Transformers are critical assets in
power networks. Maximizing their use
requires increasing power throughput
and reducing aging. Digital monitoring
of key parameters helps operators
protect their transformer investments.
CoreTec™ 4 is a modular monitoring
platform that collects, aggregates and
analyzes critical data to assure a
transformer continuously delivers
optimal performance.
Optimize your transformer with live data CoreTec™ 4 enables real-time management of a transformer by monitoring key health parameters such as oil temperature, ambient temperature and load. Using live data, CoreTec™ 4 models algorithms based on IEC and IEEE standards to warn the operator of any sudden changes in a transformer’s condition.
Detect faultsAvoid unplanned outages by continuously measuring oil temperature, load and gas formation. Variations in these health thresholds are flagged by CoreTec™ 4 in real time and can trigger advanced investigations when needed, not when scheduled.
Reduce insulation agingOil and Paper aging is linked to temperature, moisture and oxygen variations. CoreTec™ 4 tracks these parameters and activates the coolers sooner than conventional systems to delay insulation aging.
Increase load capacityMake informed decisions on overloading your trans-former. CoreTec™ 4 tracks current environmental conditions and uses international standards to provide an overview of the short-term overload capacity. This allows the operator to consider transformer aging versus increased throughput and revenues.
Delay replacement of a sick transformerCoreTec™ 4 can help operators with a sick transformer by enabling them to run it below recommended critical limits for temperature and gas generation. Ultimately, this helps to better plan for maintenance or delay replacement.
Integrate with ABB’s digital offeringThe CoreTec™ 4 platform is modular and expandable to suit your present and future requirements. Choose from a variety of transformer sensors like ABB’s CoreSense™ for DGA sensing or ABB’s eDevices to feed the CoreTec™ 4 with additional actionable data. CoreTec™ 4 can also integrate within ABB Ability™ Ellipse® asset performance management software.
—01 Fluctuations in power generation from wind farms can shorten a transformer’s life. Online condition monitoring with CoreTec™ 4 is a better way to manage your transformers.
— TR A NS FO R M ER S ERV I CE
CoreTec™ 4ABB Ability™ condition monitoring for transformers
—02 Transformer equipped with ABB’s digital sensors connected to a CoreTec™ 4 enclosed in a control cabinet.—03 CoreSense™ M10 multigas sensor integrates seamlessly with CoreTec™ 4.
—02
—03
—ABB Inc.Transformer Services (TRES)
www.abb.com/transformerservice
—We reserve the right to make technical changes or modify the contents of this document without prior notice. With regard to purchase orders, the agreed particulars shall prevail. ABB does not accept any responsibility whatsoever for potential errors or possible lack of information in this document.
We reserve all rights in this document and in the subject matter and illustrations contained therein. Any reproduction, disclosure to third parties or utilization of its contents – in whole or in parts – is forbidden without prior written consent of ABB. © Copyright 2018 ABB. All rights reserved. 1L
AB
00
06
31
04
.20
18
Functionalities
Measure Top oil temperature, ambient temperature, current, and other digital inputs(depending on device selection)
Model Winding hot-spot temperature, load ratio, aging, loss of life, and overload capacity
Control 2 cooling banks with adjustable thresholds
Electrical specifications
Voltage input 100 to 240 VAC (50 to 60 Hz)
Power consumption 100 VA
Fuse type 1 x 1.6 A / 300 V (5 x 20 mm) slow blow (IEC60127 type T)
Mechanical specifications
Dimensions 295 x 255 x 105 mm
Weight 1.7kg
Enclosure IP20 panel and DIN rail mount Optional IP66 cabinet
Communication specifications
Ultrabright LED 3 color-coded LEDs indicating system, process and uplink status
Communication interfaces RS485 serial port2 RJ45 100 base-T Ethernet ports100 base-FX fiber-optic Ethernet port
Protocols Modbus RTU, Modbus IP and DNP3
Hardware interfaces 3 dry-contact relays for alarms2 analog 4-20 mA outputs for publishing values3 analog 4-20 mA inputs for reading external sensors
Environmental specifications
Operating ambient temperature -40°C to 60°C (-40°F to 140°F)
Operating ambient humidity 5 to 95% RH, non-condensing