Transcript

Solid-Ceiling Mounting•Drilltwo3/16in(4.6mm)pilotholesfortheprovidedscrewanchors.

•Presstheanchorsintotheholesandtapflushwithahammer.

•Placetheflatsideofthemountingbracketagainsttheceilingandinstallthetwoprovidedscrewsusingahandscrewdriver.

•AttachtheSensortothemountingbracketbyinsertingandtwistinginaclockwisedirectionuntiltheSensorlocksintoplace.

WiththeSensormountedontheceiling,pressandreleasethe“Test”button.Thelenswillglowbriefly,indicatingthetestmodehasbeenentered.

NOTE:Thereisawarm-upperiodof90secondsafterthebatteriesareinstalledbeforethetestmodeisactivated.Ifthebuttonispressedduringthistime,thelenswillflashcontinuouslyuntilthewarm-upperiodiscomplete,andthenthetestmodewillbeautomaticallyentered.

Confirmthecoverageareabywalkingthroughthespaceandobservingthelens.Thelenswillglowsolideverytimemotionisdetected.Ifthelensremainsoffduringmotion,theSensorcannotdetectmotionatthatlocation.

Pressandreleasethe“Test”buttonagaintoexitthetestmode.Ifthebuttonisnotpressed,thetestmodewillautomaticallytimeout15minutesafterbeingenabled,or5minutesafterthelastdetectedmotioniftheroomisvacated.

IftheSensorhassignificanttroubledetectingmotionduringthetest,itshouldbemovedtoanotherlocationandre-tested.NOTE:IftheSensorisdetectingmotioninareasthatarenotdesirable,suchashallwaysoradjacentrooms,refertowww.lutron.com/occsensors

IfSensordetectionissatisfactoryduringthistest,performthewirelesscommunicationtestasdescribedinsectionG. Testing Wireless Communication.

ThistestshouldbeperformedtoverifytheSensorhasbeencorrectlysetupwiththecorrespondingdimmingorswitchingdeviceandthatthereisproperwirelesscommunicationfromthechosenSensorlocation.

Pressandreleasethe“Light”buttonmultipletimestotogglethelightsonandoff.

EnglishRadio Powr Savr™Installation Instructions Please Read Before Installing

Wireless Battery-Powered Occupancy and Vacancy Sensors California Title 24 CompliantLRF2-OCR2B-P 3V- 14mA434MHz(Occupancy/Vacancy)LRF2-VCR2B-P 3V- 14mA434MHz(VacancyOnly)

Compatible Products/Additional InformationForafulllistofcompatibleproductsandotheradditionalinformationvisitwww.lutron.com/occsensors

Product DescriptionLutron’sceiling-mountedOccupancyandVacancySensorsarewireless,battery-powered,passiveinfrared(PIR)devicesthatautomaticallycontrollightsviaRFcommunicationwithadimmingorswitchingdevice.

Important Notes1. ThisSensorispartofasystemandcannotbeusedtocontrolaloadwithoutacompatibledimmingor

switchingdevice.Refertotheinstructionsheetsofthereceivingdevice(s)forinstallationinformation.

2. Useonlyhigh-qualitylithiumbatteries,sizeCR123,3V-(ANSI-5018LC,IEC-CR17345).DONOTuserechargeablebatteries.UsingimproperlyratedbatteriescoulddamagetheSensor.

NOTICE:DONOTdisassemble,crush,puncture,orincineratebatteries.DONOTdisposeofbatteriesinnormalhouseholdwaste.Pleaserecycle,taketoaproperbatterydisposalfacility,orcontactyourlocalwastedisposalproviderregardinglocalrestrictionsonthedisposalorrecyclingofbatteries.

WARNING: Entrapment hazard.Toavoidtheriskofentrapment,seriousinjury,ordeath,thesecontrolsmustnotbeusedtocontrolequipmentwhichisnotvisiblefromeverycontrollocationorwhichcouldcreatehazardoussituationssuchasentrapmentifoperatedaccidentally.Examplesofsuchequipmentwhichmustnotbeoperatedbythesecontrolsinclude(butarenotlimitedto)motorizedgates,garagedoors,industrialdoors,microwaveovens,heatingpads,etc.Itistheinstaller’sresponsibilitytoensurethattheequipmentbeingcontrolledisvisiblefromeverycontrollocationandthatonlysuitableequipmentisconnectedtothesecontrols.Failuretodosocouldresultinseriousinjuryordeath.

FCC InformationThis device complies with part 15 of the FCC Rules and Industry Canada license-exempt RSS standard(s).Operation is subject to the following two conditions: (1) This devicemay not cause interference, and (2) thisdevicemustacceptanyinterference,includinginterferencethatmaycauseundesiredoperation.ModificationsnotexpresslyapprovedbyLutronElectronicsCo.,Inc.couldvoidtheuser’sauthoritytooperatethisequipment.“Note:ThisequipmenthasbeentestedandfoundtocomplywiththelimitsforaClassBdigitaldevice,pursuanttopart15oftheFCCRules.Theselimitsaredesignedtoprovidereasonableprotectionagainstharmfulinterferenceina residential installation.Thisequipmentgenerates,usesandcanradiate radio frequencyenergyand, ifnotinstalledandusedinaccordancewiththeinstructions,maycauseharmfulinterferencetoradiocommunications.However,thereisnoguaranteethatinterferencewillnotoccurinaparticularinstallation.Ifthisequipmentdoescauseharmfulinterferencetoradioortelevisionreception,whichcanbedeterminedbyturningtheequipmentoffandon,theuserisencouragedtotrytocorrecttheinterferencebyoneormoreofthefollowingmeasures:—Reorientorrelocatethereceivingantenna.—Increasetheseparationbetweentheequipmentandreceiver.—Connecttheequipmentintoanoutletonacircuitdifferentfromthattowhichthereceiverisconnected.—Consultthedealeroranexperiencedradio/TVtechnicianforhelp.”

Sensor OperationOccupancy Version – TheSensorwillautomaticallyturnthelightsonwhenthespaceisoccupiedandautomaticallyturnthelightsoffafterthespaceisvacated. Vacancy Only Version – Thelightsmustbemanuallyturnedonatthedimmingorswitchingdevice.TheSensorwillautomaticallyturnthelightsoffafterthespaceisvacated.

Limited Warranty(Valid only in U.S.A., Canada, Puerto Rico, and the Caribbean.)Lutron will, at its option, repair or replace any unit that is defective in materials or manufacture within one year after purchase. For warranty service, return unit to place of purchase or mail to Lutron at 7200 Suter Rd., Coopersburg, PA 18036-1299, postage pre-paid.This warranTy is in lieu of all oTher express warranTies, and The implied warranTy of merchanTabiliTy is limiTed To one year from purchase. This warranTy does noT cover The cosT of insTallaTion, removal or reinsTallaTion, or damage resulTing from misuse, abuse, or damage from improper wiring or insTallaTion. This warranTy does noT cover incidenTal or consequenTial damages. luTron’s liabiliTy on any claim for damages arising ouT of or in con nec Tion wiTh The manufacTure, sale, insTallaTion, delivery, or use of The uniT shall never exceed The pur chase price of The uniT.This warranty gives you specific legal rights, and you may have other rights which vary from state to state. Some states do not allow the exclusion or limitation of incidental or consequential damages, or limitation on how long an implied warranty may last, so the above limitations may not apply to you.

Lutron, Maestro Wireless, and the Sunburst logo are registered trademarks and Radio Powr Savr is a trademark of Lutron Electronics Co., Inc. ANSI is a registered trademark of the American National Standards Institute. IEC is a trademark of the International Electrotechnical Commission.

© 2011 Lutron Electronics Co., Inc.

Technical AssistanceForquestionsconcerningtheinstallationoroperationofthisproduct,calltheLutron Technical Support Center.Pleaseprovideexactmodelnumberwhencalling.

U.S.A. and Canada (24 hrs / 7 days) 1.800.523.9466 Fax +1.610.282.6311 Mexico 8am – 8pm ET+1.888.235.2910Other countries 8am – 8pm ET +1.610.282.3800 www.lutron.com

Instructions

12

1

BeforesettinguptheSensor,thecorrespondingdimmingorswitchingdevice(s)mustbeinstalled.

Twistandremovemountingbrackettoinsertbatteryintobatterycavity.

InorderfortheSensortooperateproperly,itmustfirstbesetupwithacorrespondingdimmingorswitchingdevice.TheprocedureforsettingupaSensorwithaMaestroWirelessR(MRF2only)DimmerorElectronicSwitchisdetailedbelow.IfsettingupaSensorwithadifferentdevice,visitwww.lutron.com/occsensorsorconsulttheinstallationguideforthatdevice.

Setting up a Sensor with a Maestro Wireless® Dimmer or Electronic SwitchPlacetheDimmerorSwitchinset-upmodebypressingandholdingthetapbuttonfor6secondsuntilallLEDsonthedevicebeginflashing.Releasethetapbutton.

AddtheSensortotheDimmerorSwitchbypressingandholdingthe“Light”buttononthefrontoftheSensorfor6secondsuntilthelensflashesbriefly.Thelightsintheroomwillalsoflash3times,indicatingtheSensorhasbeensuccessfullyadded.TheDimmerorSwitchwillexitset-upmodeautomatically.

The“Light”buttonshouldnowswitchthelightsintheroomonandoffwhenpressed.RepeattheaboveproceduretosetuptheSensorwithadditionaldevices. 2

1

1

4

5

3

2

A Pre-Installation

B Set-Up

G Testing Wireless Communication

C Sensor Detection Range

E Mounting Methods

D Sensor Placement and Coverage

F Testing Sensor Coverage

Drop-Ceiling MountingPuttheSensorinplaceonthetileandeithertakethetiledownorremoveanadjacenttiletogainaccesstothelegsofthemountingwireonthebackofthetile.Twistthewirelegstogethertightly.

NOTE:Fordetailsontemporarymountingonsolidceilingsurfaces,visitwww.lutron.com/occsensors

Before mounting the Sensor, please note the following:• TheSensorisdesignedforceilinguseonly.DO NOTinstallonceilingshigherthan12ft(3.7m).

(SeesectionC.Sensor Detection Range)

• TheSensorshouldbeinstalledinalocationwhereithasagoodviewofallpartsoftheroom.TheSensorrequireslineofsighttooperateproperly.If you cannot see the Sensor, it cannot see you. TheSensorcannotseethroughglassobjectssuchaspatioorshowerdoors.(SeesectionC.Sensor Detection Range)

• DO NOTmounttheSensorwithin6ft(1.8m)ofHVACventsormicrowaveovens,within6in(15cm)ofotherRFdevices,orwithin4ft(1.2m)oflightbulbsinstalledbelowtheceilingline.(SeesectionC.Sensor Detection Range)

• TheSensormaybeinstalledupto60ft(18.3m)awayfromtheassociateddimmingorswitchingdevice(s)iftheyareindirectlineofsight.IftherearewallsorotherbarriersbetweentheSensorandreceivingdevice(s),theSensorshouldbelocatedwithin30ft(9.1m).(SeesectionC.Sensor Detection Range)

• Wheneverpossible,avoidplacingtheSensorinalocationwhereithasabroadviewoutsidetheintendedspace.Ifthisisunavoidable,thelenscanbemaskedtoblocktheviewofundesiredareas(seewww.lutron.com/occsensors).

2

Lutron Electronics Co., Inc.7200 Suter RoadCoopersburg, PA 18036-1299, U.S.A.Printed in the U.S.A. 05/2011 P/N 041-315 Rev. A

• Easy-to-follow Instructions

P/N041-315a

3

13ft(4.0m)RadiusofCoverageatFloorwhenmountedonan8ft(2.4m)Ceiling

15ft 12ft 9ft 6ft 3ft 0ft 3ft 6ft 9ft 12ft 15ft(4.6m) (3.7m) (2.7m) (1.8m) (0.9m) (0m) (0.9m) (1.8m) (2.7m) (3.7m) (4.6m)

8ft(2.4m)Ceilingheight

Ceiling

Floor

RadiusofCoverageatFloor

Sensor

Occupant

18x18ft(5.5x5.5m)MaximumRoomDimensionsforCompleteCoveragewhen

mountedonan8ft(2.4m)Ceiling

Symptom Possible Causes Solution

LightsdonotturnONwhenspaceisoccupied.

Sensorisnotcorrectlyaddedtodimming/switchingdevice(s). RefertosectionB. Set-Up.

Sensor’sAuto-Onsettingissetto“Lowlight”or“Disable”. RefertosectionH. Advanced Set-Up.

Thelightswererecentlyturnedoffmanuallyandthetimeouthasnotyetexpired.

Formoredetails,refertoFrequently Asked Questionsatwww.lutron.com/occsensors

Sensordoesnothavefullviewofroom. Refertosection C. Sensor Detection Range.

Sensorisoutsidewirelessrangeofdimming/switchingdevice. RefertosectionD. Sensor Placement and Coverage or G. Testing Wireless Communication.

Batteryhasbeeninstalledincorrectly. RefertosectionA. Pre-Installation.

Dimming/switchingdevicehasbeenimproperlywired. RefertotheinstructionsheetofthereceivingdeviceorcallLutronTechnicalSupportCenterat800.523.9466.

Lightbulb(s)burnedout.

Breakerisoffortripped.

LightsturnOFFwhilespaceisoccupied. Sensor’stimeoutistooshortforthisapplication. RefertosectionH. Advanced Set-Up.

Sensordoesnothavefullviewofroom. RefertosectionC. Sensor Detection Range.

Lensmaskisimproperlyapplied. Refertowww.lutron.com/occsensors

Sensor’sactivitysettingistoolow. RefertosectionH. Advanced Set-Up.

LightsstayONafterspaceisvacated. Sensor’stimeouthasnotyetexpired. RefertosectionH. Advanced Set-Up.

AnexternalnoisesourcesuchasanHVACventisinterfering. TrymovingSensortoanewlocationorreducingsensitivity.RefertosectionD. Sensor Placement and Coverage or H. Advanced Set-Up.

Batteryhasbeeninstalledincorrectly. RefertosectionA. Pre-Installation.

LightsturnONwhenwalkingpastroom. Sensorcoverageextendsbeyondroomperimeter. RefertosectionD. Sensor Placement and Coverage.

BehavioroflightsdoesnotmatchSensorsettings.

Theintendedsettingwasnotsaved. RefertosectionH. Advanced Set-Up.

MultipleSensorsareaddedtoadimming/switchingdeviceandtheirsettingsdonotmatch.

RefertosectionH. Advanced Set-Up.

SensorlensdoesnotglowinresponsetomotionduringSensorcoveragetesting.

Sensorcannotseemotionduetoobstruction. MoveSensortoanotherlocation.RefertosectionC. Sensor Detection Range.

Roomistoobigoroddlyshaped. MultipleSensorsmaybenecessaryforfullroomcoverage.Formoredetails,refertoFrequently Asked Questionsatwww.lutron.com/occsensors

Batteryhasbeeninstalledincorrectly. RefertosectionA. Pre-Installation.LensdoesnotstopglowingduringSensorcoveragetestingevenwhenthereisnomotion.

AnexternalnoisesourcesuchasanHVACventisinterfering. TrymovingSensortoanewlocationorreducingsensitivity.RefertosectionD. Sensor Placement and Coverage or H. Advanced Set-Up.

Lightsdonotrespondcorrectlyduringwirelesscommunicationtesting.

Sensorisnotcorrectlyaddedtodimming/switchingdevice. RefertosectionB. Set-Up.

Sensorisoutsidewirelessrangeofdimming/switchingdevice. MoveSensorclosertodimming/switchingdeviceandretrytest.RefertosectionG. Testing Wireless Communication.

Batteryhasbeeninstalledincorrectly. RefertosectionA. Pre-Installation.

Dimming/switchingdevicehasbeenimproperlywired. RefertotheinstructionsheetofthereceivingdeviceorcallLutronTechnicalSupportCenterat800.523.9466.

Lightbulb(s)burnedout.

Breakerisoffortripped.

SensorlensflashesandlightsdonotturnONwhenspaceisoccupied.

Batteryislow. Replacebattery.Formoredetails,refertoFrequently Asked Questionsatwww.lutron.com/occsensors

Sensorisintestmode. Removesensorfromtestmode.RefertosectionF. Testing Sensor Coverage.

Troubleshooting

TheSensorfeaturesseveraladvancedset-upmodes.Forthemajorityofinstallations,thedefaultsettingswillprovidethebestperformanceandyouwillnotneedtoutilizetheadvancedset-up.

TheOccupancyversionoftheSensorhasthreeadjustableadvancedset-upmodes:Timeout,Auto-On,andActivity.TheVacancy-Onlyversionhasonlytwomodes(Auto-Onnotavailable).Thedefaultsettingsarelistedbelow.

Default Settings:

Timeout: 15minutes

Auto-On: Enabled(Occupancyversiononly)

Activity: LowActivity

Advanced Set-Up Modes

TimeoutTheSensorwillturnthelightsoffifnomotionoccursforthedurationofthetimeoutperiod.Therearefouravailabletimeoutsettings:1*, 5, 15, and 30 minutes.

Auto-On (Occupancyversiononly)Theautomatic-onfunctionalityoftheSensorcanbeadjustedtocontrolhowthelightsresponduponinitialoccupancy.Therearethreeavailablesettings:Always,Lowlight,andDisable.

Enabled: Thelightswillalwaysturnon.

Low light: Thelightswillonlyturnonautomaticallyuponentryifthereisnotalreadysufficientambientlightintheroom.

Disabled: ThissettingconvertstheSensortovacancymode.Thelightswillnotautomaticallyturnonbutwillstillautomaticallyturnoffaftervacancy.Thelightsmustbemanuallyturnedonbyusingtheassociateddimmingorswitchingdevice.

ActivityThesensitivityoftheSensorcanbeadjustedbasedontheexpectedlevelofactivitywithintheroom.Therearethreeavailableactivitysettings:LowActivity,MediumActivity,andHighActivity.

Low Activity: Thisisthemostsensitivesettingandwilldetectveryslightmotions.Thisistherecommendedsetting,asitwillworkwellfornearlyallapplications.Itisidealforspaceswhereoccupantswilloftenbeseatedforlongperiodsoftime.

Medium Activity**:ThissettingisslightlylesssensitivethantheLowActivitysettingandcanbeusedforspacesthatexperiencenormalactivity.

High Activity**:Thisistheleastsensitivesettingandcanbeusedforspacesthatwillgenerallyonlyexperiencelargemotions,suchasfoottraffic.

* Toselecta1-minutetimeout,pressandholdthetimeoutbuttonforapproximately10secondsuntilall3LEDsbeginflashingrapidly.Tosavethe1-minutetimeoutsetting,pressandholdthetimeoutbuttonuntilall3LEDsturnonsolid,indicatingthe1-minutetimeouthasbeensaved.

** TheLowActivitysettingisthedefaultandwillperformbestformostapplications.Rarely,iftheSensorisplacednearexternalnoisesourcessuchasheatingvents,airconditioningvents,orlightbulbs,itmayturnthelightsonwithoutoccupancyorkeepthelightsontoolongaftervacancy.Ifthisoccurs,changingthesensitivitytoMediumActivityorHighActivityshouldresolvetheproblem.

Timeout30 min15 min5 min

Auto-On ActivityAlwaysLow lightDisable

PULL

PULL

H Advanced Set-Up (Optional)

Flashing lens indicates “Low Battery”

Auto-OnEnabledLowLightDisabled

30 min15 min5 min

Activity Timeout

Change settings:• Hold buttons until LED blinks• Press button to choose setting• Hold buttons until LED turns solid

Top Related