CSI 9420 WirelessMachinery HealthTransmitterWireless HART Connectivity
-
7/31/2019 CSI 9420 Wireless_para Clientes
2/13
Company Confidential
CSI 9420 Wireless Machinery HealthTransmitterWhile sensor should be
mounted on the machinebeing monitored, thetransmitter should be mounted
off the machine.
Transmitter contains:signal processing,battery, radiocommunication
Overall Velocity,PeakVue and
Temperature scalarvalues
Transmitter can connectto one accelerometer,one accelerometer withembedded temperature,or two accelerometers
-
7/31/2019 CSI 9420 Wireless_para Clientes
3/13
Company Confidential
300 feet / 100 meters) ) )
Outputs (scalar values)
1. Overall Vibration Units: Velocity (in/sec or mm/sec)
Range: 2 Hz 1000 Hz (per ISO 10816 standard).Comment: Identifies problems like imbalance and looseness
2. PeakVueVibration Units: Gs PeakRange: 1,000 Hz 20,000 HzComment: Quantify early bearing & gearbox defects
3. Temperature Range: -30 to +250 F / -34 to +120 CComment: When sensor with embedded temperature used
CSI 9420 Wireless ApplicationPlace on any equipment
Mount transmitteraway from machine
Measurement processing Radio communication Power Module
1420Smart Wireless Gateway
CSI 9420Wireless Vibration Transmitter
Application Works on any equipment Not application specific
Typical: 10 ft / 3 m
-
7/31/2019 CSI 9420 Wireless_para Clientes
4/13
Company Confidential
Vibration Measurements MoreThan a Single Overall Value
Overall Vibration measured in Velocityunits (in/sec)
2Hz-1000Hz per ISO 10816 standard.Guidelines and tables in velocity units exist toguide plant engineers and maintenance staffson alert limits
PeakViewTM Overallmeasured in gs pk
PeakView is a numerical method to detectpeak vibration typically due to rolling elementbearing failures
1kHz to 20kHz
-
7/31/2019 CSI 9420 Wireless_para Clientes
5/13
Company Confidential
PeakVue Provides Superior BearingDefect Detection
PeakVue provides theearliest indication of abearing defect
Increase in PeakVue valueis proportional to bearing
defect severity In the late stage bearing
failure a decrease inPeakVue with acorresponding increaseOverall vibration indicateslate stage bearing failure.
-
7/31/2019 CSI 9420 Wireless_para Clientes
6/13
-
7/31/2019 CSI 9420 Wireless_para Clientes
7/13
Company Confidential
EDDL Enabled Trend of Sensor 1Velocity Value in AMS Device Manager
-
7/31/2019 CSI 9420 Wireless_para Clientes
8/13
Company Confidential
EDDL Enabled Gauges Show AllProcess Variables in a Single View
-
7/31/2019 CSI 9420 Wireless_para Clientes
9/13
Company Confidential
Fan Monitoring Application
Sensor mountedon the bearing.
Bearing defectdetected withPeakVue
-
7/31/2019 CSI 9420 Wireless_para Clientes
10/13
Company Confidential
Closer View of Early Stage BearingFault Identified with PeakVueTM
Bearing defect showsevidence of early-stage
Impacting.
-
7/31/2019 CSI 9420 Wireless_para Clientes
11/13
Company Confidential
Get Started With a CSI 9420 SmartPack
1420Gateway
CSI 9420Machinery Health
Transmitters
5 CSI 9420Transmitters
1 1420 Gateway
INSTALL service
SmartStart service AMS Device
Manager 5 Tag
HART Modem
SmartStart
INSTALL
-
7/31/2019 CSI 9420 Wireless_para Clientes
12/13
Company Confidential
CSI 9420 Advantages
Delivers overall velocity AND PeakVue per sensor
Overall measurement good down to 2Hz
Two channel inputs
Update rate configurable for 1 minute updates
Delivers data through same network as process valuestemperature, pressure, flow, level
Can communicate data to multiple hosts simultaneously
Wireless HART standard exists and will be part of ISA100
standard.
-