Data SheetIt is the responsibility of the person installing the electrical equipment to ensure that the installation meets the requirements of the IET wiring regulations and is therefore ‘fit for purpose’. Factors such as correct selection of components, cable sizing, protective devices and Earth bonding are all critical and should be checked prior to full testing and power-up. Any other regulations applicable to the equipment being installed such as the Machinery Directive and current health and safety legislation must also be adhered to.
All connections (including factory made) must be checked for the correct tightness prior to commissioning of the electrical installation.All connections should be inspected periodically to ensure correct tightness.
DO NOT USE POWER TOOLS ON THESE PRODUCTS
Europa Helpline: email: [email protected] / tel: 01582 692 444
Page 1 of 12
Europa House, Airport Way, Luton, Beds, LU2 9NH Tel: 01582 692 440
e-mail: [email protected] website: www.europacomponents.com
EDS1331-001
Automatic Transfer Switch (ATS)Amperage:40, 60, 80, 100, 125
Number of poles:2 = Single phase 230V4 = Three phase 415V
A T S P M EC O N_
Maximum Cable size mm² 10 16 25 35 50Operational Current AC1 A 40 60 80 100 125Compliance / Approvals Low Voltage Control Gear & Switch GearBritish / European / International Standard BS/EN/IEC 60947-6-1
Data Sheet
Page 2 of 12EDS1331-001
Mains Failure Relay (MFR)Set the overvoltage and undervoltage thresholds, hysteresis and time delay in accordance with the phase failure relay datasheet.
Delay On Start Timer (DOST) Set the time for how long you want to delay the generator start signal following the loss or under/over voltage of the mains supply. Reference ECTDOFF datasheet. Please see footnote.
Mains Return Timer (MRT)Set the time for how long you want to delay the ATS from returning the load back to the mains supply following the mains supply being available. Reference ECMFT datasheet.
Cool Down Timer (CDT)Set the time for how long you want to delay the generator stop signal following the load beingtransfered back to the mains supply. Reference ECTDOFF datasheet.
Changeover Timer (DOCT)Set the time for how long you want to delay the ATS unit switching to the generator supply.Reference ECTON datasheet. Please see footnote.
Footnote:The Changeover timer (DOCT) setting will determine delay before the ATS unit switches the load from mains to generator. The delay on start timer (DOST) will determine the delay before the generator start signal is given after the mains fails. Therefore the changeover timer (DOCT) must be set to incorporporate the start-up time required for the generator to reach full speed and deliver the correct output voltage and frequency.
Time required for generator to reach required output = Changeover timer - Start timer 2 = 7 - 5
Wiring Diagram:
L L L NKM1 KM2
LOADMAINS SUPPLY
GENERATOR SUPPLY
L L L NTHREE PHASE
L L L N
Parameter Settings:
SINGLE PHASEL N L N L N
SINGLE PHASE
L L L NTHREE PHASE
Data Sheet
Page 3 of 12EDS1331-001
Single Phase Circuit Diagram
Data Sheet
Page 4 of 12EDS1331-001
Three Phase Circuit Diagram
Data Sheet
Page 5 of 12EDS1331-001
Data SheetIt is the responsibility of the person installing the electrical equipment to ensure that the installation meets the requirements of the IET wiring regulations and is therefore ‘fit for purpose’. Factors such as correct selection of components, cable sizing, protective devices and Earth bonding are all critical and should be checked prior to full testing and power-up. Any other regulations applicable to the equipment being installed such as the Machinery Directive and current health and safety legislation must also be adhered to.
All connections (including factory made) must be checked for the correct tightness prior to commissioning of the electrical installation.All connections should be inspected periodically to ensure correct tightness.
DO NOT USE POWER TOOLS ON THESE PRODUCTS
Europa Helpline: 01582 692 444 / Email: [email protected]
Page 1 of 2
Europa House, Airport Way, Luton, Beds, LU2 9NH Tel: 01582 692 440
e-mail: [email protected] website: www.europacomponents.com
EDS1210-101
Data ECPF02Function Monitoring voltage
Supply terminals A1-A2
Rated supply voltage AC/DC110-240V
Rated supply frequency 45-65Hz
Hysteresis 5% - 20%
Supply indication Green LED
Time delay Adjustable 0.1-10s, 10%
Measurement error ≤ 1%
Run up delay at power up 0.5s time delay
Knob setting accuracy 1% of scale value
Reset time 1000msTemperature coecient 0.05%/°C, at-20°C(0.05%°F, at-68°F)
Output 1 x SPDT
Current rating 10A / AC1
Switching voltage 250VAC / 24VDC
Minimum breaking capacity 500mW
Output indication Red LED
Mechanical life 1 x 107
Electrical life (AC1) 1 x 106
Operating temperature -20°C to +55°C (-4°F to 131°F)
Storage temperature -35°C to +75°C (-22°F to 158°F)
Mounting / din rail Din rail EN/IEC 60715
Protection degree IP40 for front panel / IP20 terminals
Operating position Any
Overvoltage category III.
Pollution degree 2
Maximum cable size (mm2) Solid wire maximum 1x2.5 or 2x1.5 / With sleeve maximum 1x2.5 (AWG 12)
Dimensions 90 x 18 x 64mm
Weight 59g
Standards IEC/EN 60255-6, IEC/EN61010-1
Technical Data: ECPF02 Single Phase Failure Relay
Data Sheet
Page 6 of 12EDS1331-001
Data Sheet
Page 2 of 2EDS1210-101
Panel DiagramPanel Diagram:
-1-
Instruction Manual
Panel Diagram
Supply indication(green)
Supply indication(green)
Output indication(red)
Output indication(red)
Operating function selector
Overvoltage threshold setting
Voltage threshold setting
Hysteresis setting
Undervoltage threshold setting
Time delay setting
Time delay setting
GEYA ELECTRICAL CO.,LTDAdd:Wenzhou Brige Industrial Zone,Beibaixiang Town,Yueqing,Zhejiang,China 325603
Tel:0086-577-62711079Fax:0086-577-62711751Mobile:0086-13567770207E-mail:[email protected]:www.geya.net
Monitoring voltage relay GRV8-01.02
■Applications -Protect electrical equipment and motors from over-voltage and under-voltage. -Normal/emergency power supply switching.■ Function Features -Controls its own supply voltage(True RMS measurement) -.User may select operation mode through knob. - Voltage measurement accuracy<1%. - Relay status is indicated by LED. - 1-MODULE,DIN rail mounting.
General
GRV8
GRV8 Series
■Model and connotation
Function
Supply terminals
DC12V,AC/DC24V-48V,AC/DC110V-240V,AC220V
A1-A2
Rated supply voltage
5%-20%
Supply indication
Time delay
green LED
Adjustable 0.1s-10s,10%
0.5s time delayRun up delay at power up
Reset time
Konb setting accuracy 1% of scale value
0.05%/℃,at=20℃(0.05%℉,at=68℉)
1×SPDT
10A/AC1
250VAC/24VDC
Temperature coecient
Output
500mW
red LED
1×10
1×10
Min.breaking capacity DC
Switching voltage
Current rating
Output indication
Mechanical life
Electrical life(AC1)
-20℃ to +55℃(-4℉ to 131℉)
-35℃ to +75℃(-22℉ to 158℉)
Din rail EN/IEC 60715
IP40 for front panel/IP20 terminals
any
solid wire max.1×2.5or 2×1.5/with sleeve max.1×2.5(AWG 12)
90×18×64mm
64g
IEC/EN 60255-6,IEC/EN61010-1
Operating temperature
Storage temperature
Mounting/DIN rail
Protection degree
Operating position
Overvoltage cathegory
Pollution degree
Dimensions
Weight
Standards
Monitoring voltage
GRV8-01 GRV8-02
Rated supply frequency 45Hz-65Hz,0
Hysteresis 3%fixed
Measurement error ≤1%
1000ms
Technical parameters
GRV8-01
Un R
U> U<
20
30
4050
60
70
80V
AC/DC
U
5
810
12 1416
20%H6
18
0.1 10s
2
4 6
8
GRV8-02
Un R
20
30
4050
60
70
80V
AC/DC
0.1 10s
2
4 6
8
20
30
40 60
70
80V
AC/DC50
U>
T
U<
Tt
Dimensions:
Dimensions(mm) Wiring Diagram
-2-
Functions Diagram
http://www.geya.net
Disposal of Electrical WasteAll electrical waste should bedisposed of in compliance withcurrent WEEE regulations.
CautionThe products must be installed by qualified electricians. All andany electrical connections of the time relay shall comply withthe appropriate safety standards.
GRV8-01
GRV8-02
Wrong setting of GRV8-01 Wrong setting of GRV8-02
U> U< U<
20
U>
30
4050 60
70
80V 20
30
4050 60
70
80V
As shown in the figure above,they are wrong settings.In that cases , LED-Un and LED-R will flash at the same time, which indicate the setting error. Normal operation will be resumed through resetting after power-off. If the operating function is changed after power-on, the two LED indicatorswould flash while the relay operates based on original operating functions;the LED would resume the normal indication after the original setting is recovered.
The set overvoltage threshold value must be larger than undervoltage thresholdvalue. Otherwise, all LEDs would flash and the output relay would be disconnected.
Locking Modes
Dimensions(mm) Wiring Diagram
-2-
Functions Diagram
http://www.geya.net
Disposal of Electrical WasteAll electrical waste should bedisposed of in compliance withcurrent WEEE regulations.
CautionThe products must be installed by qualified electricians. All andany electrical connections of the time relay shall comply withthe appropriate safety standards.
GRV8-01
GRV8-02
Wrong setting of GRV8-01 Wrong setting of GRV8-02
U> U< U<
20
U>
30
4050 60
70
80V 20
30
4050 60
70
80V
As shown in the figure above,they are wrong settings.In that cases , LED-Un and LED-R will flash at the same time, which indicate the setting error. Normal operation will be resumed through resetting after power-off. If the operating function is changed after power-on, the two LED indicatorswould flash while the relay operates based on original operating functions;the LED would resume the normal indication after the original setting is recovered.
The set overvoltage threshold value must be larger than undervoltage thresholdvalue. Otherwise, all LEDs would flash and the output relay would be disconnected.
Wiring Diagram:Dimensions(mm) Wiring Diagram
-2-
Functions Diagram
http://www.geya.net
Disposal of Electrical WasteAll electrical waste should bedisposed of in compliance withcurrent WEEE regulations.
CautionThe products must be installed by qualified electricians. All andany electrical connections of the time relay shall comply withthe appropriate safety standards.
GRV8-01
GRV8-02
Wrong setting of GRV8-01 Wrong setting of GRV8-02
U> U< U<
20
U>
30
4050 60
70
80V 20
30
4050 60
70
80V
As shown in the figure above,they are wrong settings.In that cases , LED-Un and LED-R will flash at the same time, which indicate the setting error. Normal operation will be resumed through resetting after power-off. If the operating function is changed after power-on, the two LED indicatorswould flash while the relay operates based on original operating functions;the LED would resume the normal indication after the original setting is recovered.
The set overvoltage threshold value must be larger than undervoltage thresholdvalue. Otherwise, all LEDs would flash and the output relay would be disconnected.
Functions Diagram:
Dimensions(mm) Wiring Diagram
-2-
Functions Diagram
http://www.geya.net
Disposal of Electrical WasteAll electrical waste should bedisposed of in compliance withcurrent WEEE regulations.
CautionThe products must be installed by qualified electricians. All andany electrical connections of the time relay shall comply withthe appropriate safety standards.
GRV8-01
GRV8-02
Wrong setting of GRV8-01 Wrong setting of GRV8-02
U> U< U<
20
U>
30
4050 60
70
80V 20
30
4050 60
70
80V
As shown in the figure above,they are wrong settings.In that cases , LED-Un and LED-R will flash at the same time, which indicate the setting error. Normal operation will be resumed through resetting after power-off. If the operating function is changed after power-on, the two LED indicatorswould flash while the relay operates based on original operating functions;the LED would resume the normal indication after the original setting is recovered.
The set overvoltage threshold value must be larger than undervoltage thresholdvalue. Otherwise, all LEDs would flash and the output relay would be disconnected.
Data Sheet
Page 7 of 12EDS1331-001
Data SheetIt is the responsibility of the person installing the electrical equipment to ensure that the installation meets the requirements of the IET wiring regulations and is therefore ‘fit for purpose’. Factors such as correct selection of components, cable sizing, protective devices and Earth bonding are all critical and should be checked prior to full testing and power-up. Any other regulations applicable to the equipment being installed such as the Machinery Directive and current health and safety legislation must also be adhered to.
All connections (including factory made) must be checked for the correct tightness prior to commissioning of the electrical installation.All connections should be inspected periodically to ensure correct tightness.
DO NOT USE POWER TOOLS ON THESE PRODUCTS
Europa Helpline: 01582 692 444 / Email: [email protected]
Page 1 of 2
Europa House, Airport Way, Luton, Beds, LU2 9NH Tel: 01582 692 440
e-mail: [email protected] website: www.europacomponents.com
EDS1238-001
ECTDOFF - Single Function True Delay OFF TimerTechnical Parameters ECTDOFF
Supply terminals A1-A2Voltage range AC/DC 12-240V(50-60Hz)Burden AC 0.7-3VA/DC 0.5-1.7WSupply voltage tolerance -15%;+10%Supply indication green LEDTime ranges 0.1s-10minTime setting potentionmeterTime deviation 5%-mechanical settingRepeat accuracy 0.2%-set value stabilityMininum power time 200msTemperature coecient 0.05%/°C, at=20°C (0.05%/°C at=68°C)Output 1×SPDTCurrent rating 16A / AC1Switching voltage 250VAC / 24VDCMin.breaking capacity DC 500mWOutput indication red LEDMechanical life 1×10Electrical life(AC1) 1×10Reset time max.200msOperating temperature -20°C to +55°C -4°C to 131°CStorage temperature -35°C to +75°C -22°C to 158°CMounting/DIN rail Din rail EN/IEC 60715Protection degree IP40 for front panel/IP20 terminalsOperating position anyOvervoltage category solid wire max.1×2.5 or 2×1.5/with sleeve max.1×2.5(AWG 12)Pollution degree 2Dimensions 90×18×64mmWeight 66gStandards IEC/EN 61812-1,IEC/EN61010-1
Panel Diagram
Supply indication(green)
Output indication(red)
Time setting
Wiring Diagram
Time range setting
General
■Applications
-Back-up source for Delay OFF in case of voltage failure (emergency lighting, emergency respirator,or protection of el. controlled doors - in case of fire).
■Function Features
-Time range (adjustable by rotary switch and fine setting by potentiometer): -0.1 s - 10 min.-Voltage range: AC/DC12-240V , clamp terminals.-Relay status is indicated by LED.-1-MODULE,DIN rail mounting.
Technical parameters
Function
Supply terminals
AC/DC 12-240V(50-60Hz)
A1-A2
Voltage range
Burden AC 0.7-3VA/DC 0.5-1.7W
-15%;+10%Supply voltage tolerance
Supply indication
Time ranges
green LED
0.1s-10min
potentionmeterTime setting
Time deviation
Repeat accuracy
5%-mechanical setting
0.2%-set value stability
0.05%/℃,at=20℃(0.05%℉,at=68℉)
1×SPDT
16A/AC1
250VAC/24VDC
Temperature coecient
Output
500mW
red LED
1×10
1×10
max.200ms
Min.breaking capacity DC
Switching voltage
Current rating
Output indication
Mechanical life
Electrical life(AC1)
Reset time
-20℃ to +55℃(-4℉ to 131℉)
-35℃ to +75℃(-22℉ to 158℉)
Din rail EN/IEC 60715
IP40 for front panel/IP20 terminals
any
solid wire max.1×2.5or 2×1.5/with sleeve max.1×2.5(AWG 12)
90×18×64mm
66g
IEC/EN 61812-1,IEC/EN61010-1
Operating temperature
Storage temperature
Mounting/DIN rail
Protection degree
Operating position
Overvoltage cathegory
Pollution degree
Dimensions
Weight
Standards
ECTDOFF
Mininum power time 200ms
Un R
10
20
3040 50 60 70
80
90
10m
1m10s
1s
ECTDOFF | single function true delay OFF time relay
Data Sheet
Page 8 of 12EDS1331-001
Data Sheet
Page 2 of 2
Dimensions
Wiring Diagram
EDS1238-001
Functions Diagram
Dimensions(mm)
Un R
10
20
3040 50 60 70
80
90
10m
1m10s
1s
16
1815
A1 A2
95
4.2
Panel Diagram
Panel Diagram
Supply indication(green)
Output indication(red)
Time setting
Wiring Diagram
Time range setting
General
■Applications
-Back-up source for Delay OFF in case of voltage failure (emergency lighting, emergency respirator,or protection of el. controlled doors - in case of fire).
■Function Features
-Time range (adjustable by rotary switch and fine setting by potentiometer): -0.1 s - 10 min.-Voltage range: AC/DC12-240V , clamp terminals.-Relay status is indicated by LED.-1-MODULE,DIN rail mounting.
Technical parameters
Function
Supply terminals
AC/DC 12-240V(50-60Hz)
A1-A2
Voltage range
Burden AC 0.7-3VA/DC 0.5-1.7W
-15%;+10%Supply voltage tolerance
Supply indication
Time ranges
green LED
0.1s-10min
potentionmeterTime setting
Time deviation
Repeat accuracy
5%-mechanical setting
0.2%-set value stability
0.05%/℃,at=20℃(0.05%℉,at=68℉)
1×SPDT
16A/AC1
250VAC/24VDC
Temperature coecient
Output
500mW
red LED
1×10
1×10
max.200ms
Min.breaking capacity DC
Switching voltage
Current rating
Output indication
Mechanical life
Electrical life(AC1)
Reset time
-20℃ to +55℃(-4℉ to 131℉)
-35℃ to +75℃(-22℉ to 158℉)
Din rail EN/IEC 60715
IP40 for front panel/IP20 terminals
any
solid wire max.1×2.5or 2×1.5/with sleeve max.1×2.5(AWG 12)
90×18×64mm
66g
IEC/EN 61812-1,IEC/EN61010-1
Operating temperature
Storage temperature
Mounting/DIN rail
Protection degree
Operating position
Overvoltage cathegory
Pollution degree
Dimensions
Weight
Standards
ECTDOFF
Mininum power time 200ms
Un R
10
20
3040 50 60 70
80
90
10m
1m10s
1s
ECTDOFF | single function true delay OFF time relay
Panel Diagram
Supply indication(green)
Output indication(red)
Time setting
Wiring Diagram
Time range setting
General
■Applications
-Back-up source for Delay OFF in case of voltage failure (emergency lighting, emergency respirator,or protection of el. controlled doors - in case of fire).
■Function Features
-Time range (adjustable by rotary switch and fine setting by potentiometer): -0.1 s - 10 min.-Voltage range: AC/DC12-240V , clamp terminals.-Relay status is indicated by LED.-1-MODULE,DIN rail mounting.
Technical parameters
Function
Supply terminals
AC/DC 12-240V(50-60Hz)
A1-A2
Voltage range
Burden AC 0.7-3VA/DC 0.5-1.7W
-15%;+10%Supply voltage tolerance
Supply indication
Time ranges
green LED
0.1s-10min
potentionmeterTime setting
Time deviation
Repeat accuracy
5%-mechanical setting
0.2%-set value stability
0.05%/℃,at=20℃(0.05%℉,at=68℉)
1×SPDT
16A/AC1
250VAC/24VDC
Temperature coecient
Output
500mW
red LED
1×10
1×10
max.200ms
Min.breaking capacity DC
Switching voltage
Current rating
Output indication
Mechanical life
Electrical life(AC1)
Reset time
-20℃ to +55℃(-4℉ to 131℉)
-35℃ to +75℃(-22℉ to 158℉)
Din rail EN/IEC 60715
IP40 for front panel/IP20 terminals
any
solid wire max.1×2.5or 2×1.5/with sleeve max.1×2.5(AWG 12)
90×18×64mm
66g
IEC/EN 61812-1,IEC/EN61010-1
Operating temperature
Storage temperature
Mounting/DIN rail
Protection degree
Operating position
Overvoltage cathegory
Pollution degree
Dimensions
Weight
Standards
ECTDOFF
Mininum power time 200ms
Un R
10
20
3040 50 60 70
80
90
10m
1m10s
1s
ECTDOFF | single function true delay OFF time relay
Panel Diagram
Supply indication(green)
Output indication(red)
Time setting
Wiring Diagram
Time range setting
General
■Applications
-Back-up source for Delay OFF in case of voltage failure (emergency lighting, emergency respirator,or protection of el. controlled doors - in case of fire).
■Function Features
-Time range (adjustable by rotary switch and fine setting by potentiometer): -0.1 s - 10 min.-Voltage range: AC/DC12-240V , clamp terminals.-Relay status is indicated by LED.-1-MODULE,DIN rail mounting.
Technical parameters
Function
Supply terminals
AC/DC 12-240V(50-60Hz)
A1-A2
Voltage range
Burden AC 0.7-3VA/DC 0.5-1.7W
-15%;+10%Supply voltage tolerance
Supply indication
Time ranges
green LED
0.1s-10min
potentionmeterTime setting
Time deviation
Repeat accuracy
5%-mechanical setting
0.2%-set value stability
0.05%/℃,at=20℃(0.05%℉,at=68℉)
1×SPDT
16A/AC1
250VAC/24VDC
Temperature coecient
Output
500mW
red LED
1×10
1×10
max.200ms
Min.breaking capacity DC
Switching voltage
Current rating
Output indication
Mechanical life
Electrical life(AC1)
Reset time
-20℃ to +55℃(-4℉ to 131℉)
-35℃ to +75℃(-22℉ to 158℉)
Din rail EN/IEC 60715
IP40 for front panel/IP20 terminals
any
solid wire max.1×2.5or 2×1.5/with sleeve max.1×2.5(AWG 12)
90×18×64mm
66g
IEC/EN 61812-1,IEC/EN61010-1
Operating temperature
Storage temperature
Mounting/DIN rail
Protection degree
Operating position
Overvoltage cathegory
Pollution degree
Dimensions
Weight
Standards
ECTDOFF
Mininum power time 200ms
Un R
10
20
3040 50 60 70
80
90
10m
1m10s
1s
ECTDOFF | single function true delay OFF time relay
Data Sheet
Page 9 of 12EDS1331-001
Data SheetIt is the responsibility of the person installing the electrical equipment to ensure that the installation meets the requirements of the IET wiring regulations and is therefore ‘fit for purpose’. Factors such as correct selection of components, cable sizing, protective devices and Earth bonding are all critical and should be checked prior to full testing and power-up. Any other regulations applicable to the equipment being installed such as the Machinery Directive and current health and safety legislation must also be adhered to.
All connections (including factory made) must be checked for the correct tightness prior to commissioning of the electrical installation.All connections should be inspected periodically to ensure correct tightness.
DO NOT USE POWER TOOLS ON THESE PRODUCTS
Europa Helpline: 01582 692 444 / Email: [email protected]
Page 1 of 2
Europa House, Airport Way, Luton, Beds, LU2 9NH Tel: 01582 692 440
e-mail: [email protected] website: www.europacomponents.com
EDS1278-001
ECTOFF - Single Function Delay OFF Time RelayECTON - Single Function Delay ON Time Relay
-1-
ECTON | Single function delay ON time relay ECTOFF | Single function delay OFF time relay
Panel Diagram
Supply indication(green)
Output indication(red)
Time setting
Un R
10
20
3040 50 60 70
80
90
OFFON
10d1d
10h1h10m
1m
10s1s
It is possible to connect load between S-A2 (e.g contactor , control of light or any other device, without disturbing a correct function of relay(load is energized while the switch is ON.)
Wiring Diagram
LOAD 15
16 18
General
■Applications
-Suitable for applications where function and time requirements are know.-Time switch , possible to be used for pump decay time after switching heatingoff , switching of fans.
■Function Features
-Single-function relay with possibility of time setting by a potentiometer.-Choice of 2 functions:A:Delay ONB:Delay OFF
-Time scale 0.1 s - 10 days divided into 10 ranges..-Relay status is indicated by LED.-1-MODULE,DIN rail mounting.
Technical parameters
Function
Supply terminals
AC/DC 12-240V(50-60Hz)
A1-A2
Voltage range
Burden
Voltage range
delay ON delay OFF
AC 0.7-3VA/DC 0.5-1.7W
AC 230V(50-60Hz)
AC max.12VA/1.3W AC max.12VA/1.9W
-15%;+10%
Power input
Supply voltage tolerance
Supply indication
Time ranges
green LED
potentionmeterTime setting
Time deviation
Repeat accuracy
5%-mechanical setting
0.2%-set value stability
0.05%/℃,at=20℃(0.05%℉,at=68℉)
1×SPDT 2×SPDT
16A/AC1
250VAC/24VDC
Temperature coecient
Output
500mW
red LED
1×10
1×10
max.200ms
Min.breaking capacity DC
Switching voltage
Current rating
Output indication
Mechanical life
Electrical life(AC1)
Reset time
-20℃ to +55℃(-4℉ to 131℉)
-35℃ to +75℃(-22℉ to 158℉)
Din rail EN/IEC 60715
IP40 for front panel/IP20 terminals
any
solid wire max.1×2.5or 2×1.5/with sleeve max.1×2.5(AWG 12)
90×18×64mm
1×SPDT:W240-60g,A230-59g
2×SPDT:W240-81g,A230-79g
IEC/EN 61812-1,IEC/EN61010-1
Operating temperature
Storage temperature
Mounting/DIN rail
Protection degree
Operating position
Overvoltage cathegory
Pollution degree
Dimensions
Weight
Standards
0.1s-10days,ON,OFF
ECTON ECTOFFFunction delay ON delay OFFSupply terminals A1-A2Voltage range AC/DC 12-240V(50-60Hz) Burden AC 0.7-3VA/DC 0.5-1.7W Voltage range AC 230V(50-60Hz)Power input AC max.12VA/1.3W AC max.12VA/1.9WSupply voltage tolerance -15%;+10%Supply indication green LEDTime ranges 0.1s-10days,ON,OFFTime setting PotentionmeterTime deviation 5%-mechanical settingRepeat accuracy 0.2%-set value stabilityTemperature coecient 0.05%/°C, at=20°C(0.05%°Cat=68°C)Output 1×SPDT 1×DPDTCurrent rating 16A / AC1Switching voltage 250VAC / 24VDCMin.breaking capacity DC 500mWOutput indication red LEDMechanical life 1×10Electrical life(AC1) 1×10Reset time max.200msOperating temperature -20°C to +55°C, -4°C to 131°CStorage temperature -35°C to +75°C, -22℉ to 158°CMounting/DIN rail Din rail EN/IEC 60715Protection degree IP40 for front panel/IP20 terminals Operating position AnyOvervoltage cathegory III.Pollution degree 2Max. Cable Size (mm2) solid wire max.1×2.5or 2×1.5/with sleeve max.1×2.5(AWG 12) Dimensions 90×18×64mm
Weight 1×SPDT: W240- 60g,A230-59g1×DPDT: W240- 81g,A230-79g
Standards IEC/EN 61812-1,IEC/EN61010-1Time Range
Data Sheet
Page 10 of 12EDS1331-001
Data Sheet
Page 2 of 2
Time Range
Functions DiagramDimensions
Wiring Diagram
EDS1237-001
Functions Diagram
Dimensions(mm)
25
Time Range
95
4.2
Panel Diagram
-1-
ECTON | Single function delay ON time relay ECTOFF | Single function delay OFF time relay
Panel Diagram
Supply indication(green)
Output indication(red)
Time setting
Un R
10
20
3040 50 60 70
80
90
OFFON
10d1d
10h1h10m
1m
10s1s
It is possible to connect load between S-A2 (e.g contactor , control of light or any other device, without disturbing a correct function of relay(load is energized while the switch is ON.)
Wiring Diagram
LOAD 15
16 18
General
■Applications
-Suitable for applications where function and time requirements are know.-Time switch , possible to be used for pump decay time after switching heatingoff , switching of fans.
■Function Features
-Single-function relay with possibility of time setting by a potentiometer.-Choice of 2 functions:A:Delay ONB:Delay OFF
-Time scale 0.1 s - 10 days divided into 10 ranges..-Relay status is indicated by LED.-1-MODULE,DIN rail mounting.
Technical parameters
Function
Supply terminals
AC/DC 12-240V(50-60Hz)
A1-A2
Voltage range
Burden
Voltage range
delay ON delay OFF
AC 0.7-3VA/DC 0.5-1.7W
AC 230V(50-60Hz)
AC max.12VA/1.3W AC max.12VA/1.9W
-15%;+10%
Power input
Supply voltage tolerance
Supply indication
Time ranges
green LED
potentionmeterTime setting
Time deviation
Repeat accuracy
5%-mechanical setting
0.2%-set value stability
0.05%/℃,at=20℃(0.05%℉,at=68℉)
1×SPDT 2×SPDT
16A/AC1
250VAC/24VDC
Temperature coecient
Output
500mW
red LED
1×10
1×10
max.200ms
Min.breaking capacity DC
Switching voltage
Current rating
Output indication
Mechanical life
Electrical life(AC1)
Reset time
-20℃ to +55℃(-4℉ to 131℉)
-35℃ to +75℃(-22℉ to 158℉)
Din rail EN/IEC 60715
IP40 for front panel/IP20 terminals
any
solid wire max.1×2.5or 2×1.5/with sleeve max.1×2.5(AWG 12)
90×18×64mm
1×SPDT:W240-60g,A230-59g
2×SPDT:W240-81g,A230-79g
IEC/EN 61812-1,IEC/EN61010-1
Operating temperature
Storage temperature
Mounting/DIN rail
Protection degree
Operating position
Overvoltage cathegory
Pollution degree
Dimensions
Weight
Standards
0.1s-10days,ON,OFF
ECTON ECTOFF
-1-
ECTON | Single function delay ON time relay ECTOFF | Single function delay OFF time relay
Panel Diagram
Supply indication(green)
Output indication(red)
Time setting
Un R
10
20
3040 50 60 70
80
90
OFFON
10d1d
10h1h10m
1m
10s1s
It is possible to connect load between S-A2 (e.g contactor , control of light or any other device, without disturbing a correct function of relay(load is energized while the switch is ON.)
Wiring Diagram
LOAD 15
16 18
General
■Applications
-Suitable for applications where function and time requirements are know.-Time switch , possible to be used for pump decay time after switching heatingoff , switching of fans.
■Function Features
-Single-function relay with possibility of time setting by a potentiometer.-Choice of 2 functions:A:Delay ONB:Delay OFF
-Time scale 0.1 s - 10 days divided into 10 ranges..-Relay status is indicated by LED.-1-MODULE,DIN rail mounting.
Technical parameters
Function
Supply terminals
AC/DC 12-240V(50-60Hz)
A1-A2
Voltage range
Burden
Voltage range
delay ON delay OFF
AC 0.7-3VA/DC 0.5-1.7W
AC 230V(50-60Hz)
AC max.12VA/1.3W AC max.12VA/1.9W
-15%;+10%
Power input
Supply voltage tolerance
Supply indication
Time ranges
green LED
potentionmeterTime setting
Time deviation
Repeat accuracy
5%-mechanical setting
0.2%-set value stability
0.05%/℃,at=20℃(0.05%℉,at=68℉)
1×SPDT 2×SPDT
16A/AC1
250VAC/24VDC
Temperature coecient
Output
500mW
red LED
1×10
1×10
max.200ms
Min.breaking capacity DC
Switching voltage
Current rating
Output indication
Mechanical life
Electrical life(AC1)
Reset time
-20℃ to +55℃(-4℉ to 131℉)
-35℃ to +75℃(-22℉ to 158℉)
Din rail EN/IEC 60715
IP40 for front panel/IP20 terminals
any
solid wire max.1×2.5or 2×1.5/with sleeve max.1×2.5(AWG 12)
90×18×64mm
1×SPDT:W240-60g,A230-59g
2×SPDT:W240-81g,A230-79g
IEC/EN 61812-1,IEC/EN61010-1
Operating temperature
Storage temperature
Mounting/DIN rail
Protection degree
Operating position
Overvoltage cathegory
Pollution degree
Dimensions
Weight
Standards
0.1s-10days,ON,OFF
ECTON ECTOFF
-1-
ECTON | Single function delay ON time relay ECTOFF | Single function delay OFF time relay
Panel Diagram
Supply indication(green)
Output indication(red)
Time setting
Un R
10
20
3040 50 60 70
80
90
OFFON
10d1d
10h1h10m
1m
10s1s
It is possible to connect load between S-A2 (e.g contactor , control of light or any other device, without disturbing a correct function of relay(load is energized while the switch is ON.)
Wiring Diagram
LOAD 15
16 18
General
■Applications
-Suitable for applications where function and time requirements are know.-Time switch , possible to be used for pump decay time after switching heatingoff , switching of fans.
■Function Features
-Single-function relay with possibility of time setting by a potentiometer.-Choice of 2 functions:A:Delay ONB:Delay OFF
-Time scale 0.1 s - 10 days divided into 10 ranges..-Relay status is indicated by LED.-1-MODULE,DIN rail mounting.
Technical parameters
Function
Supply terminals
AC/DC 12-240V(50-60Hz)
A1-A2
Voltage range
Burden
Voltage range
delay ON delay OFF
AC 0.7-3VA/DC 0.5-1.7W
AC 230V(50-60Hz)
AC max.12VA/1.3W AC max.12VA/1.9W
-15%;+10%
Power input
Supply voltage tolerance
Supply indication
Time ranges
green LED
potentionmeterTime setting
Time deviation
Repeat accuracy
5%-mechanical setting
0.2%-set value stability
0.05%/℃,at=20℃(0.05%℉,at=68℉)
1×SPDT 2×SPDT
16A/AC1
250VAC/24VDC
Temperature coecient
Output
500mW
red LED
1×10
1×10
max.200ms
Min.breaking capacity DC
Switching voltage
Current rating
Output indication
Mechanical life
Electrical life(AC1)
Reset time
-20℃ to +55℃(-4℉ to 131℉)
-35℃ to +75℃(-22℉ to 158℉)
Din rail EN/IEC 60715
IP40 for front panel/IP20 terminals
any
solid wire max.1×2.5or 2×1.5/with sleeve max.1×2.5(AWG 12)
90×18×64mm
1×SPDT:W240-60g,A230-59g
2×SPDT:W240-81g,A230-79g
IEC/EN 61812-1,IEC/EN61010-1
Operating temperature
Storage temperature
Mounting/DIN rail
Protection degree
Operating position
Overvoltage cathegory
Pollution degree
Dimensions
Weight
Standards
0.1s-10days,ON,OFF
ECTON ECTOFF
Functions Diagram
Dimensions(mm)
25
Time Range
95
4.2
Functions Diagram
Dimensions(mm)
25
Time Range
95
4.2
Functions Diagram
Dimensions(mm)
25
Time Range
95
4.2
Functions Diagram
Dimensions(mm)
25
Time Range
95
4.2
Data Sheet
Page 11 of 12EDS1331-001
Data SheetIt is the responsibility of the person installing the electrical equipment to ensure that the installation meets the requirements of the IET wiring regulations and is therefore ‘fit for purpose’. Factors such as correct selection of components, cable sizing, protective devices and Earth bonding are all critical and should be checked prior to full testing and power-up. Any other regulations applicable to the equipment being installed such as the Machinery Directive and current health and safety legislation must also be adhered to.
All connections (including factory made) must be checked for the correct tightness prior to commissioning of the electrical installation.All connections should be inspected periodically to ensure correct tightness.
DO NOT USE POWER TOOLS ON THESE PRODUCTS
Europa Helpline: 01582 692 444 / Email: [email protected]
Page 1 of 2
Europa House, Airport Way, Luton, Beds, LU2 9NH Tel: 01582 692 440
e-mail: [email protected] website: www.europacomponents.com
EDS1176-001
ECMFT - Multi Function Timer 12-230V AC/DCTechnical Parameters ECMFT
Function A, B, C, D, E, F, G, H, I, JSupply Terminals A1 - A2Voltage Range AC/DC 12-240V(50-60Hz)Burden AC 0.7-3VA/DC 0.5-1.7WVoltage Range AC 230V(50-60Hz)Power Input AC max.12VA/1.3WSupply Voltage Tolerance -15%;+10%Supply Indication green LEDTime Ranges 0.1s - 10days, ON ,OFFTime Setting PotentionmeterTime Deviation 5%-mechanical settingRepeat Accuracy 0.2%-set value stabilityTemperature Coecient 0.05%/oC,at=20oC(0.05%oF, at=68oF)Output 1 × SPDTCurrent Rating 16A/ AC1Switching Voltage 250VAC / 24VDCMin Breaking Capacity DC 500mWOutput Indication red LEDMechanical Life 1×107
Electrical Life(Ac1) 1×106
Reset Time max.200msOperating Temperature -20oC to +55oC(-4oF to 131oF)Storage Temperature -35oC to +75oC(-22oF to 158oF)Mounting/Din Rail Din rail EN/IEC 60715Protection Degree IP40 for front panel / IP20 terminalsOperating Position AnyOvervoltage Category III.Pollution Degree 2Max Cable Size (mm2) Solid wire max 1×2.5 or 2×1.5 / With sleeve max.1×2.5 (AWG 12)Dimensions 90 × 18 × 64mmWeight 1 × SPDT: W240 - 62g, A230 - 60gStandards IEC / EN 61812-1, IEC / EN61010-1
Data Sheet
Page 12 of 12EDS1331-001
Data Sheet
Page 2 of 2
Dimensions
Function Diagrams
EDS1176-001
-2-
http://www.geya.net
Disposal of Electrical WasteAll electrical waste should bedisposed of in compliance withcurrent WEEE regulations.
CautionThe products must be installed by qualified electricians. All andany electrical connections of the time relay shall comply withthe appropriate safety standards.
Time Range
Functions Diagram
D:
E:
F:
G:
H:
I:
J:
Dimensions(mm)
95
4.2
Time Diagrams
-2-
http://www.geya.net
Disposal of Electrical WasteAll electrical waste should bedisposed of in compliance withcurrent WEEE regulations.
CautionThe products must be installed by qualified electricians. All andany electrical connections of the time relay shall comply withthe appropriate safety standards.
Time Range
Functions Diagram
D:
E:
F:
G:
H:
I:
J:
Dimensions(mm)
95
4.2
-2-
http://www.geya.net
Disposal of Electrical WasteAll electrical waste should bedisposed of in compliance withcurrent WEEE regulations.
CautionThe products must be installed by qualified electricians. All andany electrical connections of the time relay shall comply withthe appropriate safety standards.
Time Range
Functions Diagram
D:
E:
F:
G:
H:
I:
J:
Dimensions(mm)
95
4.2