDADE DE SAO MATEUS”
Maritime Safety Investigation Report
5
PROSAFE PRODUCTION SERVICES PTE. LTD., and held in class by the Classification
Society American Bureau of Shipping (ABS). This platform is authorized to operate in Brazilian
Jurisdictional Waters (AJB), according to Concession Agreement, issued by the National
Petroleum Agency (ANP), in favor of the PETROBRAS company. Its average production
figures for the year 2013 corresponds to 2.484.717,79m³ / day of gas, 426,66m³ / day of
condensate (coming from the gas production) and did not produce oil.
Main data and physical characteristics:
Operator: BRAZIL'S PPB, MARITIME SERVICES LTD.
Registration Number: 341E001031.
IMO number: 8706014.
International call sign: 3ENO.
Gross Tonnage: 143,323.
Hull material: steel.
Year Built: 1989
Conversion Year: 2008
Overall Length: 311,7m.
Length between perpendiculars: 310m.
Breadth: 54,50m.
Depth: 29,50m.
Design draft: 19,8m.
Propulsion: unpowered.
Accommodations: up to 85 people.
7/23/2019 Fpso Cidade Smateus En
http://slidepdf.com/reader/full/fpso-cidade-smateus-en 6/44
BRAZILIAN NAVY
Directorate of Ports and CoastsMarine Safety Superintendence
Department of Inquiries and Investigations of Navigation Accidents
Explosion with victims on “FPSO CIDADE DE SAO MATEUS”
Maritime Safety Investigation Report
6
Photo # 01 - Platform FPSO CIDADE DE SAO MATEUS, on 02/13/2015, two days after the accident.
(B) documents and deck Certificates, at the date of the accident
The statutory certificates and classification societies and the documents that the platform
should bear, are listed below:
Certificate Name : Issuing Authority: Issuer Date: Issue Validity:
Class Certificate/Certificate of Classification - ABS 8/27/2014 18/03/2019
Security Protection Certificate / International Ship Security Certificate - ISPS Code - flag
Country(Panama) 9/09/2014 09/15/2019Certificate Mobile Unit Production / Mobile Offshore Unit Safety Certificate - MODU - flag
Country (Panama) 27/08/2014, 18/03/2019
Safety Management / Safety Managment Certificate - SMC - DNV-GL
02/02/2015 15/09/2019
International Certificate of Load Line / International Load Line Certificate- LL- ABS
8/27/2014 03/18/2019
7/23/2019 Fpso Cidade Smateus En
http://slidepdf.com/reader/full/fpso-cidade-smateus-en 7/44
BRAZILIAN NAVY
Directorate of Ports and CoastsMarine Safety Superintendence
Department of Inquiries and Investigations of Navigation Accidents
Explosion with victims on “FPSO CIDADE DE SAO MATEUS”
Maritime Safety Investigation Report
7
International Oil Pollution Prevention Certificate / International Oil Pollution Prevention
Certificate IOPP - ABS 8/27/2014 03/18/2019
Security / Crew Minimum Safe Manning Certificate card - Captaincy of Rio de Janeiro
. 27/04/2010 19/02/2015
International Tonnage Certificate / International Tonnage Certificate (1969) - ABS
04/08/2008 Undetermined
Registration Certificate / Navigation Statutory Registry - Country flag (Panama)
23/09/2014 10/07/2019
International Prevention Air Pollution Certificate / Air Pollution Certificate – IAPP - ABS
8/27/2014 18/03/2019
Sewage Pollution Prevention Certificate / International Sewage Pollution Prevention Certificate -
ABS 8/27/2014 03/18/2019
Certificate of Foreign Vessel Temporary registration - AIT - Port Captaincy of Espirito Santo
20/02/2009 19/02/2015
Certificate of Foreign Vessel Temporary registration - AIT the Port Captaincy of Rio de Janeiro
14/01/2015 10/03/2018
Compliance Statement for Operation in Brazilian Jurisdictional Waters / Statement of
Compliance for Operation in Brazilian Waters - Port Captaincy of Espirito Santo
07/19/2013 04/18/2015
Insurance of Personal Injury Caused by vessels or their cargo (DPEM) Bradesco Seguros e
Previdencia 03/25/2014 25/03/2015
P & I insurance / Certificate of Entry - Mobile Offshore Unit Entry- Gard P & I
13/2/2014 13/2/2015
Continuous Synopsis Record / Continuous Synopsis Record - CSR - flag Country
(Panama) 09/17/2013 Undetermined
(C) Condition of the platform during the investigation
On February 13, 2015, day of the first visit on board, the platform had aft inclination due to
flooding of the engine room and pump room. All operations were paralyzed. On the main deck,
lay twisted cabinets, warped doors, parts of personal protective equipment, damaged
communications, and many expelled debris from internal compartments of the rooms by the blasteffect.
7/23/2019 Fpso Cidade Smateus En
http://slidepdf.com/reader/full/fpso-cidade-smateus-en 8/44
BRAZILIAN NAVY
Directorate of Ports and CoastsMarine Safety Superintendence
Department of Inquiries and Investigations of Navigation Accidents
Explosion with victims on “FPSO CIDADE DE SAO MATEUS”
Maritime Safety Investigation Report
8
The salvage material was incomplete by the absence of both lifeboats and many lifejackets
used during abandonment. There was no generation of electricity on board because of the
damage in parts of the electric cables and circuit breaker panels and, therefore, the lighting was
limited to the use of portable lamps. The stairs of access to the engine room and pump room
were unfit for use due to deformation and / or interruptions resulting from the explosion effects.
Access to the pump room and the higher levels of the engine room required the monitoring of
possible gas leaks using portable detectors. There were on board only two crew members
monitoring the platform stability and performing procedures to implement the rescue plan. The
initial actions would start by the external buffering of sea chests, to be performed by divers to cut
the communication of the engine room and pump room with the sea. Saltwater networks were
found themselves damaged by the effects of the explosion and such a situation prevented the
drain of the water in both the engine room and the pump room, necessary to ensure the safety of
the platform and to facilitate the recovery of the bodies of crew members still missing.
IV - ACCIDENT LOCAL DATA
(A) Location: geographical coordinates Lat: 19 ° 55.35'S and Long: 039 ° 38.0'W in Camarupim
field, Espirito Santo Basin, at a depth of 792 meters. It is an open sea navigation area, far about
40 km from the coast, as demonstrated by plotting the Nautical Chart DHN 22800, 2nd edition
(Photo No. 02).
22800, 2nd edition, Conceiçao da Barra - Victoria, Lat. 19 ° 55.35'S and Long. 039 ° 38.0'W
Photo # 02 - Position of the FPSO CIDADE DE SAO MATEUS in Nautical Chart DHN-
7/23/2019 Fpso Cidade Smateus En
http://slidepdf.com/reader/full/fpso-cidade-smateus-en 9/44
BRAZILIAN NAVY
Directorate of Ports and CoastsMarine Safety Superintendence
Department of Inquiries and Investigations of Navigation Accidents
Explosion with victims on “FPSO CIDADE DE SAO MATEUS”
Maritime Safety Investigation Report
9
(B) Environmental conditions at the time of the accident: wind intensity with eight knots,
direction north, calm seas, good weather and good visibility. These environmental conditions did
not contribute to the accident.
V - HUMAN FACTORS AND CREW
(A) Crew list and safety crew personnel.
On the day of the accident there was on board 74 people, including crew and crew members
not professionals. The certificates and documents of these people (specialization courses, the
enrollment and registration books extracts, occupational health certificates, statements of work
permits and social security, employment contracts extracts and plugs records of the company
BW Offshore were examined and the following non-conformities were found:
(1) - was not submitted the proficiency certificate of the Vessel Supervisor.
(2) – non- compliance of the Minimum Safe Manning certificate (CTS) - a crew member that
should occupy the Sailor Deck function provided for the certificate , held also the pumping
function. Consequently, the operating of the platform do not complied with the CTS certificate.
(B) periods of work and rest.
There was no evidence of breach of the minimum periods of rest, as established by the
STCW / 78 Convention.
(C) accommodations:
The accommodations were adequate for the crew, in accordance with the standards of
comfort, cleanliness, temperature, lighting and noise, common to the platforms of that type.
(D) alcohol, drugs and medicines.
No evidence has been obtained from the use of alcohol, drugs and or drug without medical
prescription by the crew.
(E) Safety Management:
The platform had the Safety Management Certificate issued by the classification society Det
Norske Veritas / Norway and Germanischer Lloyd / Germany (DNV-GL), under the
International Safety Management Code (ISM Code), valid until September 15, 2019. This
document attesting that the platform has been audited and that its security management system
meets the requirements of the ISM Code.
7/23/2019 Fpso Cidade Smateus En
http://slidepdf.com/reader/full/fpso-cidade-smateus-en 10/44
BRAZILIAN NAVY
Directorate of Ports and CoastsMarine Safety Superintendence
Department of Inquiries and Investigations of Navigation Accidents
Explosion with victims on “FPSO CIDADE DE SAO MATEUS”
Maritime Safety Investigation Report
10
VI - CHRONOLOGICAL SEQUENCE OF EVENTS
The chronology of the accident described below is founded on the records made in Status
Table, in the control room during the emergency on board, reported by the deck crew,
examination of documents received from PETROBRAS and BW Offshore companies, records
of the platform automation system and the observations of the investigators during the four
visits on board.
February 11, 2015:
- 8h30m - exchange of crew members, among which stand out exchanges of the Offshore
Installation Manager (GIO) and the Maintenance Supervisor. The Passage Reports of GIO and
Passage Report of the Maintenance Supervisor were checked.
- 8h53m - initiated the opening of the suction valves and discharge networks of the drain pump
(oil pump stripping) in the pump room, for transferring the condensate water from the 6C cargo
tank to the portside oily residue tank (slop tank).
- 9h - was started the drain pump.
- 9h30m – was began, in the meeting room, a videoconference between the Operations Manager
on land, the GIO, the Vessel Supervisor, Maintenance Supervisor, the Production Supervisor, the
Planner and the Safety Technician.
- 10h – the videoconference is ended ; the GIO returned to his office to complete the reading of
the Passage Reports of GIO.
- 11h30m - condensate leakage in the pump room were shown the CCTV camera 5 without being
noticed by anyone who was in the control room.
- 11h31m - The gas sensor TAG 73AB370, in the pump room, accused the presence of gas, and
automatically triggered the gas presence alarm and, as planned at the ESD, FIRE & GAS
SYSTEM CAUSE AND EFFECTS MATRIX, the exhaustion was stopped automatically. The
GIO came out of his office and went to the control room. There, upon learning of which sensor
had been activated, sent disclose in the Public Address Ads System this information; so, all the
crew drove to the meeting points. Then, when was told by the Supervisor that there was the
condensate transfer operation of the vessel using the drain pump the GIO ordered the arrest of
that operation. The personal count was started at the meeting point, coordinated by the person
designated in the control room.
7/23/2019 Fpso Cidade Smateus En
http://slidepdf.com/reader/full/fpso-cidade-smateus-en 11/44
BRAZILIAN NAVY
Directorate of Ports and CoastsMarine Safety Superintendence
Department of Inquiries and Investigations of Navigation Accidents
Explosion with victims on “FPSO CIDADE DE SAO MATEUS”
Maritime Safety Investigation Report
11
- 11h32m - The gas sensor, TAG 73AB326 also alarmed, accusing the presence of gas in the
pump room.
- 11h36m - The gas sensor, TAG 73AB327 in the pump room also alarmed accusing the
presence of gas in the compartment. The general alarm due to activation of the gas sensors was
muted to improve communication. The GIO had doubts about the gas leak source and ordered a
team made up of an Occupational Safety Technical an Instrumentation Technician and a Pump
Expert, to go to the pump room to identify the source of the gas.
- 11h40m - the emergency situation was reported to BW Offshore Company in Victoria.
- 11h44m - the technical team was in the pump room while the GIO, the Vessel Supervisor and
the Maintenance Supervisor assessed the situation in the control room.
- 11h47m - the technical team returned from the pump room and told the GIO that there was a
liquid puddle on the compartment floor, coming from the OP-068 valve, the portable gas
detectors used by his team accused high level of gas in atmosphere of the pump house and still
dripped from the vicinity of the OP-068 valve. The GIO asked if there was another source of gas
leak and was informed that there was only a pool that could be removed with water jet. The GIO
held cleaning with absorbent and determined the Maintenance Supervisor assess how the valve
could be repaired.
- 11h58m to 12h02m - another team was composed and instructed to go to the pump room and
investigate what should be done to "solve" the leak. This team was the Occupational Safety
Technician of the previous team, the Supervisor of Maintenance and the Maintenance
Technician.
- 12h09m - in the pump room, the staff asked for shovels and stairs.
- 12h10m - the staff went out of the house pumps for fresh air and to recuperate the breath.
- 12h15m - three crew members of the fire brigade, on the main deck and near the entrance to the
pump room, arranged absorbent mats to remove and clean the condensate pool. The GIO
released the staff that was in the meeting point considered not essential to toil for lunch.
- 12h20m - the GIO instructed to another team was formed to go to the pump room to clean and
contain the leak. Two Area men and three Maintenance Technicians are assigned.
- 12h22m to 12h26m - the team went to the pump room and started to contain the leak and
cleaning; first with absorbent webs, then with the use of sea water fire hose (a 1.5 inch hose and
45 meters in length was introduced at the pump room through the openings in the deck atstarboard side).
7/23/2019 Fpso Cidade Smateus En
http://slidepdf.com/reader/full/fpso-cidade-smateus-en 12/44
BRAZILIAN NAVY
Directorate of Ports and CoastsMarine Safety Superintendence
Department of Inquiries and Investigations of Navigation Accidents
Explosion with victims on “FPSO CIDADE DE SAO MATEUS”
Maritime Safety Investigation Report
12
- 12h35m to 12h37m - the explosion occurred in the pump room and its immediate effects were
seen in the control room, invaded by smoke and debris. All the platform systems were turned off
and the control room was evacuated. It was started the flooding of the pump room and engine
room, caused by disruption of fire networks, then pressurized, and salt water networks from the
sea chests. The first victims were identified and the GIO, along with the PETROBRAS`
Inspector, requested helicopters to evacuate the wounded. On deck, crew disoriented sought
refuge in the stern, under the helicopters deck, and in the bow deck, fearing further explosions
and possibly the platform to sink. The procedures for the abandonment of the unit have been
initiated; all aboard were instructed to follow for meeting points. The GIO guided 32 peoples to
board the starboard lifeboat.
- 12h47m -The GIO was ordained the platform abandonment by starboard lifeboat. They
remained on board the GIO and the nurse with other crew members to take care of removal the
victims by helicopter.
February 12, 2015:
- 2h - completely abandoned, the platform was without people on board.
VII - PROCEDURES AFTER THE ACCIDENT
After the accident took place the stoppage of the whole platform operation and started the
abandonment procedures and the rescue of the victims with ground support. After all peoples
leaving the platform, the stability and buoyancy was being monitored with the use of offshore
support vessels, while it was being prepared the rescue plan.
VIII - CONSEQUENCES OF THE ACCIDENT
(A) - Personal Injury:
This accident caused the death of nine professional and injuries to others twenty six. There
are no disappeared persons.
(B) - Environmental damage:
There was no environmental damage.
(C) - Property Damage:
The platform suffered severe structural damage to the aft section having been affected
habitable compartments, the engine room, the pump room, equipment and structural accessoriescontained in these compartments. These breakdowns were characterized by deformation, tipping
7/23/2019 Fpso Cidade Smateus En
http://slidepdf.com/reader/full/fpso-cidade-smateus-en 13/44
BRAZILIAN NAVY
Directorate of Ports and CoastsMarine Safety Superintendence
Department of Inquiries and Investigations of Navigation Accidents
Explosion with victims on “FPSO CIDADE DE SAO MATEUS”
Maritime Safety Investigation Report
13
and breaks bulkheads, stringers and caves. In addition, the effects of the flooding that followed
the engine room and pump room caused the destruction of motors, pumps, electrical panels and
equipment in general that could not have contact with seawater. The following images illustrate
the severity of damage that led to the stoppage of all operations and the platform abandonment.
There is no evidence of damage to condensate load and existing oil in cargo tanks.
(1) - Outside Deck in section and aft, corridors of accommodation and access to the elevator:
Photo # 03 Photo # 04
Cabinets twisted by the explosion and expelled from the internal compartments.
Photo # 05 - watertight door leading into the pump house, by
port, torn by the explosion.
Photo # 06 - parts of a flashlight used on board.
7/23/2019 Fpso Cidade Smateus En
http://slidepdf.com/reader/full/fpso-cidade-smateus-en 14/44
BRAZILIAN NAVY
Directorate of Ports and CoastsMarine Safety Superintendence
Department of Inquiries and Investigations of Navigation Accidents
Explosion with victims on “FPSO CIDADE DE SAO MATEUS”
Maritime Safety Investigation Report
14
Photo # 07 - access door to the elevator deformed by the explosion.
Photo # 08 - hall which gives access to the control room on the main deck level.
(2) – Engine room:
The flooding of the engine room after the explosion crippled the Auxiliary Combustion
Engines (MCA) and the electrical panel located in the compartment, including the Main Electric
Switchboard. Structural reinforcement elements and the system networks that pass through the
compartment were severely damaged by the explosion followed by flooding. The Engine Control
Center (ECC) was destroyed by the wave caused by the explosion pressure coming from the
Pump Room.
Photo # 09 - Flooding in the Engine Room( by the hatchway on the main deck aft)
7/23/2019 Fpso Cidade Smateus En
http://slidepdf.com/reader/full/fpso-cidade-smateus-en 15/44
BRAZILIAN NAVY
Directorate of Ports and CoastsMarine Safety Superintendence
Department of Inquiries and Investigations of Navigation Accidents
Explosion with victims on “FPSO CIDADE DE SAO MATEUS”
Maritime Safety Investigation Report
15
Photo # 10 - Top of the partially destroyed Engine Room
Photo #11 - Engine Room next to the starboard side with
destruction of networks and structural elements
Photo # 12 - CCM inside the Engine Room destroyed by the effects of the explosion
(3) - Pump Room:
The Pump Room is vertically divided into five levels from the main deck to the bottom of the
bay, as the following drawings:
7/23/2019 Fpso Cidade Smateus En
http://slidepdf.com/reader/full/fpso-cidade-smateus-en 16/44
BRAZILIAN NAVY
Directorate of Ports and CoastsMarine Safety Superintendence
Department of Inquiries and Investigations of Navigation Accidents
Explosion with victims on “FPSO CIDADE DE SAO MATEUS”
Maritime Safety Investigation Report
16
Photo #13 - Profile view of the stern part of the platform, highlighting the Pump Room
7/23/2019 Fpso Cidade Smateus En
http://slidepdf.com/reader/full/fpso-cidade-smateus-en 17/44
BRAZILIAN NAVY
Directorate of Ports and CoastsMarine Safety Superintendence
Department of Inquiries and Investigations of Navigation Accidents
Explosion with victims on “FPSO CIDADE DE SAO MATEUS”
Maritime Safety Investigation Report
17
Bulkhead affected by the explosion
Photo #14 - Vertical structure of the Pump Room Explosion center
Breakdowns of this compartment are partially shown in the following images:
roof of the pump room located above the main deck was moved and severely damaged by the
explosion. Just below the 1st level reinforcements of vertical uprights of the aft bulkhead, which
7/23/2019 Fpso Cidade Smateus En
http://slidepdf.com/reader/full/fpso-cidade-smateus-en 18/44
BRAZILIAN NAVY
Directorate of Ports and CoastsMarine Safety Superintendence
Department of Inquiries and Investigations of Navigation Accidents
Explosion with victims on “FPSO CIDADE DE SAO MATEUS”
Maritime Safety Investigation Report
18
separates the Pump Room and Engine Room, was founded heavily warped and no longer
fulfilled the role of increasing the rigidity of the panel formed by the bulkhead.
Photo #15 - Ceiling Pump Room on the main deck. The explosion damaged the fire network. This contributed to the flooding
of the magazine because it was kept pressurized
In the 2nd level of the Pump Room, the floor near the duct of the starboard air extraction was
found itself deformed.
Photo #16 - Floor located on the second level had severe
deformation
Photo #17 - Vertical air duct completely destroyed by the
blastwave pressure
7/23/2019 Fpso Cidade Smateus En
http://slidepdf.com/reader/full/fpso-cidade-smateus-en 19/44
BRAZILIAN NAVY
Directorate of Ports and CoastsMarine Safety Superintendence
Department of Inquiries and Investigations of Navigation Accidents
Explosion with victims on “FPSO CIDADE DE SAO MATEUS”
Maritime Safety Investigation Report
19
In the 3rd level of Pump Room, the air extraction ducts found themselves destroyed by the
pressure caused by the explosion. Access ladders found themselves also destroyed. Access to the
lower levels of the Pump Room was only possible after installation of scaffolding by the crew.
The bulkhead separating the Pump Room and Engine Room found itself deformed and tumbled
aft, opening sections that communicated the two compartments. The bulkhead was separated in
the upper welded joint with the structure of the unit due to the upward pressure caused by the
explosion in the bottom of the compartment.
Photo #18 - aft bulkhead between the Pump Room and the
Engine Room found itself overturned
Photo #19 - bulkhead between the Pump Room and the
Engine Room collapsed
In the 5th level of the Pump Room, the lower level of this compartment is divided at the time
by an intermediate floor consists of pallets that allows access to equipment such as drain tanks
pump (stripping pump). These platforms have been severely affected by the explosion. The
7/23/2019 Fpso Cidade Smateus En
http://slidepdf.com/reader/full/fpso-cidade-smateus-en 20/44
BRAZILIAN NAVY
Directorate of Ports and CoastsMarine Safety Superintendence
Department of Inquiries and Investigations of Navigation Accidents
Explosion with victims on “FPSO CIDADE DE SAO MATEUS”
Maritime Safety Investigation Report
20
stripping pump had superficial damage to the insulation housing and the drainage system
manifold.
Photo #20 - Drain pump (stripping pump) had superficial damage
On the floor of Pump Room a strong deformation was noted at the junction of the sixth beam
(longitudinal structural reinforcement of the bottom plating) told from the starboard bulkhead
with a walk-to-ram (vertical beam that supports the roof on the bottom panel).
7/23/2019 Fpso Cidade Smateus En
http://slidepdf.com/reader/full/fpso-cidade-smateus-en 21/44
BRAZILIAN NAVY
Directorate of Ports and CoastsMarine Safety Superintendence
Department of Inquiries and Investigations of Navigation Accidents
Explosion with victims on “FPSO CIDADE DE SAO MATEUS”
Maritime Safety Investigation Report
21
Photo #21 - 6th reinforcement stringer in the background
plating of the Pump Room severely damaged
Photo #22 - Detail of collapsed and deformed structure in the
vertical direction
Photo #23 - Below damaged structure; there are still remnants
of oily mixture
The shape of the strain these structural reinforcements indicates that the pressure caused bythe explosion was concentrated in the compartment floor near the condensate leak and expanded
7/23/2019 Fpso Cidade Smateus En
http://slidepdf.com/reader/full/fpso-cidade-smateus-en 22/44
BRAZILIAN NAVY
Directorate of Ports and CoastsMarine Safety Superintendence
Department of Inquiries and Investigations of Navigation Accidents
Explosion with victims on “FPSO CIDADE DE SAO MATEUS”
Maritime Safety Investigation Report
22
vertically upwards, which corroborates with the strains found in the structure and bulkhead
Pump Room levels above. The magazine also presented oily water at the bottom, between the
structural reinforcements of the compartment background plating.
IX- EXPERT EXAMINATIONS
The expert examinations started as soon as the platform security conditions showed
satisfactory levels. Four visits were made to the platform to map the network equipment and the
pump room, estimating the damage and assess the arrangements of the networks and valves
associated with the drain pump.
In addition to the onboard visits, certificates and platform plans were examined the various
documents provided by PETROBRAS and BW Offshore companies by requests from the
investigators; the data of the automation system were analyzed and were heard people who could
help to elucidate the accident in question.
X - ANALYSIS AND CAUSAL FACTORS
(A) Data from the automation system.
Data from the automation system, referred to herein, were contained in computers and data
discs removed from the platform after the accident and transported to the office of the company
BW Offshore in Vitoria, State of Espirito Santo. The importance of the information recorded
translates to allow the technical understanding of the operation and activation of the equipment
and the visualization of the condensate leak and drive a gas alarm warning light inside the Pump
Room, through the circuit images of closed circuit television (CCTV). In the case under
consideration, in addition to CCTV images, data were extracted relating to the valves, drain
pump (oil pump stripping) and gas sensors inside the Pump Room. This information in
spreadsheet format, refer to data disc.
(B) - Recovery and reading data.
The recovery and reading of data by technical company BW Offshore occurred in
PETROBRAS' installations in the city of Macae, State of Rio de Janeiro, from 24 to 28 February
2015.
(C) - criteria adopted for the selection of data for this research.
The CCTV images and data selected for examination were those contained in the HD BallastCargo N / S 9RX7JG4S (Post-EventLog.xlsx) and HD Server B - N / S 3LN2CQ1H (1E4F-
7/23/2019 Fpso Cidade Smateus En
http://slidepdf.com/reader/full/fpso-cidade-smateus-en 23/44
BRAZILIAN NAVY
Directorate of Ports and CoastsMarine Safety Superintendence
Department of Inquiries and Investigations of Navigation Accidents
Explosion with victims on “FPSO CIDADE DE SAO MATEUS”
Maritime Safety Investigation Report
23
AlarmLog-MostRecent.xlsx), with the date of February 11, 2015, related to the equipment
contained in the platform Pump Room, as it was on that date that the leak occurred of condensate
(network discharge drain pump), followed by automatic activation of the gas sensors and
explosion.
(D) - Timing Method of times of computers and CCTV.
(1)
- Computers.
When computers were linked it was found that there was no synchronization of their
clocks. In view of the need to use information to describe the chain of the explosion-related
events, the technicians made comparisons of computer clocks with the information of a cell
phone, and produced photographic records. The following images show the results of the
comparisons to the systems of interest, already mentioned.
Photograph # 24 - Position Ballast HD N / S 9RX7JG4S
Computer controlling the ballast maneuvers and platform load
Date and time of the computer: 02/26/2015, 10h07m01s
Date and time of cell phone: 02.27.2015, 09h03m
The image shows that:
a) the computer had one day delay in relation to the cell date.
b) the computer clock was early 1h4m01s.
7/23/2019 Fpso Cidade Smateus En
http://slidepdf.com/reader/full/fpso-cidade-smateus-en 24/44
BRAZILIAN NAVY
Directorate of Ports and CoastsMarine Safety Superintendence
Department of Inquiries and Investigations of Navigation Accidents
Explosion with victims on “FPSO CIDADE DE SAO MATEUS”
Maritime Safety Investigation Report
24
Synchronization - disregarding the seconds:
Given that the computer was delayed by one day and that was taken aboard in force when
daylight saving time (0h of October 19, 2014, to 0h of 22 February 2015) the synchronization is
done by:
a) add one day to the computer date.
b) reduces 1h4m of computer time.
Therefore, considering this timing criterion, the following example is presented:
Which reads the first row of data Post-EventLog.xlsx table, Appendix 2:
Time Description
10/02/2015 12:29:17 Wrote new value (1) to ICONICS.ModbusEthernetDA.2 \
Sixnet.DO.HMI_BA002_Close
Read:
Time Description
02/11/2015 11:25:17 Wrote new value (1) to ICONICS.ModbusEthernetDA.2 \
Sixnet.DO.HMI_BA002_Close
Photo #25 - HD Server B - N / S 3LN2CQ1H
Server that records the platform alarms
Date and time of the computer: 02/27/2015 12h09m
Date and time of cell phone: 02.27.2015 11h02m
7/23/2019 Fpso Cidade Smateus En
http://slidepdf.com/reader/full/fpso-cidade-smateus-en 25/44
BRAZILIAN NAVY
Directorate of Ports and CoastsMarine Safety Superintendence
Department of Inquiries and Investigations of Navigation Accidents
Explosion with victims on “FPSO CIDADE DE SAO MATEUS”
Maritime Safety Investigation Report
25
The image shows that the computer clock was early 7minutos.
Synchronization:
Reduce by 7minutos the computer time.
Therefore, considering this timing criterion, the following example is presented:
The 1E4F-AlarmLog-MostRecent.xlsx table, which reads the first line of data
ActiveTime EventTime Source
2/11/2015 13:51:31 2/11/2015 13:51:31 P_73BF319 - FAULT
Read:
ActiveTime EventTime Source
2/11/2015 13:51:31 2/11/2015 13:44:31 P_73BF319 - FAULT
(2) - CCTV.
The CCTV recording system was delayed 1h23m16s regarding the Brasilia time
(conference held on 27/02/2015 at 16h19m - Brasilia time).
(E) the transferring of the content of water and condensate from 6C cargo tank to port
waste tank (portside slop tank):
The operation consists in transferring the condensate and water from the 6C central cargo
tank to port waste tank. The arrangement of valves and networks are shown in illustration 1.
The section of interest (suction and discharge flow) is marked in red. The start of the suction
line (center suction header) until the pump, there are OP-041, OP-050, OP-047 and OP-071
valves and the pump discharge passage to the slop tank is the OP-079 and OP-084 valves. All
these valves should be opened during the transfer.
The diagram also shows another shunt in the pump discharge into the waste tank,
highlighted in yellow. This passage includes a flanged connection and OP-068 valve and is
shorter than represented in the embodied array. However, it could not be used because the OP-
068 valve was broken (was inside passage). Therefore, this valve does not retain the contentsof the tank and was the reason that the flange connection was blocked by a racket on 12
January 2014. This change will prove to be the weak point of the network system used to
maneuver that will culminate in an accident, as will be shown below.1 The flanged connections are easily detachable connections; employed mainly to 51mm tubes (2 ''), or larger, in the
following cases: to connect the pipes with valves and equipment (pumps, compressors, tanks, etc.) and also at certain points tothe along the pipe where you want ease of disassembly. Note: as a general rule it is recommended to use the smallest possiblenumber of flanged connections. A flange connection is composed of two flanges, a set of screws or bolts or case cover withnuts and a gasket. (SEA, Vocational Education Department of the Navy - Directorate of Ports and Coasts- Machines
Principles - Rio de Janeiro., 1989.).2 rackets: are used on networks when you want a strict and absolute lock. Widely used on board to insulate pipes pumps thatare used sporadically. They are usually installed between two flanges, making a tight seal. (SEA, Vocational Education Department of the Navy - Directorate of Ports and Coasts - Machines Principles- Rio de Janeiro. 1989).
7/23/2019 Fpso Cidade Smateus En
http://slidepdf.com/reader/full/fpso-cidade-smateus-en 26/44
BRAZILIAN NAVY
Directorate of Ports and CoastsMarine Safety Superintendence
Department of Inquiries and Investigations of Navigation Accidents
Explosion with victims on “FPSO CIDADE DE SAO MATEUS”
Maritime Safety Investigation Report
26
llustration 1 - network diagram
(F) Change in alignment of the suction and discharge networks during the transfer operation
and the condensate of the leak:
On February 11, 2015, after being initiated the transfer, was found that the tank level 6C
not lowered, although the drain pump was working. This fact could be originated in the
Drain
pump
6C Cargo tank
suction
Discharges into the
oily residue porttank
This network could not be used to discharge thetank because there was a
racket in this flange
7/23/2019 Fpso Cidade Smateus En
http://slidepdf.com/reader/full/fpso-cidade-smateus-en 27/44
BRAZILIAN NAVY
Directorate of Ports and CoastsMarine Safety Superintendence
Department of Inquiries and Investigations of Navigation Accidents
Explosion with victims on “FPSO CIDADE DE SAO MATEUS”
Maritime Safety Investigation Report
27
malfunctioning of valves in internal tanks and waste 6C, since the suction passed network used
by two tanks. In an attempt to solving the problem the Vessel Supervisor decided to change the
tank suction line 6C of the center section to the starboard (starboard suction header) through the
OP-042 valves, OP-051, OP-048 and OP-071 in order to avoid passing through the valves that
might be defective. The temporary destination of discharge in this arrangement was amended
from the slop tank to the cargo tank 2C through the OP-080 valve in the face of the starboard
suction line contain very pure condensate that should not be stored in the waste tank port, by
decision of the Vessel Supervisor. Thus OP-valve 084 should be closed. Consequently, if we
take this arrangement to practice, the discharge line should be free to 2C tank.
It was found that, in fact, the OP-084 valve was closed, but this was done while the drain
pump still running at 8% of their capacity to work without the discharge flow to the 2C tank (in
the new arrangement) was unimpeded through the OP 080 valve. Table 1 with the records of
the opening and closing of the valves, stop commands and departures of drain pump obtained
from the records of the automation system clarifies this issue.
Table 01 - Drain pump and valves - HD Cargo Ballast N / S 9RX7JG4S:
Events starting and stopping the drain pump and handling of the valves of the suction and
discharge networks.
Suction line valves OP047, OP048, OP050 and OP071
Discharge line valves: OP079 and OP084.
7/23/2019 Fpso Cidade Smateus En
http://slidepdf.com/reader/full/fpso-cidade-smateus-en 28/44
BRAZILIAN NAVY
Directorate of Ports and CoastsMarine Safety Superintendence
Department of Inquiries and Investigations of Navigation Accidents
Explosion with victims on “FPSO CIDADE DE SAO MATEUS”
Maritime Safety Investigation Report
28
Eve
nt
Comput
er timeLocal time
Drain
Pump
Valves of the suction network
Valves of the
discharge
network
OP04
7
OP04
8
OP05
0
OP07
1
OP07
9
OP08
4
01 08:57:09 08:53:09 open
02 08:57:14 08:53:14 open
03 08:57:20 08:53:26 open
04 08:57:26 08:53:26 open
05 08:57:34 08:53:34 open
06 08:57:55 08:53:55 open
07 09:04:31 09:00:31start
(10%)
08 11:31:35 11:27:31 start (8%)
09 11:31:48 11:27:48 shut
10 11:32:02 11:28:02 shut
11 11:33:44 11:29:44 open
12 11:34:28 11:30:28 start (7%)
13 11:34:30 11:30:30 stop(0)
14 11:34:33 11:30:33 open
15 11:42:52 11:38:52 shut
16 11:42:59 11:38:59 shut
17 11:43:02 11:39:02 shut
18 11:43:08 11:39:08 shut
19 11:43:14 11:39:14 shut
20 11:43:38 11:39:38 shut
21 11:43:52 11:39:52 shut
22 12:10:03 12:06:03 open
7/23/2019 Fpso Cidade Smateus En
http://slidepdf.com/reader/full/fpso-cidade-smateus-en 29/44
BRAZILIAN NAVY
Directorate of Ports and CoastsMarine Safety Superintendence
Department of Inquiries and Investigations of Navigation Accidents
Explosion with victims on “FPSO CIDADE DE SAO MATEUS”
Maritime Safety Investigation Report
29
Event 09 – the OP084 valve (pump discharge line) was closed at 11h31m48s, while the pump
was still running.
• Event 13 - the pump was stopped at 11h34m30s.
As the drain pump was of the type of positive displacement, its operations for more than
two minutes with the OP 080 and OP-084 closed valves, brought up the pressure in the discharge
network and caused the condensate leaking in the gasket flange connection upstream the OP-068
valve. This arrangement is marked in blue in the illustration 2.
7/23/2019 Fpso Cidade Smateus En
http://slidepdf.com/reader/full/fpso-cidade-smateus-en 30/44
BRAZILIAN NAVY
Directorate of Ports and CoastsMarine Safety Superintendence
Department of Inquiries and Investigations of Navigation Accidents
Explosion with victims on “FPSO CIDADE DE SAO MATEUS”
Maritime Safety Investigation Report
30
llustration 2 - network diagram indicating the valves closed during the operation of the drain pump
3 Positive displacement pumps have one or more cameras, within which the movement of a driving piece communicates
pressure energy to the liquid, causing it to flow. They are those in which each complete revolution deducts the same amount of
liquid and to vary the flow we have to change the speed. The resistance imposed on the flow rate does not change (is the amount
of liquid discharged in a pump unit of time and a given discharge pressure. It is expressed in m³ / h or l / min). (SEA, Maritime
Professional Education - Brazilian Navy. - Directorate of Ports and Coasts - Auxiliary Machines II - Rio de Janeiro 1989).
Drain
pump
working
leakage ofcondensate bythe flange
conection.
ValveOP080
shut
Valve
OP084
shut
7/23/2019 Fpso Cidade Smateus En
http://slidepdf.com/reader/full/fpso-cidade-smateus-en 31/44
BRAZILIAN NAVY
Directorate of Ports and CoastsMarine Safety Superintendence
Department of Inquiries and Investigations of Navigation Accidents
Explosion with victims on “FPSO CIDADE DE SAO MATEUS”
Maritime Safety Investigation Report
31
CFTV images taken from the camera's shooting 05, installed in the pump house to port,
show the condensate leaks:
Photo # 26
Camera 05 - 02/11/2015 -
10h07m01s - local time
11h30m17s leaks of evidence
of leaks.
The condensate leaked trickle
in this sector. Its origin is in a
network that, about three
meters above this point, the
following image shows.
Photograph # 27
Camera 05 - 02/11/2015 -
10h07m07s - local time
11h30m23s appear the first
condensate leak signals
highlighted by the red circle.
The camera lens has condensate
residue drops.
Photo # 28
Camera 05 -11/02/2015 -
10h28m55s - local time
11h52m11s about 22m later -
the leak traces are reduced as
well. This time the drain pump
was already off. (11h30m30s).
The black spot with
condensate remains in the pipe
is lower, but the camera lens is
dirtier with the product
splashes.
(G) The weakness of the network system used to maneuver.
Notwithstanding the operational error of closing the OP-valve 084 while the pump was
running, this action, by itself, does not cause leakage of the condensate if the integrity of the
flanged connection (obstructed by the racket) was maintained. Note that the pump worked to 8%
of their capacity, his hydrostatic test pressure was 30 kg / cm² and that had a security system that
could relieve the pressure when reached 16.5 kg / cm², beyond all network load be tested in
manufacturing and installation with 1.5 times the working pressure (item 4.6.2 - 7.3 and 4.6.2 -7.3.3 of the ABS of the ship's rules).
7/23/2019 Fpso Cidade Smateus En
http://slidepdf.com/reader/full/fpso-cidade-smateus-en 32/44
BRAZILIAN NAVY
Directorate of Ports and CoastsMarine Safety Superintendence
Department of Inquiries and Investigations of Navigation Accidents
Explosion with victims on “FPSO CIDADE DE SAO MATEUS”
Maritime Safety Investigation Report
32
Photo # 29 – Pump Room – port side
Photo # 30 Photo # 31
Details of the flange gasket wear
(images obtained after the leak - PETROBRAS source)
The company BW Offshore was consulted on the installation of the racket and reported that the
installation of this component was treated as a routine operation, with no need for approval of the
classification society. The ABS Classification Society was also consulted because the entire load
transfer system and ballast was classified, and replied that he had not received the request for
Valve OP-068 (defective) in thenetwork of discharge drain pump. This
branch of the network was not used.
Across the bulkhead is the port residue
tank (slop tank)..
Condensate leak point.
Flanged connection obstructed byracket. I was under pressure to
discharge the drain pump.
Network stretch
without pump
ressure.
7/23/2019 Fpso Cidade Smateus En
http://slidepdf.com/reader/full/fpso-cidade-smateus-en 33/44
BRAZILIAN NAVY
Directorate of Ports and CoastsMarine Safety Superintendence
Department of Inquiries and Investigations of Navigation Accidents
Explosion with victims on “FPSO CIDADE DE SAO MATEUS”
Maritime Safety Investigation Report
33
installation of the Owner racket and did not have sufficient information to assess whether the
material used met the technical parameters involved. The facts show that the weakness of the
flange connection and the condensate leaked into the pump room.
(H) The hydrocarbon cloud in the pump room:
The condensate leaked according to the information contained in the Material Safety Data
Sheet (MSDS) is a compound of oil that can form hydrocarbon vapors, as reported by
PETROBRAS. Effectively, this gas cloud existed and was generated from the condensate leaked
by the board, sprinkled by the effect of pressure, and the puddle is left on the floor because soon
after the gas leak sensors have been activated automatically, as well as the corresponding gas
alarm. Table 2 shows the dynamics of activations of gas sensors in the pump room according to
the records of the automation system.
Table 02 - Gas sensors - HD Server subsystem B - N / S 3LN2CQ1H:
Trigger events of gas sensors in the pump house, with the corresponding alarm level. The
gas cloud was concentrated in the lower compartment levels causing the activation of existing
sensors in the lowest compartment (main floor): 73AB326 TAG, TAG and TAG 73AB327
73AB37.
EventCompute
r time
Local time
(corrected
- 7min)
TAG
73AB326
TAG
73AB327
TAG
73AB370
TAG
73AB3
68
TAG
73AB3
69
01 11:38:04 11:31:04 HI
02 11:38:18 11:31:18 HIHI
03 11:39:16 11:32:16 HI
04 11:40:27 11:33:27 HIHI
05 11:41:59 11:34:59 FAULT
06 11:42:46 11:35:46 FAULT
07 11:43:06 11:36:06 HI
08 11:43:32 11:36:32 HIHI
09 11:44:34 11:37:34 FAULT
10 11:44:36 11:37:36 NORMALI
ZED
7/23/2019 Fpso Cidade Smateus En
http://slidepdf.com/reader/full/fpso-cidade-smateus-en 34/44
BRAZILIAN NAVY
Directorate of Ports and CoastsMarine Safety Superintendence
Department of Inquiries and Investigations of Navigation Accidents
Explosion with victims on “FPSO CIDADE DE SAO MATEUS”
Maritime Safety Investigation Report
34
11 11:45:33 11:38:33 NORMALI
ZED
12 11:45:36 11:38:36 HI - HIHI
13 11:46:33 11:39:33 HI – HIHI
14 11:47:22 11:40:22 HI - HIHI
15 11:50:26 11:43:26 INHIBIT
16 11:50:28 11:43:28 INHIBIT
17 11:50:31 11:43:31 INHIBIT
18 12:07:04 12:00:04
NORMALI
ZED
19 12:08:03 12:01:03 HI - HIHI
20 12:08:48 12:01:48INHIBI
T
21 12:08:52 12:01:52INHIBI
T
22 12:09:54 12:02:54
NORMALI
ZED
23 12:10:53 12:03:53 HI - HIHI
24 12:12:20 12:05:20 NORMALI
ZED
25 12:13:19 12:06:19 HI - HIHI
26 12:44:52 12:37:52 NORMALI
ZED
NORMALI
ZED
NORMALI
ZED
• HI - High level - indicates 20% of the explosion threshold level.
• HIHI - very high - 80% indicate the explosion threshold level. With this statement the
automation system automatically closes the dampers compartment and stops the fan.
• FAULT - failure - means that the gas level is above 100% of the explosion limit level (more
than the sensor can register).
• Normalized - normalized - the sensor returns to its normal condition of gas detection.
• HI - HIHI - high and very high - means that the high level of drive and very high level were
very close and marked at the same time.
7/23/2019 Fpso Cidade Smateus En
http://slidepdf.com/reader/full/fpso-cidade-smateus-en 35/44
BRAZILIAN NAVY
Directorate of Ports and CoastsMarine Safety Superintendence
Department of Inquiries and Investigations of Navigation Accidents
Explosion with victims on “FPSO CIDADE DE SAO MATEUS”
Maritime Safety Investigation Report
35
• INHIBIT - inhibited - means that the sensor continues detecting gas (if any) but does not
trigger the effects of stopping ventilation and close the dampers in the compartment.
Gas alarm signal light. Extracted images from the camera's shooting 04 positioned to starboard
in the pump house.
Photo # 32
Camera 04 - 11h31m52s local time.
The camera is in a position to view the red
signal light that is turned on when the gas alarm
occurs. The next image shows
Photo # 33
Camera 04 - local time 11h31m56s
The red signal light was turned on when the
TAG 73AB370 gas sensor was triggered with
HIHI (11h31min18s) - lag of 18s
It is noteworthy that the platform automation system off the exhaust fans of the pump room
in the gas alarm occurrence according to the Cause and Effect Matrix. Therefore, the alarms, the
properties of the atmosphere of the pump room were changed by creating an emergency situation
and turning the place in a potentially explosive area when they were activated. Thus, the pump
room began to show similar characteristics of confined space, pursuant to Regulatory Standard
No. 33 - SAFETY AND HEALTH IN THE WORK IN CONFINED SPACES (NR-33) of the
Brazilian Ministry of Labor and Employment, which defines: "33.1. 2 Confined Space is any
area or environment not designed for continuous human occupation, which has limited means of
entry and exit, whose existing ventilation is insufficient to remove contaminants or where there
may be a deficiency or oxygen enrichment”. The abovementioned standard also defines theconcept of oxygen deficiency as "atmosphere containing less than 20.9% oxygen by volume at
7/23/2019 Fpso Cidade Smateus En
http://slidepdf.com/reader/full/fpso-cidade-smateus-en 36/44
BRAZILIAN NAVY
Directorate of Ports and CoastsMarine Safety Superintendence
Department of Inquiries and Investigations of Navigation Accidents
Explosion with victims on “FPSO CIDADE DE SAO MATEUS”
Maritime Safety Investigation Report
36
normal atmospheric pressure, unless the reduction percentage is appropriately monitored and
controlled."
(I) the explosion:
The hydrocarbon cloud remained at the bottom of the compartment, for only the gas sensors
installed in the pump house background have been activated, so there were present the
flammable gas (fuel) and oxygen (oxidizing).
The source of ignition for the explosion occurred is uncertain and may have occurred spark in
the face of the crewmembers tools jobs in an attempt to remedy the leak; or generation of static
electricity by the use of fire hose cleaning; or use of a portable radio communication VHF; or by
action of natural heat that the magazine was submitted after the stop of exhaustion; or other
unknown causes. The following images produced by CCTV show the time of the explosion.
Photo # 34
01 camera - 12h38m01s, local
time
Photo # 35
01 camera - 12h38m03s, local
time.
Photo # 36
01 camera - 12h38m09s, local
time
7/23/2019 Fpso Cidade Smateus En
http://slidepdf.com/reader/full/fpso-cidade-smateus-en 37/44
BRAZILIAN NAVY
Directorate of Ports and CoastsMarine Safety Superintendence
Department of Inquiries and Investigations of Navigation Accidents
Explosion with victims on “FPSO CIDADE DE SAO MATEUS”
Maritime Safety Investigation Report
37
Photo #37 - 03 camera -
11/Feb/2015 - 11h14m42s -
local time 12h37m58s
Photo # 38 - 03 camera -
11/Feb/2015 - 11h14m45s -
local time 12h38m01s
Photo # 39 - 03 camera -
11/Feb/2015 - 11h14m48s -
local time 12h38m04s
(J) Non-compliance with current legislation (regulations, resolutions and codes):
- The Brazilian NORMAN-01 / DPC states in item 0117 that the safety of the crew of the fixed
and mobile platforms, FPSO, FSU and drillship prospecting and exploration of oil, is made up of
maritime crew and not maritime crew in accordance with the operational circumstances which
these units are involved. Part of maritime safety crew is provided in Resolution A.891 (21) of the
International Maritime Organization (IMO) and is known as Operations Section and, depending
on the type of platform, can be composed of:
- Offshore Installation Manager (GIO) - A person officially designated by the ship owner, owner
or company, as most responsible for the platform, to which all crew members are subordinate;
- Vessel Supervisor – a person to control ballast operation on mobile units (not applicable to
fixed platforms);
- Ballast Control Operator - Person responsible for the conduct of ballast operations in mobile
units (not applicable to fixed platforms); and
- Maintenance Supervisor - Person responsible for the inspection, operation, testing and
maintenance of engines and equipment essential to the safety of life on board and pollution
prevention, it can be caused by the platform or its operation. The level and the staff hierarchy the
edge of the platform, FPSO, FSU and ships probe will be according to the following flowchart:
7/23/2019 Fpso Cidade Smateus En
http://slidepdf.com/reader/full/fpso-cidade-smateus-en 38/44
BRAZILIAN NAVY
Directorate of Ports and CoastsMarine Safety Superintendence
Department of Inquiries and Investigations of Navigation Accidents
Explosion with victims on “FPSO CIDADE DE SAO MATEUS”
Maritime Safety Investigation Report
38
OFFSHORE INSTALLATION
MANAGER (GIO)
MAINTENANCE RESCUE GROUP
SUPERVISOR VESSEL SUPERVISOR
ENGINE SECTION CREW DECK SECTION CREW BALLAST CONTROL
OPERATOR
Therefore, according to the cited standards, it is clear that the GIO is the most responsible
for the platform, to who all crew members are subordinate.
In carrying out its responsibility and authority on board the platform, fit the GIO risk
assessment and decision on the entry of people in the pump house, as described in the Summary
Chronological accident, although there was doubt as to the existence of gas therein.
The decision taken, which subjected the crew to risk, bucked the security procedures for such
cases in various rules and instructions, as described below:
- Code for the Construction and Equipment of Mobile Offshore Drilling Units (MODU
Code1989), adopted by Resolution A.649 (16) on 19 October 1989, by which the platform was
certified. Item 14.1 of the Code, when dealing with Platform Operations Manual provides that
they should be included in this special operations procedures manual for uncontrolled leakage
events of hydrocarbon and emergency stops. Continuing in item 14.5, it is established that the
procedures for entry into confined spaces shall be those set out in IMO Resolution A.1050 (27).
- IMO Resolution A.1050 (27) brings recommendations for entry into confined spaces
aboard ships. This Resolution establishes the need for risk assessment, permission for entry,
general precautions, atmosphere test, precautions during the stay of people in confined spaces,
etc. and explains that accidents can occur, among other reasons, lack of care by the personnel
involved; and explicitly recommended the adoption of safety procedures.
7/23/2019 Fpso Cidade Smateus En
http://slidepdf.com/reader/full/fpso-cidade-smateus-en 39/44
BRAZILIAN NAVY
Directorate of Ports and CoastsMarine Safety Superintendence
Department of Inquiries and Investigations of Navigation Accidents
Explosion with victims on “FPSO CIDADE DE SAO MATEUS”
Maritime Safety Investigation Report
39
- The Brazilian Technical Regulations of the Operational Safety Management System of
Maritime Facilities Drilling and Production of Oil and Natural Gas (SGSO), and the National
Petroleum Agency (ANP) approved by ANP Resolution No. 3, of December 6, 2007, published
in the Official Gazette on December 7, 2007, and amended in the Official Gazette on December
10, 2007 and in the Official Gazette of 12 December 2007. This Regulation, which applies to all
platforms operating in Brazilian waters deals with, among other things, the work of running on
platforms risk areas such as the following transcript: "Work Permit 17.2 - 17.2.1 The Operator
Installation should establish a work permit system and other means of control to manage
activities in hazardous areas. In preparing this system should consider: 17.2.1.1 The Operator of
the installation shall establish the types of activity that may pose risks to operational safety and
requiring Work Permit. 17.2.1.2 That Work Permit must include additional precautionary
measures and mitigation that may be required to carry out the task safely. 17.2.1.3 The need for
prior analysis of safety conditions for the execution of tasks and hazards in the workplace. 17.2.2
The operator of the installation must ensure that the work permit system: a) Be documented and
that the instructions and forms permits are clear and concise; b) Establish that the controls and
work permits are approved at an appropriate level of management / supervision of installation.
17.3 - Monitoring - The Installation Operator will be responsible for: 17.3.1 Monitor the
performance of activities in accordance with the requirements for approved procedures, the work
permits and information and related documentation. 17.3.2 Ensure that work permits and
controls are used to completion of the work. ".
- The Contingency Plan and Emergency Response of the FPSO CIDADE DE SAO
MATEUS.
This Plan, in Section 4.1, presents the response to emergencies and organizational chart in
item 5 describes the role of GIO as the "Strategist and Incident Commander." In the control
room, he would have the functions to activate a command structure that would meet the
organizational needs to protect lives, the environment and damage to the facility; and initiate
rapid and effective action to control the incident, as well as manage response actions to ensure
that the climbing potential, the risk of injury to personnel and damage to the installation to be
minimized.
The entrance of people in the pump house without risk analysis, without the issuance of the
work permit document and no monitoring of the atmosphere compartment conditions,demonstrates a flagrant breach of regulations.
7/23/2019 Fpso Cidade Smateus En
http://slidepdf.com/reader/full/fpso-cidade-smateus-en 40/44
BRAZILIAN NAVY
Directorate of Ports and CoastsMarine Safety Superintendence
Department of Inquiries and Investigations of Navigation Accidents
Explosion with victims on “FPSO CIDADE DE SAO MATEUS”
Maritime Safety Investigation Report
40
(K) The failures in the ship's safety management system:
The platform provides the Safety Management Certificate issued by the classification
society Det Norske Veritas / Norway and Germanischer Lloyd / Germany (DNV-GL), under the
International Safety Management Code (ISM Code), valid until September 15, 2019. This
document certifies that the platform has been audited and that its security management system
meets the requirements of the ISM Code.
The ISM Code is expressed in broad terms and can be applied at different levels of
management, both on land and at sea, requiring varying levels of knowledge and awareness.
According to that contained in the said Code, the foundation of a good security management is
the attitudes, commitment, competence and motivation of individuals at all levels. Therefore, the
Safety Management System should be structured and documented enabling the effective
implementation of safety and environmental protection policy of the company.
The Code's objectives are to ensure safety at sea, prevention of human injury or loss of life,
and the prevention of environmental damage, in particular to the marine environment, and
property. To meet these goals the Company's security management must continually improve the
skills of the personnel security management ashore and aboard, including preparing for
emergencies related both to safety as to environmental protection by ensuring compliance with
mandatory rules and regulations; and codes, guidelines and standards, recommended by the
Organization, Administrations, classification societies and maritime industry organizations are
taken into account.
The Code classifies the noncompliance with the rules and mandatory rules for the two types
of non-compliance:
"Non-compliance” - an observed situation where the objective evidence indicates the non-
fulfillment of a specified requirement; and
“Greater non-compliance” - an identifiable deviation which poses a serious threat to the safety of
personnel or the ship or a serious risk to the environment that requires immediate corrective
action or the lack of effective and systematic implementation of a requirement of this Code. "
In this particular case, the following failures were recorded:
(1) the document submitted by BW Offshore Brazil Ltd. as the Safety Management Manual have
in your cover letter warning that the procedures contained therein should be checked before being used because it is a manual on development. This warning shows that there is no procedure
7/23/2019 Fpso Cidade Smateus En
http://slidepdf.com/reader/full/fpso-cidade-smateus-en 41/44
BRAZILIAN NAVY
Directorate of Ports and CoastsMarine Safety Superintendence
Department of Inquiries and Investigations of Navigation Accidents
Explosion with victims on “FPSO CIDADE DE SAO MATEUS”
Maritime Safety Investigation Report
41
for prompt adoption of onboard emergency case, going against the security management
certification issued by DNV-GL;
(2) Drain pump discharge line was altered with the installation of the racket without the
knowledge or approval of the classification society ABS;
(3) the change in alignment of the suction and discharge networks drain pump, while
maneuvering 6C cargo tank condensate transfer did not take into account the fragility of the
discharge network, in the face of the racket on the link setup flanged network;
(4) improper blocking the discharge network of the drain pump during its operation of drain of
the 6C cargo tank, by closing the valve OP-084;
(5) the failure during the passage of function between the GIO resulting from incomplete
operational information. The 6C tank condensate transfer maneuver was not in the Passage
Reports of GIO. The new GIO only became aware of the aforementioned maneuver after the gas
alarm sounded;
(6) the entries of the teams in the pump room after it was found the existence of gas, with no
identification and analysis of risks and without the issuance of the corresponding work permits;
and
(7) the absence in the board manuals of special procedures for uncontrolled leakage events of
hydrocarbon and emergency stops in the pump room.
Such failures attest to the inconsistency of the board management system, giving rise to
improvised decisions that resulted in non-compliances.
XI - LESSONS LEARNED AND PRELIMINARY CONCLUSIONS:
(A) The existence of the Safety Management Certificate issued under the ISM Code is not
enough to ensure safe operations on board the platform. There are needs to the Company's
compliance and safety principles of the platform crew to establish safe working conditions for all
operations aboard platforms.
(B) The inconsistency of the platform's operating manuals and contingency plan can be reflected
as disastrous consequences in emergency situations. It is necessary that these manuals are
correctly written, understood and which are met by the rig crew.
(C) the commitment of operators and contracting companies in maintaining the principles of
safety management of platforms is required.
7/23/2019 Fpso Cidade Smateus En
http://slidepdf.com/reader/full/fpso-cidade-smateus-en 42/44
BRAZILIAN NAVY
Directorate of Ports and CoastsMarine Safety Superintendence
Department of Inquiries and Investigations of Navigation Accidents
Explosion with victims on “FPSO CIDADE DE SAO MATEUS”
Maritime Safety Investigation Report
42
(D) Discard the importance of hydrocarbon leak can lead to devastating consequences for the
property and for shipboard lives.
(E) The platform management needs to be clear and properly exercised. It is necessary that the
function passages allow the transmission of all information related to ongoing operations in order
to ensure continued control of planned actions. The service passages must be made in person,
following a regularly scheduled and not only based on written reports.
(F) A classification society should always be informed of respect to change of equipment kept in
class. In this particular case, it was found that changing the network without the knowledge and
approval of the classification society proved to be disastrous for the outcome of the accident.
(G) any modification needs in selecting networks for hydrocarbon pumping implementation
should take into account the situation in which they find the equipment and should be evaluated
the risks of such changes.
(H) Ballast system operations must have a training program in order to update the operators in
the relevant technical knowledge and in order to be able to assess the consequences of failures in
the control valves and pumps.
(I) Training programs should emphasize the law requirements in force linked to the operations of
the platform highlighting the Regulatory Standards of the Brazilian Ministry of Labor and
Employment, Brazilian Maritime Authority and the Brazilian National Petroleum Agency. In
times of crisis aboard this knowledge can be applied to avoid accidents, such as improper entry
into compartment with confined space features.
(J) The atmosphere inside a confined space can be lethal.
(K) It is mandatory never to go into space containing explosive atmosphere.
(L) The Platform Operating Guide and Contingency Plan shall include all requirements of
current legislation.
(M) The crew must comply with the procedures established by the Companies with respect to
safety and, in particular, as regards the proper use of relevant safety equipment to each task.
In view of what was found, it is concluded that the accident was due to screen flammable
substance leak in the pump room, which led to the formation of gas, the resulting emergence of
explosive atmosphere, and the subsequent explosion; is not possible to determine the ignition
source of the explosion.
7/23/2019 Fpso Cidade Smateus En
http://slidepdf.com/reader/full/fpso-cidade-smateus-en 43/44
BRAZILIAN NAVY
Directorate of Ports and CoastsMarine Safety Superintendence
Department of Inquiries and Investigations of Navigation Accidents
Explosion with victims on “FPSO CIDADE DE SAO MATEUS”
Maritime Safety Investigation Report
43
XII - SAFETY RECOMMENDATIONS:
(A) The Company, in its Annual Training Program for the crew, must exercise on entry
procedures for confined space and indicate formally a responsible for the compliance;
(B) the Company must establish controls to ensure that the entry of people in confined spaces is
only done as there is a risk analysis and the corresponding issue of the Work Permit, and prevent
the entry into spaces containing explosive atmosphere;
(C) all of the safety management system, both the platform and the Company should be
subjected to any audits by the classification society that issued the Safety Management
Certificate and the Document of Compliance;
(D) Platform Operation Manual and the contingency plan should be reviewed and updated in
accordance with the legislation in force;
(E) Company should exercise strict supervision of the procedure to inform the classification
society on changes of equipment and systems kept in class; and
(F) Ballast System Operators should be subject to an ongoing program of training with this
system.
(G) The atmosphere inside a confined space can be lethal and all safety measures should be
taken before entry.
(H) It is mandatory never to go into space containing explosive atmosphere.
================================================== =========
7/23/2019 Fpso Cidade Smateus En
http://slidepdf.com/reader/full/fpso-cidade-smateus-en 44/44
BRAZILIAN NAVY
Directorate of Ports and CoastsMarine Safety Superintendence
Department of Inquiries and Investigations of Navigation Accidents
Explosion with victims on “FPSO CIDADE DE SAO MATEUS”
Maritime Safety Investigation Report
XIII - APPENDIX
Particulars of the Platform "FPSO CIDADE DE SAO MATEUS".
PARTICULARS OF THE PLATAFORM
“ FPSO CIDADE DE SÃO MATEUS”:
2.1. Unit main caracteristics:
Description
The FPSO Cidade de São Mateus is a floating production, storage and transfer
of oil and also processing and exporting gas, with the following characteristics:
2.1.1. Physical Characteristics:
a) Overall length = 322.07 m.
b) Length between perpendiculars = 310.00 m.
c) Breadth = 54.50 m.
d) Depth = 29.50 m.
e) Gross tonnage =: 143 323; net: 42 996.
f) Draft (project) = 19.8 m.
g) Accommodations = 85 people. This number may vary according to the stage of the
installation life cycle, or need to perform activities requiring labor increase, and will
be determined by the maximum permissible number of places available in salvage
equipment and conditioned the rules established by specific regulations of the
MODU Code, the Brazilian Ministry of Labor and Employment and the Brazilian
Navy.