Download - DSE8661 Data Sheet
-
DSE8661TWO PART AUTO TRANSFER SWITCH & MAINS CONTROL MODULE
DSEGenset
The DSE8661 is an easy-to-usetwo part mains controller withautomatic transfer switch capabilitybetween remote breakers of upto 1.2 km . Designed to synchronisesingle or multiple DSE8x10s andDSE8680s with a single mains(utility) supply, the DSE8661 willautomatically control the changeover from mains (utility) to generatorsupply or run generators insynchronisation with the mains(utility) to provide no-break, peaklopping and peak shaving powersolutions.
The module can indicateoperational status and faultconditions on the LCD screen(multiple languages available), byilluminated LED, audible sounderand SMS messaging.
Comprehensive communicationsare also available via RS232,RS485 & Ethernet for remote PCcontrol and monitoring, andintegration into buildingmanagement systems. The comprehensive event log willrecord up to 250 events to facilitatemaintenance.
An extensive number of fixed andflexible monitoring and protectionfeatures are included. Easyalteration of the sequences, timersand alarms can be made using theDSE PC Configuration SuiteSoftware. Selected configuration isalso available via the modules frontpanel.
With all communication portscapable of being active at the sametime, the DSE8xxx Series is idealfor a wide variety of demandingload share applications.
KEY LOAD SHARE FEATURES: Peak lopping/sharing Sequential set start Manual voltage/frequencyadjustment
R.O.C.O.F. and vector shiftprotection
Generator load demand Automatic hours run balancing Mains (Utility) de-coupling Mains (Utility) de-couplingtest mode
Bus failure detection Volts and frequency matching. kW & kV Ar load sharing
FEATURES
ENVIRONMENTAL TESTING STANDARDS
ELECTRO MAGNETIC COMPATIBILITYBS EN 61000-6-2EMC Generic Immunity Standard for theIndustrial EnvironmentBS EN 61000-6-4EMC Generic Emission Standard for theIndustrial Environment
ELECTRICAL SAFETYBS EN 60950Safety of Information Technology Equipment,including Electrical Business Equipment
TEMPERATUREBS EN 60068-2-1Ab/Ae Cold Test -30oCBS EN 60068-2-2Bb/Be Dry Heat +70oC
VIBRATIONBS EN 60068-2-6Ten sweeps in each of three major axes5Hz to 8Hz @ +/-7.5mm, 8Hz to 500Hz @ 2gn
HUMIDITYBS EN 60068-2-30Db Damp Heat Cyclic 20/55oC @ 95% RH 48HoursBS EN 60068-2-78Cab Damp Heat Static 40oC @ 93% RH 48Hours
SHOCKBS EN 60068-2-27Three shocks in each of three major axes15gn in 11mS
DEGREES OF PROTECTIONPROVIDED BY ENCLOSURESBS EN 60529IP65 - Front of module when installed into thecontrol panel with the supplied sealing gasket.
COMPREHENSIVE FEATURE LIST TO SUIT A WIDEVARIETY OF LOAD SHARE APPLICATIONS
1ph2ph3ph
1ph2ph3phN
RS232 ANDRS485
DSENETEXPANSION
USBPORT
USBHOST
CONFIGURABLEINPUTS
DC OUTPUTS DC POWER SUPPLY 8-35V
7
OTHER
ETHERNET
11 x 2
232 485
6 x 2
PCMODBUSMODEM
+
VOLT FREEOUTPUTS
BUSSENSING
VOLT FREE OUTPUTS
MAINS (UTILITY) SENSING
VOLTSCURRENT
1ph2ph3phN
2 2
ISSUE 1
2 x DSE8661 MSC75105510 8x10 8661
1 of 2 DSE8661 1 of 2 DSE8661
RS485 8661
LOADSENSING
LOADSENSING
1ph2ph3phN
1ph2ph3phN
DSE2130DSE2131DSE2133DSE2152DSE2157DSE2548
-
DEEP SEA ELECTRONICS PLC UKHighfield House, Hunmanby Industrial Estate, Hunmanby YO14 0PHTELEPHONE +44 (0) 1723 890099 FACSIMILE +44 (0) 1723 893303EMAIL [email protected] WEBSITE www.deepseaplc.com
DEEP SEA ELECTRONICS INC USA3230 Williams Avenue, Rockford, IL 61101-2668 USATELEPHONE +1 (815) 316 8706 FACSIMILE +1 (815) 316 8708EMAIL [email protected] WEBSITE www.deepseausa.com
055-169/10/13 (1)
KEY FEATURES Mains (utility) failure detection Mains (utility) power monitoring(kW, kV Ar, kV A and pf)
Comprehensive synchronisingand loadsharing capabilities
Peak lopping & shavingfunctionality
Mains (utility) kW export protection
Mains (utility) de-couplingprotection
Advanced integral PLC editor User configurable RS232, RS485& Ethernet communications
MODBUS RTU & TCP support User configurable MODBUSpages
Advanced SMS control and faultmessaging (addition GSMmodem required)
DSENet expansion compatible Data logging and trending 4-Line back-lit LCD text display Multiple display languages Five key menu navigation Front panel editing with PINprotection
Customisable status screens Configurable inputs (11) Configurable outputs (8) Configurable timers and alarms Multiple entry scheduler Configurable event log (250) Easy access diagnostic pages LED and LCD alarm indication USB connectivity Backed up real time clock Fully configurable via DSEConfiguration Suite PC Software
KEY BENEFITS Two part solution allows upto 1.2 kmbetween mains (utility) &bus breakers.
Compatible with DSE5510,DSE7510 & DSE8x10 series ofmodules
132 x 64 pixel ratio display forclarity
Real-time clock provides accurateevent logging
Ethernet communication providedbuilit in advanced remotemonitoring.
Can be integrated into buildingmanagement systems (BMS) andprogrammable logic control (PLC)
Increased input and outputexpansion capability via DSENet
Licence-free PC software IP65 rating (with supplied gasket)offers increased resistance to wateringress
Advanced Internal PLC editor allowsuser configurable functions to meetspecific application requirements.
EXPANSION DEVICES DSE124 CAN/MSC Extender DSE2130 Input Expansion Module DSE2131 Ratio-metric InputExpansion Module
DSE2133 RTD & Thermo-coupleExpansion Module
DSE2152 Ratio-metric OutputExpansion Module
DSE2157 Output ExpansionModule
DSE2548 LED Expansion Module
RELATED MATERIALSTITLE PART NOSDSE8661 Installation Instructions 053-091DSE8661 Operator Manual 057-204DSE8600 PC Configuration Suite Manual 057-119DSE8610 Data Sheet 055-083
DSE8661TWO PART AUTO TRANSFER SWITCH & MAINS CONTROL MODULE
DSEGenset
FEATURES
Registered in England & Wales No.01319649VAT No.316923457
Deep Sea Electronics Plc maintains a policy of continuous development and reserves the right to changethe details shown on this data sheet without prior notice. The contents are intended for guidance only.
SPECIFICATION
DC SUPPLYCONTINUOUS VOLTAGE RATING8 V to 35 V Continuous
CRANKING DROPOUTSAble to survive 0 V for 50 mS, providing supply was at least 10 V before dropoutand supply recovers to 5 V. This is achieved without the need for internal batteries.LEDs and backlight will not be maintained during cranking.
MAXIMUM OPERATING CURRENT340 mA at 12 V, 160 mA at 24 V
MAXIMUM STANDBY CURRENT160 mA at 12 V, 80 mA at 24 V
MAINS (UTILITY) VOLTAGE RANGE15 V to 333 V AC (L-N)
FREQUENCY RANGE3.5 Hz to 75 Hz
LOADVOLTAGE RANGE15 V to 333 V AC (L-N)
FREQUENCY RANGE3.5 Hz to 75 Hz
BUSVOLTAGE RANGE15 V to 333 V AC (L-N)
FREQUENCY RANGE3.5 Hz to 75 Hz
OUTPUTSOUTPUTS C & D8 A at 250 V AC (Volt free)
AUXILIARY OUTPUTS E,F,G,H, I & J2 A DC at supply voltage
DIMENSIONSOVERALL240 mm x 181 mm x 42 mm 9.4 x 7.1 x 1.6
PANEL CUT-OUT220 mm x 160 mm8.7 x 6.3
MAXIMUM PANEL THICKNESS8 mm0.3
OPERATING TEMPERATURE RANGE-30C to +70C
STORAGE TEMPERATURE RANGE-40C to +85C
RS485
1.2 km
MAINS BREAKER CONTROLLER BUS BREAKER CONTROLLER