Direct Digital Control System
Index of DrawingsSheet# Description1 Title and Cover Page2 Supervisory Controller3 FCU Wiring
5 AHU Flow Diagram6 AHU 1 Wiring Diagram
Cover Page
Pittsburgh Air Systems, Inc.
208 Bilmar DrPittsburgh, PA
412.539.1234 412.539.1245 Fwww.PittsburghAirSystems.com
06/04/2013
11" x 17"
CHECKED BY DRAWN BY REVJ. Konley B. Woods 1
SCALE NONE Job# SHEET 1 of 13
7 AHU 2 Wiring Diagram
9 Boiler Panel10 Boiler Panel Expansion11 Wireless Temperature Monitoring12 First Floor Layout13 Basement Layout
4 FCU Sequence of Operation
8 AHU 1 & 2 Sequence of Operation
NOTES:BUS DEVICES ARE NOT LOCATION OR ORDER SPECIFIC ON NETWORK BUS.COMMUNICATION BUS WIRE MUST BE 22 AWG, 3 CONDUCTOR, TWISTED SHIELDED AND RATED FOR 78K BAUD.END DEVICES ON BACnet BUS MUST HAVE NETWORK TERMINATOR.KEEP ALL COMMUNICATION WIRING AWAY FROM LINE VOLTAGE.INSTALL END OF LINE TERMINATORS AT EACH END OF BACnet COMMUNICATION TRUNK
QTY. TAG PART NO. DESCRIPTION
4 E.O.L MS-BACEOL-0 BACnet NETWORK END OF LINE TERMINATOR
RESET
OFF
120V10 amp Max
JOHNSON CONTROLSFX 60
CO
M4
CO
M3
CO
M2
LAN
2
LAN
1
CAT5 OR CAT6 ETHERNET CABLETO BUILDING NETWORK
(BY OTHERS)
BACNET BUS 1
MOUNTED IN BOILER PANEL
1 FX-60 LP-FX6021N-1 FACILITY EXPLORER FRONT END
1 LP-FXPMUS-0 WALL PLUG POWER MODULE FOR FX-20
1 PS-1 PSPT2RB10 ENCLOSED POWER MODULE W/BREAKER SWITCH
PS-1
120 VAC
BY OTHERS
BACNET BUS 2
Supervisory Controller
Pittsburgh Air Systems, Inc.
208 Bilmar Dr
Pittsburgh, PA
412.539.1234 412.539.1245 F
www.PittsburghAirSystems.com
06/04/2013
11" x 17"
CHECKED BY DRAWN BY REV
J. Konley B. Woods 1
SCALE NONE Job# SHEET 2 of 13
NOTE:
1.) THERMOSTAT IS PROVIDED WITH
UNIT. UNIT IS FACTORY WIRED.
T-X
THERMOSTAT
DETAIL
BO1/AO1
BO2BO4/AO2
BI1 RS Scom BI2
-
REF
+
FANM
FANL
FANH
24VHOT
24VCOM BO5
AUXBO5AUX
BO3
UI3
BACNET BUS 1
IC FCU Schedule
Unit
TAG #
Siz
e
CFM
MED Location
NOTES
FC1 6 497 VESTRY Bar GRILLS
FC2 3 275 NAVE
FC3 2 186 RIGHT FRONT
ENTRY
Discharge
toward rear
FC4 12 848 NAVE/CHAPPEL
FC5 12 848 NAVE/CHAPPEL
FC6 12 848 NAVE
FC7 12 848 NAVE
FC8 12 848 NAVE
FC9 2 186 RIGHT REAR ENTRY
FC10 4 394 NARTHEX
FC11 4 394 NARTHEX
FC12 2 186 BAPTISTRY Add 2" extra
base height
FC13 2 186 LEFT REAR ENTRY
FC14 12 848 NAVE
FC15 12 848 NAVE
FC16 12 848 NAVE
FC17 12 848 NAVE/CHAPPEL
FC18 12 848 NAVE/CHAPPEL
FC19 12 848 NAVE
FC20 12 848 NAVE
FC21 8 525 SANCTUARY Bar GRILLS
FC22 8 525 SANCTUARY Bar GRILLS
FC23 2 186 LEFT FRONT ENTRY Discharge
toward rear
FC24 3 275 NAVE
FC25 6 497 SACRISTY Bar GRILLS
FC26 4 394 AMBULATORY
FC27 4 394 AMBULATORY
FC28 8 525 CHOIR LOFT
FC29 8 525 CHOIR LOFT
FC30 2 186 LADIES TOILET
FC31 2 186 MENS TOILET
563340 16698
AHU1
AHU2
325200 10400
207 888,540 1,487,660
74.05 TONS
NOTES:
1 ALL UNITS SHALL BE 115 VAC
2 Cooling capacity based on 45 deg entering water 30% EG
3 ALL UNITS SHALL HAVE MODULATING CONTROL VALVE
4 ALL UNITS SHALL HAVE JCI UNIT MOUNT BAC NET CAPABLE T'STAT
5 MIN FLOW VIA 3-WAY VALVES = 88 GPM
GPMCooling
BTU
Heating
BTU
LH/R
H
Unit
Mount
Valve type
Modulating
3.3 15,030 31,520 RH YES 2-WAY
2.5 7,730 17,490 RH YES 2-WAY
1.1 4,860 11,840 LH YES 2-WAY
8 31,780 56,680 RH YES 2-WAY
8 31,780 56,680 RH YES 3-WAY
8 31,780 56,680 RH YES 3-WAY
8 31,780 56,680 RH YES 3-WAY
8 31,780 56,680 RH YES 3-WAY
1.1 4,860 11,840 RH YES 2-WAY
1.9 8,500 22,850 RH YES 2-WAY
1.9 8,500 22,850 RH YES 2-WAY
1.1 4,860 11,840 LH YES 2-WAY
1.1 4,860 11,840 RH YES 2-WAY
8 31,780 56,680 LH YES 3-WAY
8 31,780 56,680 RH YES 3-WAY
8 31,780 56,680 RH YES 3-WAY
8 31,780 56,680 RH YES 3-WAY
8 31,780 56,680 RH YES 2-WAY
8 31,780 56,680 RH YES 3-WAY
8 31,780 56,680 LH YES 3-WAY
4 17,110 33,800 RH YES 2-WAY
4 17,110 33,800 LH YES 2-WAY
1.1 4,860 11,840 LH YES 2-WAY
2.5 7,730 17,490 RH YES 2-WAY
3.3 15,030 31,520 RH YES 2-WAY
1.9 8,500 22,850 RH YES 2-WAY
1.9 8,500 22,850 RH YES 2-WAY
4 17,110 33,800 LH YES 3-WAY
4 17,110 33,800 RH YES 3-WAY
1.1 4,860 11,840 RH YES 2-WAY
1.1 4,860 11,840 RH YES 2-WAY
TOTALS 138.9 1087660
34 162,600 200,000 5200 SOCIAL HALL 2-WAY
34 162,600 200,000 5200 SOCIAL HALL 2-WAY
TOTALS 68 400000
NOTE:
1.) INSTALL END OF LINE
TERMINATOR AT THE LAST UNIT ON
EACH BACNET BUS
BACnet Thermostats
Pittsburgh Air Systems, Inc.
208 Bilmar Dr
Pittsburgh, PA
412.539.1234 412.539.1245 F
www.PittsburghAirSystems.com
06/04/2013
11" x 17"
CHECKED BY DRAWN BY REV
J. Konley B. Woods 1
SCALE NONE Job# SHEET 3 of 13
SUPPLY FAN CONTROL:
When the thermostat fan mode is set to low, the supply fan will run continuously at low speed. When the thermostat fan mode is set
to medium, the supply fan will run continuously at medium speed. When the thermostat fan mode is set to high, the supply fan will
run continuously at high speed. When the thermostat fan mode is set to auto, Medium & High speed will operate automatically on
temperature error from setpoint. Low speed operates auto on demand. When there is no demand low speed will shutdown and will
reactivate based on demand.
TEMPERATURE CONTROL:
The unit will control to maintain the zone temperature setpoint as sensed by the zone temperature sensor.
OCCUPIED MODE:
The occupancy mode will be controlled via a network input.
HEATING\COOLING COIL:
The heating\cooling coil will be modulated to maintain the temperature setpoint.
CONFIGURATION INSTRUCTIONS:
Hold the menu key for approximately 8 seconds to access the installer configuration menu. If the default value is desired, press the
no key to advance to the next parameter. Press the yes key to edit the parameter. Use the up and down keys to change the value.
PSWRD: sets the protective access password to prevent unauthorized access to the installer configuration menu. (default: 0)
COM ADDR: set MS/TP address of the thermostat (default 254, range 4-127)
BI1: leave at default value (none)
BI2: leave at default value (none)
UI3: leave at default value (none)
MENUSCRO: gives option to have display continuously scroll through parameters (default on)
AUTOMODE: enables auto changeover from heating to cooling via the mode key (default on)
C or F: provides temperature scale options (default F)
LOCKOUT: set to (0) for all access, set to (1) for access to all except occupancy, set to (2) for occupancy and occupied
setpoints, set to (3) for occupied setpoints only, set to (4) for occupancy only, set to (5) for no access.
PIPE NO: number of pipes, set to (2.0 pipes)
CNTRLTYP: define control output for valves, set to (floating)
SEQOPRA: set to (0) for dual temperature coil with automatic changeover
FAN MENU: sets the fan mode options. Set to (2)
ST-BY TM: sets the time delay between the moment where the pir cover detected the last movement in the area and the time
which the thermostat stand-by mode and setpoints become active. (default: 0.5 hours)
UNOCC TM: sets the time delay between the moment when the thermostat controller toggles to stand-by mode and the time
which the thermostat unoccupied mode and setpoints become active. (default: 0.0 hours)
ST-BY HT: sets standy-by heating setpoint value (default 69.0 F/20.5 C)
ST-BY CL: sets stand-by cooling setpoint value (default 78.0 F/25.5 C)
UNOCC HT: sets unoccupied heating setpoint value (default 62.0 F/16.5 C)
UNOCC CL: sets unoccupied cooling setpoint value (default 80.0 F/26.5 C)
HEAT MAX: set to maximum occupied and unoccupied heating setpoint values (default 90 deg F)
COOL MIN: set to minimum occupied and unoccupied cooling setpoint values (default 54 deg F)
PBAND: sets the proportional band used by the thermostat controller proportional-integral (pi) control loop. (default: 3.0F°/
1.2C°)
SET TYPE: provides option of temporarily changing the heating or cooling setpoints via the up/down keys. SET TO (temporar)
for changes to remain effective for specified tocctime, or set to (permnent) to permanently store changes.
SPT FUNC: sets the operation and usage of local setpoint interface by the user (default dual stp)
TOCCTIME: set the duration of temporary occupied (default 2 hours)
DEADBAND: set minimum dead band between heating and cooling setpoints (default 2.0 deg F)
CAL RS: set zone sensor calibration offset (default 0.0)
AUX CONT: set to (0) for unused or used for reheat
AUTO FAN: as = auto speed only: as ad = auto speed / auto demand (set to as ad, 1.5 min)
FL TIME: set maximum actuator stroke time set to (1.0 min)
FCU
Sequence of Operation
Pittsburgh Air Systems, Inc.
208 Bilmar Dr
Pittsburgh, PA
412.539.1234 412.539.1245 F
www.PittsburghAirSystems.com
06/04/2013
11" x 17"
CHECKED BY DRAWN BY REV
J. Konley B. Woods 1
SCALE NONE Job# SHEET 4 of 13
TO
SPACEFROM
RTU
MAD-O
HTGCLG-O
SF-C
SF-S DA-TLTD-S
RA
OA DA
MA-T
Space Temperature Sensor
ZN-T
SMK-S
SF-O
AHU
Pittsburgh Air Systems, Inc.
208 Bilmar Dr
Pittsburgh, PA
412.539.1234 412.539.1245 F
www.PittsburghAirSystems.com
06/04/2013
11" x 17"
CHECKED BY DRAWN BY REV
J. Konley B. Woods 1
SCALE NONE Job# SHEET 5 of 13
124816
32
64
12
8
ON
Address:
6
SA
PW
R
CO
M
+ -
SA BUS
+ -
FC BUS
CO
M
SH
LD
+1
5V
IN 1
ICO
M 1
IN 2
ICO
M 2
+1
5V
IN 3
ICO
M 3
IN 4
ICO
M 4
+1
5V
IN 5
ICO
M 5
IN 6
ICO
M 6
IN 7
ICO
M 7
IN 8
ICO
M 8 Sensor
UNIVERSAL BINARY
FC BUS
BINARY
OU
T4
OC
OM
4
OU
T5
OC
OM
5
OU
T6
OC
OM
6
OU
T7
OC
OM
7
OU
T8
OC
OM
8
OU
T9
OC
OM
9
CONFIGURABLE ANALOG
HO
T
24V
CO
M
PCG-1
OU
T1
OC
OM
1
OU
T2
OC
OM
2
OU
T3
OC
OM
3
FC EOL
IN
TRIAC JUMPERS
OUT1INT
EXT
OUT2 OUT3
XFR-1 : COM
XFR-1 : 24VAC
XFR-1 : COM
1
H
N
G
2
PCG-1 : IN1
PCG-1 : INCOM1DISCHARGE AIR TEMPERATURE
3
4
PCG-1 : IN2
PCG-1 : INCOM2
120VAC
BY OTHERS
XFR-1 : 24vac
XMR-1
MIXED AIR TEMPERATURE
7
8
PCG-1 : IN4
PCG-1 : INCOM4
11
12
PCG-1 : IN8
PCG-1 : INCOM8
5
6
PCG-1 : IN3
PCG-1 : INCOM3
MA-T
DA-T
SPARE
LOW TEMPERATURE DETECTOR
RETURN AIR SMOKE DETECTOR
BACNET BUS BACNET BUS
9
10
PCG-1 : IN7
PCG-1 : INCOM7
SUPPLY FAN STATUS
SF-S
CT
12
4
8
R-1
SAFETY
RELAY
XFR-1 : 24VAC
SMK-S
15XFR-1 : 24vac LTD : LINE 2
16 LTD : M2
LTD : LINE 1
LTD-SLTD : M1
17 SMK : 11
18 SMK : 10
19
RE-1 : 14
TB-1 : 18
20 VFD : F
VFD : P24
TB-1
14XFR-1 :COM SMK : 6
13XFR-1 : 24vac SMK : 5+
-POWER TO SMOKE DETECTOR
RE-2 : 1
RE-2 : 9
7
8
13 14
9
5
1
R-2
FAN
PCG-1 : Out1 XFR-1 : COM14
10
2
6
9
1
5
13
XFR-1 : COM
PCG-1 : Ocom1
TB-1 : 19
TB-1 : 20TB-1 : 27
TB-1 : 24
LOW TEMPERATURE DETECTOR
SAFETY INTERLOCK
SMOKE DETECTOR
SAFETY INTERLOCK
SUPPLY FAN COMMANDSF-C
21
22 VFD : CC
VFD : VIA
PCG-1 : Ocom 7
PCG-1 : OUT 7
SUPPLY FAN SPEEDSF-O
+
-
23 MAD : 1 BLK
24
25 MAD : 3 GRY
MAD : 2 RED
PCG-1 : OUT 8
RE-1 : 6 MIXED AIR DAMPERS
MAD-O
+
-XFR-1 :COM
26 VLV : 1 BLK
27
28 VLV : 3 GRY
VLV : 2 RED
PCG-1 : OUT 9
RE-1 : 5 HEAT/COOL VALVE
HTGCLG-O
+
-XFR-1 :COM
Space Temperature Sensor
SA PWR
COM
+-
SA BUS ZONE SENSOR
AHU 1
Pittsburgh Air Systems, Inc.
208 Bilmar Dr
Pittsburgh, PA
412.539.1234 412.539.1245 F
www.PittsburghAirSystems.com
06/04/2013
11" x 17"
CHECKED BY DRAWN BY REV
J. Konley B. Woods 1
SCALE NONE Job# SHEET 6 of 13
124816
32
64
12
8
ON
Address:
6
SA
PW
R
CO
M
+ -
SA BUS
+ -
FC BUS
CO
M
SH
LD
+1
5V
IN 1
ICO
M 1
IN 2
ICO
M 2
+1
5V
IN 3
ICO
M 3
IN 4
ICO
M 4
+1
5V
IN 5
ICO
M 5
IN 6
ICO
M 6
IN 7
ICO
M 7
IN 8
ICO
M 8 Sensor
UNIVERSAL BINARY
FC BUS
BINARY
OU
T4
OC
OM
4
OU
T5
OC
OM
5
OU
T6
OC
OM
6
OU
T7
OC
OM
7
OU
T8
OC
OM
8
OU
T9
OC
OM
9
CONFIGURABLE ANALOG
HO
T
24V
CO
M
PCG-2
OU
T1
OC
OM
1
OU
T2
OC
OM
2
OU
T3
OC
OM
3
FC EOL
IN
TRIAC JUMPERS
OUT1INT
EXT
OUT2 OUT3
XFR-2 : COM
XFR-2 : 24VAC
XFR-2 : COM
1
2
PCG-2 : IN1
PCG-2 : INCOM1DISCHARGE AIR TEMPERATURE
3
4
PCG-2 : IN2
PCG-2 : INCOM2
XFR-2 : 24vac
XMR-2
MIXED AIR TEMPERATURE
7
8
PCG-2 : IN4
PCG-2 : INCOM4
11
12
PCG-2 : IN8
PCG-2 : INCOM8
5
6
PCG-2 : IN3
PCG-2 : INCOM3
MA-T
DA-T
SPARE
LOW TEMPERATURE DETECTOR
RETURN AIR SMOKE DETECTOR
BACNET BUS BACNET BUS
9
10
PCG-2 : IN7
PCG-2 : INCOM7
SUPPLY FAN STATUS
SF-S
CT
12
4
8
R-3
SAFETY
RELAY
XFR-2 : 24VAC
SMK-S
15XFR-2 : 24vac LTD : LINE 2
16 LTD : M2
LTD : LINE 1
LTD-SLTD : M1
17 SMK : 11
18 SMK : 10
19
RE-3 : 14
TB-2 : 18
20 VFD : F
VFD : P24
TB-2
14XFR-2 :COM SMK : 6
13XFR-2 : 24vac SMK : 5+
-POWER TO SMOKE DETECTOR
RE-4 : 1
RE-4 : 9
7
8
13 14
9
5
1
R-4
FAN
PCG-2 : Out1 XFR-2 : COM14
10
2
6
9
1
5
13
XFR-2 : COM
PCG-2 : Ocom1
TB-2 : 19
TB-2 : 20TB-2 : 27
TB-2 : 24
LOW TEMPERATURE DETECTOR
SAFETY INTERLOCK
SMOKE DETECTOR
SAFETY INTERLOCK
SUPPLY FAN COMMANDSF-C
21
22 VFD : CC
VFD : VIA
PCG-2 : Ocom 7
PCG-2 : OUT 7
SUPPLY FAN SPEEDSF-O
+
-
23 MAD : 1 BLK
24
25 MAD : 3 GRY
MAD : 2 RED
PCG-2 : OUT 8
RE-3 : 6 MIXED AIR DAMPERS
MAD-O
+
-XFR-2 :COM
26 VLV : 1 BLK
27
28 VLV : 3 GRY
VLV : 2 RED
PCG-2: OUT 9
RE-3 : 5 HEAT/COOL VALVE
HTGCLG-O
+
-XFR-2 :COM
Space Temperature Sensor
SA PWR
COM
+-
SA BUS ZONE SENSOR
VLV : BLK
VLV : REDPCG-2: OUT2HEATING VALVE FOR
CONFESSIONAL SPACEHTG1-C
+
-PCG-2: Ocom2
AHU 2
Pittsburgh Air Systems, Inc.
208 Bilmar Dr
Pittsburgh, PA
412.539.1234 412.539.1245 F
www.PittsburghAirSystems.com
06/04/2013
11" x 17"
CHECKED BY DRAWN BY REV
J. Konley B. Woods 1
SCALE NONE Job# SHEET 7 of 13
QTY. TAG PART NO. DESCRIPTION
1 XMR-1 PSB100AB10-TC CONTROL POWER TRANSFORMER
2 PCG-1 FX-PCG2611 GENERAL PURPOSE CONTROLLER
2 ZN-T NS-BTB7003-0 NETWORK THERMOSTAT
2 DA-T TE-6311M-1 DUCT TEMPERATURE SENSOR
2 MA-T TE-6316M-1 DUCT AVERAGING TEMPERATURE SENSOR
2 SF-S CSD-CA1GO-1 CURRENT SWITCH
1 CP-1 SCE-36N2406 CONTROL ENCLOSURE
4 MAD-O M9208-GGA DAMPER ACTUATOR
2 SMK-S SM-501-N-AP SMOKE DETECTOR
2 STS-10-AP SAMPLING TUBE
2 VA9208-GGA-3 VALVE ACTUATOR
2 LTD-S A70GA-1C LOW TEMPERATURE DETECTOR
SUPPLY FAN CONTROL:
The constant speed supply fan (SF-C) will be started based on occupancy schedule. When the supply fan
status (SF-S) indicates the fan started, the control sequence will be enabled. Upon a loss of airflow (SF-S), the
system will attempt to automatically restart until positive status is received. .
ECONOMIZER CONTROL:
When the outdoor air (OA-T) is cooler than the economizer setpoint, cooling will be provided by the OA damper
as required.
When outside air damper (MAD-O) is greater than the exhaust damper enable setpoint, the two position
exhaust damper (EAD-C) will open.
MINIMUM OA CONTROL:
The fresh air intake of the unit will be limited to prevent the mixed air temperature (MA-T) from falling below the
low limit setpoint (OALT-SP).
TEMPERATURE CONTROL:
The discharge air temperature setpoint (DAT-SP) will be reset as the zone temperature (ZN-T) changes.
OCCUPIED MODE:
The occupancy mode will be controlled via a network input (OCC-SCHEDULE). The occupancy mode can also
be overridden by a network input (OCC-OVERRIDE) or a temporary occupancy switch (ZN-TOCC) on the zone
temperature sensor (ZN-T).
UNOCCUPIED MODE:
The unit will cycle to maintain unoccupied zone setpoints (CLGUNOCC-SP & HTGUNOCC-SP) during
unoccupied periods.
HEATING/COOLING COIL:
The heating/cooling coil will modulate to maintain the discharge air temperature setpoint (DAT-SP). The
summer/winter switchover will be accomplished using a network command (SUMWIN-C). When the unit is
shutdown, the heating/cooling coil will be commanded to a preset position should the outdoor air temperature
fall below the low outdoor air temperature setpoint (OALT-SP). Upon a loss of airflow, the heating/cooling coil
will be commanded to a preset position should the outdoor air temperature fall below the low outdoor air
temperature setpoint (OALT-SP).
UNIT PROTECTION:
Low Temperature Alarm (LT-A) - When in "Alarm", the control sequence will stop running, the valve(s) will
open and the fan(s) will be disabled via a hard wired shutdown circuit.
Return Air Smoke Detector (RA-SD) - Disables the fan(s) via a hard wired shutdown circuit.
ADDITIONAL POINTS MONITORED BY THE FMS:
Return Air Smoke Alarm (RA-SD)
AHU 1 & AHU 2
Sequence of Operation
Pittsburgh Air Systems, Inc.
208 Bilmar Dr
Pittsburgh, PA
412.539.1234 412.539.1245 F
www.PittsburghAirSystems.com
06/04/2013
11" x 17"
CHECKED BY DRAWN BY REV
J. Konley B. Woods 1
SCALE NONE Job# SHEET 8 of 13
124816
32
64
12
8
ON
Address:
6
SA
PW
R
CO
M
+ -
SA BUS
+ -
FC BUS
CO
M
SH
LD
+1
5V
IN 1
ICO
M 1
IN 2
ICO
M 2
+1
5V
IN 3
ICO
M 3
IN 4
ICO
M 4
+1
5V
IN 5
ICO
M 5
IN 6
ICO
M 6
IN 7
ICO
M 7
IN 8
ICO
M 8 Sensor
UNIVERSAL BINARY
FC BUS
BINARY
OU
T4
OC
OM
4
OU
T5
OC
OM
5
OU
T6
OC
OM
6
OU
T7
OC
OM
7
OU
T8
OC
OM
8
OU
T9
OC
OM
9
CONFIGURABLE ANALOG
HO
T
24V
CO
M
PCG-1
OU
T1
OC
OM
1
OU
T2
OC
OM
2
OU
T3
OC
OM
3
FC EOL
IN
TRIAC JUMPERS
OUT1INT
EXT
OUT2 OUT3
XFR-1 : COM
XFR-1 : 24VAC
XFR-1 : COM
XFR-1 : 24VAC
1
2
PCG-1 : IN1
PCG-1 : INCOM1BOILER 1 SUPPLY TEMPERATURE
18
19
PCG-1 : OUT1
20
21
30PCG-1 : OUT9
3
4
PCG-1 : IN2
PCG-1 : INCOM2
120VAC
BY OTHERS
XFR-1 : 24vac
RE-1
BOILER 1 ENABLE
HOT/CHILLED PUMP 2 SPEED
XMR-1
BOILER 2 SUPPLY TEMPERATURE
7
8
PCG-1 : IN4
PCG-1 : INCOM4
11
12
PCG-1 : IN6
PCG-1 : INCOM6
5
6
PCG-1 : IN3
PCG-1 : INCOM3
BLR2LW-T
BLR1LW-T
BLDGR-T
BUILDING RETURN TEMPERATURE
BUILDING SUPPLY TEMPERATURE
HOT/CHILLED WATER DP
PCG-1 : OCOM9
BACNET BUS BACNET BUS
31
9
10
PCG-1 : IN5
PCG-1 : INCOM5
OUTSIDE AIR TEMPERATURE
28PCG-1 : OUT8
HOT/CHILLED PUMP 1 SPEED
PCG-1 : OCOM8 29
BLR1-EN
P1-O
P2-O
BLDGS-T
R-1 : WHT/BLU
R-1 : WHT/YEL
RE-2
BOILER 2 ENABLE
BLR2-EN
22
23
RE-3
HOT/CHILLED PUMP 1 ENABLE
P1-EN
24
25P2-EN
XFR-1 : COM
C
WHT/BLU
WHT/YEL
BLR ENABLE
BLR ENABLE ORANGE
YELLOW
RE-1, RE-2
13XFR-1 : 24VAC
OUT
COM
POWER
BLDG-DP
XFR-1 : COM
C
WHT/BLU
WHT/YEL
VFD ENABLE
VFD ENABLE ORANGE
YELLOW
RE-3, RE-4
FIELD VERIFY BOILER TERMINATIONS WIRE
N.O. TO THE BOILER ENABLE TERMINALS
MOUNT RIB RELAY AT STARTERP1-S
CT
OA-T
14
15
PCG-1 : IN7
PCG-1 : INCOM7
HOT CHILLED PUMP 1 STATUS
P2-S
CT
16
17
PCG-1 : IN8
PCG-1 : INCOM8
HOT CHILLED PUMP 2 STATUS
FIELD VERIFY TERMINATIONS
XFR-1 : COM
XFR-1 : COM
XFR-1 : COM
PCG-1 : OUT2
PCG-1 : OUT3
PCG-1 : OUT4
R-2 : WHT/BLU
R-2 : WHT/YEL
R-3 : WHT/BLU
R-3 : WHT/YEL
R-4 : WHT/BLU
R-4 : WHT/YEL
26
27P3-EN
XFR-1 : COM
PCG-1 : OUT5 R-5 : WHT/BLU
R-5 : WHT/YEL
RE-4
HOT/CHILLED PUMP 2 ENABLE
RE-5
CHILLER PUMP 3 ENABLE
C
WHT/BLU
WHT/YEL
AUTO
AUTO ORANGE
YELLOW
RE-5
FIELD VERIFY STARTER TERMINATIONS WIRE
N.O. TO THE AUTO SIDE OF THE STARTER
MOUNT RIB RELAY AT STARTER
FIELD VERIFY TERMINATIONS
AT VFD
MOUNT OA SENSOR
ON A NORTH FACING
EXPOSURE
BOILER PANEL
Pittsburgh Air Systems, Inc.
208 Bilmar Dr
Pittsburgh, PA
412.539.1234 412.539.1245 F
www.PittsburghAirSystems.com
06/04/2013
11" x 17"
CHECKED BY DRAWN BY REV
J. Konley B. Woods 1
SCALE NONE Job# SHEET 9 of 13
124816
32
64
12
8
ON
Address:
SA
FC
+1
5V
IN 1
ICO
M 1
IN 2
ICO
M 2
+1
5V
IN 3
ICO
M 3
IN 4
ICO
M 4
+1
5V
IN 5
ICO
M 5
IN 6
ICO
M 6
IN 7
ICO
M 7
IN 8
ICO
M 8
UNIVERSAL BINARY
SA/FC BUS
BINARY
OU
T4
OC
OM
4
OU
T5
OC
OM
5
OU
T6
OC
OM
6
OU
T7
OC
OM
7
OU
T8
OC
OM
8
OU
T9
OC
OM
9
CONFIGURABLE ANALOG
HO
T
24V
CO
M
PCX-1
OU
T1
OC
OM
1
OU
T2
OC
OM
2
OU
T3
OC
OM
3
FC EOL
IN
TRIAC JUMPERS
OUT1INT
EXT
OUT2 OUT3
SA
PW
R
CO
M
+ -
+ - CO
M
SH
LD
SA/FC BUS
XFR-1 : 24VAC
XFR-1 : COM
SA BUS ON
PCG-1
5
P3-S
CT
32
33
PCX-1 : IN1
PCX-1 : INCOM1
CHILLED WATER PUMP 3 STATUS
PCX-1 : IN2HEAT
MODEPCX-1 : ICOM2
PCX-1 : IN3COOL
MODEPCX-1 : ICOM3
3 POSITION
SWITCH MOUNT
ON PANEL FACE
PCX-1 : IN8 OCCUPIED
OVERRIDE
TIMERPCX-1 : ICOM8
SPRING WOUND WIND
UP TIMER MOUNT ON
PANEL FACE
QTY. TAG PART NO. DESCRIPTION
1 XMR-1 PSB100AB10-TC CONTROL POWER TRANSFORMER
1 PCG-1 FX-PCG2621 GENERAL PURPOSE CONTROLLER
1 PCX-1 FX-PCX4711 GENERAL PURPOSE EXPANSION
3 R-X RIBU1C CONTROL RELAY
1 BLDG-DP PWLX04S VERIS PRESSURE TRANSMITTER
4 TE-631AM-1 WELL TEMPERATURE SENSOR
4 TE-6300W-101 THERMAL WELL
1 SW-1 W22S3-HW 3 POS SWITCH 2 N.O.
1 OA-T TE-6313P-1 OUTSIDE AIR TEMPERATURE SENSOR
3 PX-S CSD-CA1GO-1 CURRENT SWITCH
1 CP-1 CONTROL ENCLOSURE
1 TMR-1 FD6HW WIND UP TIMER
SW-1 TMR-1
PCX-1 : IN8 OCCUPIED
OVERRIDE
TIMERPCX-1 : ICOM8
SPRING WOUND WIND
UP TIMER MOUNT IN
SACRISTY
TMR-2
PCX-1 : IN4 OCCUPIED
TEMPERATURE
OVERRIDEPCX-1 : ICOM4
TEMPERATURE
SETPOINT OVERIDE
MOUNT IN SACRISTY
STPT-1
1 TMR-2 FD6HW WIND UP TIMER
1 STPT-1 TE-67NT-1B00 REMOTE SETPOINT OVERRIDE
SET PT
SET PT COM
BOILER PANEL EXPANSION
Pittsburgh Air Systems, Inc.
208 Bilmar Dr
Pittsburgh, PA
412.539.1234 412.539.1245 F
www.PittsburghAirSystems.com
06/04/2013
11" x 17"
CHECKED BY DRAWN BY REV
J. Konley B. Woods 1
SCALE NONE Job# SHEET 10 of 13
WIRELESS RECEIVER
Space Temp/Humidity SensorWest side of Church
Address: 201
124816
32
64
12
8
ON
Address:
2
SA
PW
R
CO
M
+ -
SA BUS
+ -
FC BUS
CO
M
SH
LD
+1
5V
IN 1
ICO
M 1
IN 2
ICO
M 2
+1
5V
IN 3
ICO
M 3
IN 4
ICO
M 4
+1
5V
IN 5
ICO
M 5
IN 6
ICO
M 6
IN 7
ICO
M 7
IN 8
ICO
M 8
Sensor
UNIVERSAL BINARY
FC BUS
BINARY
OU
T4
OC
OM
4
OU
T5
OC
OM
5
OU
T6
OC
OM
6
OU
T7
OC
OM
7
OU
T8
OC
OM
8
OU
T9
OC
OM
9
CONFIGURABLE ANALOG
HO
T
24V
CO
M
PCG2621
OU
T1
OC
OM
1
OU
T2
OC
OM
2
OU
T3
OC
OM
3
FC EOL
IN
TRIAC JUMPERS
OUT1
INT
EXT
OUT2 OUT3
BOILER PCG
Note:Mount Receiver Around Sanctuary Area. Mount
roughly at same height as wireless Temperature
sensors.
Notes: 1.)WiFi access points should be mounted at least 20 ft from any FX-WRZ Series Sensor or FX-WRZ7860 Receiver2.)FX-WRZ Series Sensors should not be mounted less than 3 ft from a FX-WRZ7860 Receiver
Space Temperature SensorChoir Loft
Address: 202
Space Temperature SensorNarthex
Address: 203
Space Temperature SensorAltar
Address: 204
QTY. TAG PART NO. DESCRIPTION
1 WR-1 FX-WRZ7860-0 ONE TO ONE WIRELESS RECEIVER
1 ZN1-T FX-WRZTHN00-0 TEMPERATURE HUMIDITY SENSOR
3 ZN3,4,5-T FX-WRZTTR00-0 TEMPERATURE SENSOR
1 CBL-1 CBL-NETWORK100 100' MODULAR JACK SA BUS CABLE
WR-1
ZN1-T ZN2-T ZN3-T ZN4-T
CBL-1
WIRELESS SENSORS
Pittsburgh Air Systems, Inc.
208 Bilmar Dr
Pittsburgh, PA
412.539.1234 412.539.1245 F
www.PittsburghAirSystems.com
06/04/2013
11" x 17"
CHECKED BY DRAWN BY REV
J. Konley B. Woods 1
SCALE NONE Job# SHEET 11 of 13
DOWN TO FC#30 LADIES TOILET
BUS1 DOWN TO
FX-60
DOWN TO AHU-1 & 2
DOWN TO FC#31 MENS TOILET
BUS1 DOWN TO
BOILER PCG
Remote Twist Timer
Remote Setpoint Adjust
BACNET BUS 1
BACNET BUS 2
NOTE: SET ALL DEVICES FOR A BAUD RATE OF 38400
ADD #32
ADD #33
ADD #4ADD #5
ADD #6
ADD #39
ADD #8
ADD #9
ADD #10
ADD #7ADD #28
WR
-1CBL-1
ADD #35
ADD #27
ADD #22
ADD #20
ADD #19
ADD #21
ADD #26
ADD #25
ADD #24ADD #23
ADD #18
ADD #17
ADD #16ADD #15
ADD #14
ADD #12
ADD #13
ADD #11
ADD #29
FIRST FLOOR LAYOUT
Pittsburgh Air Systems, Inc.
208 Bilmar Dr
Pittsburgh, PA
412.539.1234 412.539.1245 F
www.PittsburghAirSystems.com
06/04/2013
11" x 17"
CHECKED BY DRAWN BY REV
J. Konley B. Woods 1
SCALE NONE Job# SHEET 12 of 13
Boiler Panel
AHU PANEL
DOWN FROM FCU 16
UP TO FCU 15DOWN FROM
FCU 29
E.O.L
FX-60
FROM FCU 1
FROM FCU 2
DOWN FROM FCU 28
E.O.L
BACNET BUS 1
BACNET BUS 2
NOTE: SET ALL DEVICES FOR A BAUD RATE OF 38400
ADD #30
ADD #31 ADD #5 ADD #6
ADD #38
BASEMENT LAYOUT
Pittsburgh Air Systems, Inc.
208 Bilmar Dr
Pittsburgh, PA
412.539.1234 412.539.1245 F
www.PittsburghAirSystems.com
06/04/2013
11" x 17"
CHECKED BY DRAWN BY REV
J. Konley B. Woods 1
SCALE NONE Job# SHEET 13 of 13