Transcript
Page 1: FIELD FUSIBLE LINK REPLACEMENT - Moffitt Corporation · 05.10.2016  · FIELD FUSIBLE LINK REPLACEMENT 1. Manually open the vent doors by pulling the roof level release. 2. Manually

 MoffittCorp.com 1351 13th Avenue South, Suite 130 Jacksonville Beach, FL 32250 (904) 241‐9944 (800) 474‐3267  

 

FIELD FUSIBLE LINK REPLACEMENT  

1. Manuallyopentheventdoorsbypullingtherooflevelrelease.

2. Manuallypushthetopofeachlatchoutward,towardstheoutsideofthevent,

about114"to112",andclamplatchestocenterbraceusingvisegrips,locking

pliers,orsmallc‐clamps.

3. Using7/16"wrenches,carefullyremovetheexistingfusiblelinkfromthe

equalizerspringandthelatch.

4. Installreplacementfusiblelinkbetweenthelatchandtheequalizerspring.

CAUTIONDONOTOVERTIGHTEN

NotethatnyloninsertlockingnutsareutilizedFusiblelinkmustbefreetopivot.

5. Manuallyclosetheventdoors,andcheckforproperlatching.STBP6

6. Pulltheroof‐levelrelease,toinsureproperopeningoftheventdoors.

7. Manuallyclosetheventdoors.

 

   

Page 2: FIELD FUSIBLE LINK REPLACEMENT - Moffitt Corporation · 05.10.2016  · FIELD FUSIBLE LINK REPLACEMENT 1. Manually open the vent doors by pulling the roof level release. 2. Manually

MofiCorp.com(904) 241-9944

Page 3: FIELD FUSIBLE LINK REPLACEMENT - Moffitt Corporation · 05.10.2016  · FIELD FUSIBLE LINK REPLACEMENT 1. Manually open the vent doors by pulling the roof level release. 2. Manually

 MoffittCorp.com 1351 13th Avenue South, Suite 130 Jacksonville Beach, FL 32250 (904) 241‐9944 (800) 474‐3267  

 

INSTALLATIONINSTRUCTIONS‐FX250FIREX

1. Lifttheunittotheroof‐notetheliftpointsstenciledonthedoors.Ifunitiscrated,lifttotheroofinthecrate.

2. Positiontheunitadjacenttotheroofopeninganduncrate,ifcrated.3. Placetheunitovertheroofopening(ifself‐flashingtype)orontheroofcurb(ifcurb

type).Theunitsmustbeflatandtrueonthemountingsurfaceandnotbeinatwisttoinsureproperoperationandweatherseal.

4. Anchortheunitinplace.5. Carefullyremovetheshippingstrapthatisinstalledatmiddletopofventdoors.See

sketch250‐10fordetails.6. Theunitcannowbeopenedmanuallytocheckforproperoperationbypullingthe

rooflevelmanualreleasehandle.BESURETOSTAYCLEAROFTHESPRINGLOADEDDOORS.

7. Ifmanualinsidereleasecableisfurnished,itwillnowbeaccessiblewhilethedoorsareopen.Theinsidereleasewillbetapedontothecabletotheroofrelease.Untapeanddropinsidereleasehandle.

8. Resetthedoorsbypushingdowninthecenterofthedooruntilthelatchesengage.Besurethatthesealsalongthecentergutterareproperlyaligned.

9. Innormaloperationnolubricationormaintenancewillberequiredforthelifeoftheunit.

NOTE:USEOFTHEUNITFORVENTILATIONORASANACCESSHATCHVOIDSALLWARRANTIES.

NOTE:FIELDPAINTINGOFUNITVOIDSALLWARRANTIES

Page 4: FIELD FUSIBLE LINK REPLACEMENT - Moffitt Corporation · 05.10.2016  · FIELD FUSIBLE LINK REPLACEMENT 1. Manually open the vent doors by pulling the roof level release. 2. Manually

MofiCorp.com

(904) 241-9944

Page 5: FIELD FUSIBLE LINK REPLACEMENT - Moffitt Corporation · 05.10.2016  · FIELD FUSIBLE LINK REPLACEMENT 1. Manually open the vent doors by pulling the roof level release. 2. Manually

MofiCorp.com

(904) 241-9944

Page 6: FIELD FUSIBLE LINK REPLACEMENT - Moffitt Corporation · 05.10.2016  · FIELD FUSIBLE LINK REPLACEMENT 1. Manually open the vent doors by pulling the roof level release. 2. Manually

 MoffittCorp.com 1351 13th Avenue South, Suite 130 Jacksonville Beach, FL 32250 (904) 241‐9944 (800) 474‐3267  

 

MAINTENANCERECOMMENDATIONSMODELFX‐250

Thebasicdesignandconstructionofthisautomaticallyoperatedroofventisvirtuallymaintenancefree.Allcomponentpiecesoftheoperatingmechanismaremanufacturedofcorrosionresistantmaterials.Allpivotsarebrass,bronzeorstainlesssteel.BasedontheaboveMoffittCorporationmakesthefollowingrecommendations:

I. Unitsshouldbemanuallyopenedonceevery12months,byuseoftheroofrelease.II. Afteropening,unitshouldbevisuallycheckedwithparticularattentiontotheintegrityof

springs,fusiblelinkandlatchcomponents.Nolubricatantsorcoatingsshouldbeapplied.III. Doorsshouldbemanuallyresetfromroofline.IV. Inordertoinsuretheautomaticreleaseoftheseunits,NOmaterialsmaybestoredonorin

theseunitsandunitsmustNOTbeusedforgeneralventilation,norshouldtheybefieldpainted.

V. Intheunlikelyeventreplacementpartsarerequired,theyshouldbepurchasedfromthemanufacturertoinsuretheintegrityandproperoperationoftheunit.