Page 1: B249VS Technical Data Sheet - Belimo · 2019-10-14 · Technical Data 2195 Power Supply 24 VAC, ±20%, 50/60 Hz, 24 VDC, ±10% Power consumption in operation 4 W Power consumption

Technical Data 96737

Fluid chilled or hot water, up to 60% glycol, steam

Flow characteristic modified equal percentageControllable flow range 90° rotationValve Size [mm] 2” [50]Pipe connection NPT female endsHousing Bronze B584-C84400Housing seal PTFEBall 316 stainless steelRetainer B584-C84400 bronzeStem 316 stainless steelStem seal RPTFESpindle bearing RPTFELock nut stainless steelSeat RPTFEBody Pressure Rating 600 psig WOG psiMaximum Inlet Pressure (Steam) 35 psi [241 kPa]Max Differential Pressure (Steam) 35 psiClose-off pressure ∆ps 600 psiMaximum Velocity 15 FPSCv 108 Weight 6.17 lb [2.8 kg]Fluid Temp Range (water) -22...280°F [-30...138°C]Leakage rate ANSI Class VI

Flow/Mounting Details

ApplicationThis valve is typically used in air handling units on heating or cooling coils, and fan coil unit heating or cooling coils. Some other common applications include Unit Ventilators, VAV Box re-heat coils and bypass loops. This valve is suitable for use in a hydronic system with variable flow.This valve is designed with MFT functionally which facilitates the use of various control input.Up to 35 psi steam1/2” - 2” 600 PSIG WOG, Cold Non-ShockFederal Specification: WW-V-35C, Type IIComposition: BZStyle: 3

Suitable Actuators Non-Spring Spring Electronic fail-safeB249VS GMB(X), SY1,

PRB(X)AF PKRB(X)

Dimensions (Inches [mm])

Safety NotesWARNING: This product can expose you to lead which is known to the State of California to cause cancer and reproductive harm. For more information go to www.p65warnings.ca.gov

B249VS Technical Data SheetBronze Body, Stainless Steel Ball and Stem

800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA / CARIBBEAN

Date

cre

ated

, 04/

03/2

020

- Sub

ject

to c

hang

e. ©

Bel

imo

Airc

ontro

ls (U

SA),

Inc.

Page 2: B249VS Technical Data Sheet - Belimo · 2019-10-14 · Technical Data 2195 Power Supply 24 VAC, ±20%, 50/60 Hz, 24 VDC, ±10% Power consumption in operation 4 W Power consumption

Technical Data 2195

Power Supply 24 VAC, ±20%, 50/60 Hz, 24 VDC, ±10%Power consumption in operation 4 WPower consumption in rest position

2 W

Transformer sizing 6 VA (class 2 power source)Electrical Connection 18 GA plenum cable, 3 ft [1 m], with 1/2”

conduit connector, degree of protection NEMA 2 / IP54

Overload Protection electronic throughout 0...95° rotationInput Impedance 600 ΩAngle of rotation Max. 95°, adjustable with mechanical stopTorque motor 360 in-lb [40 Nm]Direction of motion motor selectable with switch 0/1Position indication Mechanically, 30...65 mm strokeManual override external push buttonRunning Time (Motor) 150 s, constant, independent of loadAmbient humidity max. 95% r.H., non-condensingAmbient temperature -22...122°F [-30...50°C]Storage temperature -40...176°F [-40...80°C]Degree of Protection IP54, NEMA 2, UL Enclosure Type 2Agency Listing cULus acc. to UL60730-1A/-2-14, CAN/CSA

E60730-1:02, CE acc. to 2014/30/EU and 2014/35/EU

Noise level, motor 45 dB(A)Servicing maintenance-freeQuality Standard ISO 9001Weight 4.0 lb [1.8 kg]

†Rated Impulse Voltage 800V, Type action 1, Control Pollution Degree 3.

GMB24-3-X1 Technical Data SheetOn/Off, Floating Point, Non-Spring Return, 24 V

800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA / CARIBBEAN

Date

cre

ated

, 04/

03/2

020

- Sub

ject

to c

hang

e. ©

Bel

imo

Airc

ontro

ls (U

SA),

Inc.

Page 3: B249VS Technical Data Sheet - Belimo · 2019-10-14 · Technical Data 2195 Power Supply 24 VAC, ±20%, 50/60 Hz, 24 VDC, ±10% Power consumption in operation 4 W Power consumption

Wiring Diagrams

INSTALLATION NOTES

A Actuators with appliance cables are numbered.

Provide overload protection and disconnect as required.

Actuators may also be powered by 24 VDC.

Actuators Hot wire must be connected to the control board common. Only connect common to neg. (-) leg of control circuits. Terminal models (-T) have no-feedback.

Actuators may be connected in parallel if not mechanically linked. Power consumption and input impedance must be observed.

Meets cULus requirements without the need of an electrical ground connection.

! WARNING! LIVE ELECTRICAL COMPONENTS!During installation, testing, servicing and troubleshooting of this product, it may be necessary to work with live electrical components. Have a qualified licensed electrician or other individual who has been properly trained in handling live electrical components perform these tasks. Failure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious injury.

2 3 1824 VAC Transformer

Blk (1) Common

Red (2) + Hot

Wht (3) Y Input

LineVolts

1

On/Off

2 3 1824 VAC Transformer

Blk (1) Common

Red (2) + Hot

Wht (3) Y Input

LineVolts

1

Floating Point

ComHot2 3 18

Blk (1) Common

Red (2) + Hot

Wht (3) Y Input

LineVolts

24 VAC Transformer

1

2 18Blk (1) Common

Red (2) + Hot

Wht (3) Y Input

LineVolts

24 VAC Transformer

ComHot6 1

Floating Point - Triac Sink