DOCUMENT COVER SHEET
Direct Stroke Lightning Protection Calculation
400 / 220 / 33kV Indrapuram Substation
0 27.11.12Rev. Date Description PREPARED BY Checked By Approved By
PROJECT :
NAME DATE DOCUMENT STATUS DOCUMENT TITLE SHEET SIZE
VIK 27.11.12 A4
For Construction
As Built DOCUMENT NO. NO. OF SHEETS
COVER + 06
Western Uttar Pradesh Power Transmission Corporation Limited
S-3, 2nd Floor,Aditya Mega Mall,Indirapuram,Ghaziabad 201010,
Megha Engineering and Infrastructure Limited
7th floor Tower c Building No. 10 DLF Cyber city phase-II Gurgaon India
765/400 kV Intra - State Transmission Project.
PREPARED BY
For Approval
Direct Stroke Lightning Protection Calculation
CHECKED BY
APPROVED BY
![Page 2: Dslp Calculation by Vikas](https://reader036.vdocuments.us/reader036/viewer/2022082315/55cf9a76550346d033a1d94c/html5/thumbnails/2.jpg)
Substation Name Document Name Document No.
TABLE OF CONTENTS
CLAUSE NO. DESCRIPTION SHEET NO.
1.0 PURPOSE 2
2.0 CODES & STANDARDS 2
3.0 SIZING CRITERIA 2
4.0 FORMULAE USED FOR CALCULATIONS 3
5.0 CALCULATION 4
6.0 CONCLUSION 6
Sheet No. 1 of 6
400/220/33kV Indrapuram Substation
Direct stroke lightning protection Calculations
![Page 3: Dslp Calculation by Vikas](https://reader036.vdocuments.us/reader036/viewer/2022082315/55cf9a76550346d033a1d94c/html5/thumbnails/3.jpg)
Substation Name Document Name Document No.
1.0 PURPOSE:
2.0 CODES & STANDARDS:
a) High Voltage Engineering by " Prof.Razevig"
3.0 SIZING CRITERIA:
3.1 The height of Lightning Masts depend on the
a) Height of the equipment to be protected.
b) Area to be protected.
3.2 Data for 400KV Switchyard:
a) Height of Lightning mast h 40 m
b) Height of the livepart to be protected: hx 10 m
All the heights has taken from the plinth level.
3.2 Data for 220KV Switchyard:
a) Height of Lightning mast h 40 m
b) Height of the livepart to be protected: hx 6 m
All the heights has taken from the plinth level.
3.2 Data for 33KV Switchyard:
a) Height of Lightning mast h 40 m
b) Height of the livepart to be protected: hx 4 m
All the heights has taken from the plinth level.
SHEET NO. 2 OF 6
400/220/33 KV Indrapuram Substation
Direct stroke lightning protection Calculations
The purpose of this calculation is to determine the height of Lightning Masts for 400/220/33 kV Indrapuram Substation.
![Page 4: Dslp Calculation by Vikas](https://reader036.vdocuments.us/reader036/viewer/2022082315/55cf9a76550346d033a1d94c/html5/thumbnails/4.jpg)
Substation Name Document Name Document No.
400/220/33 KV Indrapuram Substation
Direct stroke lightning protection Calculations
4.0 Formulae Used:
A Protective radius (rx) :
1 If , hx <= (2/3)h and h > 30m:-
2 If , hx <= (2/3)h and h <= 30m:-
3 Co-efficient for the Lightning Mast Height P m
4 Allowable distance between two LMs S 7 x ha x P m m
5 Allowable diagonal distance between two LMs D 8 x ha x P m m
Where ha= h - hx m
B Midway point protective Height (ho) and Midway Point Protective Distance (bx)
1 m
2 If hx < (2/3)ho and ho > 30 m :- m
3 If hx < (2/3)ho and ho < 30 m :- m
4 If hx > (2/3)ho and ho < 30 m :- m
P
Shh
7 0
r x=1 .5h×(1− hx0 . 8h )× P m
r x=1 .5h×(1− hx0 .8h ) m
5 .5/ √h
bx=1. 5ho×(1− hx0 .8ho )×P
bx=1.5ho×(1− hx0 .8ho )
bx=0 .75ho×(1−hxho )
![Page 5: Dslp Calculation by Vikas](https://reader036.vdocuments.us/reader036/viewer/2022082315/55cf9a76550346d033a1d94c/html5/thumbnails/5.jpg)
Substation Name Document Name Document No.
400/220/33 KV Indrapuram Substation
Direct stroke lightning protection Calculations
SHEET NO. 3 OF 6
![Page 6: Dslp Calculation by Vikas](https://reader036.vdocuments.us/reader036/viewer/2022082315/55cf9a76550346d033a1d94c/html5/thumbnails/6.jpg)
Substation Name Document Name Document No.
400/220/33 KV Indrapuram Substation
Direct stroke lightning protection Calculations
5.0 Calculation
a) For LM1
Height of the LM h 40 m
Height to be protected 10 m
Protective radius
P =
0.870
Protective radius
=
35.8875 m
Hence protection area of LM1 covers the 400 kV Substation area which have to be protected.
b)For LM2 & LM3
Height of the LM h 40 m
Height to be protected 6 m
Protective radius
P =
0.870
hx
5.5 / Öh
5.5/Ö40
1.5 X 40((1-(10/0.8 x 40))x0.870
hx
5.5 / Öh
5.5/Ö40
r x=1 .5h×(1− hx0 . 8h )× P m
r x=1 .5h×(1− hx0 . 8h )× P m
r x=1 .5h×(1− hx0 . 8h )× P m
![Page 7: Dslp Calculation by Vikas](https://reader036.vdocuments.us/reader036/viewer/2022082315/55cf9a76550346d033a1d94c/html5/thumbnails/7.jpg)
Substation Name Document Name Document No.
400/220/33 KV Indrapuram Substation
Direct stroke lightning protection Calculations
SHEET NO. 4 OF 6
![Page 8: Dslp Calculation by Vikas](https://reader036.vdocuments.us/reader036/viewer/2022082315/55cf9a76550346d033a1d94c/html5/thumbnails/8.jpg)
Substation Name Document Name Document No.
400/220/33 KV Indrapuram Substation
Direct stroke lightning protection Calculations
Protective radius
=
42.4125 m
Hence protection area of LM1 & LM2 covers the 220 kV Substation area which have to be protected.
c) For LM4
Height of the LM h 40 m
Height to be protected 5 m
Protective radius
P =
0.870
Protective radius
=
44.04375 m
Hence protection area of LM4 covers the 33 kV Substation area which have to be protected.
1.5 X 40((1-(6/0.8 x 40))x0.870
hx
5.5 / Öh
5.5/Ö40
1.5 X 40((1-(5/0.8 x 40))x0.870
r x=1 .5h×(1− hx0 . 8h )× P m
r x=1 .5h×(1− hx0 . 8h )× P m
r x=1 .5h×(1− hx0 . 8h )× P m
![Page 9: Dslp Calculation by Vikas](https://reader036.vdocuments.us/reader036/viewer/2022082315/55cf9a76550346d033a1d94c/html5/thumbnails/9.jpg)
Substation Name Document Name Document No.
400/220/33 KV Indrapuram Substation
Direct stroke lightning protection Calculations
SHEET NO. 5 OF 6
![Page 10: Dslp Calculation by Vikas](https://reader036.vdocuments.us/reader036/viewer/2022082315/55cf9a76550346d033a1d94c/html5/thumbnails/10.jpg)
Substation Name Document Name Document No.
Table
S.No. LM Protection area
1 LM1 40 10 35.8875 400 kV Switchyard area2 LM2 40 6 42.4125 220 kV Switchyard area3 LM3 40 6 42.4125 220 kV Switchyard area4 LM4 40 5 44.04375 33 kV Switchyard area
Hence from the above calculated protection area of LM1,LM2,LM3 and LM4 we can protect the indrapuramswitch yard area from the direct lightning.
SHEET NO. 6 OF 6
400/220/33 KV Indrapuram Substation
Direct stroke lightning protection Calculations
Height of LM(m)
Height of the equipment to be protected.(m)
Radius of LM(m)
Conclusion