Transcript
Page 1: Ampacity simulation of high voltage cables• For ampacity calculations for simple configurations the IEC standard calculation agrees with the simulation results • With higher complexity

COMSOL Conference Milan 2012

Eva Pelster

Ampacity simulation of high voltage cables

10.10.2012

Excerpt from the Proceedings of the 2012 COMSOL Conference in Milan

Page 2: Ampacity simulation of high voltage cables• For ampacity calculations for simple configurations the IEC standard calculation agrees with the simulation results • With higher complexity

Content (1) Introduction (2) Comparison of IEC standard calculation method with COMSOL

Mutliphysics (3) Evaluation of a three-conductor high voltage cable configuration (4) Conclusion

10.10.2012 2 Ampacity simulaion of high voltage cables

Page 3: Ampacity simulation of high voltage cables• For ampacity calculations for simple configurations the IEC standard calculation agrees with the simulation results • With higher complexity

(1) Introduction • Cable ampacity typically depends largely on the cross-section of ist

conductor • Due to cost reduction it is of interest to keep the conductor cross-

section low • Usually semi-empirical methods, including larger safety margins, are

used to determine ampacity • Here COMSOL Multiphysics is used to determine the temperature

distribution

10.10.2012 3 Ampacity simulaion of high voltage cables

Page 4: Ampacity simulation of high voltage cables• For ampacity calculations for simple configurations the IEC standard calculation agrees with the simulation results • With higher complexity

Content (1) Introduction (2) Comparison of IEC standard calculation method with COMSOL

Mutliphysics (3) Evaluation of a three-conductor high voltage cable configuration (4) Conclusion

10.10.2012 4 Ampacity simulaion of high voltage cables

Page 5: Ampacity simulation of high voltage cables• For ampacity calculations for simple configurations the IEC standard calculation agrees with the simulation results • With higher complexity

(2) Comparison of IEC standard calculation method with COMSOL Mutliphysics

• Comparison of IEC-standard ampacity calculation with COMSOL

Multiphysics simulation for: – single-conductor cable – three bundled single-conductor cable

10.10.2012 5 Ampacity simulaion of high voltage cables

Page 6: Ampacity simulation of high voltage cables• For ampacity calculations for simple configurations the IEC standard calculation agrees with the simulation results • With higher complexity

(2) Comparison of IEC standard calculation method with COMSOL Mutliphysics

• A single-conductor cable is implemented to evaluate the maximum

allowable current, while keeping the conductor temperature at a defined maximum temperature

• The cable consists of a conductor material as well as different isolating layers and armour

10.10.2012 6 Ampacity simulaion of high voltage cables

Page 7: Ampacity simulation of high voltage cables• For ampacity calculations for simple configurations the IEC standard calculation agrees with the simulation results • With higher complexity

(2) Comparison of IEC standard calculation method with COMSOL Mutliphysics

• IEC standard ampacity calculation:

– Simple calculation of radial heat conduction – Aim is to limit the conductor temperature to 90°C – The conductor generates heat, depending on the current

according to the suppliers information – The maximum allowable current is determined via a iteration

algorithm – The outer surface is cooled via radiation as well as convective

cooling for which the heat transfer coefficient is estimated by adequate correlations

10.10.2012 7 Ampacity simulaion of high voltage cables

Page 8: Ampacity simulation of high voltage cables• For ampacity calculations for simple configurations the IEC standard calculation agrees with the simulation results • With higher complexity

(2) Comparison of IEC standard calculation method with COMSOL Mutliphysics

• COMSOL Multiphysics ampacity calculation:

– A equivalent model is defined in COMSOL – The heat source is defined according to the IEC calculation

method – The same cooling parameters on the outer surface are used – An iteration is carried out by using a Global equation iterating

towards the maximum allowed conductor temperature

10.10.2012 8 Ampacity simulaion of high voltage cables

Page 9: Ampacity simulation of high voltage cables• For ampacity calculations for simple configurations the IEC standard calculation agrees with the simulation results • With higher complexity

(2) Comparison of IEC standard calculation method with COMSOL Mutliphysics

• Single-conductor cable, comparison of temperature distribution and

iterated ampacity

• As expected for a simple radial heat conduction problem the results agree with each other 10.10.2012 9 Ampacity simulaion of high voltage cables

Page 10: Ampacity simulation of high voltage cables• For ampacity calculations for simple configurations the IEC standard calculation agrees with the simulation results • With higher complexity

(2) Comparison of IEC standard calculation method with COMSOL Mutliphysics

• The same procedure is carried out for a bundled geometry of three

single-conductor cables

10.10.2012 10 Ampacity simulaion of high voltage cables

Page 11: Ampacity simulation of high voltage cables• For ampacity calculations for simple configurations the IEC standard calculation agrees with the simulation results • With higher complexity

(2) Comparison of IEC standard calculation method with COMSOL Mutliphysics

• IEC standard ampacity calculation:

– Simple calculation of radial heat conduction is amended by a factor considering the bundled geometry

– Heat source and cooling is implemented according to the first case • COMSOL Multiphysics ampacity calculation:

– The exact geometry is implemented in COMSOL – Heat source and cooling is implemented according to the first case

10.10.2012 11 Ampacity simulaion of high voltage cables

Page 12: Ampacity simulation of high voltage cables• For ampacity calculations for simple configurations the IEC standard calculation agrees with the simulation results • With higher complexity

(2) Comparison of IEC standard calculation method with COMSOL Mutliphysics

• Three boundled single-conductor cables, comparison of temperature

distribution and iterated ampacity

• With a still simple but more complex geometry results start to differ

10.10.2012 12 Ampacity simulaion of high voltage cables

Page 13: Ampacity simulation of high voltage cables• For ampacity calculations for simple configurations the IEC standard calculation agrees with the simulation results • With higher complexity

Content (1) Introduction (2) Comparison of IEC standard calculation method with COMSOL

Mutliphysics (3) Evaluation of a three-conductor high voltage cable configuration (4) Conclusion

10.10.2012 13 Ampacity simulaion of high voltage cables

Page 14: Ampacity simulation of high voltage cables• For ampacity calculations for simple configurations the IEC standard calculation agrees with the simulation results • With higher complexity

(3) Evaluation of a complex three-conductor geometry • Next COMSOL Multiphysics was used to evaluate a more complex

configuration containing free convection in a cylindrical casing • Those configurations are often used in off shore wind farms to route

the cable in a wind turbine to the generator

10.10.2012 14 Ampacity simulaion of high voltage cables

Page 15: Ampacity simulation of high voltage cables• For ampacity calculations for simple configurations the IEC standard calculation agrees with the simulation results • With higher complexity

(3) Evaluation of a complex three-conductor geometry • The geometry contains multiple conductors, screen and armour as well

as several isolating matterials • The cable itself runs vertivally through an air-filled metal cylinder • The partly extruded geometry:

10.10.2012 15 Ampacity simulaion of high voltage cables

Page 16: Ampacity simulation of high voltage cables• For ampacity calculations for simple configurations the IEC standard calculation agrees with the simulation results • With higher complexity

(3) Evaluation of a complex three-conductor geometry • Implementation • Cable:

– 3D Heat Transfer in solids – Heat sources in conductot, armour and screen

• Outer cylinder – 2D-axisymmetric Conjugate Heat Transfer – Free convection resulting from the temperature field – Outer surface is cooled via Radiation and Convective Cooling

boundary • Cable surface and air filled cylinder are linked with an Extrusion

Operator

10.10.2012 16 Ampacity simulaion of high voltage cables

Page 17: Ampacity simulation of high voltage cables• For ampacity calculations for simple configurations the IEC standard calculation agrees with the simulation results • With higher complexity

(3) Evaluation of a complex three-conductor geometry • Results

– The model was evaluated for different load cases, determining the typical temperatures for different conditions

10.10.2012 17 Ampacity simulaion of high voltage cables

Page 18: Ampacity simulation of high voltage cables• For ampacity calculations for simple configurations the IEC standard calculation agrees with the simulation results • With higher complexity

Content (1) Introduction (2) Comparison of IEC standard calculation method with COMSOL

Mutliphysics (3) Evaluation of a three-conductor high voltage cable configuration (4) Conclusion

10.10.2012 18 Ampacity simulaion of high voltage cables

Page 19: Ampacity simulation of high voltage cables• For ampacity calculations for simple configurations the IEC standard calculation agrees with the simulation results • With higher complexity

(4) Conclusion • For ampacity calculations for simple configurations the IEC standard

calculation agrees with the simulation results • With higher complexity of the cable configuration the two methods start

to differ, the standard calculation method contains larger safety margins where the simulation has a better ability in resolving the geometrical relations

• It was shown that a larger configuration containing free convection inside a cylinder could be implemented to further investigate cable designs

10.10.2012 19 Ampacity simulaion of high voltage cables

Page 20: Ampacity simulation of high voltage cables• For ampacity calculations for simple configurations the IEC standard calculation agrees with the simulation results • With higher complexity

Kontakt: Dr.-Ing. David Wenger

Wenger Engineering GmbH Einsteinstr. 55

89077 Ulm 0731-159 37 500

[email protected]