Download - EnergyDistribution
www.hagerbr.com.au
Catalogue
1011
1
DisclaimerWhilst Hager B&R has made every effort to ensure that all information contained herein is correct at the time of printing, we reserve the right, to improve or modify product specifications as and when necessary, without prior notification.
1011
Catalogue
Energy distribution
All hager loadcentres have been developed with a strong aesthetic design integrating unique features as a result of feedback from homeowners, electrical contractors and house builders.With pre-configured and configurable variants available, choice comes as standard. So, whether you require a 48 pole, IP56 rated panelboard or a 24 pole, flush mounted loadcentre, there’s sure to be a hager enclosure to suit your application.
Loadcentres
D.1
Load
cent
res
Guide to the hager enclosure system D.2
GD surface mounted enclosures D.4
VM plastic enclosures D.5
GT plastic enclosures D.6
VT metal enclosures D.7
Golf plastic enclosures D.8
Vega plastic enclosures D.11
Vector plastic enclosures D.12
Automation enclosures D.13
Vega D accessories D.14
Package enclosures D.15
D.2
Guide to the hager enclosure system
Villas / TownhouseResidence
Free standingResidence
CommercialResidence
IP30
Mini Gamma Series
Page D.4
VM Series1-4 I
Page D.5
GT Series6-10 I
Page D.6
Vega Series18-72 I
Page D.11
IP40
Mini Gamma Series
Page D.4
Golf4-36 I flush/surface
Page D.8
Golf VC18-54 I - flush
Page D.10
IP41
Golf4-36 I flush/surface
Page D.8
Vega Series18-72 I
Page D.11
Vega D Series96 - 168 I
Page D.13
Vega Series18-72 I
Page D.11
IP42
Jyka 25018-72 pole
Page E.3
IP56
Jyka IP18-72 pole
Page E.5
IP65
Vector Series36-36 I
Page D.12
Vector Series36-36 I
Page D.12
IP66
Jyka IP18-72 pole
Page E.5
D.3
Load
cent
res
Commercial Office / Retail Industrial Complex
VT Series9-48 I - flush / surface
Page D.7
Jyka XL24-48 pole
Page E.2
VT Series9-48 I - flush / surface
Page D.7
Jyka XL24-48 pole
Page E.2
Golf4-36 I flush/surface
Page D.8
Golf VC18-54 I - flush
Page D.10
Vega Series18-72 I
Page D.11
Vega D Series96 - 168 I
Page D.13
Vega Series18-72 I
Page D.11
Vega D Series96 - 168 I
Page D.13
Jyka 25018-72 pole
Page E.3
Jyka 25018-72 pole
Page E.3
Jyka IP18-72 pole
Page E.5
Jyka IP18-72 pole
Page E.5
Vector Series36-36 I
Page D.12
Vector Series36-36 I
Page D.12
Jyka IP18-72 pole
Page E.5
Jyka IP18-72 pole
Page E.5
D.4 Subject to technical change.
A
B
GP106P
GD104T
VZ313
GP110T
GD surface mounted enclosures IP30
Technical information
Mini Gamma1 row enclosure for 2 to 10I surface mounted with a rigid
chassis housing, a 47mm DIN rail.
- facility for cover to be sealed.
- cover fixed by quarter turn screws
- IP40 with door installed
Options:- opaque or transparent doors- key lock- pole fillers - JP011- for technical details refer to
hager B&R
description width in I17.5mm
catref.
1 row, 2I 2 GD102T
1 row, 4I 4 GD104T
1 row, 6I 6 GD106T
1 row, 8I c/- earth / neutral links
8 GD108T
1 row, 10I c/- earth / neutral links
10 GD110T
Accessoriesopaque doors
suits GD102Tsuits GD104Tsuits GD106Tsuits GD108Tsuits GD110T
GP102P GP104P GP106P GP108P GP110P
transparent doors
suits GD102Tsuits GD104Tsuits GD106Tsuits GD108Tsuits GD110T
GP102T GP104T GP106T GP108T GP110T
locking kitspare keys
VZ313 VZ312
references enclosure size
width height depth
row A B CGD102T 1 55 160 75GD104T 1 110 180 75GD106T 1 148 180 75GD108T 1 182 180 75GD110T 1 218 180 75
D.5Subject to technical change.
Load
cent
res
VM04C
VM01C
42
153
A
B
VM surface mounted enclosures IP30Series VM1 row covers for 1 to 4Imonobloc chassis and cover of insulating material. Fixed DIN rail for devices of a shoulder measurement of 47mm.
Options:- Pole fillers JP011, PF6TR- facility to be sealed- colour: RAL9001- cover fixed by screws- for technical details refer to
hager B&R
description width in I17.5mm
catref.
1 row, 1I 1 VM01C
1 row, 2I 2 VM02C
1 row, 4I 3 - 4 VM04C
references enclosure sizerow width height depth
A B CVM01C 1 23 155 65VM02C 1 40 155 65VM04C 1 82 155 65
Technical information
D.6 Subject to technical change.
B
A
D
A
B
GT06A
GT09A
GT surface mounted enclosures IP41Series GT1 row enclosures for 6 to 18IThis enclosure range is designed with ample wiring room and a separate soft fireproof back for easy entry of cables
Options:- Pole fillers JP011, PF6TR- doors- colour: RAL9001- supplied with:
- links- forked busbar- circuit ID labels
- for technical details refer to hager B&R
description pole fillers width in I17.5mm
catref.
1 row, 6I x 2 6 GT06A
1 row, 9I x 3 9 GT09A
1 row, 12I x 4 12 GT12A
1 row, 18I x 6 18 GT18A
1 row, 10I x 5 10 GD10
doors to suit
suits GT06A - opaque doorsuits GT06A - transparent door
GP06P GP06T
suits GT09A - opaque doorsuits GT09A - transparent door
GP09P GP09T
suits GT12A - opaque doorsuits GT12A - transparent door
GP12P GP12T
suits GT18A - opaque doorsuits GT18A - transparent door
GP18P GP18T
references enclosure size
width height depth
row A B CGT06A 1 134 210 100GT09A 1 188 210 100GT12A 1 242 210 100GT18A 1 350 210 100GD10 1 250 140 65GD1OLN 1 250 140 65
Technical information
D.7Subject to technical change.
Load
cent
res
VT24F
VT24S
A
B
A
B
VT metal surface and flush mounted enclosures IP30
description pole fillers width in I17.5mm
catref.
1 row, surface mount1 row, surface mount1 row, surface mount2 rows, surface mount3 rows, surface mount4 rows, surface mount
x 3 x 4 x 6 x 8 x 12 x 16
91218243648
VT09S VT12S VT18S VT24S VT36S VT48S
1 row, flush mount1 row, flush mount1 row, flush mount2 rows, flush mount3 rows, flush mount4 rows, flush mount
x 3 x 4 x 6 x 8 x 12 x 16
91218243648
VT09F VT12F VT18F VT24F VT36F VT48F
doorsoptional extra - with easy knockout for additional lock
suits VT09S, VT09Fsuits VT12S, VT12Fsuits VT18S, VT18Fsuits VT24S, VT24Fsuits VT36S, VT36Fsuits VT48S, VT48F
VT041 VT042 VT043 VT044 VT045 VT046
lockoptional extra - Key lock suits all VT series enclosures LCLK
VT Surface references*Door = 22mm
enclosure sizes
row width height depthA B
VT09S 1 254 245 71VT12S 1 304 254 71VT18S 1 412 254 71VT24S 2 364 414 71VT36S 3 364 604 71VT48S 4 460 745 71
VT Flush references*Door = 22mm
enclosure sizeswall box escutcheon
row width height depth width heightVT09F 1 254 245 62 304 304VT12F 1 304 254 62 354 304VT18F 1 412 254 62 462 304VT24F 2 362 414 62 414 464VT36F 3 364 604 62 414 654VT48F 4 460 745 62 514 799
Series VT1 to 4 rows for 9 to 48Ithis range of enclosures has been designed for applications that require a robust construction.
Options:- Pole fillers JP011, PF6TR- doors- key locks- material: 1.0mm zinc anneal- colour: RAL9016- supplied with:
- links- forked busbar- circuit ID labels
- for technical details refer to hager B&R
Technical information
D.8 Subject to technical change.
VS12PT
VS04PT
VZ311
������� ��� ��
�
�
��
�
Golf surface mounted enclosures IP41IP41 surface mounted enclosures1 to 3 rows, 4 to 36 modules. Enclosures are of an insulating material coloured RAL9010.Fixed DIN rail for devices of a maximum shoulder measurement of 47mm. Distance between rails 125mm. Reversible door opening 1800.
Options:- Pole fillers JP011- keylock- colour: RAL9010- supplied with:
- links (63A rated)- forked busbar- circuit ID labels
- for technical details refer to hager B&R
description pole fillers width in I17.5mm
catref.
1 rowopaquetransparent
x 2 4 VS04PT VS04TT
1 rowopaquetransparent
x 2, x 1 8 VS08PT VS08TT
1 rowopaquetransparent
x 4, x 1 12 VS12PT VS12TT
2 rowopaquetransparent
x 8, x 2 24 VS24PT VS24TT
3 rowopaquetransparent
x 12, x 2 36 VS36PT VS36TT
keylock to suit all golf enclosures VZ311
dimension (mm) fixingA B D E F
VS04.. 1 row 4 130 180 84 90 140
VS08.. 1 row 8 200 180 84 120 140
VS12.. 1 row 12 275 225 95 205 160
VS24.. 2 rows 12 275 350 95 205 285
VS36.. 3 rows 12 275 500 95 205 410
Technical information
D.9Subject to technical change.
Load
cent
res
VF12PT
VF24PT
������� ��� ��
�
�
�
�
�
�Golf flush mounted enclosures IP41
description pole fillers width in I17.5mm
catref.
1 rowopaquetransparent
x 2 4 VF04PT VF04TT
1 rowopaquetransparent
x 2, x 1 8 VF08PT VF08TT
1 rowopaquetransparent
x 4, x 1 12 VF12PT VF12TT
2 rowopaquetransparent
x 8, x 2 24 VF24PT VF24TT
3 rowopaquetransparent
x 12, x 2 36 VF36PT VF36TT
keylock to suit all golf enclosures VZ311
earthed metal back plate to suit 12 pole VFBP12
earthed metal back plate to suit 24 pole VFBP24
IP41 flush mounted enclosures1 to 3 rows, 4 to 36 modules. Enclosures are of an insulating material coloured RAL9010.Fixed DIN rail for devices of a maximum shoulder measurement of 47mm. Distance between rails 125mm reversible door opening 1800.
Options:- Pole fillers JP011- keylock- IP 41- colour: RAL9010- supplied with:
- links (63A rated)- forked busbar- circuit ID labels
- for technical details refer to hager B&R
references dimension (mm) wall boxA B C D E F
VF04.. 1 row 4 162 220 73 90 122 177
VF08.. 1 row 8 250 230 67 94 209 189
VF12.. 1 row 12 322 265 70 97 281 224
VF24.. 2 rows 24 322 390 70 97 281 349
VF36.. 3 rows 36 322 535 70 97 281 491
Technical information
D.10 Subject to technical change.
VC18PT
VC36TT
VZ311
B
H H
B
E
150
D
T
Golf flush mounted enclosures IP41IP41 flush mounting enclosures1 to 3 rows, 18 to 54 modules. Enclosures are of an insulating material coloured RAL 9010.Adjustable DIN rail for devices of a maximum shoulder measurement of 47mm. Reversible door opening 180o
Supplied with:- links - busbar- circuit ID labels- pole fillers- for technical details refer to
hager B&R
description characteristics width in I17.5mm
door catref.
1 row x 7 x 1 18 opaquetransparent
VC18PT VC18TT
2 row x 14 x 2 36 opaquetransparent
VC36PT VC36TT
3 row x 21 x 3 54 opaquetransparent
VC54PT VC54TT
keylock to suit all golf enclosures VZ311
earthed metal back plate to suit 18 pole VCBP18
references dimensions (mm)cut-out sizes enclosure
row H B H B T D EVC18PT 18 1 295 390 335 430 70 74 13VC18TT 18 1 295 390 335 430 70 74 13VC36PT 36 2 445 390 485 430 70 74 13VC36TT 36 2 445 390 485 430 70 74 13VC54PT 54 3 595 390 635 430 70 74 13VC54TT 54 3 595 390 635 430 70 74 13
Technical information
D.11Subject to technical change.
Load
cent
res
135A
E
150150
H FG
VB36TT
VB18PT
Vega surface mounted enclosures IP41
description characteristics
width in I17.5mm
catref.
1 rowopaquetransparent
x 4, x 1 8 VB18PT VB18TT
2 rowopaquetransparent
x 8, x 2 36 VB36PT VB36TT
3 rowopaquetransparent
x 12, x 3 54 VB54PT VB54TT
4 rowopaquetransparent
x 16, x 4 72 VB72PT VB72TT
keylock for transparent or opaque doors
supplied with 2 keys VZ310
references dimension(mm)fixing
A B E F GVB18 18 370 300 300 236 32
VB36 36 370 450 300 386 32
VB54 54 370 600 300 536 32
VB72 54 370 750 300 686 32
IP40 surface mounted enclosureswith transparent or opaque doors. 1 to 4 rows, 18 to 72 modules. Enclosures are of an insulating material coloured RAL9010 white. The enclosures feature a removable chassis with DIN rails for ease of installation. Top and bottom cable entry plates are removable and interchangeable. The door is also reversible with an integral flush handle.
Options:- Pole fillers JP011- door lock- colour: RAL9010- supplied with:
- links- forked busbar- circuit ID labels
- for technical details refer to hager B&R
Technical information
D.12 Subject to technical change.
VE212H
F
151
73,5
59
47,5
A
H 150
E
Vector enclosures - IP65Surface mounted enclosures with transparent doors1 to 2 rows, 6 to 36 I- adjustable DIN rail for
shoulder measurement 47 and 63mm
- transparent hinged door- 2 lateral knockouts for cable
entry- supplied with:
- links- forked busbar- circuit ID labels
- pole fillers - JP010- premarked knock outs for
bushes or cable glands M20, M25, M32, M40 and M50; supplied with IP54 cable glands
- colour: RAL7035- sealable cover- reversible door- for technical details refer to
hager B&R
description width in I17.5mm
catref.
1 rowsupplied cable glands2xM20 + 2xM25 + 1xM32
4 + 2 VE106H
1 rowsupplied cable glands4xM20 + 2xM25 + 1xM32
8 + 2 VE110H
1 rowsupplied cable glands10xM20 + 2xM25 + 1xM32
12 VE112H
2 rowsupplied cable glands14xM20 + 4xM25 + 1xM32
24 VE212H
1 rowsupplied cable glands14xM20 + 4xM25 + 1xM32
18 VE118H
2 rowsupplied cable glands 8xM20 + 14xM25 + 1xM32
36 VE218H
keylock supplied with 2 keys VZ311
references enclosure sizes fixingrow A B E F
VE106H 6 1 165 190 108 158VE110H 10 1 237 210 180 173VE112H 12 1 310 302 230 155VE212H 24 2 310 427 230 280VE118H 18 1 418 302 338 155VE218H 36 2 418 452 338 305
Technical information
D.13
Load
cent
res
FD52D
FU72D
JKD144D
XLD90
3D solutions system - automation enclosuresVega D, Jyka D & XLD enclosures- The 3D System consists
of three enclosure ranges, Vega D, Jyka D and XLD. Each of the three ranges have been designed to complement the vast array of installations.
- The Vega D is available in either surface or flush mounting configurations, while the Jyka D, and XLD are surface mounted versions.
Modular Distribution Enclosures
- All 3D products conform to the various DIN and enclosure standard and are in modular rows of either 24 or 18 modules
- Vega D enclosures are configured from 4-7 rows of 24 modules (96 -168 ) They combine sheet metal and injected plastic so as to achieve a light yet strong enclosure.
- An additional internal insulation guarantees class II
isolation.- The Jyka D has 4-6 rows of
24 modules (96 -144 ) while the XLD has 5 rows of 18 modules (90 ).
- Colour RAL 9002.- for technical details refer to
hager B&R
description characteristics height catref.
Vega D Surfacewithout doorw. 550mm x d. 185mm
4 rows (96 )1x(5x25mm2 + 17x4mm2)
700mm FD42D
5 rows (120 )1 x (5x25mm2 +17x4mm2)1 x (6x25mm2 + 20x4mm2)
850mm FD52D
6rows (144 )3 x (6x25mm2 + 20x4mm2)
1000mm FD62D
7 rows (168 )3 x (6x25mm2 + 20x4mm2)
1150mm FD72D
Vega D Flushwithout doorw. 600mm x d. 152mmframe width 40mm
4 row (96 )1 x (5x25mm2 + 17x4mm2)
800mm FU42D
5 rows (120 )1 x (5x25mm2 + 17x4mm2)1 x (6x25mm2 + 20x4mm2)
950mm FU52D
6 rows (144 )3 x (6x25mm2 + 20x4mm2)
1150mm FU62D
7 rows (168 )3x (6x25mm2 + 20x4mm2)
1350mm FU72D
Jyka D Surfacewith doorw. 560mm x d. 166mm
4 rows (96 ) 750mm JKD96
6 rows (144 ) 970mm JKD144
XLD Surfacewith doorw.481mm x d. 130mm
5 rows (90 ) 765mm XLD90
D.14
FD52T FD52P
FZ497
UD22C2
UZ50A1
VZ405
KN00A
KN22N
UZ25V1
UZ25V2
UZ01V1
Vega D accessories
description characteristics catref.
Door options
Transparent doors reversible
for surface and flush
enclosures. Sheet metal,
powder coated.
c/- 3mm hardened glass
* inclusion of door provides
IP41
To suit FD42D or FU42D
To suit FD52D or FU52D
To suit FD62D or FU62D
To suit FD72D or FU72D
FD42T
FD52T
FD62T
FD72T
Plain door
reversible for surface and
flush enclosures. Sheet metal
and powder coated
* inclusion of door provides
IP41
To suit FD42D or FU42D
To suit FD52D or FU52D
To suit FD62D or FU62D
To suit FD72D or FU72D
FD42P
FD52P
FD62P
FD72P
Locks
To replace the standard lock lock, key No. 1242E FZ497
Circuit schedule holder FZ794
Terminals
Universal support to mount terminal blocks KN00A
Neutral terminal blocks
terminal block
terminal block
terminal block
terminal block
terminal block
terminal block
2x25mm2 + 8x4mm2 terminal
3x25mm2 + 11x4mm2 terminal
4x25mm2 + 14x4mm2 terminal
5x25mm2 + 17x4mm2 terminal
6x25mm2 + 20x4mm2 terminal
bridging clip x 10
KN10N
KN14N
KN18N
KN22N
KN26N
KN99N
Earth terminal blocks
terminal block
terminal block
terminal block
terminal block
terminal block
terminal block
2x25mm2 + 8x4mm2 terminal
3x25mm2 + 11x4mm2 terminal
4x25mm2 + 14x4mm2 terminal
5x25mm2 + 17x4mm2 terminal
6x25mm2 + 20x4mm2 terminal
bridging clip x 10
KN10E
KN14E
KN18E
KN22E
KN26E
KN99E
Phase terminal blocks
terminal block
terminal block
terminal block
terminal block
terminal block
terminal block
2x25mm2 + 8x4mm2 terminal
3x25mm2 + 11x4mm2 terminal
4x25mm2 + 14x4mm2 terminal
5x25mm2 + 17x4mm2 terminal
6x25mm2 + 20x4mm2 terminal
bridging clip x 10
KN10P
KN14P
KN18P
KN22P
KN26P
KN99P
Gear tray module
(not suitable for flush
enclosures)
415mm x 235mm UD22C2
Cable management accessories
Cable management retainer
* Not suitable for flush
enclosures
(x20) large UZ25V1
Cable management retainer (x20) small UZ25V2
Retainer support / exten arms (x20) UZ01V1
Support arms
for DIN rail / trunking (x2) UZ50A1
DIN rail to suit Vega D UZ38D1
Mounting anchors (x4) VZ405
for plaster walls to suit flush enclosures
D.15
Load
cent
res
JT202
Package enclosures
Descriptionfor applications where an RCCB is being added to an existing installation or where other DIN type fixing facilities are not available.
To overcome this problem we present a range of RCCBs complete with DIN rail enclosures and where necessary an integral neutral link for up to three circuits.
This range has been designed for ease of installation and ease of ordering.
description residualcurrentIrn
currentrating (A)
width in I17.5mm
cat.
ref
2 pole RCCB complete with enclosure and 2 holes neutral link
30mA 40A 2 JT201
2 pole RCCB complete with enclosure
30mA 40A 2 JT202
2 pole RCCB complete with enclosure and 3 holes neutral link
30mA 63A 2 JT203
4 pole RCCB complete with enclosure
30mA 40A 4 JT204
4 pole RCCB complete with enclosure and 3 holes neutral link
30mA 40A 4 JT205
The Jyka series of panelboards are designed for ease of installation, maximising internal space and presenting commercially required aesthetics. Regardless of specifications, the XL, Series 2, and IP ranges meet and surpass the growing demands of the industry.
Energy distributionPanelboards
E.1
Pan
elb
oard
s
Jyka XL series panelboards E.2
Jyka 250 series 2 panelboards E.3
Jyka IP series panelboards E.5
Jyka SS series panelboards E.7
E.2 Subject to technical change.
JK48XL
W
DH
Jyka XL series panelboardsThe Jyka XL series of panelboards are the recommended solution when both installation and economic constraints arise- 18 poles DIN standard- type tested busbar- neutral and earthbar- colour: RAL9002- 1.6mm construction- removable gland plates- AS/NZS3439.1
- lockable door- circuit schedule card- separate escutcheon & door- Australian made- for technical details refer to
hager B&R
NEW IMPROVED CHASSIS- extra moulding on chassis
shoulders provides a positive alignment point for the breakers and the escutcheon cutout.
- push the breaker into the chassis until it stops then tighten to guarantee correct alignment
description catref.
24 way panelboard JK24XL
36 way panelboard JK36XL
48 way panelboard JK48XL
incoming devices
loadbreak switch JK16S/C
160A 3 pole DIN rail mounted loadbreak switch & connection kit
loadbreak switch JK20S
200A 3 pole DIN rail mounted loadbreak switch & connection kit
accessories
extension box
complete with 18 modules of DIN space JK00XL
flush surround
to suit JK24XLto suit JK36XLto suit JK48XL
JKFL1/XL JKFL2/XL JKFL3/XL
polefillers
6 pole PF6TR
chassis finger cap (10 pack) JK90B
chassis shroud caps (2 pack) JK91B
dimensionscat. ref. height H width W depth DJK24XL 658 481 130JK36XL 765 481 130JK48XL 872 481 130
extension boxJK00XL 350 481 130
Technical information
E.3Subject to technical change.
Pan
elb
oard
s
JKS18P
JKS36P
H
W
D
Jyka 250 series 2 panelboardsDesigned for ease of installation and maximising internal space while presenting commercially required aesthetics, the Jyka 250 series of panelboards is recommended for internal commercial applications.- type tested busbar- neutral and earthbar- colour: RAL9002- 1.6mm construction- removable gland plates- AS/NZS3439.1
- separate hinged escutcheon and door
- removable mounting pan- lockable door- reversible door- circuit schedule card- cable tie anchors- Australian made- custom built options- custom lock options- IP42- for technical details refer to
hager B&R
NEW IMPROVED CHASSIS- extra moulding on chassis
shoulders provides a positive alignment point for the breakers and the escutcheon cutout.
- push the breaker into the chassis until it stops then tighten to guarantee correct alignment
description catref.
18 way panelboard24 way panelboard30 way panelboard36 way panelboard42 way panelboard48 way panelboard60 way panelboard72 way panelboard
JKS18P JKS24P JKS30P JKS36P JKS42P JKS48P JKS60P JKS72P
incoming devices
connection kits - kits only, excluding switchgear
for 250A MCCB in the top centre position c/- cable zone enclosure JK16K
for 80/100A ‘SB’ switches (SB380/SB399) in the top centre position JK11S
for 80/100A MCB in the lower left & right position, includes cable & hardware
JK12S
for 80/100A MCB’s in the top centre includes busbar & hardware JK15S
connection kits - including switchgear160A 3 pole loadbreak switch & connection kit 200A 3 pole loadbreak switch & connection kit 225A 3 pole loadbreak switch & connection kit 250A 3 pole loadbreak switch & connection kit
JK16S/C JK20S JKS22S/B JKS25S
outgoing devices
connection kit - kit only, excluding switchgearfor 160A 3 pole MCCB in the lower position, includes cable & hardware JK15K
dimensions
cat. ref. height H width W depth D
JKS18P 750 560 166
JKS24P 750 560 166
JKS30P 860 560 166
JKS36P 860 560 166
JKS42P 970 560 166
JKS48P 970 560 166
JKS60P 1200 560 166
JKS72P 1200 560 166
extension box
JKS00E 350 560 166
Technical information
E.4
PF6TR
LT052
Jyka 250 series 2 panelboards
description catref.
accessories for Jyka 250 series
pole fi llers
6 pole PF6TR
chassis caps & shrouds
chassis finger cap, 10 pack
chassis shroud caps, 2 pack
JK90B
JK91B
extension box
empty enclosure to house mounting kits JKS01E, JKS02E & JKS03E
JKS00E
joining plateFor joining 2 Jyka panels together JK/GP
extension box mounting kits
to suit 18 modules of DIN
to suit LT052 fuse carrier - 160A
to suit LT150 fuse carrier - 250A
cable zone top mount
to suit 36 modules of DIN
JKS01E
JKS02E
JKS05E
JKS06E
JKS07E
flush surrounds
to suit JKS18P and JKS24P
to suit JKS30P and JKS36P
to suit JKS42P and JKS48P
to suit JKS60P and JKS72P
JKSFL1
JKSFL2
JKSFL3
JKSFL4
fuse carriers
fuse carrier to suit size 00/160A DIN blade fuses
fuse carrier to suit size 1/250A DIN blade fuses
fuse carrier to suit size 2/400A DIN blade fuses
cable clamps to suit LT052 (6-70mm2)
cable clamp to suit LT150 (70-150mm2)
cable clamps to suit LT250 (120 - 240mm2)
LT052
LT150
LT250
LZ051
LZ151
LZ152
DIN blade fuses
available on request
chassis
18 way double-ended
24 way double-ended
30 way double-ended
36 way double-ended
42 way double-ended
48 way double-ended
60 way double-ended
72 way double-ended
JK18C
JK24C
JK30C
JK36C
JK42C
JK48C
JK60C
JK72C
18 way single-ended
24 way single-ended
36 way single-ended
48 way single-ended
JK18C1
JK24C1
JK36C1
JK48C1
chassis rating
250A
250A
rated short time
18kA 0.2sec
10kA 1.0sec
peak withstand current
36kA17kA
E.5Subject to technical change.
Pan
elb
oard
s
JK24IP
�
�
�
Jyka IP series panelboardsDesigned and constructed for use in locations that require the highest levels of protection from the surrounding environment.- type tested busbar- neutral and earthbar- colour: RAL9002- 1.6mm construction- removable gland plates- IP56 (IP66 available upon
request)
- AS/NZS3439.1- lockable door- separate hinged escutcheon
and door- circuit schedule card- cable tie anchors- Australian made- custom built options- custom lock options
NEW IMPROVED CHASSIS- extra moulding on chassis
shoulders provides a positive alignment point for the breakers and the escutcheon cutout.
- push the breaker into the chassis until it stops then tighten to guarantee correct alignment
- for technical details refer to hager B&R
description catref.
$ex-GST
$incl-GST
18 way panelboard24 way panelboard30 way panelboard36 way panelboard42 way panelboard48 way panelboard60 way panelboard72 way panelboard
JK18IP JK24IP JK30IP JK36IP JK42IP JK48IP JK60IP JK72IP
incoming devices
connection kits - kits only, excluding switchgear
for 250A MCCB in the top centre position for 80/100A ‘SB’ switches in the top centre position for SB380 + SB390 in the lower position, includes cable & hardwarefor 80/100A MCB’s in the top centre includes busbar & hardware
JK17K JK11S JK12S JK15S
connection kits - including switchgear160A 3 pole loadbreak switch & connection kit 200A 3 pole loadbreak switch & connection kit 225A 3 pole loadbreak switch & connection kit 250A 3 pole loadbreak switch & connection kit
JK16S/C JK20S JKS22S/B JKS25S
outgoing devices
connection kit - kit only, excluding switchgear
for 160A 3 pole MCCB in the lower position, includes cable & hardware JK15K
dimensions
cat. ref. height width depth
JK18IP 750 600 250
JK24IP 750 600 250
JK30IP 860 600 250
JK36IP 860 600 250
JK42IP 970 600 250
JK48IP 970 600 250
JK60IP 1200 600 250
JK72IP 1200 600 250
extension box
JKE/IP 350 600 250
JK2IE/IP 350 600 250
Technical information
E.6
LT052
PF6TR
Jyka IP series panelboards
description catref.
accessories for Jyka IP series
pole fi llers
6 pole PF6TR
chassis caps & shrouds
chassis finger cap, 10 pack
chassis shroud caps, 2 pack
JK90B
JK91B
extension box
complete with blank escutcheon & mounting pan
(refer mounting kits)
complete with 21 modules of DIN space
JKE/IP
JK21E/IP
mounting kits
DIN rail kit 4.5 modules JK16A
flush surrounds
to suit JK18IP and JK24IP
to suit JK30IP and JK36IP
to suit JK42IP and JK48IP
to suit JK60IP and JK72IP
JKFL1/IP
JKFL2/IP
JKFL3/IP
JKFL4/IP
fuse carriers
fuse carrier to suit size 00/160A DIN blade fuses
fuse carrier to suit size 1/250A DIN blade fuses
fuse carrier to suit size 2/400A DIN blade fuses
cable clamps to suit LT052 (6-70mm2)
cable clamp to suit LT150 (70-150mm2)
cable clamps to suit LT250 (120 - 240mm2)
LT052
LT150
LT250
LZ051
LZ151
LZ152
DIN blade fuses
available on request
chassis
18 way double-ended
24 way double-ended
30 way double-ended
36 way double-ended
42 way double-ended
48 way double-ended
60 way double-ended
72 way double-ended
JK18C
JK24C
JK30C
JK36C
JK42C
JK48C
JK60C
JK72C
18 way single-ended
24 way single-ended
36 way single-ended
48 way single-ended
JK18C1
JK24C1
JK36C1
JK48C1
chassis rating
250A
250A
rated short time
18kA 0.2sec
10kA 1.0sec
withstand current
36kA
17kA
E.7Subject to technical change.
Pan
elb
oard
s
JK24IP
�
�
�
Jyka SS series panelboardsDesigned & constructed for use in corrosive environments or improved aesthetics- enclosure body from 1.5mm
316 grade stainless steel, unpainted N4 finish
- internals from 1.6mm zinc-anneal
- type tested 250A chassis- neutral & earth bars- IP66 rated- hinged & painted internal
escutcheon (zinc anneal)
- schedule card & holder- stainless steel top & bottom
gland plates- turnbuckle style door locks- contact us for custom
requirements
NEW IMPROVED CHASSIS- extra moulding on chassis
shoulders provides a positive alignment point for the breakers and the escutcheon cutout.
- push the breaker into the chassis until it stops then tighten to guarantee correct alignment
- for technical details refer to hager B&R
description catref.
24 way stainless steel panelboard36 way stainless steel panelboard48 way stainless steel panelboard72 way stainless steel panelboard
JK24IP/S JK36IP/S JK48IP/S JK72IP/S
incoming devices
connection kits - kits only, excluding switchgear
for 250A MCCB in the top centre position for 80/100A ‘SB’ switches in the top centre position for SB380 + SB390 in the lower position, includes cable & hardwarefor 80/100A MCB’s in the top centre includes busbar & hardware
JK17K JK11S JK12S JK15S
connection kits - including switchgear160A 3 pole loadbreak switch & connection kit 200A 3 pole loadbreak switch & connection kit 225A 3 pole loadbreak switch & connection kit 250A 3 pole loadbreak switch & connection kit
JK16S/C JK20S JKS22S/B JKS25S
outgoing devices
connection kit - kit only, excluding switchgear
for 160A 3 pole MCCB in the lower position, includes cable & hardware JK15K
dimensions cat. ref. height width depthJK18IP 750 600 250JK24IP 750 600 250JK30IP 860 600 250JK36IP 860 600 250JK42IP 970 600 250JK48IP 970 600 250JK60IP 1200 600 250JK72IP 1200 600 250
Technical information
E.8
This section includes moulded case circuit breakers and load break switches which are utilised to ensure the switching, protection and distribution of low voltage installations.
Energy distributionMain incomers
F.1
Mai
nin
com
ers
Moulded case circuit breakers F.2
Technical information for circuit breakers F.9
Prospective fault current F.10
Load break switches F.11
Load break switches - characteristics F.13
F.2
HH147
25,4
25,4
76
25,4
79041
7590
70
54
HY121
Moulded case circuit breakers
description currentrating (A)
poles1
poles3
frame: H125H- 25kA
MCCBMCCBMCCBMCCBMCCBMCCBMCCBMCCBMCCBMCCB
1620253240506380
100125
HH101 HH102 HH103 HH104 HH105 HH106 HH107 HH108 HH109 HH110
-- HH143- HH145- HH147 HH148 HH149 HH150
frame: H160H - 25kA
MCCB 160 - HH151
frame: H125N - 40kA
MCCBMCCBMCCBMCCBMCCBMCCB
25406380
100125
------
HN143 HN145 HN147 HN148 HN149 HN150
frame: H125E - 70kA
MCCBMCCBMCCBMCCBMCCBMCCB
25406380
100125
------
HE143 HE145 HE147 HE148 HE149 HE150
h125 and h160xsdescriptionHager MCCB’s offer contractors, switchboard builders and OEM’s, a wide choice of options.
The range is available in 1, and 3 poles with breaking capacities including 25kA, 40kA and 70kA.
frame Icu Un Ui
h125h 25kA 240/415V~ 500Vh160h 25kA 240/415V~ 500Vh125n 40kA 240/415V~ 500Vh125e 70kA 240/415V~ 500V
technical data- Connection capacity
h125: 95mm2 - rigidh125: 50mm2 - flexibleh160xs: 95mm2 - rigidh160xs: 75mm2 - flexible
approvals and tests- AS3947-2- IEC60947-2thermal setting 0.8 - 1 x In
magnetic setting fixed at 10-20xIn
description characteristics catref.
shunt trip 24V - 60V~ HX101E
shunt trip 110V - 240V~ HX104E
shunt trip 380V - 600V~ HX105E
undervoltage release 48V - 60V~ HX111E
undervoltage release 208V - 240V~ HX114E
undervoltage release 380V - 500V~ HX115E
auxiliary switch 1 NO/NC, 230V/6A HX121
auxiliary switch 2 NO/NC, 230V/6A HX122
aux / alarm switch 1 NO/NC + 1NO/NC 230V/6A HX123
rotary handle c/w: 200mm shaft HX131A
locking kit HX139
interphase barrier HY119
terminal cover HY121
accessories and auxiliaries
Mai
nin
com
ers
F.3
HN204
931
104,8
871
35 35
35
96
110
87
001
Moulded case circuit breakers
description currentrating (A)
poles3
frame :h250n - 40kAelectromechanical trip unit 160 HN254
electromechanical trip unit 200 HN203
electromechanical trip unit 250 HN204
electronic trip unit 250 HN205
frame :h250e - 70kAelectronic trip unit 250 HE205
description characteristics cat.ref
shunt trip 24V - 60V~ HX101E
shunt trip 110V - 240V~ HX104E
shunt trip 380V - 600V~ HX105E
undervoltage release 48V - 60V~ HX111E
undervoltage release 208V - 240V~ HX114E
undervoltage release 380V - 500V~ HX115E
auxiliary switch 1 NO/NC, 230V/6A HX121
auxiliary switch 2 NO/NC, 230V/6A HX122
aux / alarm switch 1 NO/NC + 1NO/NC HX223E
230V/6A
rotary handle c/w: 200mm shaft HX231
rotary handle mounted on device HX230
locking kit HX239
interphase barrier HY219
terminal cover HY221
cable connection terminals 25 - 185mm2 HY201
busbar extensions HY212
h250descriptionHager MCCB’s offer contractors, switchboard builders and OEM’s, a wide choice of options.
The range, h250 isavailable in 3 pole with breaking capacities including 40kA and 70kA.
frame Icu Un Ui
h250n 40kA 400V~ 690Vh250e 70kA 400V~ 690V
technical dataapprovals and tests- AS3947-2- IEC60947-2- Connection capacity: 185mm2 - rigid: 185mm2 - flexible
- electromechanical trip unit thermal setting 0.8 - 1.0 x In magnetic setting 5 - 10 x In
- electronic trip unitthermal setting 0.4 - 1 x Inmagnetic setting 2 - 14 x Indelay setting 0 - 300ms
accessories and auxiliaries
F.4
HN303E
5,412
139,2
2,752
43,7 43,7
43,7
100
136
001
Moulded case circuit breakers
description currentrating(A)
poles3
frame :h400n - 50kAelectromechanical trip unit 320 HN302E
electromechanical trip unit 400 HN303E
electronic trip unit 400 HN305E
frame :h400e - 70kAelectronic trip unit 400 HE305E
description characteristics cat.ref
shunt trip 24V - 60V~ HX101E
shunt trip 110V - 240V~ HX104E
shunt trip 380V 600V~ HX105E
undervoltage release 48V - 60V~ HX111E
undervoltage release 208V - 240V~ HX114E
undervoltage release 380V - 500V~ HX115E
auxiliary switch 1 NO/NC, 230V/6A HX121
auxiliary switch 2 NO/NC, 230V/6A HX122
aux / alarm switch 1 NO/NC + 1NO/NC
230V/6A
HX223E
rotary handle mounted on device HX330E
rotary handle c/w: 200mm shaft HX331E
locking kit HX339E
interphase barrier HY719
terminal cover HY321E
cable connection terminals 35 - 240mm2 HY301E
cable connection twin terminals 35 - 240mm2 HY303E
bus bar extensions spreaders HY312E
technical dataapprovals and tests- AS3947-2- IEC60947-2- Connection capacity: 240mm2 - rigid: 195mm2 - flexible
- electromechanical trip unit thermal setting 0.8 - 1.0 x In magnetic setting 5 - 10 x In
- electronic trip unitthermal setting 0.4 - 1 x Inmagnetic setting 2 - 14 x Indelay setting 0 - 300ms
accessories and auxiliaries
h400xsdescriptionHager MCCB’s offer contractors, switchboard builders and OEM’s, a wide choice of options.
The range, h400xs isavailable in 3 pole with breaking capacities including 50kA and 70kA.
frame Icu Un Ui
h400n 50kA 400V~ 750Vh400e 70kA 400V~ 750V
Mai
nin
com
ers
F.5
HN353E
5,412
139,2
2752
43,7 43,7
43,7
100
136
001
Moulded case circuit breakers
h630xsdescriptionHager MCCB’s offer contractors, switchboard builders and OEM’s, a wide choice of options.
The range, h630xs isavailable in 3 pole with breaking capacities including 50kA and 70kA.
frame Icu Un Ui
h630n 50kA 400V~ 750Vh630e 70kA 400V~ 750V
description currentrating (A)
poles3
frame :h630n - 50kAelectromechanical trip unit 500 HN352E
electromechanical trip unit 630 HN353E
electronic trip unit 630 HN355E
frame :h630e - 70kAelectromechanical trip unit 630 HE355E
description characteristics cat.ref
shunt trip 24V - 60V~ HX101E
shunt trip 110V - 240V~ HX104E
shunt trip 380V 600V~ HX105E
undervoltage release 48V - 60V~ HX111E
undervoltage release 208V - 240V~ HX114E
undervoltage release 380V - 500V~ HX115E
auxiliary switch 1 NO/NC, 230V/6A HX121
auxiliary switch 2 NO/NC, 230V/6A HX122
aux / alarm switch 1 NO/NC + 1NO/NC
230V/6A
HX223E
rotary handle mounted on device HX330E
rotary handle c/w: 200mm shaft HX331E
locking kit HX339E
interphase barrier HY719
terminal cover HY321E
cable connection terminals 35 - 240mm2 HY301E
cable connection twin terminals 35 - 240mm2 HY303E
bus bar extensions spreaders HY312E
technical dataapprovals and tests- AS3947-2- IEC60947-2- Connection capacity: 240mm2 - rigid: 195mm2 - flexible
- electromechanical trip unit thermal setting 0.8 - 1.0 x In magnetic setting 5 - 10 x In
- electronic trip unitthermal setting 0.4 - 1 x Inmagnetic setting 2 - 14 x Indelay setting 0 - 300ms
accessories and auxiliaries
F.6
HN806
70
372
242
209,6
4,604
70
70
Moulded case circuit breakers
h800xsdescriptionHager MCCB’s offer contractors, switchboard builders and OEM’s, a wide choice of options.
The h800 is available in 3 pole with breaking capacities including 50KA.
frame Icu Un Ui
h800n 50kA 400V~ 750V
technical dataapprovals and tests- AS3947-2- IEC60947-2- Connection capacity: 240mm2 - rigid: 195mm2 - flexible
- electronic trip unitthermal setting 0.5 - 1 x Inmagnetic setting 2 - 8 x Indelay setting 0 - 300ms
description currentrating (A)
poles3
frame :h800n - 50kAelectronic trip unit 800 HN806
description characteristics cat.ref
auxiliary switch 2 x N/O -2 x N/C
230V/6A~
HX821
alarm/auxiliary switch 1 x N/O-N/C - 1 x
NO-N/C 230V/6A~
HX822
shunt trip 110V - 440V~ HX804
undervoltage release 208V - 240V~ HX814
undervoltage release 380V - 500V~ HX815
rotary handle
200mm shaft
handle c/w: HX831
rotary handle mounted on device HX830
interphase barriers HY819
terminal kit 2 X 185 - 240mm2 HY801
padlockable handle kit HY850
accessories and auxiliaries
Mai
nin
com
ers
F.7
HN903
373
209,6
4,604
70
7070
Moulded case circuit breakers
h1250xsdescriptionHager MCCB’s offer contractors, switchboard builders and OEM’s, a wide choice of options.
The range, h1250xs isavailable in 3 pole with breaking capacities including 50kA and 70kA.
frame Icu Un Ui
h1250n 50kA 400V~ 750Vh1250e 70kA 400V~ 750V
technical dataapprovals and tests- AS3947-2- IEC60947-2- Connection capacity: 240mm2 - rigid: 195mm2 - flexible
- electronic trip unitthermal setting 0.5 - 1 x Inmagnetic setting 2 - 8 x Indelay setting 0 - 300ms
description currentrating (A)
poles3
frame :h1250n - 50kAelectronic trip unit 1250 HN903
frame :h1250e - 70kAelectronic trip unit 1250 HE903
description characteristics cat.ref
auxiliary switch 2 pole 2 x N/O-2 x N/C
230V/6A
HX921
alarm/auxiliary switch 1 x N/O-N/C - 1 x
NO-N/C 230V/6A
HX922
shunt trip 110V - 240V~ HX904
shunt trip 380V - 440V~ HX905
undervoltage release 208V - 240V~ HX914
undervoltage release 380V - 500V~ HX915
rotary handle mounted on device HX930
rotary handle c/w 200mm shaft HX931
interphase barriers HY919
busbar extension HY910
accessories and auxiliaries
F.8
HN904
373
209,6
4,604
70
7070
Moulded case circuit breakers
h1600xsdescriptionHager MCCB’s offer contractors, switchboard builders and OEM’s, a wide choice of options.
The range, h1600xs isavailable in 3 pole with breaking capacities including 50kA.
frame Icu Un Ui
h1600n 50kA 400V~ 750V
technical dataapprovals and tests- AS3947-2- IEC60947-2- Connection capacitysupplied with rear connection bars
- electronic trip unitthermal setting 0.5 - 1 x Inmagnetic setting 2 - 8 x Indelay setting 0 - 300ms
description currentrating (A)
poles3
frame :h1600n - 50kAelectronic trip unit 1600 HN904
description characteristics cat.ref
auxiliary switch 2 pole 2 x N/O-2 x N/C
230V/6A
HX921
alarm/auxiliary switch 1 x N/O-N/C - 1 x
NO-N/C
230V/6A
HX922
shunt trip 110V - 240V~ HX904
shunt trip 380V - 440V~ HX905
undervoltage release 208V - 240V~ HX914
undervoltage release 380V - 500V~ HX915
rotary handle mounted on device HX930
rotary handle c/w 200mm shaft HX931
interphase barriers HY919
busbar extension HY910
accessories and auxiliaries
F.9Subject to technical changes
Mai
nin
com
ers
Technical information for circuit breakers
fault loop impedanceWith the introduction of AS/NZS 3000:2007 there are new wiring rules for electrical contractors and electrical consultants to consider when designing an electrical installation.
This guide is only concerned with one new area, fault loop impedance, and it’s affect on the choice of conductor and circuit breaker for a given circuit. Voltage drop and overcurrent requirements should also be given consideration.
An earth fault situation is caused when an active conductor comes into contact with an earthed conductor - fault current then flows. short-circuit is formed and fault current flows. Contractors and consultants must make sure that the conductors in a circuit will allow sufficient energy to flow to cause the circuit breaker to trip in the required time (disconnection time for 230V supply is 0.4s for socket–outlets up to 63A, or handheld Class 1 equipment intended for manual movement during use. 5 seconds for other circuits including submains and final sub circuits supplying fixed or stationary equipment (clause 1.5.5.3)
To make sure that this fault current is large enough to trip a circuit breaker in the required time the fault loop impedance (Zs) must be below a certain value If Zs is too large then the circuit breaker may take too long to trip(> 0.4s) or may not trip at all.
Circuit length – Circuit impedance increases with the length of a circuit. Cross -sectional area of cable – The smaller the cross -sectional area of a cable, the higher it’s impedance per meter will be.Thermal and magnetic settings of a circuit breaker – hager circuit breakers have both rated current and magnetic characteristics.
The higher the rated current and magnetic settings, the more energy is required to trip the circuit breaker in the required time (< 0.4 s ). So a circuit breaker with a magnetic setting of 14 x In will require more energy to trip it (in the required time) than a circuit breaker with a magnetic setting of 7.5 x In.
If more energy is required to flow, then a larger cross-sectional area cable may be needed. If this is not possible then installing a hager RCD will provide a simple and economical solution.
So circuit length, cross sectional area of the cable and circuit breaker settings all need to be taken into account to ensure correct function of a circuit.
The tables below are a guide to the maximum circuit length and maximum circuit impedance for a given hager circuit breaker. Using these tables will help ensure that the disconnection time for a 230V a.c. supply is met according to AS/NZS 3000:2000.
TABLE 2 Maximum circuit length (MCL) and maximum circuit impedance (Zs) for hager MCBs (NSxxx range, NTxxxC range, NCNxxxA range, NMxxxT, NDNxxxA range).
Where: MCL = Maximum circuit lengthZs = Maximum circuit impedanceAbove table based on supply of voltage of 230V / 400V ( AS/NZS 3000: 2000 Amdt1)
conductor sizeProtective
devicerating
a
hager MCB range
Active Earth C- Curve MCBs D Curve MCBs Max Zs ( )for all
ranges -5 secsMCL (m)
Max Zs ( )0.4 secs MCL (m)
Max Zs ( )0.4 secsmm2 mm2
1 1 1 545 30.67 - - 57.50
1 1 2 273 15.33 - - 28.75
1 1 3 182 10.22 - - 19.17
1 1 4 136 7.67 - - 14.38
1 1 6 91 5.11 55 3.07 9.58
1 1 10 55 3.07 33 1.84 5.75
1.5 1.5 10 82 3.07 49 1.84 5.75
1.5 1.5 16 51 1.92 31 1.15 3.59
2.5 2.5 16 85 1.92 51 1.15 3.59
2.5 2.5 20 68 1.53 41 0.92 2.88
4 2.5 25 67 1.23 40 0.74 2.30
4 2.5 32 52 0.96 31 0.58 1.80
6 2.5 32 60 0.96 36 0.58 1.80
6 2.5 40 48 0.77 29 0.46 1.44
10 4 40 78 0.77 47 0.46 1.44
10 4 50 62 0.61 37 0.37 1.15
16 6 63 76 0.49 45 0.29 0.91
16 6 80 59 0.38 36 0.23 0.72
25 6 80 66 0.38 40 0.23 0.72
25 6 100 53 0.31 32 0.18 0.58
35 10 100 85 0.31 51 0.18 0.58
35 10 125 68 0.25 41 0.15 0.46
50 16 125 106 0.25 63 0.15 0.46
F.10 Subject to technical changes
FIGURE : 10
FIGURE : 11
Prospective fault current
Calculation of Prospective Short Circuit CurrentSeveral excellent proprietary computer programs are now available for calculating the prospective fault level at any point in the installation. They are also able to select the correct size and type of cable and match this with the correct circuit protective device.
Estimation of Prospective Fault CurrentActually calculating prospective short-circuit current is not in itself difficult but it does require basic data which is not always available to the electrical installation designer.It is therefore usual to use a simple chart as shown in Fig 10 to estimate the prospective short circuit current. This type of chart always gives a prospective fault level greater than that which would have been arrived at by calculation using accurate basic data. Therefore it is safe to use but sometimes may result in an over engineered system.
Example1 Project 40m of cable length across on to the 240mm2 cable
curve. From this point project down onto the 28kA curve. From this point projecting across we note that the prospective fault level at the panelboard is 24kA.
2 Project 60m of cable length across onto the 70mm2 cable curve. From this point project down on to the 24kA curve. From this point projecting across we see that the prospective fault level at the MCB distribution board is 10kA.
FIGURE : 12
The relationship between probable short-circuit current and service short-circuit breaking capacity is explained. The probable short circuit is the type of short circuit which is most likely to occur; this is nearly always at the extremity of the protected cable and more often than not a single phase or earth fault. Fig 11 shows a typical 3 phase 4 wire 400V system fed by a 1000 kVA transformer. The transformer is adjacent to the main switchboard so the prospective short-circuit current (PSCC*) on the main switchboard busbars is estimated as 30kA. The probable short-circuit current on the panelboard feeder circuit is estimated as 24kA, if it were a 3 phase symmetrical fault, or 12kA for a phase to neutral fault, which in fact would be the most likely type of fault. (Note: when estimating a phase to neutral prospective short-circuit current, the length of conductor is doubled.)
Therefore for this application the main switchboard incoming circuit breaker (A) should have an Ics 30kA and an Icu 30kA.
The panelboard feeder circuit breaker (B) should have an Icu 30kA and an Ics 24kA.
*Prospective Short Circuit Current (PSCC).
Mai
nin
com
ers
F.11
HA302
HA307
HA354
Load break switches
descriptionthe HA series are a multi-pole load disconnector switch with manual operation. They enable making and breaking on load and safety isolation of any low voltage installation.
technical data- visualised breaking- double breaking per
phase- DIN rail mounting- 3 or 4 pole- padlockable handle- auxiliary contacts
- rotary handlescomplete withextension shaft
- complying withIEC60947-3
description width in I17.5 mm
characteristics modulemm
cat.
ref
3 pole isolator690V~
2 In 40A 36 HA302
3 In 63A 54 HA303
3 pole isolator400V~
6 In 80A 108 HA304
6 In 100A 108 HA305
6 In 125A 108 HA306
8.5 In 160A 142 HA307
8.5 In 200A 142 HA308
8.5 In 250A 142 HA309M
3 pole isolator400V~
- In 250A - HA354
- In 400A - HA356
- In 630A - HA358
- In 800A - HA360
- In 1250A - HA362
- In 1600A - HA364
4 pole isolator400V~
6 In 125A 108 HA406
8.5 In 200A 142 HA408
F.12
HA457
HZC106
HZC003
HZC002
Load break switches
descriptionthe HA series are a multi-pole load disconnector switch with manual operation. They enable making and breaking on load and safety isolation of any low voltage installation.
technical data- visualised breaking- double breaking per
phase- DIN rail mounting- 3 or 4 pole- padlockable handle- auxiliary contacts
- rotary handles complete with extension
shaft- complying with
IEC60947-3
description width in I17.5 mm
characteristicsbox qty
cat.ref.
4 pole isolator400V~
- In 400A - AC23 HA457
- In 630A - AC23 HA458
accessoriesrotary handles
black IP65 to suit HA360/HA362/HA364 HZC003
black IP55 to suit HA354/HA356/HA358 HZC002
black IP55 to suit HA304/HA305/HA306/HA307/HA308 HZC001
extension shafts320mm to suit HA360/HA362/HA364 HZC106
320mm to suit HA354/HA356/HA358 HZC102
200mm to suit HA304/HA305/HA306/HA307/HA308 HZC103
auxiliary contacts
In 5A - 250V~suitable for HA302/HA303
HZ021
In 5A -250V~suitable for HA304/HA305/HA306/HA307/HA308
HZ022
In 16A - 250V~suitable for HA354/HA356/HA358/HA360/HA362/HA364
HZ023
terminal shrouds
1 to suit HA354/switch-line or load side
HZC203
1 to suit HA356/HA358/switch-line or load side
HZC205
1 to suit HA307/HA308switch-line or load side(cable lug connection)
HZ062
1 to suit HA307/HA308/switch c/- cable clamp/line or load side
HZ072
F.13Subject to technical changes
Mai
nin
com
ers
Load break switches - characteristics (according to IEC 60947-3)
cat
ref
HA
302
HA
303
HA
304
HA
305
HA
306
HA
307
HA
308
HA
309M
HA
354
HA
356
HA
358
HA
360
HA
362
HA
364
therm
al curr
ent
Ith
40
63
80
100
125
160
200
250
250
400
630
800
1250
1600
insu
lati
on v
olt
age U
i (V
)80
080
080
080
080
080
080
080
080
010
0010
0010
0010
0010
00
impuls
e w
ithst
and v
olt
age U
imp (kV
)8
88
88
88
88
1212
1212
12
rate
d o
pera
tion c
urr
ent
(A)
A/B
A/B
A/B
A/B
A/B
A/B
A/B
A/B
A/B
A/B
A/B
A/B
A/B
A/B
400V
AC
(1)
A
C-2
1A /
AC
-21B
40/4
063
/63
80/8
010
0/10
012
5/12
516
0/16
020
0/20
020
0/25
025
0/25
040
0/40
063
0/63
080
0/80
012
50/1
250
1600
/160
0
A
C-2
2A /
AC
-22B
40/4
063
/63
80/8
010
0/10
012
5/12
516
0/16
020
0/20
020
0/20
025
0/25
040
0/40
063
0/63
080
0/80
012
50/1
250
1600
/160
0
A
C-2
3A /
AC
-23B
32/3
263
/63
80/8
010
0/10
012
5/12
516
0/16
020
0/20
020
0/20
025
0/25
040
0/40
050
0/63
080
0/80
012
50/1
250
1250
/125
0
690V
AC
(2)
AC
-20A
/ A
C-2
0B40
/40
63/6
380
/80
100/
100
125/
125
160/
160
200/
200
200/
250
250/
250
400/
400
630/
630
800/
800
1250
/125
016
00/1
600
A
C-2
2A /
AC
-22B
40/4
063
/63
40/4
040
/40
40/4
016
0/16
016
0/16
016
0/16
020
0/25
040
0/40
050
0/50
080
0/80
010
00/1
000
1000
/100
0
A
C-2
3A /
AC
-23
20/2
050
/50
25/2
525
/25
25/2
563
/80
63/8
063
/80
125/
160
250/
315
315/
315
800/
800
1000
/100
010
00/1
000
220V
DC
DC
-20A
/ D
C-2
0B40
/40
63/6
380
/80
100/
100
125/
125
160/
160
200/
200
200/
250
250/
250
400/
400
630/
630
800/
800
1250
/125
016
00/1
600
opera
tional pow
er
(kW
)
400
VA
C11
1840
5163
8010
010
013
2/13
222
0/22
028
0/28
045
0/45
071
0/71
071
0/71
0
690
VA
C11
1833
3333
150
150
150
90/1
1015
0/18
515
0/18
518
5/22
047
5/47
547
5/47
5
shor
t ti
me
wit
hst
and c
urr
ent
1 s
ec (k
A
rms)
1.25
1.5
2.5
2.5
2.5
44
49
1313
2650
50
short
cir
cuit
makin
g c
apacit
y (k
A p
eak)
610
1212
1216
1616
3045
4555
110
110
connecti
on
max
cab
le s
ectio
n (m
m)
1650
5050
5095
9595
150
240
2X30
02X
300
4X18
56X
185
max
bus
bar
wid
th (m
m)
--
--
-20
2020
3240
5063
100
100
(1)
A/B
= c
ateg
ory
with
ind
ex -
A =
freq
uent
op
erat
ion
/ B
= in
freq
uent
op
erat
ion
(2)
with
ter
min
al s
hrou
ds
or p
hase
bar
riers
Applic
ati
on c
ondit
ion &
uti
lisati
on c
ate
gory
, a
ccord
ing t
o IE
C 6
0947-3
Uti
lisati
on c
ate
gory
Use
Applic
ati
on
AC
DC
AC
20D
C20
off-
load
mak
ing
& b
reak
ing
dis
conn
ecto
r
AC
21D
C21
resi
stiv
e lo
ads
incl
udin
g m
oder
ate
over
load
ssw
itche
s at
inst
alla
tion
head
or
for
resi
stiv
e ci
rcui
ts
(ligh
ting)
AC
22D
C22
ind
uctiv
e &
res
istiv
e m
ixed
load
s in
clud
ing
mod
erat
e ov
erlo
ads
switc
hes
in s
econ
dar
y ci
rcui
ts o
r re
activ
e ci
rcui
ts
(cap
acito
r b
anks
)
AC
23D
C23
load
s m
ade
of m
otor
s or
oth
er h
ight
ly in
duc
tive
load
s
switc
hes
feed
ing
one
or s
erve
ral m
otor
or
ind
uctiv
e ci
rcui
ts (s
erie
s m
otor
s, m
agne
tic b
rake
s)
F.14F.14<#>www.hagerbr.com.au
Hager offers a wide range of Protection Devices, such as miniature circuit breakers, auxiliaries and accessories, RCCB‘s, RCBO’s, fuse carriers, DIN HRC fuse carriers, DIN socket outlets, earth leakage add-on blocks, earth leakage relays and torroids, surge protection devices and emergency test lighting packages, providing practical solutions for protecting people, installations and equipment.
Energy distributionProtection
Pro
tect
ion
G.1
MCB’s G.2
MCB’s - 80 - 125A G.6
MCB’s - accessories G.10
Fuse carriers G.11
DIN HRC fuse carriers G.12
DIN socket outlets G.12
Earth leakage add-on blocks G.13
RCCB’s G.14
RCBO’s G.15
Safety switches - accessories G.17
Earth leakage relays and torroids G.18
SPD selection for residential, rural and commercial areas G.19
Surge protective devices G.20
Emergency lighting discharge test packages G.21
G.2
NS120
45
68
44
MCB’s - 4.5kA C - Curve
descriptionprotection and control of circuits against overloads and short-circuits:- In domestic
installations
technical data- complies with
AS/NZS60898- tripping characteristics:
magnetic level is set at5 - 10 x In(C - curve)
- breaking capacity :4500A
- voltage rating :230/400V
- current rating : 6 to 40 A
- mechanical life : 20,000operations
connection capacity - rigid conductor 25mm2
flexible conductor 16mm2
- bi-connect allowing two connection points
accessories- LZ060, MZN175
description currentrating (A)
width in I17.5mm
packpty
catref.
single pole 6 1 12 NS106
10 1 12 NS110
13 1 12 NS113
16 1 12 NS116
20 1 12 NS120
25 1 12 NS125
32 1 12 NS132
40 1 12 NS140
double pole 10 2 6 NS210
16 2 6 NS216
20 2 6 NS220
25 2 6 NS225
32 2 6 NS232
40 2 6 NS240
G.3
Pro
tect
ion
45
68
44
NT110C
NT216C
NT304C
MCB’s - 6kA C - Curve
descriptionprotection and control of circuits against overloads and short-circuits:- In commercial installations
Technical data- complies with
AS/NZS 60898- tripping characteristics:
magnetic level is set at5 - 10 x In(C - curve)
- breaking capacity : 6000 A- voltage rating : 230/400Vac- current rating : 2 to 63 A- mechanical life : 20,000
operations- bi-connect allowing two
connection points
connection capacity - 25mm2 rigid - 16mm2 flexible
accessories- LZ060, MZN175,
MZ201,MZ202,MZ203, MZ206
description currentrating (A)
width in I17.5mm
packqty
catref.
single pole 2 1 12 NT102C
4 1 12 NT104C
6 1 12 NT106C
10 1 12 NT110C
16 1 12 NT116C
20 1 12 NT120C
25 1 12 NT125C
32 1 12 NT132C
40 1 12 NT140C
50 1 12 NT150C
63 1 12 NT163C
double pole 6 2 6 NT206C
10 2 6 NT210C
16 2 6 NT216C
20 2 6 NT220C
25 2 6 NT225C
32 2 6 NT232C
40 2 6 NT240C
50 2 6 NT250C
63 2 6 NT263C
triple pole 2 3 4 NT302C
4 3 4 NT304C
6 3 4 NT306C
10 3 4 NT310C
16 3 4 NT316C
20 3 4 NT320C
25 3 4 NT325C
32 3 4 NT332C
40 3 4 NT340C
50 3 4 NT350C
63 3 4 NT363C
G.4
NDN220A
45
68
44
MCB’s - 10kA D - Curve
descriptionprotection and control of circuits against overloads and short-circuits:- In commercial and light
industrial installations
technical data- complies with
AS/NZS 60898- tripping characteristics:
magnetic level is set at10 - 20 x In
- breaking capacity :10,000A
- voltage rating :230/400V
- current rating : 6 to 63 A- mechanical life : 20,000
operations
connection capacity - 25mm2 rigid - 16mm2 flexible accessories- LZ060, MZN175,
MZ201,MZ202,MZ203, MZ206,MZN120, MZN121
description currentrating (A)
width in I17.5mm
packqty
catref.
single Pole 6 1 12 NDN106A
10 1 12 NDN110A
16 1 12 NDN116A
20 1 12 NDN120A
25 1 12 NDN125A
32 1 12 NDN132A
40 1 12 NDN140A
50 1 12 NDN150A
63 1 12 NDN163A
double pole 6 2 6 NDN206A
10 2 6 NDN210A
16 2 6 NDN216A
20 2 6 NDN220A
25 2 6 NDN225A
32 2 6 NDN232A
40 2 6 NDN240A
50 2 6 NDN250A
63 2 6 NDN263A
triple pole 6 3 4 NDN306A
10 3 4 NDN310A
16 3 4 NDN316A
20 3 4 NDN320A
25 3 4 NDN325A
32 3 4 NDN332A
40 3 4 NDN340A
50 3 4 NDN350A
63 3 4 NDN363A
four pole 6 4 3 NDN406A
10 4 3 NDN410A
16 4 3 NDN416A
20 4 3 NDN420A
25 4 3 NDN425A
32 4 3 NDN432A
40 4 3 NDN440A
50 4 3 NDN450A
63 4 3 NDN463A
G.5
Pro
tect
ion
NCN110A
NCN220A
NCN332A
45
68
44
MCB’s - 10kA C - Curve
descriptionprotection and control ofcircuits against overloads and short-circuits:- In commercial and light industrial installations
technical data- complies with
AS/NZS 60898- tripping characteristics:
magnetic level is set at5 - 10 x In
- breaking capacity :10,000A
- voltage rating :230/400Vac
- current rating : 1 to 63 A
- mechanical life : 20,000operations
connection capacity - 25mm2 rigid - 16mm2 flexible accessories- LZ060, MZN175, MZ201,
MZ202,MZ203, MZ206, MZN120, MZN121
description currentrating (A)
width in I17.5mm
packqty
catref.
single pole 1 1 12 NCN101A
2 1 12 NCN102A
3 1 12 NCN103A
4 1 12 NCN104A
6 1 12 NCN106A
10 1 12 NCN110A
16 1 12 NCN116A
20 1 12 NCN120A
25 1 12 NCN125A
32 1 12 NCN132A
40 1 12 NCN140A
50 1 12 NCN150A
63 1 12 NCN163A
double pole 1 2 6 NCN201A
2 2 6 NCN202A
3 2 6 NCN203A
4 2 6 NCN204A
6 2 6 NCN206A
10 2 6 NCN210A
16 2 6 NCN216A
20 2 6 NCN220A
25 2 6 NCN225A
32 2 6 NCN232A
40 2 6 NCN240A
50 2 6 NCN250A
63 2 6 NCN263A
triple pole 1 3 4 NCN301A
2 3 4 NCN302A
3 3 4 NCN303A
4 3 4 NCN304A
6 3 4 NCN306A
10 3 4 NCN310A
16 3 4 NCN316A
20 3 4 NCN320A
25 3 4 NCN325A
32 3 4 NCN332A
40 3 4 NCN340A
50 3 4 NCN350A
63 3 4 NCN363A
G.6 Subject to technical changes
Miniature circuit breakers 80 - 125A
Thermal magneticcircuit breakers
Curves - ‘C’ - ‘D’In 80 to 125A
These circuit breakers are intended for the protection of circuits against overloads and short circuits in residential, commercial and industrial
premises.The circuit breakers, curve ‘C’, are adapted to the protection of the circuits in residential and Commercial premises.
The circuit breakers, curve ‘D’, are particularly adapted to the protection of the circuits where the
installations are subject to high in-rush currents.HMC curve ‘C’ 1500015kA of 80 - 100 - 125A :width 1.5 / pole
HMD curve ‘D’ 1500015kA of 80 - 100 - 125 A :width 1.5 / pole
HMF curve ‘C’ 1000010kA of 80 - 100 - 125 A :width 1.5 / pole
Series HMC, HMD, HMF at a glance;
Reinforcement of terminal harness:The reduction in distortion ensures maximum torque can be applied directly to conductor. 3.5Nm
Front product labelling.MCB’s are equipped with a pull down window that allows identification of protective device.
The ‘OFF’ position is clearly shown by a green indicator on the handle.
Trip free mechanism:MCB’s have quick and simultaneous closing of contacts, regardless of operating cycle, hence, the working life is increased.
Options ;Auxiliaries; standard 63A MCB auxiliaries (shunt, trip etc...) can be facilitated.
Accessories, Interphase barriers and terminal cover.
Tightening compensation system;The unique design of the terminal compensates and corrects any cable distortion.
Fast on connection;The MCB’s are equipped with top & bottom ‘fast-on’ terminals. They are used to supply low powered auxiliaries such as meters, indicating lights etc...
Lockable handle ;MCB’s can be locked in the <OFF> position by the integrated locking facility within the handle. The lock allows either sealing wire or a cable tie that may have a warning card attached ensuring safe working environment.
Model Icc/Curve Accessories Fast-on
connection
Tightening
comp. system
Lockable
handle
Front product
labelling
HMF 10kA, C YES YES YES YES YES
HMD, HMC 15kA, C, D YES YES YES YES YES
G.7
Pro
tect
ion
HMF199T
HMF299T
HMF399T
MCB’s - 80 - 125AHMF : ‘C’ 10000 - 10kA
Curve ‘C’ 10000(IEC 60898-1)10kAIEC 60947-2In 80 to 125A
Tripping curves :‘C’ magnetic settingbetween 5 and 10In.
Use :residential, commercialand industrial premises
Connection capacity :- 35mm flexible wire- 70mm rigid wire
KEMAIn conformity with the IEC 60898-1, 947-2 approved
description In / A width in I17.5mm
catref.
Circuit breakers 1 pole 80 1.5 HMF180T
100 1.5 HMF190T
125 1.5 HMF199T
Circuit breaker 2 pole 80 3 HMF280T
100 3 HMF290T
125 3 HMF299T
Circuit breakers 3 poles 80 4.5 HMF380T
100 4.5 HMF390T
125 4.5 HMF399T
G.8
HMC199T
HMC299T
HMC399T
N
HMC499T
MCB’s - 80 - 125AHMC : ‘C’ 15000 - 15kA
Curve ‘C’ 15000(IEC 60898-1)15kAIEC 60947-2In 80 to 125A
Tripping curves :‘C’ magnetic settingbetween 5 and 10In.
Use :residential, commercialand industrial premises
Connection capacity :- 35mm flexible wire- 70mm rigid wire
KEMAIn conformity with the IEC 60898-1947-2. Certification approved to AS/NZS 60898
description In / A width in I17.5mm
catref.
Circuit breakers 1 pole 80 1.5 HMC180T
100 1.5 HMC190T
125 1.5 HMC199T
Circuit breaker 2 pole 80 3 HMC280T
100 3 HMC290T
125 3 HMC299T
Circuit breakers 3 poles 80 4.5 HMC380T
100 4.5 HMC390T
125 4.5 HMC399T
Circuit breakers 4 poles 80 6 HMC480T
100 6 HMC490T
125 6 HMC499T
G.9
Pro
tect
ion
N
HMD199T
HMD399T
HMD499T
MZN130
MZN131
MCB’s - 80 - 125AHMD : ‘D’ 15000 - 15kA
Curve ‘D’ 15000(IEC 60898-1)15kAIEC 60947-2In 80 to 125A
Tripping curves :‘D’ magnetic settingbetween 10 and 20In.
Use : commercial and industrial premises
Connection capacity : - 35mm flexible wire- 70mm rigid wire
KEMAIn conformity with the IEC 60898-1947-2.Certification approved to AS/NZS 60898
description In / A width in I17.5mm
catref.
Circuit breakers 1 pole 80 1.5 HMD180T
100 1.5 HMD190T
125 1.5 HMD199T
Circuit breaker 2 pole 80 3 HMD280T
100 3 HMD290T
125 3 HMD299T
Circuit breakers 3 poles 80 4.5 HMD380T
100 4.5 HMD390T
125 4.5 HMD399T
Circuit breakers 4 poles 80 4.5 HMD480T
100 4.5 HMD490T
125 4.5 HMD499T
description characteristics catref.
Terminal covers terminal cover,
sealable
MZN130
Phase barrier 1 set of 3 phase
barriers
MZN131
Accessories for circuit breakers HMF, HMC HMD
G.10
MZ202
MZ203
MZN175
13 21
14 22
91
92
93
94
C1
C2
A1
U<
MCB’s - Accessories
descriptionall auxiliaries are common to both single and multi-pole circuit breakers and safety switches (RCCBs and RCBOs). These auxiliaries are fitted to the left hand side of devices.
(Auxiliary contact, shunt trip and undervoltage relays are not suitable for use with 4.5kA MCBs)
description characteristics width in I17.5mm
catref.
auxiliary contact5A - 230V~
NO + 1NC allows remote indication of main contact status
0.5 MZ201
auxiliarycontact with reset
auxiliary contact asabove.Reset switch triggerson overload or short circuit
0.5 MZ202
shunt trip relay allows for remote tripping of MCB. The coil is protected by a contact whichcuts the supply after MCB trips
1 MZ203
undervoltage if supply falls to 35 to 70% of nominalvoltage the MCBwill trip
1 MZ206
MZ203 MZ201 MZ201 MCB or or MZ206 MZ202
locking device to lock the MCB handle in on/off position
2 MZN175
heat dissipationinserts
avoids overheatingfor DIN rail moduleswhen several devicesmounted side by side are carrying high continuous loads
0.5 LZ060
terminal cover & screw shield
MZN120
phase barriers (1 set of 3)
MZN121
G.11
Pro
tect
ion
LS201
Fuse carriers
descriptionprotection and control of circuits against overloads and short circuits:- suitable for fuses which comply with BS88: Part I:1998
technical data - rated voltage: 415V ac 250V dc- fusing factor : class Q1- rated breaking capacity;80kA at 415 Vac40kA at 250 Vdc
- fuse cartridge not supplied
connection capacity- 16mm2 rigid cable- 16mm2 flexible + busbar
description currentrating (A)
width in I17.5mm
cat.
ref
fuse carriers for BS88 fuses.
(supplied without fuse
cartridge)
32A max 1 LS201
Locking kit MZN178
BS88 cartridge fuse
29 x 12.7mm
6A L17300
8A L17400
10A L17500
16A L17600
20A L17700
25A L17800
32A L17900
handle link pin 2 L022
handle link pin 3 L023
spare fuse holder
(DIN mounted)
1 L14700
service fuse back-wired 100A
for 22mm
LH901
service fuse back-wired 100A
anti-intrusion
LH904
fuse carrier (wedge) to suit
LH901
LH901/W
100A neutral link, 4 way KM06A
G.12
LT150
SNO15DA
DIN HRC Fuse carriers
DIN Socket Outlets
descriptionsize according to DIN from 00 to 2 to suit fuses according to AS/NZS60269
technical dataDIN fuses typically have breaking capacity to 100kA at 500V (supplied without fuse cartridge)- connection capacity
70 - 240mm
description width in I17.5mm
cat.
ref
DIN mounted socket outlets
DIN mounted 10A double pole auto switched completewith safety shutters and ‘on’indicator
2.5 SNO10DA
DIN mounted 15A doublewith safety shutters and ‘on’indicator
2.5 SNO15DA
description characteristics cat.
ref
fuse switchdisconnectors
3 x size 00 160A DIN blade fuses
LT052
3 x size 1 250A LT150
DIN blade fuses 3 x size 2 400ADIN blade fuses
LT250
cable clamps suitable for LT052(6 - 70mm2)
LZ051
suitable for LT150(70 - 150mm2)
LZ151
suitable for LT250 (120 - 240mm2)
LZ152
G.13
Pro
tect
ion
BD325T
Earth leakage add-on blocks
descriptionfor use with NCN + NDN + NT MCB’s- these devices are
designed to be fitted tothe right hand side of 2, 3 or 4 pole MCBs
- the combination devicethen providesprotection againstoverload, short circuits
and earth leakage faults. Satisfiesmechanical protectionclauses of AS3000:2007
- all devices have a testfacility
- all devices are type A- nuisance tripping
protection- protected against
transient voltages
technical data- complies with
AS/NZS61009.1
connection capacityflexible: 25A = 6mm2
40A = 16mm2
63A = 16mm2
rigid: 25A = 10mm2
40A = 25mm2
63A = 25mm2
description residualcurrentIIr n
currentrating (A)
width in I17.5mm
cat.
ref
2 pole RCCBadd-on blocks
30mA 25A 2 BD225T
30mA 40A 2 BD240T
30mA 63A 2 BD263T
100mA 25A 2 BE225T
100mA 63A 2 BE263T
300mA 25A 2 BF225T
300mA 40A 2 BF240T
300mA 63A 2 BF263T
3 pole RCCBadd on blocks
30mA 25A 2 BD325T
30mA 40A 3 BD340T
30mA 63A 3 BD363T
100mA 63A 3 BE363T
300mA 63A 3 BF363T
4 pole RCCBadd-on blocks
30mA 25A 2 BD425T
30mA 40A 3 BD440T
30mA 63A 3 BD463T
100mA 25A 2 BE425T
100mA 63A 3 BE463T
300mA 25A 2 BF425T
300mA 40A 3 BF440T
300mA 63A 3 BF463T
G.14
CD240T
CD440T
Safety switches - RCCB’s
descriptionthe safety switch is designed to open a circuit automatically in the case of a fault between phase and earth and or neutral and earth, greater than or equal to rated tripping current.use in domestic, commercial or industrial installationstechnical data- Approved to -
AS/NZS61008.1
- 10mA, 2 modules, 16A- 30mA, 2 and 4 modules, 25A, 40A, 63A, 80A, 100A- 100mA, 2 modules, 25A
40A,63A, 80A, 100A,4 modules -80A, 100A
- voltage rating, 230/400V~
connection capacity- 25mm2 - Rigid
(50mm2 for 80A,100A)- 16mm2 - Flexible
(35mm2 for 80A, 100A)
- positive contact indication windows- earth fault indication
window- trip free mechanisms
accessories- auxiliary & alarm
contacts- toggle locking device- neutral links- 400V shunt trip- 230V undervoltage
release
description residualcurrentIr n
currentrating (A)
width in I17.5mm
cat.
ref
double poletype AC
30mA 25A 2 CD225T
30mA 40A 2 CD240T
30mA 63A 2 CD263T
30mA 80A 2 CD280T
30mA 100A 2 CD284T
100mA 25A 2 CE225T
100mA 40A 2 CE240T
100mA 63A 2 CE263T
100mA 80A 2 CE280T
100mA 100A 2 CE284T
four poletype AC
30mA 25A 4 CD425T
30mA 40A 4 CD440T
30mA 63A 4 CD463T
30mA 80A 4 CD480T
30mA 100A 4 CD484T
100mA 80A 4 CE480T
100mA 100A 4 CE484T
double poletype AAC and pulsating DCresidual currents
10mA 16A 2 CC216T
30mA 25A 2 CD227T
30mA 40A 2 CD242T
30mA 63A 2 CD265T
100mA 80A 2 CE281T
100mA 100A 2 CE285T
four poletype Apulsating DCand AC residualcurrents
30mA 25A 4 CD427T
30mA 40A 4 CD442T
30mA 63A 4 CD465T
30mA 80A 4 CD481T
30mA 100A 4 CD485T
100mA 80A 4 CE481T
100mA 100A 4 CE485T
G.15
Pro
tect
ion
AD820T
AD917T
AD120T
Ph N
Ph N
Ph N
Ph N
Ph N
45
68
44
RCBO’s - 2 modules
descriptionCompact combination devices which provide MCB overcurrent protection & earth leakage protection. All units are two pole with line neutral switched & are 2 modules wide.The units are available with various current rating ranging from 6A-40A. The range includes Type A & Type AC devices.Type AC devices are the standard unit & will detect an
a.c. sinusoidal residual current. Type A device is designed with intrinsic features that can detect a.c. as well as pulsating d.c. residual currents.Solid state devices that are connected to permanent wiring have an increased possibility of generating residual current containing a d.c. component. Type A devices are able to tolerate this d.c. component. Standard type AC devices may become saturated by the d.c. component & may not detect a
residual current.features- earth fault indication
window- trip free mechanismsconnection capacity- 16mm2 flexible- 25mm2 rigidaccessories- auxiliary & alarm contact - toggle locking device- shunt trip- undervoltage release
description residualcurrentIrn
currentrating (A)
width in I17.5mm
cat.
ref
2 module RCBO4.5 kA Type AC
30mA 6A 2 AD806T
30mA 10A 2 AD810T
30mA 13A 2 AD813T
30mA 16A 2 AD816T
30mA 20A 2 AD820T
30mA 25A 2 AD825T
30mA 32A 2 AD832T
2 module RCBO4.5kA Type A
30mA 10A 2 AD811T
30mA 16A 2 AD817T
30mA 20A 2 AD821T
30mA 32A 2 AD833T
2 module RCBO6kA Type AC
30mA 6A 2 AD906T
30mA 10A 2 AD910T
30mA 13A 2 AD913T
30mA 16A 2 AD916T
30mA 20A 2 AD920T
30mA 25A 2 AD925T
30mA 32A 2 AD932T
30mA 40A 2 AD940T
2 module RCBO6kA Type A
10mA 10A 2 AC911T
10mA 16A 2 AC917T
2 module RCBO6kA Type A
30mA 6A 2 AD907T
30mA 10A 2 AD911T
30mA 13A 2 AD914T
30mA 16A 2 AD917T
30mA 20A 2 AD921T
30mA 25A 2 AD926T
30mA 32A 2 AD933T
30mA 40A 2 AD941T
G.16G.16
N N L FEout out
load
N N L FEout out
load
N N L FEout out
load
ADA120T
FU
TU
RE
RE
LEA
SE
FU
TU
RE
RE
LEA
SE
RCBO’s - 1 module description residual
currentIrn
currentrating (A)
width in I17.5mm
cat.
ref
1 module RCBO6kA Type AC
30mA 10A 1 AD110T
30mA 16A 1 AD116T
30mA 20A 1 AD120T
30mA 25A 1 AD125T
30mA 32A 1 AD132T
1 module RCBO6kA Type A
30mA 10A 1 ADA110T
30mA 16A 1 ADA116T
30mA 20A 1 ADA120T
30mA 25A 1 ADA125T
30mA 32A 1 ADA132T
1 module RCBO6kA Type A
10mA 10A 1 ACA110T
10mA 16A 1 ACA116T
10mA 20A 1 ACA120T
10mA 25A 1 ACA125T
Technical information for RCCB’s & RCBO’s
Discrimination between ResidualCurrent Devices
In theory it is possible to achieve current discrimination between residual current devices, but the limit of discrimination is far too low for practical purposes. Time delay is the only reliable and by far the best method used to obtain discrimination. It can only be achieved by delaying the tripping of the upstream residual current devices.
The down stream device would typically be a 30mA or occasionally a 10mA residual current device. Typically they will operate within 40ms and occasionally much faster.
Hager residual current relays (HR210, HR212) have adjustable time delay and residual current settings. They can be used as an upstream device to achieve residual current protection of the entire installation. It is advisable to set the residual current relay at a residual higher tripping current than a downstream devices (> 30mA) since the upstream device will see the accumulation of leakage currents from the entire installation. The residual current setting will depend on the quantity and type of equipment connected to the installation (Immersion water heaters, switch mode power supplies are particularly prone to leak currents to earth). The time delay should be set above zero to 300ms.
If further levels of protection are required upstream from the hager residual current relay, then another residual current relay can be installed upstream and the settings of the upstream device ( time and residual current) adjusted higher again.
G.17
Pro
tect
ion
CZ001
MZ 203... + CZ001 Safety Switch MZ206 (CA + SD)
Safety switches - accessories
function description width in I17.5mm
cat.
ref
combination auxiliary & alarm switch2xNO + 2xNC6A-230V~3A-440V~
CA allows remote indication of main contact status SD indicates a fault condition (eg Safety Switch tripped)
1 CZ001
If shunt trip or undervoltagerelease is required, theCZ001 must be used as acoupler.
auxiliary switch 1xNO + 1xNC6A-230V~3A-440V~
allows remote indication of main contact status
0.5 MZ201
alarm switch 1xNO + 1xNC6A-230V~3A-440V~
indication of a fault condition
0.5 MZ202
AC shunt trip230-415V AC110-130V DC
allows remote tripping of device
1 MZ203
AC undervoltage - when voltage falls by 35% of Un; fitted with an auxiliary switch
1 MZ206
Looking Kit supplied withoutpadlock
allows locking of the device; toggle in the on/off position; will accept two padlocks . with hasps of 4.75mm diameter max
MZN175
G.18
supply contactortrip
earthleakagerelay
detectiontorroid
conforms to IEC 1008
HR410
HR420
HR804
HR441
Earth leakage relays & torroids
descriptionThese units ensure the protection of electrical installations and the protection of persons against direct and indirect contact.This range of products contains a set of earth leakage relays, designed on an electronic basis, which ensure the monitoring of earth fault currents. When the fault current rises above the selected level, the outputs of the relay operate & depending on the relay selected, it can have both adjustable sensitivity and time delay that can provide selectivity/
discrimination. The relays are linked with detection torroids.common characteristics- positive safety: the relay
trips in the event of a break in the connection between relay and torroid.
- positive / local reset required after a fault is detected.
- protected against nuisance tripping
- class A - output: 1 c/o contact
250V~ 6A AC1- visual display of fault
- supply voltage 230V +/- 20% 50 / 60Hz
- adjustable sensitivity & time delay (sealable)
- display of fault current prior to triggering relay (5%-75%)
- extra output contact (250V-AC1/6A) to enable remote indication of fault currents above 50% of Irn
- remote test and reset by three wire link
torroidcircular diameter;- 35mm
- 70mm- 105mm- 140mmconnection capacity- flexible - 1 to 2.5mm- rigid - 1.5 to 4mm
description width in I17.5mm
characteristics cat.
ref
earth leakage relaystandard
3 c/o contact 250V 6A ~ AC1 adjustable sensitivity I�n= 0.03/0.1/0.3/0.5/1/3/10Aadjustable time delay�t= 0/0.1/0.3/0.4/0.5/1/3sec
HR410
earth leakage relay premium
3 c/o contact 250V 6A ~ AC1 fail safe contact 250V 6A ~ AC1pre-alarm contact 250V 6A ~ AC1adjustable sensitivityI�n= 0.03/0.1/0.3/0.5/1/3/10Aadjustable time delay�t= 0/0.1/0.3/0.4/0.5/1/3secbargraph = 5% - 75% I�n
HR420
earth leakage relay integral torroid
6 c/o contact 250V6A ~ AC1 adjustable ssensitivityI�n= 0.03/0.1/0.3/0.5/1/3Aadjustable time delay�t= 0/0.1/0.3/0.5/0.75/1sec� of torroid: 35mm
HR441
circular sectiontorroids
of torroid: 35mm HR801
� of torroid: 70mm HR802
� of torroid: 105mm HR803
��of torroid: 140mm HR804
G.19Subject to technical changes
Pro
tect
ion
1
2
31
3
SPD selection for residential, rural and commercial areas
Direct lightning protection
The criteria for installing a lightning protective product.
- Does the installation contain a lightning rod?
- Is the installation adjacent to tall structures, tall trees or near a hill top in a lightning prone area?
If the answer is YES to any of the above, it is recommended to install the SPA212A (3 phase = SPA412A) spark gap device. This will provide protection against direct lightning strikes.
Both references, SPA212A & SPA412A (single & three phase respectively) have dual earth and phase / neutral terminals. This connection method reduces any additional voltage drop in the connecting cables to virtually zero thereby obtaining the best possible Up to the installation. Further installation protection is provided by the fact that the devices are connected in both common and differential modes (L-E/N-E/L-N) together within inbuilt auto protection up to 12.5kA.
If the answer is NO to the above, then a spark gap device is not required.
Tip: If maximum demand of the installation is 125A or less then use both terminal screws per pole for through connection. This will minimise the residual current. If the maximum demand is greater than 125A then tap off each phase for parallel connection. Refer to the user instructions for a wiring diagram.
The next step is the selection of the Transient Protective device.
Indirect Transient ProtectionTo ensure protection of the installation it is vital to have adequate
protection from the harmful effect of transients.
Hager Thunder Day Map
This regional map illustrates the lightning activity across Australia and is based upon the ‘Thunder Day Map’ that appears in AS/NZS 1768 (Int): 2003. This map is compiled by the Bureau of Meteorology.As indicated, the country is split into three zones of activity. The orange zone is maximum exposure, the yellow zone is high exposure and the grey zone is moderate exposure to lightning activity. The process of selecting the correct SPD for protection against transients is a simple one.
- In what region is the installation located?
1 Install SPN165R; the installation is protected from indirecttransients up to 65kA.
2 Install SPN140D/R; the installation is protected from indirecttransients up to 40kA.
3 Install SPN115D/R; the installation is protected from indirecttransients up to 15kA.
Tip: For three phase installations, you will require three of the selected SPDs E.g: 3 x SPN165R
All Hager Class II medium protection products have plug-in cartridges available in two versions:
- SPD’s with a base element and cartridge with a status indicator (to show the end of the life of the device). This is indicated with the suffix D at the end of the item number.
- SPD’s with a base element which contains an auxiliary contact for remote signalling (audible and visual), and a cartridge with a reserve status indicator. The reserve status function has an added intermediate step which indicates that the cartridge needs to be replaced. While the installation is still protected, the cartridge should be replaced as soon as possible. This product is indicated with the suffix R at the end of the item number.
- SPN165 only available as R
The next system consideration is the protection of the installation’s sensitive and valuable electronic equipment.
Equipment Protection
To ensure that today’s and importantly tomorrow’s, sensitive and
valuable electronic devices continue to provide entertainment and
service, it is vital to bring the residual voltage below 800V. This will
minimise the chance of damage to microchips within these devices.
Answering the question below will allow you to ascertain which Hager
device best suits the needs of the installation.
- Does the installation contain electronic appliances? Eg.
TV’s,VCR’s, microwave ovens, Hi-Fi system, computers, fax
machines, DVD players, etc...
If the answer is YES, install SPN208S. By installing this device the
residual voltage (Up) remaining in the system will be less than 800V. If
the installation is 3 phase then install a SPN408S.
If the answer is NO, the installation requires no further protection.
For quick selection of the best SPD product while in the field, please
refer to the Hager ‘pocket size SPD selection guide’.
G.20
SPN505
SPN040D
SPA212A
SPA412A
SPN208S
SPN408S
Surge protective devices
descriptionhager SPD’s protect electric and electronic equipment against transients,originating from lightning and switching transient sources .These transients can cause anything from the premature
aging of equipment, logic failures and down time, to the complete destruction of electrical components and the entire electrical distribution system.Surge protective devices are strongly recommended in sites
that are exposed to lightning, to protect sensitive and expensive electrical equipment such as TV’s, washing machines, Hi-Fi’s, PC’s, VCR’s, alarms etc..
For detailed information, please consult the hager Surge Protective Devices technical handbook
description poles IimpkA
InkA
UpkV
UcV
width in I17.5mm
cat.
ref
Class ISpark gap arresterfor areas where risk of lightning isprevalent.Test wave 10/350us
2
4
12.5
12.5
-
-
<2.5
<2.5
255
255
4
8
SPA212A
SPA412A
description poles Iimp InkA
UpkV
Uc V
width in I17.5mm
cat ref.
Class IIMedium ProtectionMetal Oxide Varistors(MOV’s)high divertingcapacity
11
111
6540
401515
2015
1555
<1.5<1.2
<1.2<1.0<1.0
275275
275275275
11
111
SPN165R SPN140R
SPN140D SPN115R SPN115D
replaceable cartridgereserve option indication and changeover contacton ‘R’ catalogue reference
description poles Iimp InkA
UpkV
Uc V
width in I17.5mm
cat ref.
Class IIFine Protectionto be used incascade withmedium protection devicesRefer to cascade table for Up values
24
88
22
1.21.25
255255
23
SPN208S SPN408S
Designation Poles reservestatus ind.
standardstatus ind.
width in I17.5mm
catref.
Class IIreplacementcartridge forSPN1XXX
11111
YesYes-Yes-
--Yes-Yes
11111
SPN065R SPN040R SPN040D SPN015R SPN015D
designation
line InkA
characteristics width in I17.5mm
catref.
Protection for those devicesconnected to the telephonenetwork. Protection is assured in both common &differential modes.
analog 10 Un: 130vd.cUc: 170vd.c
1.5 SPN505
G.21
Pro
tect
ion
EMERG1W
Emergency lighting discharge test package -1
Red
PUSH BUTTONSVN391
N
Green
15 EET
18
B1 A2 EET
A1
EZN004TIMER
EM1
ES480 CONTACTOR
FROM 6A MCB CONTROL
EM1-1
EMERGENCY LIGHTING
GENERAL LIGHTING
CIRCUIT 1
GENERAL LIGHTING
EMERGENCY LIGHTING
EM1-2
CIRCUIT 2
EMERGENCY LIGHTING
GENERAL LIGHTING
EM1-3
CIRCUIT 3
EMERGENCY LIGHTING
GENERAL LIGHTING
EM1-4
CIRCUIT 4
These breakers are not supplied as part of the standard test package.
A1 A2
1 2
3 4
1 2
3 4
5 6
7 8
1. Standard Emergency Test Components:
SVN391: Momentary Pushbutton, 6A 240V 1 NO (green, Pushbutton A), 1 NC (red, Pushbutton B)
EZNOO4: Delay Timer (EET) Set at 2 hours for initial commissioning (90mins there after) Clauses 2.2.1 and 2.2.2 of AS2293.1-2005
ES480: 4 pole normally closed contactor (EM1) 4P 40A AC1, 240V AC coil
2. Basic Operating Procedure:
Upon engaging Pushbutton A for 1 second the Delay Timer (EET) starts its operation and energises the coil of Contactor EM1. The four normally closed contacts of EM1 then open, initiating the operation of the emergency lights. After 2 hours Timer EET completes its operation, de-energising the coil of EM1 and returning the contacts to the normally closed position. In accordance to AS2293.1-2005 4.3.1(b) the test facility is capable of being manually reset. If the Red Pushbutton is pressed for 1 second, Timer EET resets and is ready for Green Pushbutton to start the timing cycle again.
descriptionThe Hager Emergency Lighting Discharge Test Package has been developed to meet the needs of the electrical industry.
In accordance with AS2293.1-2005 and AS/NZS2293.2 1995 ‘Emergency Evacuation Lighting for Buildings’ a discharge test circuit MUST be installed in both existing and new installation for the purpose of testing the charge.
applicationHager’s EMERG1W offers a convenient and versatile discharge test facility for maintenance of emergency
lighting systems. This package may be mounted separately using the supplied enclosure in situations where space in the switchboard is limited. It can also be included in the hager range of Jyka panelboards by taking advantage of the DIN rail area at the top of the switchboard
The EMERG1W test package includes- 6 pole surface mount enclosure, together with a lockable door- IP 40- 4 Pole 40A N/C Contactor
- push button 1N/O (green) + 1N/C (red)- delay timer 0.1 second to 10 hours
use and implementationThe EMERG1W works on the following principle:Upon engaging the Green push button for 1 second, the timer starts it’s operation and energises the contactor coil. The four normally closed contacts open, initiating operation of the emergency lights. The timer, to be set at 2 hours (2hrs for initial commissioning, 90mins thereafter, completes its operation, de-energising the
contactor coil returning the contacts to the normally closed position.In accordance with AS2293.1-2005 4.3.1(b) the test facility is capable of being manually reset. If the red push button is pressed the timer resets and is ready for the green push button to start the timing cycle again.
This wired ‘off-the-shelf’ package offers the contractor a time saving solution and answers the needs of the industry in regard to the testing and maintenance of emergency lighting systems.
description characteristics cat.
ref
emergency lighting discharge test package - wired
enclosure c/- control gear & internal wiring
EMERG1W
G.22G.22
Emergency lighting discharge test package - 2
Red
PUSH BUTTONSVN391
N
Green
15 EET
18
B1 A2 EET
A1
EZN004TIMER
EM1
ES230 CONTACTOR
FROM 6A MCB CONTROL
EM1-1
EMERGENCY LIGHTING
GENERAL LIGHTING
CIRCUIT 1
GENERAL LIGHTING
EMERGENCY LIGHTING
EM1-2
CIRCUIT 2
These breakers are not supplied as part of the standard test package.
A1 A2
1 2
3 4
1 2
3 4
1. Standard Emergency Test Components:
SVN391: Momentary Pushbutton, 6A 240V 1 NO (green, Pushbutton A), 1 NC (red, Pushbutton B)
EZNOO4: Delay Timer (EET) Set at 2 hours for initial commissioning (90mins there after) Clauses 2.2.1 and 2.2.2 of AS2293.1-2005
ES230: 2 pole normally closed contactor (EM1) 2P 25A AC2, 240V AC coil.
2. Basic Operating Procedure:
Upon engaging the Green Pushbutton for 1 second the Delay Timer (EET) starts its operation and energises the coil of Contactor EM1. The two normally closed contacts of EM1 then open, initiating the operation of the emergency lights. After 2 hours Timer EET completes its operation, de-energising the coil of EM1 and returning the contacts to the normally closed position. In accordance to AS2293.1-2005 4.3.1(b) the test facility is capable of being manually reset. If the Red Pushbutton is pressed for 1 second, Timer EET resets and is ready for Green Pushbutton to start the timing cycle again.
descriptionThe Hager Emergency Lighting Discharge Test Package has been developed to meet the needs of the electrical industry.
In accordance with AS2293.1-2005 and AS/NZS2293.2 1995 ‘Emergency Evacuation Lighting for Buildings’ a discharge test circuit MUST be installed in both existing and new installation for the purpose of testing the charge.
applicationHager’s EMERG2W offers a convenient and versatile discharge test facility for maintenance of emergency
lighting systems. This package may be mounted separately using the supplied enclosure in situations where space in the switchboard is limited. It can also be included in the hager range of Jyka panelboards by taking advantage of the DIN rail area at the top of the switchboard
The EMERG2W test package includes- 4 pole surface mount enclosure, together with a lockable door- IP 40- 2 Pole 25A N/C Contactor- push button 1N/O (green) + 1N/C (red)
- delay timer 0.1 second to 10 hours
use and implementationThe EMERG2W works on the following principle:Upon engaging the Green push button for 1 second, the timer starts it’s operation and energises the contactor coil. The two normally closed contacts the open, initiating operation of the emergency lights. The timer, to be set at 2 hours (2hrs for initial commissioning, 90mins there after) completes its operation, de-energising the contactor coil returning the contacts to the normally closed position.
In accordance with AS2293.1-2005 4.3.1(b) the test facility is capable of being manually reset. If the red push button is pressed the timer resets and is ready for the green push button to start the timing cycle again.
This wired ‘off-the-shelf’ package offers the contractor a time saving solution and answers the needs of the industry in regard to the testing and maintenance of emergency lighting systems.
description characteristics cat.
ref
emergency lighting discharge test package - wired
enclosure c/- control gear & internal wiring
EMERG2W
G.23
Energy Distribution Enclosure systemsWiring Accessories + Building Automation
Cable management
Energy distributionProtection(sec. G.)
there are times when you’reglad you were prepared...
Surge Protection
Ask yourself...What is the total value of all your electrical appliances, entertainment and IT equipment?
Be preparedHager’s three step (cascade) system approach will ensure you have the best level of protection for all your valuables. A proven solution from Europe’s leading manufacturer.A small investment, for you and your family.
www.hagerbr.com.au
G.24
This section provides a range of switches, voltmeters, ammeters, push buttons, indicator lights, transformers, bells and buzzers that are used for isolation, installation monitoring and circuitry control.
Energy distributionControl & indication
Con
trol
&
ind
icat
ion
H.1
Isolating switches H.2
Changeover switches H.3
Selector switches voltmeters and ammeters H.4
Indicator lights H.5
Push buttons H.6
Analogue voltmeters, ammeters H.7
Current transformers (CT’s) H.8
Digital voltmeters, ammeters H.9
Digital multimeter H.9
Kilowatt hour meters and hours counter H.10
Transformers, bells and buzzers H.11
Dimmers - range overview H.12
Dimmers H.13
Dimmer system - 1/10V pilots H.16
Motion detectors - IP55 H.17
Motion detectors H.18
Presence detectors H.20
H.2
SB163T
SB499T
N
45
68
44
Isolating switches
descriptionfor use as a switch isolator in all types of circuits. As defined in AS/NZS3000-2007, clause 2.3.3.2, domestic installations require no more than one main switch for each metered supply.
technical data- In : 40, 63, 80A
(1, 2, 3 pole)- AC 22B dutyspecification (mixedresistive and inductiveloads. Not motors)
connection capacity:25mm2 rigid cables16mm2 flexible cables
- In : 63A & 100A(1, 2, 3, 4 poles)- AC 22B dutyspecification (mixed resistive and inductive loads. Not motors)
-50mm2 rigid cables-35mm2 flexible cables
description characteristics width in I17.5mm
cat.
ref
single pole 1 x 40A 250V~ 1 SB140T
1 x 63A 250V~ 1 SB163T
1 x 80A 250V~ 1 SB180T
1 x 100A 250V~
1 SB199T
double pole 2 x 40A 250V~ 1 SB240T
2 x 63A 250V~ 1 SB263T
2 x 80A 250V~ 1 SB280T
2 x 100A 250V~
1 SB299T
triple pole 3 x 40A 400V~ 3 SB340T
3 x 63A 400V~ 3 SB363T
3 x 80A 400V~ 3 SB380T
3 x 100A 400V~
3 SB399T
four poleneutral right
4 x 63A 400V~ 4 SB463T
4 x 100A 400V~
4 SB499T
Con
trol
&
ind
icat
ion
H.3
SF115
SF219
SF263
NEW
Changeover switches
2 way, centre off modular change over switchesdescriptionmanual change over switches for the control between two power supplies
description characteristics width in I17.5mm
cat.ref.
double pole
1 3
2 4
2 x 25A 250V~ 1 SF115
switch, 2 ways single pole
2 4
1
1 x 25A 250V~ 1 SF118
switches centre - offchangeover
1 x 25A 250V~ 1 SF119
double pole
2 4
1
6 8
5
2 x 25A 250V~ 2 SF218
switches centre - off changeover
2 4
1
6 8
5
2 x 25A 250V~ 2 SF219
double pole 2 x 63A 230V~ 4 SF263
four pole 4 x 63A 400V~ 8 SF463
SF263 - double pole SF463 - four pole
H.4
SK602
SK603
SK606
����
�
�
��� ���
��
�
�� � � ��
�� ����
����
�� ��
�
�
��
��
�
�
�
��
��
��
� � �� �
��
��
����
��
�
��
�� ��
�
� ��
��
�
��
�
��
��
��
�
�
Selector switches voltmeters and ammeters
descriptionTo provide command signals or program selection in electri-cal control schemes
ApplicationFor domestic and commercial installations
Connection capacity :- Rigid conductor : 1.5 to 10mm2
- Flexible conductor : 1 to 6mm2
Conform to IEC947-3 BS EN 60947-3
Isolating voltage : 500V~Nominal current : 10-20A
description characteristics width in 17.5mm
cat.ref.
1 pole selector switch 20A 400V~non spring return
3 SK600
2 pole selector switch 20A 400V~non spring return
3 SK601
Voltmeter selector 3Ph&N3 readings between phases3 readings between phase & neutral null position (no reading)
20A 400V~ 3 SK602
Ammeter selector4 positionsuse in 3Ph&Nreading by phase0 position (no reading)should be used with current transformer (CT)
20A 400V~ 3 SK603
Step selector switch 20A 400V~ 3 SK604
Key selector switch 10A 400V~ 3 SK606
spare keyfor SK606
SK001
Con
trol
&
ind
icat
ion
H.5
SVN122M SVN125M
SVN124M
SVN121M SVN122M
SVN126M SVN127M
Indicator lights
descriptionIndicator lights and push buttonsThese products are used for remote controlling signalisation of any event in any electric installation (domestic, tertiary & industrial)
LED technology providing longer life, new design and integrated label holder.
connection capacity- 10mm2 rigid cable- 6mm2 flexible cable
Standard conformity:IEC 62094-1 for indicatorlights
description characteristics width in I17.5mm
cat.ref.
indicatorlights
with light230V~
1 x green 1 SVN121M
1 x red 1 SVN122M
1 x blue 1 SVN124M
1 x clear 1 SVN125M
1 x green/red 1 SVN126M
3 x red 1 SVN127M
H.6
SVN311M
SVN413M
45
68
44
Push buttons
description2 versions:- impulse push buttons- latching push buttons
These versions with indicator lights are equipped with green or red diffuser. (led technology)
connection capacity- 10mm2 rigid cables- 6mm2 flexible cables
Standard conformity:IEC 60947-5-1 for push buttonsIEC 62094-1 for indicator lights
description characteristics width in I17.5mm
cat.ref.
pushbuttonsimpulse
without indicator light16A - 250V~
contacts: 1NO 1 SVN311M
contacts: 1NC 1 SVN321M
contacts: 1NO+1NC(stop / start)
1 SVN391M
pushbuttonsimpulse
with indicator light
contacts: 1NO green
1 SVN411M
contacts: 1NCred
1 SVN422M
pushbuttonslatching
without indicator light16A - 250V~
contacts: 1NO 1 SVN312M
contacts: 1NO + 1NC 1 SVN352M
pushbuttonslatching
with indicator light
contacts: 1NO green
1 SVN413M
Con
trol
&
ind
icat
ion
H.7
* Please check availability with your local Hager B&R sales office at time of ordering*
SM500*
SM030*
Analogue voltmeters, ammeters
descriptionfor domestic and commercial installations- single phase :direct connection- three phase :
use of a voltmeterselector switch SK602
frequency : 50/60Hzconnection capacity- 10mm2 rigid- 6 mm2 flexibleanalogue ammetersfor domestic and commercial installations
direct reading :up to 30Aindirect reading via current transformers:50, 100, 150, 250, 400, 600A
description characteristics width in I17.5mm
cat.ref.
analogue voltmeter accuracy : 2%consumption : 2.5VA0 - 500V
4 SM500*
analogue ammeterdirect
0 - 5A 4 SM005*
0 - 15A 4 SM015*
0 - 30A 4 SM030*
analogue ammetercurrent transformeroperated
accuracy : 1.5% (full scale)
- reading via CT SR 051 scale : 0 - 50A 4 SM050*
- reading via CT SR 101 scale : 0 - 100A 4 SM100*
- reading via CT SR 150 scale : 0 - 150A 4 SM150*
- reading via CT SR 250 scale : 0 - 250A 4 SM250*
- reading via CT SR 400 scale : 0 - 400A 4 SM400*
- reading via CT SR 600 scale : 0 - 600A 4 SM600*
H.8
SR300
SR 051
21mmØ
34mmØ22mmØ
0L1L2
L2L3
L3L1
SK 602
L1
L2
L3
SM 500
1000200 400
500
V
300
3 51
244 62
7
8
9
10
Current transformers (CT’s)
descriptionCurrent transformers are used to feed analogue and digital ammeters, as well as kWh meters.Their current on secondary circuit (0-5A) is proportional to the current on primary circuit class : 1
- can be mounted on copper busbar or on cable
- can be mounted on DINrail with adaptors
description characteristics cat.ref.
current transformers (CT)* ratio:
for use with SM050 50/5 SR051
for use with SM100 100/5 SR101
for use with SM150 150/5 SR150
for use with SM250 250/5 SR250
for use with SM400 400/5 SR400
for use with SM600 600/5 SR600
Electrical connection (voltmeter) Electrical connection (ammeter)
Current transformations (CT)Technical specifi cationsElectrical characteristics- primary current: 50 to 400A (depend. on model) secondary current: 5A- frequency: 50/60Hz
Range of CT’sSR 051: 50/5ASR 101: 100/5A
SR 150: 150/5ASR 200: 200/5ASR 250: 250/5A
SR 300: 300/5ASR 400: 400/5ASR 600: 600/5A
busbar entry = 30mm x 10mm busbar entry = 40mm x 10mm
Con
trol
&
ind
icat
ion
H.9
* Please check availability with your local Hager B&R sales office at time of ordering*
* Please check availability with your local Hager B&R sales office at time of ordering*
SM020*
SM001
SM501
Digital multimeter
Digital voltmeters, ammeters
description characteristics width in I17.5mm
cat.ref.
Digital voltmeter voltage rating :220/230V; 50/60Hzaccuracy : ±1%consumption : 4VAscale : 0 -500V
4 SM501
Digital ammeters voltage rating :220/230V; 50/60Hzaccuracy : ±1%consumption : 4VA
- direct scale : 0-20A 4 SM020*
- reading via CT150/5A(SR 150)
scale : 0-150A 4 SM151*
- reading via CT 400/5A (SR 400)
scale : 0-400A 4 SM401*
- reading via CT 600/5A (SR 600)
scale : 0-600A 4 SM601*
Digital voltmetersSM501For domestic and commercial installations.
- three phase : use of a voltmeter selector switch SK 602- Digital ammeters from SM 020 to SM 911 SM 020 : direct reading from SM 151 to SM 601 :
reading via a current transformer (see below)
MultimeterFor monitoring the electricalnetwork : single, two or three phases (with or without neutral).Connection on current transformer (not provided).
Enables the display 3 electrical values at the same time, as instantaneous, average or maximum (voltage and intensity per phase in RMS value).
For monitoring of powergenerator, it measures the frequency and working time.
description characteristics width in 17.5mm
cat.ref.
Multimeter voltage supply: 230/400V50/60hz
4 SM001*
displayvoltage
- 35-480V
- accuracy + 0.5%
- consumption: <0.5VA
current - via c/t
- primary 5-8000A
- secondary 0.1-6A
- accuracy: + 0.5%
- consumption: <0.5VA
frequency - range 40-80hz
- accuracy: + 2hz
hour counter - 7 digits 999999.9
H.10
* Please check availability with your local Hager B&R sales office at time of ordering*
EC050
EC121*
EC321*
45
5741
Kilowatt hour meters and hours counter
descriptionkilowatt hour meters measure the active energy used in an electric installation. The range includes meters with pulsed output for remote indication or linking into an energy management system.kWh meters can be used for local metering of installations or monitoring of power consumption in individual machines.
All meters offer part (resettable) counter and total (non-resettable) counter(except EC050/ EC051)In addition meters are available for direct or CT operated with single or dual tariff. (second tariff is suitable for ‘time of use’ not ‘off-peak’)
technical data- in accordance to
IEC61036, class 1 & class 2 accuracy
- display with a LCD7 digits (6+1)
- single and doubletariff options
- with pulsed output- For CTs refer to page I.2
description characteristics width in I17.5mm
cat.ref.
single phasedirect reading
230V 50Hz20mA to 32A
1 EC050
230V 50Hz20mA to 32Apulsed output
1 EC051
single phaseCT operation
230V 50Hz100/5A CT operatedsingle tariff
3 EC120
230V 50Hz100/5A CT operateddual tariff
3 EC121*
sealing kit for single phase kwh meters direct reading only(EC110, EC111)
EC001
three phasedirect reading
400V 50Hz800mA to 80Asingle tariff
7 EC310
400V 50Hz800mA to 80Adual tariff
7 EC311*
three phaseCT operated
400V 50Hz50 - 1500/5A CT operated single tariff
4 EC320
400V 50Hz50 - 1500/5A CT operated dual tariff
4 EC321*
hours counter 230V 50Hz 2 EC100*
Con
trol
&
ind
icat
ion
H.11
* Please check availability with your local Hager B&R sales office at time of ordering*
ST312*
SU212*
SU214*
58
44
45
Transformers, bells and buzzers
descriptionprovide safety extra low voltage 8, 12, 24V~.technical data- secondary voltage : 8V,
12V, 24V- bell transformers are
short - circuit protected- bells/buzzers : Max
continuous duty < 30minutes
connection capacity- cable clamp typeoutput- Bells : 85 dBA- Buzzers : 78 dBAWhen a bell transformer is installed in an enclosure with mains voltage equipment, 230V cable should be used on the secondary side of the transformer or extra low voltage cable should
be sheathed within the enclosure.noteThe transformers have a higher no load voltage. The stated voltages correspond to the voltages at nominal load
description characteristics width in I17.5mm
cat. ref.
safety
transformers
230V / 12-24V~
50/60Hz
25VA 50/60Hz 4 ST312*
60VA 50/60Hz 6 ST315*
bell transformers
230V/8~12V~50/60Hz
8VA - 8V : 1A
-12V : 0.67A
2 ST303*
230V/8 -
12V~50/60Hz
16VA - 8V : 2A
-12V : 1.33A
- 24V : 0.67A
3 ST305*
bells 8/12V~
4VA - 0.35A
1 SU212*
230V~
6.5VA - 0.03A
1 SU213*
buzzers 8/12V~
4VA - 0.35A
1 SU214*
230V~
6.5VA - 0.03A
1 SU215*
H.12 Subject to technical changes
�� ���� �
��
��
��
Transformers
Safety transformersThese transformers are designed to ensure personal safety, their primary winding are electrically separated from their secondary windings and they are intended to feed safety extra low voltage (SELV) circuits < 50V. A thermal overload, in the primary windings, ensures that if a short circuit or an overload occurs in the output it will not damage the device.
Bell transformersBell transformers are similar to safety transformers but the secondary voltages do not exceed 24 volts, they are also similarly protected against short circuits and overloads, by thermal protection in the primary winding.
Technical specification
Reference ST303 ST305 ST312 ST315
Nominal power 8VA 16VA 25VA 60VA
Designation bell bell safety safety
Primary voltage U1 230 volts 230 volts 230 volts 230 volts
Secondary voltage U2 8 volts 8 volts 12 volts 12 volts
In = 1A In = 2A In = 2.08A In = 5.25A
U3 12 volts 12 volts 24 volts 24 volts
In = 0.67A In = 1.33A In = 1.04A In = 2.63A
No load secondary U2 15 volts 12.4 volts 14 volts 13.6 volts
voltage U3 21.8 volts 18.5 volts 29 volts 27 volts
Galvanic insulation 4kV 4kV 4kV 4kV
Max functional temperature 35°C 35°C 35°C 35°C
Overload and S/C protection thermal cut out in the primary winding
number of products that can be operated simultaneously by a transformer
transformer reference ST303 ST305 ST312 ST315
8V 12V 8V 12V 12V 24V 12V 24V
power (VA) 8 8 16 16 25 25 60 60
bell SU212 8/12V 3 2 5 3 - - - -
buzzer SU214 8/12V 3 2 5 3 - - - -
H.13Subject to technical changes
system dimmers1-10 V pilots
EV106 EV108
dimmers 300 W
EV011 EV012
universal dimmers 600 W
EV002 EV004
system dimmersuniversal dimmers 1000 W
EV100 EV102
FU
TU
RE
RE
LEA
SE
Dimmers- range overview
Incandescent/halogen 230V
Halogen ELV (12 or 24V) via electronic transformer
1/10V control (output only)fluoro with electronic 1/10V ballast
Input 1/10 V, 50 mA
Halogen ELV (12 or 24V) ferromagnetic transformer suitablefor dimming. The transformer shouldn’t be used with less than 75% of nominal load
functioning as a standalone product
0W 20W 60W 100W 300W 600W 1000W
EV011, EV012
EV002, EV004EV100, EV102 switch to “local” position
EV011
EV002, EV004EV100, EV102 switch to “local” position
EV012
EV002, EV004EV100, EV102 switch to “local” position
EV102 pilot : switch to “master” position
EV 102 pilot : switch to “master” position
functioning in system : association of dimmers with 1/10V max 30 x 1kW
EV102 + n x EV100 or EV102 (slave position)
EV106
EV102 + n x EV100 or EV102 (slave position)
EV 102 pilot : switch to “master” position
EV102 + n x EV100 or EV102 (slave position)
EV108 with scene inputs
300 W 600 W 1000 W Pilot 1/10 V
Technical featuresEV011EV012
EV002EV004
EV100 EV102 EV106 EV108
Controls available - on the product - external with illuminated pushbutton- input 1/10 V- ambient lighting setting
-yes--
yes yes -1 (EV004)
yes yes yes (slave)-
yes yes yes (slave)2 levels
yes yes --
yes yes -2 levels
Types of outputs :- direct (capacitive/inductive load)- input 1/10 V
yes -
yes -
yes -
yes yes (master)
-yes
-yes
Functions :- protection overheating / overloads- level indicator- memory- softstart
yes *-yesyes
yes EV004yesyes
yes -yesyes
yes yesyesyes
yes yes yes -
yes yes yes -
Parameter setting :- mini, max. level- dimming speed- speed at start / stop- transition speed for level call
----
EV004EV004EV004-
yes yesyesyes
yes yesyesyes
yes yesyesyes
* EV011 : protection via integrated fuse, electronic protection for other products
H.14
EV011*
EV004*
LZ060
FU
TU
RE
RE
LEA
SE
FU
TU
RE
RE
LEA
SE
FU
TU
RE
RE
LEA
SE
Dimmers
Common characteristics :- Softstart (progressive start) to increase the working live of lamps- last dimming level memorised- protection against overheating- control possible by illuminated pushbutton until 5mA.
Dimmer300 W :- control by several pushbuttons- can replace a latching relay with dimming function
Dimmers 600 and 1000 W :- universal products with automatic recognition of the load
type (inductive/capacitive)- electronic protection against overheating and overload- Indicators : 230 V / overheating / overload
description characteristics width in I17.5mm
cat.ref.
Dimmers 300 Wfor :- incandescent 230 V- halogen 230 V- ELV halogen lamps with :• ferromagnetic trans-former (inductive load EV 011 )• dimmable electronic transformer (capacitive load (EV 012 )
20 ... 300 W / VA230 V / 50 Hzinductive load
capacitive load
1
1
EV011*
EV012*
Universal remote control dimmer 600 Wfor :- incandescent 230 V- halogen 230 V- ELV halogen lamps supplied by ferromagnetic or dim-mable electronic trans-former(cos w � 0,95)
20 ... 600 W / VA230 V / 50 Hz- products with automatic loadrecognition- dimming function
4 EV002*
Enhanced universal dim-mer 600 W
in addition to EV 002 features :- min/max level setting- recall mode with pushbutton, override mode with switch - scene level setting0 ... 99 %
4 EV004*
Heat dissipation insert 0.5 LZ060
* Please check availability with your local Hager B&R sales office at time of ordering*
Con
trol
&
ind
icat
ion
H.15
EV102*
EV100*
FU
TU
RE
RE
LEA
SE
Dimmers
description characteristics width in I17.5mm
cat.ref.
Universal dimmer 1000 W for :• Functional mode selection via local switch :- control via pushbutton (local)- remote control via 1/10V (slave)• Min/Max setting via potentiometer• LED indication :- 230V power supply/load error- overload / overheatingLoad type :- incandescent- 230V halogen lamps- ELV halogen lamps associated to ferromagnetic transformer (inductive)- ELV halogen lamps associated to electronic transformer (capacitive)
230 V AC / 50 Hz
20 ...1 000W
1/10V-input
5 EV100*
Universal dimmer 1000 W with scene inputs• Functional mode selection via local switch :- control via pushbutton (local)- remote control via 1/10V (slave)- control of the other dimmers as 1/10V (master)• Display to show the dim level and to set the parameters: - dimming rise time (4s ..99s)- min dim level (0...49%)- max dim level (51..99%)- rise time when switching ON (1s..99s)- fall time when switching OFF (1s..99s)- scene level- dimming rise time for each scene- scene working mode :recall or override mode• Output contact to display the dim state (load is OFF, contact is opened, if load is dimmed the contact is closed)• LED indication :- 230V power supply / load error- overload / overheatingLoad type :- incandescent- 230V halogen lamps- ELV halogen lamps associa-ted ferromagnetic transformer (inductive)- ELV halogen lamps asso-ciated electronic transformer (capacitive)
230 V AC / 50 Hz
20 ...1 000W
1/10V-input/output(max. 50mA, 30 EV100 / EV102) defined via the local switch
Contact output :1 NO, 250V AC1, potential free
5 EV102*
* Please check availability with your local Hager B&R sales office at time of ordering*
H.16
EV106*
EV108*
FU
TU
RE
RE
LEA
SE
FU
TU
RE
RE
LEA
SE
Dimmer system : 1/10V pilots
EV 106 and EV 108 pilot dimmers- To control several dimmers
or electronic ballasts via the 1/10V output
- Display to show the dim level and for parameter setting
- Wiring of illuminated push buttons possible up to 5mA
- Min/max level setting- Contact output for state information- Dimming rise time setting- Setting of rise time and fall
time EV 108 pilot dimmer- Scene inputs used for over-
ride (3 levels) or simple recall (2 levels).
Use : to control lighting in meeting
and conference rooms, or in restaurants
Dimmers conform to standards EN 50081-1, EN 50082-1,CEI 669-1, CEI 669-2-1.
description characteristics width in I17.5mm
cat.ref.
1/10V pilot dimmer
• To control EV100 and EV102 (max. 30)
• To dim electronic ballasts• Wiring of illuminated
pushbuttons possible up to 5mA
• Display to show the dim level and to set the parameters:
- dimming rise time (4s ..99s)- min dim level (0..49%)- max. dim level (51..99%)Contact output to display the dim state (load is OFF, contact is opened, if load is dimmed the contact is closed). It is used to switch ON/OFF the electronic ballast
230 V M / 50Hz
1/10V - interfaceOutput /max 50mA
contact output :1NO, 250V AC 10A AC1 potential free
4 EV106*
1/10V pilot dimmer with scene input
In addition to EV106 features :• Scene inputs used for
override (3 levels) or simple recall (2)
• For each scene- dimming rise time- scene level- and scene mode (recall or- override)
4 EV108*
* Please check availability with your local Hager B&R sales office at time of ordering*
Con
trol
&
ind
icat
ion
H.17
EE806
EE871
EE870
EE872
Sensitivity:Min. 20%Max. 100%
1 sec5 sec - 15 min
Lux5-1000
Remote Control
I R- +
lux
autotest15 min
5 s5 min
16 m
4 m
8 m 16 m
2,5 m
Ø 6 m
10 m
10 m
α = 220/360°
Motion detectors- IP 55
Premium detectorsThese devices are made forautomatic control of lighting in both the residential and private/public industry sectors.
They automatically switch on lighting when movement is detected. They turn off the circuit after the preset duration.
They bring comfort and enhance security for exterior accesses to residential homes, garages. They also
provide signifi cant savings in lighting power consumption by illuminating only when necessary.
Two Models:Products are equipped with Fresnel lenses that allow high frontal detection performance and downwards detection:- 220° frontal detection zone- Twin 220°/360° to detect in
a frontal & downwards zone.
- Time, Lux, sensitivity are achieved locally, via potentiometers.
- It’s also possible to set the detectors with an IR remote control which provides speed & convenience when setting fi nal adjustments.
- Detectors can be mounted in corners utilising the relevant corner mounting accessory.
description characteristic features
detector - 220°- 220°/360°
IP55230 V~ 50 Hz/60Hz
16 A AC1 potential free2300W incandescent
Detection range: - 220°- 220°/360°
16m frontal & 10m left/right 16m frontal & 10m left/right & 6m diameter down
Lux Timer
Sensitivity
5 to 1000 luxpulse, 5s. -> 15 min (30 min with IR remote control).Min. 20%, max.100%
description cat.ref.
comfort Line
Detector 220° White EE860
Detector 220° Charcoal grey EE861
Detector 220° Titanium grey EE862
evolution Line
Detector 220/360° White EE870
Detector 220/360° Charcoal grey EE871
Detector 220/360° Titanium grey EE872
Remote control IRSets time, sensitivity, lux, detection angle used (for Twin model), lock/unlock, test and override ON/OFF
EE806
Corner mounting accessory White EE855
Corner mounting accessory Charcoal grey EE856
Corner mounting accessory Titanium grey EE857
H.18
EE805
EE804
Motion detectors
descriptionThese devices are made for automatic control of lighting in both the residential and private/public industry sectors.
They automatically switch on lighting when movement is detected and light is needed.
They turn off the light after a preset duration.
- Movement detector for the automatic control of lighting in indoor circulating zones. Surface mounted (EE 804) or flush fitting (EE 805).- Setting The timer and the lux level are defined via potentiometers
- Mounting of EE805 connection system conform of false ceiling installation standards (cable clamp, fixing spring and protection cover)- Output Potential free relay contact 10A, AC1 1000W
description characteristics cat.ref.
Motion detectors - indoor 360o
white surface mount 10A, AC1
1000w
Incandescent
EE804
white flush mount 10A, AC1
1000w
Incandescent
EE805
Con
trol
&
ind
icat
ion
H.19
Innovative techniqueThe patented double lens technique ensures a very precise detection on 360° of a person moving on an area up to 13 x 7 m. The integrated lux-meter makes it also possible to differentiate the proportion of natural and artificial light.
Rotating and adaptableAccording to the architectural constraints, the detection zone can be adjusted with precision thanks to the rotation of lens on 90°.
OverrideThe command entry on the 2 channel presence detector (EE811) and on the presence regulator (EE812) allows the activation
of a lighting circuit (for example via a push button). This facility is ideal for presentations during which the room must completely or partially darkened. When no more presence is detected the module will return to the automatic mode after the pre-selected time delay. Manual dimming is also possible via the same command entry on the presence regulator.
Regulation with constant lighting: nearly a must in all open-plan offices. The presence regulator (EE812) adapts to the artificial light depending on natural light and presence. The light intensity constantly remains fixed according to the preselected set point. An effective and pleasant lighting level can be carried out easily and quickly with the range of Hager DIN rail dimmers.
Settings : lighting, time delay and manual dimming. Adjustable from 5 to 1200 Lux, the lighting/variation can also be set manually via the command entry on the presence regulator. The time delay of the lighting and presence channel can be selected individually from 30 seconds to 1 hour.Basic lighting mode : for safety in hotels, homes, hospitalsand corridors. The
detector will switch on the lighting channel in case of presence. The time delay begins once no more presence is detected. The light will then be reduced to the selected value between 0 and 50%, then released after 15 minutes for the EE812 model.
Master and slave : extended coverageThe presence detectors can be linked together for corridors or large premises. The Slave module will for example detect a presence, inform the Master module which then commands the light depending on luminosity, override and duration of lighting.
Comfortable energy saving …with the presence detectors
Benefi ts :
- Models with 1 or 2 channels- Regulation of presence / light- Detection zone of 360° on 13 x 7 m- Override entry or manual dimming- Natural and artificial light measuring- Wide setting possibilities- Basic lighting mode on presence regulators EE812 - Master/Slave function
For the control or the regulation of lighting depending on presence and natural light The new Hager presence detectors with double lens technique are adapted to all architectural requirements. Whether the regulation of the light depends on occupancy or simply to switch on the lights depending on presence and ambient luminosity, the Hager presence detectors offer the necessary flexibility for each application.Ventilation, ambient temperature or alarms can also be piloted exclusively by the detection of a movement thanks to the second channel. A push button connected on the override entry makes it for example possible to turn-off the light or reduce it to the desired level during a presentation.
comprehensive settings
rectangular capture zone
natural and artificial light measure
rotating front lens
H.20
EE810
EE813
2.5m
6m
DetectionZone
Presence detectors
description characteristics cat.ref.
presence detector 1 channel• relay output light channel- lux level and on delay(duration or pulse) defined viapotentiometers• Slave output for association with EE811/EE812 Lux OFF
230V~ 50Hzμ16A AC1 100W
triac output 0.8A
EE810
Presence detector 2 channels• Relay output light channel- lux level and On delay define via potentiometers- input slave - 230V input used with push- button to toggle the light channel state or with slave in order to enlarge the detection area
• Relay output presence channel- on delay presence defined via potentiometer
230V~ 50Hzμ16A AC1
230V input 50Hzμ2 A AC1
EE811
Presence detector 1/10V• Relay output used to switchON/OFF the electronic ballast• 1/10V output used to dim an electronic ballast or Hagerdimmers EV100/EV102• 230V input used with push button to toggle the channelor change the dimmed level or withslave in order to enlarge thedetection area • 3 functional modes defined viapotentiometersmode 1 : no regulationmode 2 : regulation with local set point via potentiometermode 3 : regulation with set pointdefined via a remote push button
230V~ 50Hzμ10 A AC1
1/10V 50mA230V input 50Hz
EE812
Accessorymounting accessory - surface
mounting accessory - recessed
EE813
WE741
High performance detectorsEE810, EE811 and EE812 High performance presence detector that will be used in premises or in passage areas, where they increase comfort and reduce drastically the energy costs.Combination of a presence area and a motion area. The presence area is especially interesting in offices, where the motion area may be used in long corridors.Head rotation for detection
area adjustment Settings via potentiometersApplicationsEE810 - 1 channel detectorDirect control of a light load or used as a slave for detection area enlargement.- Lux level and ON delay setting via potentiometers- Test mode in order to set lux level and the detection patternEE811 - 2 channels detector- Light relay output for direct control of a light load
- Presence output potential free relay.- Lux level, on delay setting for light channel and presence channel via potentiometers- Input for slave (EE810) and/or remote push button.EE812 - Light regulator 1/10VLight regulator with 1/10V output in order to control electronic ballasts and/or Hager dimmers EV100/EV102. Detector especially dedicated for energy saving and comfort purpose.
- Input for slave (EE810) and/or dimming pushbutton in order to modify the setpoints- Lux level, On delay for light channel and min level via potentiometers- 3 functional modes : no regulation, regulation with local setpoint, regulation with remote setpoint
EE813 : accessory to surface mounting
H.21
Energy Distribution Enclosure systemsWiring Accessories + Building Automation
Cable management
wiring accessories + building automation(sec. K.)
make the switchin your beautiful home
First-class quality, real glass elegance
To keep up with today’s trends, you need to move ahead of them and embrace the technology of tomorrow.
Create a modern look in your home or office - matching glass splashbacks to glass power points; flat screen TVs to flat panel glass switches. The classic and linear appeal of real glass has never been more achievable in so many places at once.
For more information on the available ranges please go to wiring accessories section K.
www.hagerbr.com.au
H.22
The scheduling of energy management solutions, including the management of lighting and heating, help to make life easier while also saving energy. Various loads are only switched on when they are actually needed, thereby saving unnecessary usage of energy. Digital and analogue time switches, delay timers, latching relays, contactors, kWh meters and CTs complete the offer.
Energy distributionModular devices
Mod
ular
dev
ices
I.1
Contactors I.2
Noise free contactors I.3
Choice of contactors I.4
Latching relays I.7
Latching relay auxiliaries I.7
Interface relays I.8
Delay timers I.9
Time lag switches I.10
Analogue time switches modular I.11
Analogue time switches 72 x 72mm I.12
Digital time switches selection chart I.13
Digital time switches I.14
Light sensitive switchesAstronomical time switches I.15
Light sensitive switch - 2 channel I.16
Time switches & light sensitive switches selection chart I.17
I.2
ES240
ES320
ES463
45
58 37
Contactors
contactorsfor the remote switching and control of power circuits (25A-63A AC1)override contactorsallows :permanent ONpermanent OFF# manual override## auto override technical datathe choice of contactor depends upon a number of
parameters e.g.- the nature of the supply- the current it is
switching- the characteristics of the
load- the control voltage
requiredAll contactors carry an Ith load rating. The use of LZ060 (heat dissipation inserts) between all contactors installed
or between contactors and adjacent devices is recommendedoptionscontact choice- normally open (NO)- normally closed (NC)
LZ060 heat dissipationinserts
auxiliary25A contactors will except auxiliary EP071 contact
description type coilAC 50/60Hz
powercircuit50/60Hz
AC1/AC3 width in I17.5mm
cat.ref.
contactors 1NO
1NO
230V
230V
25A-250V
25A-250V
4kW/1.4kW
4kW/1.4kW
1
1
ES110
ES110A#
1NO+1NC 230V 25A-250V 4kW/1.4kW 1 ES210
1NO+1NC 24V 25A-250V 4kW/1.4kW 1 ES239
2NO 230V 25A-250V 4kW/1.4kW 1 ES220
2NO 230V 25A-250V 4kW/1.4kW 1 ES220A#
2NO 230V 25A-250V 4kW/1.4kW 1 ET221##
230V 40A-400V 8.5kW/3.5kW 3 ES240
230V 63A-400V 13kW/5kW 3 ES263
24V 25A-250V 4kW/1.4kW 1 ES224
24V 25A-250V 4kW/1.4kW 1 ES224A#
2NC 230V 25A-250V 4kW/1.4kW 1 ES230
3NO 230V 25A-400V 13kW/4kW 2 ES320
230V 40A-400V 25kW/10kW 3 ES340
230V 40A-400V 25kW/10kW 3 ET341##
4NO 230V 25A-400V 13kW/4kW 2 ES420
230V 25A-400V 13kW/4kW 2 ES420A#
230V 40A-400V 25kW/10kW 3 ES440
230V 63A-400V 40kW/15kW 3 ES463
4NC 230V 40A-400V 25kW/10kW 3 ES480
230V 63A-400V 40kW/15kW 3 ES490
2NO+2NC 230V 25A-250V 4kW/1.4kW 2 ES450
230V 63A-250V 13kW/5kW 3 ES470
auxiliary suitable for 20A contactors 2A-250V 1/2 EP071
heat dissipation insert 1/2 LZ060
I.3
Mod
ular
dev
ices
ESN420B
ESN440B
60
35
5.5
43
Noise free contactors
Noise free Contactorsfor the remote switching and
control of power circuits (25A - 63A AC1)
Eg. lighting, heating, ventilation, pumps and other building automation systems. These contactors are DC driven with integrated rectifier allowing DC or AC voltage control.
Advantages- Hum free- Low noise switching- Position indicator- Coil protection
(varistor)- Suitable for use with
PLCs
description type coilAC 50/60Hzor DC
powercircuit50/60Hz
AC1/AC3 width in 17.5mm
cat.ref.
contactors 2NO 230v 20A-230V 4kW/1.3kW 1 ESN220B
230V 40A-400V 8.7kW/3.7kW 3 ESN240B
230V 63A-400V 13.3kW/5kW 3 ESN263B
3NO 230V 25A-400V 16kW/4kW 2 ESN320B
230V 40A-400V 26kW/11kW 3 ESN340B
4NO 230V 25A-400V 16kW/4kW 2 ESN420B
230V 40A-400V 26kW/11kW 3 ESN440B
230V 63A-400V 40kW/15kW 3 ESN463B
4NC 230V 25A-400V 16kW/4kW 2 ESN430B
3NO+1NC 230V 25A-250V 5kW/1.3kW 2 ESN444B
auxiliary suitable for 25A contactors 6A-250V 1/2 ESN071B
heat dissipation insert 1/2 LZ060
I.4 Subject to technical changes
Choice of contactors
HeatingThe choice of the contactor depends on the mechanical stress (number of operations) and on the electrical heating load i.e. resistive elements, infra-red element, convectors.
Choice of contactorsThe choice of contactor is dependent upon many parameters i.e. operating voltage, size of contacts, number of operations, ambient temperature, type of load supplied etc.
Type of loadLoads are categorised into various AC ratings. Slightly inductive loads (i.e. household appliances and similar applications) are given the category AC-7a. Hager contactors have been tested to IEC61095 which defines the current ratings and utilisation category as follows:
*Ith is the conventional free air thermal current and is the maximum value of test current used during temperature-rise tests. The value of Ith must be at least equal to the maximum value of the current Ie. Ith is a “static current” with no switching involved.
*Ie*
Ie is the rated operational current.This value takes into account:- the rated operational voltage
Ith (The value of Ith must be at least equal to the maximum value of the current Ie.)
Ie is a “dynamic current” allowing the contacts to open and close for a given load utilisation category.
*Utilisation category **ACx*
The Utilisation category defines the intendedapplication and is characterised by- the current Ie
- a voltage- a power-factor
Hager contactors are approved according to EN/IEC 61095 for the utilisation category AC-7a and 7b. Approved to IEC 60947-4 for the utilisation categories ACI and AC3
For AC1 and AC3 ratings see chart below.
Heat dissipation insertsTo avoid any product overheating it is strongly advised to insert a heat dissipation space every 3 contactors up to 40oC and every 2 contactors from 40 to 55oC.
Temperature deratingDerating factor between 40oC and 55oC = 0.9
Please consult us if you require help selectinga suitable contactor.
Maximum load in kW (AC1 / AC7a - eg. heating)
1 module20A
2 module20A
3 module (2 pole)40A
Standard range Noise free Std range Noise free Std range Noise free
Load type Voltage
(a.c.)
Maximumnumber ofoperations
ES110 ES110A
ES210 ES239 ES320 ESN320B
ES220 ES220A ES420 ESN420B
ET221 ES224 ES420A ESN430B
ES224A ES230 ESN220B ES450 ESN444B ES240 ESN240B
AC1/AC7a 230200 000 4kW 4kW 5kW - -
100 000 4kW 4kW 5kW 8.5kW 8.7kW
AC1/AC7a 400200 000 - 13kW 16kW - -
100 000 - 13kW 16kW 8.5kW 8.7kW
3 module (3&4 pole)
40A
3 module (2 pole)63A
3 module (4 pole)63A
Std range
Noise free
Std range
Noise free
Std range
noise free
ES340
Maximumnumber ofoperations
ET341
Voltage(a.c.)
ES440 ESN340B ES470 ES490
Load type ES480 ESN440B ES263 ESN263B ES463 ESN463B
AC1/AC7a 230200 000 - - - - - -
100 000 8.5kW 8.7kW 13kW 13.3kW 13kW 13.3kW
AC1/AC7a 400200 000 - - - - - -
100 000 25kW 26kW 13kW 13.3kW 40kW 40kW
I.5Subject to technical changes
Mod
ular
dev
ices
U R R
M
L1 U
V
M
L2
Single phase Three phase
example:function of a heating installation 200 days/annum, 100 operations per day (1 opening + 1 closing = 2 operations) mechanical life = 10 yearstotal number of operations: 200 x 100 x 10 = 200,000 in that case select an ES 240 to control a load of 4.4 kW (single phase 230V)
Motors (AC3)Single phase 230V Three phase 400V
3 module (3&4 pole)
40A
3 module (2 pole)63A
3 module (4 pole)63A
Std range Noise free Std range Noise free Std range noise free
ES340
Maximumnumber ofoperations
ET341
Voltage(a.c.)
ES440 ESN340B ES470 ES490
Load type ES480 ESN440B ES263 ESN263B ES463 ESN463B
AC3/AC7b 230300 000 - - - - - -
150 000 3.5kW 3.7kW 5kW 5kW 5kW 5kW
AC3/AC7b 400300 000 - - - - - -
150 000 10kW 11kW 5kW 5kW 15kW 15kW
Maximum load in kW (AC3/AC7b-eg motors)
1module20A
2 module20A
3 module (2 pole)40A
Standard range Noise free Std range Noise free Std range Noise free
Load type
Voltage (a.c.)
Maximumnumber ofoperations
ES110 ES110A
ES210 ES239 ES320 ESN320B
ES220 ES220A ES420 ESN420B
ET221 ES224 ES420A ESN430B
ES224A ES230 ESN220B ES450 ESN444B ES240 ESN240B
AC3/AC7b 230300 000 1.4kW 1.3kW 1.4kW 1.4kW - -
150 000 1.4kW 1.3kW 1.4kW 1.4kW 3.5kW 3.7kW
AC3/AC7b 400500 000 - - 4kW 4kW - -
150 000 - - 4kW 4kW 3.5kW 3.7kW
I.6 Subject to technical changes
Choice of contactors
Contactor Selection (lighting)
The table below indicates the number of lamps (or dual fi ttings) that can be connected to each pole of the contactor on 230V 50hz curcuits.
1-module 2-module 3-module 3-module
Type Lamp power
Maximum capacitor value per fi tting
25A / 20A 25A 40A 63A
Standard Esxxx
Noise free ESNxxxB
Standard Esxxx
Noise free ESNxxxB
Standard Esxxx
Noise free ESNxxxB
Standard Esxxx
Noise free ESNxxxB
Incandescent lamps
Tungsten & halogen lamps
40W 50 50 50 50 125 100 175 125
60W 33 33 33 33 83 65 116 85
75W 26 26 26 26 66 53 93 66
100W 20 20 20 20 50 40 70 50
150W 13 13 13 13 33 26 46 33
200W 10 10 10 10 25 20 35 25
300W 6 6 6 6 16 13 23 16
500W 4 3 4 3 10 8 14 10
1000W 2 1 2 1 5 4 7 5
Fluorescent tubes
Energy saving lamp Compact Fluoro lamp
11W 90 67 90 67 125 93 180 135
15W 66 49 66 49 92 69 133 99
20W 50 37 50 37 69 51 100 75
23W 43 32 43 32 60 45 86 64
Single - non compensated
18W 30 22 30 24 85 90 120 140
Single -parallel compensation
18W 4.5 μF 18 7 18 8 45 48 60 73
36W 4.5 μF 15 7 15 8 40 48 55 73
58W 7 μF 13 4 13 5 30 31 40 47
Double - parallel compensation (number of double fi ttings)
2 x 18W 4.5 μF 18 6 18 8 44 48 60 72
2 x 36W 10 μF 14 6 14 8 40 48 54 72
2 x 58W 18 μF 10 4 10 4 30 30 40 46
Single - electronic ballast
18W 35 25 35 35 66 100 103 140
36W 30 15 30 20 56 52 85 75
58W 17 12 17 19 31 50 47 72
Double - electronic ballast (number of double fi ttings)
2 x 18W 17 12 17 17 33 50 51 70
2 x 36W 15 7 15 10 28 26 42 38
2 x 58W 8 7 8 9 15 25 23 36
Discharge lamps
Low pressure sodium -vapour lamps (compensated)
35W 20 μF 5 1 5 1 10 11 15 11
55W 20 μF 5 1 5 1 10 11 15 11
90W 30 μF 4 1 4 1 8 8 11 8
135W 40 μF 2 - 2 - 5 5 7 5
180W 45 μF 2 - 2 - 4 4 6 4
High pressure sodium -vapour lamps (compensated)
50W 8 μF 8 6 8 6 25 18 35 26
70W 12 μF 6 4 6 4 18 13 25 19
110W 12 μF 5 4 5 4 15 11 18 13
150W 20 μF 4 1 4 1 13 11 15 16
250W 36 μF 2 - 2 1 8 6 10 10
400W 45 μF 2 - 2 - 6 4 8 6
1000W 100 μF 1 - 1 - 4 2 5 3
Metal Halide -vapour lamp (compensated)
35W 6 μF 8 5 8 6 31 36 42 50
70W 12 μF 6 2 6 3 15 18 20 25
150W 20 μF 3 1 3 1 9 11 16 15
250W 32 μF 2 0 2 1 5 6 7 9
400W 45 μF 1 0 1 1 3 6 5 8
I.7
Mod
ular
dev
ices
* Please check availability with your local Hager B&R sales office at time of ordering*
* Please check availability with your local Hager B&R sales office at time of ordering*
EPN510*
�� ��
��
EPN 050*
45
68
44
FU
TU
RE
RE
LEA
SE
FU
TU
RE
RE
LEA
SE
Latching relays
descriptionfor control of lighting circuits in private buildings, small industry buildings and administration buildings. Latching relays operate when pulsed by a signal voltage. The pulse can be provided via a push button or switch. The first impulse sets the relay into its set (opposite)
state, the next impulse returns it to its reset (original) state.connection capacity- 10 rigid cables- 6 flexible cables
description type coilVac50/60Hz
coilVdc
powercircuitAC1
width in 17.5mm
cat.ref.
latching
relays
1NO 230 110 16A-250V 1 EPN510*
2NO 230 110 16A-250V 1 EPN520*
24 12 16A-250V 1 EPN524*
1NC + 1NO 230 110 16A-250V 1 EPN515*
Auxiliaries for centralised control. The EPN 050 allows the centralised control of several light sources which can be turned on or off simultaneously the separate switching by pushing the pushbuttons, which are connected with the latching
relay, remains possible.
The EPN 052 allows a generic central control of individual central on/off EPN 050
Auxiliary contact A remote signalling can be realised with the auxiliary contact EPN 051.
Auxiliary for control by maintained contact.
When control devices with permanent impulse are externally driven, e.g. time switches or limit switches, an impulse control directly to the latching relay’s coil is possible with the auxiliary contact EPN 053.
Connection latching relay + auxiliary
Several auxiliaries can be combined with the latching relay.
Connection capacity 10I rigid cables 6I flexible cables
description characteristics width in 17.5mm
cat.ref.
auxiliary for centralisedcontrol
24 to 230V AC 0.5 EPN050*
Latching relays auxiliaries
I.8
EN145
A1 1
A2 2 4
�� ��
�� ��
�� ��
�� ��
�� ��
��
EPN051*
EPN052*
EPN053*
FU
TU
RE
RE
LEA
SE
FU
TU
RE
RE
LEA
SE
FU
TU
RE
RE
LEA
SE
Latching relays auxiliaries cont..
descriptionto interface between low voltage and extra low voltage circuits to ensure galvanic insulation between LV and ELV to 4kVapplicationinterface between fire alarm,
burglar alarm and other ELV systems and main distribution circuits
connection capacity- 6mm2 rigid cables- 4mm2 flexible cables
description characteristics width in I17.5mm
cat.ref.
interface relaysELV/LV 1 way
output: 1 changeover
coil voltage: 10 to 26V AC/DC
contactmax. 5A 230V~ -min. 10mA - 12V DC
1 EN145
description characteristics width in I17.5mm
cat.ref.
auxiliary contact 2A 250 V AC 0.5 EPN051*
auxiliary for multilevelled centralisedcontrol
24 to 230V AC 0.5 EPN052*
auxiliary for controlby maintained contact
24 to 230V AC 0.5 EPN053*
Interface relays
I.9
Mod
ular
dev
ices
EZN001
EZN006
Cd
S
T
Control
Output
Cd
S
T
Control
Output
Cd
S
T
Control
Output
��
�
�
Control
Output
��
�
�
Control
Output
Delay timers
DescriptionTo provide all types ofautomatic control i.e. lighting, ventilation, watering, machine preheating, automatic door and visual audible indication, cycle control etc.
ApplicationsFor timing and automation in domestic and commercial premises. The input signal
can be via various switching devices (push button, latching switch, time clock etc.) and the timed output used to control theapplication.
Technical dataVoltage range : 12 & 24 to 48V DC12 & 24 to 230V ACAdjustable: time delay from
0.1s to 10 hours.LED indicatorcomplies with EN 60669-2-1
Connection capacity :6mm2 max flexible 1.5 - 10mm2 rigid
description characteristics width in I17.5mm
cat.ref.
Delay ON 1 c/o contact8A / 230V~ AC1 time delay T : 0.1s to 10hr
1 EZN001
1 Delay OFF 1 c/o contact8A / 230V~ AC1time delay T : 0.1s to 10hr
1 EZN002
Adjustable time ON 1 c/o contact8A / 230V~ AC1time delay T : 0.1s to 10hr
1 EZN003
Timer 1 c/o contact8A / 230V~ AC1time delay T : 0.1s to 10hr
1 EZN004
Symmetrical flasher 1 c/o contact8A / 230V~ AC1time delay T : 0.1s to 10hr
1 EZN005
Multifunction6 individual functionsincluding :D - delay onC - delay offE - adjustable time ONB - adjustable time OFFA - timerF - symmetrical flasher - ON - OFF
1 c/o contact8A / 230V~ AC1time delay T : 0.1s to 10hr
1 EZN006
I.10
EMN001
EM002
FU
TU
RE
RE
LEA
SE
Time lag switches
description characteristics width in I17.5mm
cat.ref.
Multifunction staircase time lag switch
- basic staircase time lag switch- pre-warning mode- double delay mode30s to 10min or 1hr- double delay with pre-warning mode
supply voltage : 230V 50/60Hz
16A - 250V AC1
2300W incandescenthalogen and fluoro
1 EMN005
Add-on blockpre-warning device
voltage rating : 230V 50/60Hzrestart facilitypre-warning to switch-off bydimming the lights to 50% level24s prior to switch offoutput power :1000W incandescent1000W halogennot suitable for use with discharge lamp
2 EM002
Standard staircasetime lag switch
adjustable time delay setting: 30s until 10minretrigger
supply voltage : 230V 50/60Hz
16A - 250V AC1
2300W incandescenthalogen and fluoro
1 EMN001
DescriptionTime lag switches provide control of lighting circuits with automatic switch-off after a pre-set time. (e.g. for staircase, corridors lighting).
Compact design with a 2 position switch permanent/timed lighting implementation facility.
EMN005 incorporate a pre-warning of switch OFF to improve the safety for users and a double delay function:30s to 10min or 1hr by pressing the push-button for more than 3s.Complies with EN 60669-2-1
FU
TU
RE
RE
LEA
SE
I.11
Mod
ular
dev
ices
* Please check availability with your local Hager B&R sales office at time of ordering*
EH210*
EH010
EH111
FU
TU
RE
RE
LEA
SE
FU
TU
RE
RE
LEA
SE
FU
TU
RE
RE
LEA
SE
Analogue time switches modular
DescriptionElectromechanical time switches 1 channel for daily or weekly programming.To control lighting, heating, household appliances, shop windows etc.To improve comfort and save energy.
ApplicationsDomestic and commercialpremises.DIN rail mounting
Complies with EN60730
Technical data- programming by captive segments.- manual override : On 1 module devices : - automatic - permanent ON On 2 and 3 module devices : - automatic - permanent ON - permanent OFF
Minimum switching time:- 15 min for daily versions- 2 hours for weekly versions- 15 min and 2 hours on the daily+weekly version
Connection capacity :1 to 4mm2
description characteristic width in I17.5mm
cat.ref.
Analogue time switches modular compact
230 V50 Hz
1 NO16 A - 250 V AC1
24hrwithout battery reserve
24hrreserve: 200hrs
1
1
EH010
EH011
Analogue time switches standard modular version
230 V50 Hz
1 NO changeover16 A - 250 V AC1
24hrwithout battery reserve
24hrwithout battery reserve
24hrreserve: 200hrs
24hrreserve: 200hrs
7dayreserve: 200hrs
7dayreserve: 200hrs
3
2
3
2
3
2
EH110
EH210*
EH111
EH211*
EH171
EH271*
I.12
EH771
EH711
Analogue time switches 72 x 72mm
descriptionfor daily or weekly programming. 1 channel time switches for the control of lighting, heating, household appliances, shop windows etc. To improve comfort and save money.applicationsdomestic, commercial premises
technical data- suitable for surface, flush
or DIN rail mounting- programming by captive
segments- manual override with
automatic return toprogrammed
- operating reserve: 200hrsafter connection for120hrs
- output: voltage free
changeover contact16A/250V
daily version:programming in steps of 10 minutes. Minimum time between 2 switching intervals : 20min
weekly version:programming in steps of one hour.- minimum time between 2
switching intervals : 2hrs- switching accuracy : 10min
description characteristics cat.ref.
1 channel daily cycle supply : 230V 50/60Hz
without battery reserve 24 hr dial Manual override
EH710
with battery reserve 24 hr dial Manual override
EH711
1 channel weekly cycle
supply : 230V 50/60Hz
with battery reserve 7 day dial Manual override
EH771
I.13Subject to technical changes
Pow
er in
terf
ace
Pro
gram
min
g
Mo
du
lew
idth
op
erat
ing
cy
cle
pro
gra
m
step
sco
nta
cts/
chan
nel
sd
isp
lay
pro
gra
m
key
astr
op
uls
ecy
cle
day
-lig
ht
savi
ng
exte
rnal
in
pu
to
verr
ides
keyb
oar
d
lock
ing
ho
liday
ran
do
mh
ou
r co
un
ter
EG
010
1
1
EG
071
1
1
EG
103E
2
1
EG
203E
2
2
EG
493E
4
4
EG
293E
4
2
EG
403E
4
4
EE
180
2
1
EE
181
2
2
5656300
300
300
565620
6
Digital time switch - selection chart
I.14
EG071
EG403E
EG203E
Digital time switches
description characteristics width in I17.5mm
cat.ref
1 channel daily cycle
5 adjustable pre-recordedprograms : 6 commutations max per day (3 ON and 3 OFF)230V 50/60 Hz
1 EG010
1 channel weekly cycle
capacity : 20 program steps230V 50/60 Hz
1 EG071
1 channel weekly cycle
capacity: 56 program steps version delivered with key EG005
2 EG103E
2 channels weekly cycle
capacity: 56 program steps version delivered with key EG005
2 EG203E
4 channels weekly time switch
voltage rating: 230V~ 50/60 Hzoutput: 3 changeover contacts10A - 250V~ AC1 1 NO1NO contact : 10A - 250V ~ AC1 delivered with programming key
4 EG403E
2 channels yearly time switch
voltage rating: 230V~ 50/60 Hzoutput: 2 changeover contacts10A - 250V~ AC1
4 EG293B
4 channels yearly time switch
voltage rating: 230V~ 50/60 Hzoutput: 3 changeover contacts10A - 250V~ AC11NO contact: 10A - 250V ~ AC1 delivered with programming key
4 EG493E
Programming key
for EG403E, EG493E, EG293B EG007
Programming key
for EG103E / EG203E EG005
Keypad locking key
for EG103E / EG203E EG004
Interface and software
for computer PC with software on CD and USB
EG003U
descriptionfor the control of lighting,school bells, pumps,etc.applicationsdomestic and commercial premises, schools, irrigation.1 module time switch- 1 channel cycle- manual over ride- operating reserve 3 years- 5 pre-recorded (adjustable)
programs (EG010)- 20 program steps (EG070)
2 module time switch- ability to download
program ontomultiple time switchesvia EG005
- keypad locking key EG004- permanent & temporary
over ride & pulse- operating reserve 5 years- 56 program steps- software programming
option- bar graph for quick
program overview- holiday mode- back lit display- automatic summer/
winter adjustment
4 module time switch- ability to download
program onto multipletime switches via EG003U
- impulse control- manual over ride & pulse- programmable without
mains supply- operating reserve 5 years
300 program steps- automatic summer/ winter adjustment
I.15
Mod
ular
dev
ices
EE101*
EE110*
EE702
EE180*
EG005
FU
TU
RE
RE
LEA
SE
FU
TU
RE
RE
LEA
SE
FU
TU
RE
RE
LEA
SE
Light sensitive switchesAstronomical time switches
Light sensitive switchesA photo-electric cell measures the light level and in conjuction with the relay provides ON / OFF control of a circuit.This device controls lighting circuits in relation to ambient light, based on user settings.Front cover sealabilityApplicationsStreet lighting, display lighting, illuminated signes etc.Protected cable clamps
capacity :rigid : 1.5 to 10mm2
flexible : 1 to 6mm2
LED shows status of changeover contact.4 position override switch allowing:- auto: normal operating mode- on: permanently switched on- off: permanently switched off- test: setting mode for easy adjustmentoutput : 1 changeover AC1contact 16A AC1 230V 8A AC1 (EE702)Maximum distance : 50m between photocell & controller
Must be used in conjunction with a suitable rated contactor Astronomical time switches.The hager range is composed of two Astronomical time switches EE180/EE181The range offers the following features :- Programming of the lighting
control- Automatic change of winter /
summer time- Astro program and expert
program with individual Astro
program steps- Programming for day
or group of days (same concept as our existing clocks with key)
- Anticipation ON- Maintained ON- Temporary overrides- Programming of holidays
period- Programming via the PC
software and the associated interface (EG003)
- Weekly program
description characteristics with in I17.5mm
cat.ref.
Light sensitive switch
delivered with :a separate surface photo electric cell EE003 (EE100)a separate flush photo electric cell EE002 (EE101)
Voltage rating :230 V AC +10-15 % 50 Hzoutput : 1 changeover16 A - 250 V AC 1
sensitivity : 2 ranges- 5 to 100 lux- 50 to 2000 lux
3
3
EE100*
EE101*
Compact light switch
IP 55 / integrated cell
normally open contact16A AC12-1000W incandescentswitching delay either fixed or adjustable (1s - 120s)
- EE702
Programmable light sensitive switch with surface cell
daily cycleelectromech. switch
weekly cycleelectronical programfree setting
5
3
EE110*
EE171*
Astronomical time switch(weekly cycle)
delivered with key EG005.
1 channel 230V AC 50 Hzchangeover contact16A AC1operating reserve lithium battery 5 years
2 channels 230V AC 50 Hz2 changeover contacts16A AC1operating reserve lithium battery 5 years
EE180*
EE181*
* Please check availability with your local Hager B&R sales office at time of ordering*
I.16
EE200*
EE202*
EE002 EE003
FU
TU
RE
RE
LEA
SE
FU
TU
RE
RE
LEA
SE
Light sensitive switches2 channel
Light sensitive switch, 2 channel up to 20000 Lux
By controlling exterior and interior light sources, the light sensitive switches enable great energy savings.Providing consistent & controlled lighting across all areas while making the most of
the natural light source.Examples of use: offices, classrooms, storage rooms, production areas...
Characteristics“Auto-Test”switch:- “Auto” position, channel switching is 30s,- For each channel:
- luminance threshold setting- state display- switch: manual override, off-switch, sensitivity range selection.
Light sensitive switchEE2022 more inputs for various automation devices controlling
(time switch, presence detector, push button...).
These products can be linked together to increase the number of levels and outputs controlled by one same cell.
description characteristics width in I17.5mm
cat.ref.
Two channels light sensitive switch
the output is switched on/off according to the pre-defined lux level
230 V 50/60Hz2 contacts NO 16 A 250 VAC AC1- delivered without cell,can be associate with:- flush cell EE002- or surface cell EE003for each channel :- threshold setting- state indication LED - 4 positions selection switch : - On - Off - 2... 200 Lux - 200 ...20 000 Lux.EE200 delivered with surface cell EE003
4
4
EE200*
EE201*
Two channels light sensitive switch for cascading
As well as EE200, it integrates 2 inputs for 2 operating modes. The selected mode always applies to the both outputs.
same characteristics than EE200 above + additional automation.input E1 : 230 V, used to connect a contact like: switch, timer... operating mode selector : - mode 1 : automatic- mode 2 : half automatic, allows time delayed function (adjustable time: 1 min., 5 min., 10 min, 30 min., 45 min., 1 h 30, 2 h).delivered without cell,can be associated with :- flush cell EE002- or surface cell EE003
EE202 delivered with surface cell EE003
4
4
EE202*
EE203*
Cell flush cellIP54 for EE100, 101, 110 & 170
surface cellIP54 for EE100, 101, 110 & 170
EE002
EE003
* Please check availability with your local Hager B&R sales office at time of ordering*
I.17Subject to technical changes
Pow
er in
terf
ace
Pro
gram
min
g
wid
th in
1
:E
H0
10
, E
H0
11
EH
71
0,
EH
71
1,
EH
77
1
wid
th in
3 :
EH
01
0,E
H1
11
, E
H1
71
wid
th in
2
:E
H2
10
, E
H2
71
Analogue time switches selection chart
Technic
al
chara
cte
rist
ics
EH
010
EH
011
EH
110
EH
111
EH
171
EH
210
EH
211
EH
271
EH
710
EH
711
EH
771
Wid
th in
z
17.5
mm
11
33
32
22
surfa
ce m
ount
ed (7
2mm
x 7
2mm
)
Vol
tage
230V
230V
230V
230V
230V
230V
230V
230V
230V
230V
230V
Ope
ratin
g cy
cle
24 h
rs.
24 h
rs.
24 h
rs.
24 h
rs.
7 da
ys24
hrs
.24
hrs
.7
days
24 h
rs.
24 h
rs.
7 da
ys
Min
imum
sw
itchi
ng15
min
15 m
in15
min
15 m
in2
hrs.
30 m
in30
min
3 hr
s 30
20 m
in20
min
2 hr
s.
Sup
ply
failu
re
rese
rve
-20
0 hr
s.-
200
hrs.
200
hrs.
-20
0 hr
s.20
0 hr
s.-
200
hrs.
200
hrs.
Man
ual
over
ride
auto
/on
auto
/on
auto
/on
/off
auto
/on
/off
auto
/on
/off
auto
/on
/off
auto
/on
/off
auto
/on
/off
on/o
ffon
/off
on/o
ff
I.18I.18
Insulated busbars and connectors make it quick and easy to connect to devices mounted in loadcentres and panelboards.
Energy distributionConnection
Con
nect
ion
J.1
Insulated busbars and connectors J.1
J.2
KM03A
KB380A
KM035
Insulated busbars and connectors
descriptiona range of connection devices to simplify installation of modular devices such as MCB’s, RCD’s etc...
description characteristics width in I17.5mm
catref.
insulated busbars - fork type
1 phase 80A 12 KDN180A
1 phase 80A 56 KDN180B
1 phase 80A 18 KD180G
2 phase 80A 12 KDN280A
2 phase 80A 18 KD280G
3 phase 80A 12 KDN380A
3 phase 80A 18 KD380G
insulated busbars - tongue type
1 phase 80A 24 KB190C
2 phase 80A 12 KB280A
2 phase 80A 18 KB280G
3 phase 80A 12 KB380A
3 phase 80A 18 KB380G
insulating busbar ends -
KDN2XX/KDN3XX KZN023
cable connectors - tongue type
connection from top of cables : 25mm2
KF81A
connection from top of cables : 2 x 16 mm2
KF82A
connection from side for cables : 25mm2
KF83A
cable connectors - fork type connection from side for cables : 25mm2
KF84A
RCD neutral links 3 hole for fitting to RCD’s
KM03A
35mm2 cable adaptor to suit Golf enclosures
KM035
eco-ficient®
energy saving solutions
J.3
Energy Distribution Enclosure systemsWiring Accessories + Building Automation
Cable management
Saving energy - look global, act local
The energy-saving systems, products and services we offer all help reduce energy and the consumption of natural resources. All Hager products products comply with the European RoHS and WEEE directives and environment management systems such as ISO 14001.Whenever Hager is active, we contribute to measures for ecological efficiency and environmental protection for a safe, clean and healthy environment for consumers, users of our products, employees and the public at large.
www.hagerbr.com.au/eco-ficient
hager B&R - terms and conditions of saleACN 061 639 576 ABN 84 061 639 576
1. GENERALThese conditions of sale apply to any sale of items or equipment of the
Company or, where a quotation is made, they shall form part of that
quotation. No variation or cancellation of any of these Conditions of
Sale shall be binding on the Company unless agreed by a responsible
officer of the Company in writing. No agent or representative has
the authority to waive or alter these terms and conditions.
2. PRECEDENCEIn the event of conflict between these conditions and those
which may be included in, or implied by, any document forming
part of any enquiry, specification, order or contract then these
conditions shall prevail except insofar as they are expressly
varied by the Company in writing. If any condition is contrary to
or excluded by law these conditions shall be modified but only to
the extent of excluding that part of the conditions affected.
3. ACCEPTANCEA quotation is not to be construed as an offer or obligation to sell and
the Company reserves the right to accept or reject any orders received.
4. TERMS OF PAYMENTS(a) The purchaser has to pay for goods within 30 days of purchase.
(b) The purchaser must also pay for goods and services tax,
and other duties, taxes or government charges.
5. SURCHARGEA surcharge of $2.50 will be applied to all invoices with a
value of $20.00 or any amount less than $20.00.
6. PRICES(a) All prices are subject to change without notice and orders
are accepted by the Company on the condition that they
will be invoiced at the prices ruling at the date of despatch.
All prices are strictly net unless otherwise stated.
(b) Every endeavour will be made to give 30 days notice of any increase.
(c) All prices shown in published catalogues or price lists are
recommended selling prices only & there is no obligation
on the part of any reseller to maintain such prices.
(d) A quotation includes only such goods as are specified therein.
We reserve the right to cancel any sale where goods offered ex
stock have been previously sold or otherwise committed.
7. FREIGHT(a) Unless otherwise stated prices include delivery to purchaser’s
stores within the metropolitan areas of Australian capital cities or
major centres by normal surface means, and packing suitable
for such transport for orders of value of $250 or more.
(b) For orders less than $250 the purchaser shall nominate the
preferred freight method and be responsible for all freight charges.
(c) Goods dispatched to other destinations are sold on a Free on
Transport (FOT) basis. Where the purchaser requires freight
to be prepaid all expenses will be to his account at cost.
(d) Freight cost on return of any goods which are not in accordance
with Purchaser’s order will only be paid by the Company
if returned by the Company’s nominated transport.
8. TAXThe prices quoted do not include sales or goods
and services tax unless specifically stated.
9. DELIVERYThe delivery period quoted commences from the date the Company
receives sufficient information to proceed with supply or from the date the
Company receives the Purchaser’s written order, whichever is the later
date. Quoted delivery dates are subject to confirmation when placing
the order. Unless otherwise agreed by the Company in writing, the
Company shall not in any event be liable to the Purchaser for any delay
in the delivery or any non-delivery of the goods or any part of them.
10. CREDITSGoods will not be accepted for credit without prior approval of
personnel at the Company’s nearest Sales Office. All goods approved
for return shall be returned freight pre-paid and subject to a 15%
restocking charge. Non-Standard products will not be credited.
11. CANCELLATION OR VARIATIONAn order may, at the Company’s option, be terminated in the event
of insolvency of the Purchaser or of execution being levied against
any of the goods of the Purchaser or of the Purchaser being placed
in liquidation, whether voluntarily or otherwise or of a mortgagee
entering into possession of any assets of the Purchaser. An order
may be varied only if such variation is accepted by the Company
in writing. A variation or cancellation by the Purchaser is subject to
agreement by the Company and in any event is subject to the Company
being indemnified by the Purchaser against any loss or damage.
12. PURCHASER’S SPECIFICATIONSThe Company shall not be deemed to have agreed to comply with
any specifications and drawings referred to in any order unless such
specifications and drawings have been produced to the Company
prior to the delivery of goods and are signed by the Company.
13. VALIDITYUnless otherwise stated quotations are open for acceptance for
a period of 30 days from the date of quotation and thereafter are
subject to confirmation before acceptance. If on acceptance of
a quotation the delivery date required exceeds a period of sixty
(60) clear days then the company may amend the quotation.
Furthermore in the event of alterations to design or specifications
all quotations given are subject to withdrawal or variation at any
time prior to acceptance. Unless confirmed in writing by the
Company any verbal agreement to vary undertakings assurances
or understandings relevant to this quotation shall not be binding.
14. INSPECTIONThe Purchaser shall inspect the products delivered on their
arrival. If the Purchaser considers that the products are not
in accordance with the contract written notice must be given
to the Company within seven (7) clear days and if no notice
is received by the Company within that time the products are
deemed to be in all respects in accordance with the contract.
hager B&R - terms and conditions of saleACN 061 639 576 ABN 84 061 639 576
15. PACKINGUnless stated otherwise in the quotation the price quoted includes
packing in accordance with the Company’s standard practice. Any
other packing requested by the Purchaser or deemed necessary
by the Company will be charged in addition to the price quoted.
16. DAMAGE OR LOSS IN TRANSITWhere carriage is the responsibility of the Company, the Company
will repair or may replace free of charge contract goods lost or
damaged in transit to the contractual point of delivery provided
written notice of such loss or damage is given to the Company
within three days of delivery or expected delivery, or within such
times as will enable that Company to comply with the carrier’s
conditions of carriage affecting loss or damage in transit.
17. RISKThe goods shall be at the risk of the Purchaser from the time
of their delivery to the Purchaser’s store (where carriage is
the responsibility of the Company) or otherwise from the
time of their delivery to the Purchaser or its carrier.
18. PRODUCT DESIGNThe Company engages in a policy of continuous development and
improvement of its products. Therefore the Company reserves
the right to alter the design and/or specifications of any product
or equipment without notice and without incurring liability.
19. WARRANTYAll goods which are the Company’s own are guaranteed against faulty
workmanship, materials or design, for a period of twenty-four (24) months
from the date of despatch, after which all liability on the part of the
Company ceases. The guarantee does not apply in the following cases: -
- defect arising from materials supplied by the Purchaser
or from a design requested by the Purchaser
- replacements or repairs resulting from normal wear of
units and machinery, corrosive atmosphere, damage
or injury caused by lack of care, insufficient inspection
or maintenance, or improper use of the goods
- failure attributable to fortuitous circumstances or “force majeure”.
The guarantee consists of repairing, modifying or replacing the parts or
units recognised as defective within the shortest time at the Company’s
expense, inclusive of parts and labour, but exclusive of transport and/or
travelling expense. Subject to the above, the Company’s liability and that
of its resellers is wholly limited to the original cost of the product sold.
Any unauthorised repairs or alterations to the equipment shall
invalidate this warranty. In the case of goods not of the manufacture
of the Company or its principals, the Company undertakes that it
will, if requested in writing by the Purchaser, make all reasonable
endeavours in assisting the Purchaser to obtain from the manufacturer
the benefit of any guarantee or warranty which the manufacturer
may have expressly given as to the quality or fitness for any purpose
of the goods, except as may otherwise be provided for by law.
The fulfilment of this undertaking shall constitute the Company’s sole
liability in respect of any faulty goods not of the manufacture of the
Company or its principals. Neither the reseller nor the Company shall
be liable for any injury, damages, expense, or loss of profit, direct or
consequential, arising out of the use or installation of products supplied
by the Company all of which are supplied at the sole risk of the user.
This warranty is in addition to any statutory warranty which a Purchaser
cannot waive but all other warranties are waived by the Purchaser.
20. DEFAULT OF PURCHASERIf the Purchaser defaults in the due observance or performance of
any or all of his obligations under any contract arising out of this offer
or being a company takes or shall have taken against it any action
for the winding up of the Company or the placing of the Company
under official management or receivership, or if a mortgagee of the
Purchaser takes possession of any of the Purchaser’s assets or being
an individual the Purchaser petitions for his bankruptcy or seeks to
assign his estate for the benefit of his creditors then the Company
without prejudice to any other rights or remedies open to it may:-
(a) determine the contract and or suspend manufacture or delivery,
installation, commissioning or testing of any goods then outstanding
(b) retain any security given or money paid by the Purchaser
or available through enforcement of guarantee or security
bonds lodged and apply this against the loss and damages
incurred by it in the performance of the contract
(c) take such steps as it may deem necessary to mitigate
the damage suffered including the putting to use, hiring
out, sale or disposal of any goods supplied, or to be
supplied under the contract and in its possession
(d) exercise its rights under condition 21.
21. TITLE TO GOODSProperty in the goods does not pass to the purchaser until they,
and all other goods supplied by the company to the purchaser, have
been paid for in full. Until property passes to the purchaser:-
(a) The purchaser must store the goods so that they
are clearly identified as the company’s goods
(b) The purchaser holds the goods solely as Bailee for the company
(c) The purchaser may resell the goods as long as the purchaser
holds any money received in trust for the company; and
(d) The company may enter the purchaser’s
premises and repossess the goods.
Hager B&R Pty LtdACN 061 639 576Unit 14-17 Riverside Centre148 James Ruse DriveParramatta NSW 2150Ph (02) 9762 0200Fx (02) 9687 0022www.hagerbr.com.au
State Offices
New South WalesHager B&R Pty LtdUnit 14-17 Riverside Centre148 James Ruse DriveParramatta NSW 2150Ph (02) 9762 0200Fx (02) 9687 0011
New South Wales(Newcastle)Ross Joice Agencies Pty Ltd109-111 Broadmeadow RoadBroadmeadow NSW 2292Ph (02) 4961 4433Fx (02) 4961 2498
VictoriaHager B&R Pty Ltd50-52 Sunmore CloseHeatherton VIC 3202Ph (03) 8588 8400Fx (03) 8588 8401
Western AustraliaHager B&R Pty Ltd20 Millrose DriveMalaga WA 6090Ph (08) 9248 9744Fx (08) 9248 2033
Queensland(Brisbane)Hager B&R Pty LtdBrisbane South Industrial Park51 Stradbroke StreetHeathwood QLD 4110Ph (07) 3714 1111Fx (07) 3714 1091
Queensland(Townsville)Hager B&R Pty Ltd25 Dalrymple RoadGarbutt QLD 4814Ph (07) 4775 6255Fx (07) 4779 6736
South AustraliaB&R Enclosures Pty Ltd505 Grand Junction RoadWingfield SA 5013Ph (08) 8243 1166Fx (08) 8268 3675
Northern TerritoryJewell Distributors Pty LtdCnr Hidden Valley& Beaton RoadsBerrimah NT 0828PO Box 39362Winnellie NT 0821Ph (08) 8947 0870Fx (08) 8947 0764
Tasmania(Launceston)W.P. Martin Pty Ltd85 Elizabeth StreetLaunceston TAS 7250Ph (03) 6331 5545Fx (03) 6331 4256