Power Transfer Swtiches
- for -
F.M. Approvals- by -
James S. Nasby
Columbia Engineering
![Page 2: Fire Pump Transfer Switch Basics](https://reader033.vdocuments.us/reader033/viewer/2022061300/54cc45b94a79591e0f8b46ec/html5/thumbnails/2.jpg)
C.E. F.M. Approvals 2
Topics to be Covered
Arrangement I (Combo. Unit) Arrangement II (Separately Listed Units) Power Supply Considerations Options
![Page 3: Fire Pump Transfer Switch Basics](https://reader033.vdocuments.us/reader033/viewer/2022061300/54cc45b94a79591e0f8b46ec/html5/thumbnails/3.jpg)
C.E. F.M. Approvals 3
Note: “Alternate Source” may be a “Hot Emergency Bus” as often employed in hospitals.
In these systems, multiple MVA size gen-sets are used along w/ additional upstream Transfer Switches with a path to one or more Utility Connections.
This often results in very high fault currents on the Alternate Source Side.
Also note that two C/Bs will be required in all Arrangement I units per 2010 Edition of NFPA-20.
Two Arrangements
![Page 4: Fire Pump Transfer Switch Basics](https://reader033.vdocuments.us/reader033/viewer/2022061300/54cc45b94a79591e0f8b46ec/html5/thumbnails/4.jpg)
C.E. F.M. Approvals 4
Power Supply Systems
Power Supply Weak = Voltage Drop Problems Stiff = Careful Coordination of WIC
Type of System Wye = Typical
Grounded Neutral = Typical Ungrounded = Care & Coordination
Delta = Great Care Needed. Ungrounded Corner Ground 4 Wire High Leg (240 / 120 / 208)
![Page 5: Fire Pump Transfer Switch Basics](https://reader033.vdocuments.us/reader033/viewer/2022061300/54cc45b94a79591e0f8b46ec/html5/thumbnails/5.jpg)
C.E. F.M. Approvals 5
Options (Varations)
Added Ground Lugs (Some Jurisdictions)
Fourth Pole (Neutral) Usually “Overlapping” (Make Before Break) Supplied by Some E.F.P.C. Mfrs.
In Phase Transfer Delays Transfer Until Motor Back EMF Phase Angle
is Close to that of the Intended Source Completely Useless for Pump Motors due to Very
Low Inertia and Large Minimum Load on Motor
![Page 6: Fire Pump Transfer Switch Basics](https://reader033.vdocuments.us/reader033/viewer/2022061300/54cc45b94a79591e0f8b46ec/html5/thumbnails/6.jpg)
C.E. F.M. Approvals 6
Arrangement I (Combo. Unit)
10.8.1 General10.8.2.1 Arrangement I
(Listed Combination Fire Pump Controller and Power Transfer Switch)
10.8.3 Power Transfer Switch Requirements
![Page 7: Fire Pump Transfer Switch Basics](https://reader033.vdocuments.us/reader033/viewer/2022061300/54cc45b94a79591e0f8b46ec/html5/thumbnails/7.jpg)
C.E. F.M. Approvals 7
Arrangement I – Combo. Unit
![Page 8: Fire Pump Transfer Switch Basics](https://reader033.vdocuments.us/reader033/viewer/2022061300/54cc45b94a79591e0f8b46ec/html5/thumbnails/8.jpg)
C.E. F.M. Approvals 8
Short Circuit (WIC)
Coordination
Note: “---” means no Upstream Protection is Required.
E.g.: Self Protecting (Blow Apart) Isolating Switch Provides Suitable Protection of the Internal Transfer Switch.
![Page 9: Fire Pump Transfer Switch Basics](https://reader033.vdocuments.us/reader033/viewer/2022061300/54cc45b94a79591e0f8b46ec/html5/thumbnails/9.jpg)
C.E. F.M. Approvals 9
Arrangement II (Separate Units)
10.8.1 General 10.8.2.2 Arrangement II
(Individually Listed Fire Pump Controller and Power Transfer Switch)
10.8.3 Power Transfer Switch Requirements
![Page 10: Fire Pump Transfer Switch Basics](https://reader033.vdocuments.us/reader033/viewer/2022061300/54cc45b94a79591e0f8b46ec/html5/thumbnails/10.jpg)
C.E. F.M. Approvals 10
Russelectric F.P. Transfer Switch
![Page 11: Fire Pump Transfer Switch Basics](https://reader033.vdocuments.us/reader033/viewer/2022061300/54cc45b94a79591e0f8b46ec/html5/thumbnails/11.jpg)
C.E. F.M. Approvals 11
Arrangement II Requirements:Who Supplies What?
Section 10.8.2.2(2) "An isolating switch, or service disconnect where required, ahead of the normal input terminals of the transfer switch" 10.8.2.2(3) [and 9.2.3.4]: Xfer Switch OCP "shall be selected or set to carry indefinitely the sum of the locked rotor current of the fire pump motor" plus any additional connected loads. E.g.: 600% of motor FLA minimum10.8.3.4.2: transfer switch be sized at only 115% of the motor FLA current10.8.3.6.4: Phase Reversal Sensing
![Page 12: Fire Pump Transfer Switch Basics](https://reader033.vdocuments.us/reader033/viewer/2022061300/54cc45b94a79591e0f8b46ec/html5/thumbnails/12.jpg)
C.E. F.M. Approvals 12
WIC Coordination ExampleTransfer Switch Sizing Example for 100 Hp at 460 Vac
X 115% Thermal X 600% Breaker WIC Coord.
Motor Hp Motor FLAThermal Sizing Upstream Size Switch Size
100 Hp 124 amps 143 amps 150 amp 744 amp 800 amp 400 amp
In this Example, a 150 Amp Xfer Switch meets the 115% criteria; but, it’s Short Circuit (WIC) Rating will be invalid if the upstream device is larger than 250 amps. However, a 250 Amp OCP doesn’t meet the 600% criteria. Hence, a larger Xfer switch is needed. Who does the coordination, and who supplies what?
![Page 13: Fire Pump Transfer Switch Basics](https://reader033.vdocuments.us/reader033/viewer/2022061300/54cc45b94a79591e0f8b46ec/html5/thumbnails/13.jpg)
C.E. F.M. Approvals 13
Are All of These Supplied? 1) The two Position Indicator lights 2) The Engine Start delay timer and the Re-Transfer delay timer, 3) The Engine Start contacts, 4) The Test (Transfer) switch (pushbutton), maybe. 5) The Normal Side Service Disconnect and overcurrent protection fuses or breaker, 6) Otherwise, the required emergency side Isolating Switch which is: 7) Lockable "ON" 8) Having an external "Fire Pump Isolating Switch" placard, 9) A placard next to the controller giving the location of this Isolating Switch10) Supervision of the Isolating Switch by one of the four means given11) Audible and visible alarm to indicate Isolating Switch Open,12) Isolating Switch contacts for remote alarm,13) Means to prevent Higher-than-Normal motor in-rush currents,14) Phase reversal sensing and transfer circuitry.15) Although not required, the Bypass switch may or may not be standard equipment.
![Page 14: Fire Pump Transfer Switch Basics](https://reader033.vdocuments.us/reader033/viewer/2022061300/54cc45b94a79591e0f8b46ec/html5/thumbnails/14.jpg)
C.E. F.M. Approvals 14
Arrangement II Requirements
See:
Application Guide - for -
Fire Pump Transfer Switches- for use with -
Electric Motor Driven Fire Pumps
Note: An updated copy is in the handouts.
![Page 15: Fire Pump Transfer Switch Basics](https://reader033.vdocuments.us/reader033/viewer/2022061300/54cc45b94a79591e0f8b46ec/html5/thumbnails/15.jpg)
C.E. F.M. Approvals 15
Questions ?