Download - Advantys ETB Ethernet IP67 I/O
Advantys ETB Ethernet IP67 I/O
Introducing Schneider Electric’s new family of IP67 rated I/O modules that connect to Ethernet.
Advantys ETB
Advantys ETB Ethernet IP67 I/O modules
●Direct connection to the Ethernet network with models that support:● Ethernet Modbus TCP/IP Protocol
● EtherNet/IP Protocol
●Direct mounting on equipment, eliminates need for enclosures
● IP67 rated modules suited for harsh environments
●Complete product offer with a full set of power, sensor, and Ethernet cables and accessories
Product overviewProduct features & specificationsSystem viewCompetitive positionCost comparisonsCustomer values
●16 Point Digital Modules: available types● 16 digital Inputs● 12 Inputs/ 4 Outputs @ 2 Amps● 8 Inputs / 8 Outputs @ 2 Amps● 16 digital Inputs/Outputs configurable
●Ethernet Protocols supported● EtherNet/IP
● Modbus TCP/IP
●Protection Level, IP67 Watertight●Extended Operating Temp. - 25°C to + 70°C●Built-in 2 port switch for Daisy Chain Connection● Integrated Web Server●Scrolling LED Display
Product overview
Product overview
Modbus TCP/IP ETB 1EM 16C POO 16 point module, configurable as inputs or outputs ETB 1EM 16E PPO 16 point input module ETB 1EM 12E 04S PPO 12 point input / 4 point output module ETB 1EM 08E 08S PPO 8 point input / 8 point output module
EtherNet/IP ETB 1EI 16C POO 16 point module, configurable as inputs or outputs ETB 1EI 16E PPO 16 point input module ETB 1EI 12E 04S PPO 12 point input / 4 point output module ETB 1EI 08E 08S PPO 8 point input / 8 point output module
Product overview●Product Features
2- Power connections, type 7/8threaded connectors
8 – Input/ Output point ports,2 I/O points per connector, for M12 threaded and Ultra-Lock connectors
2 – Switched Ethernet communication ports, for M12 threaded and Ultra-Lock connectors
Scrolling 4 digit LED Display
●Complete Product Offer – Cables and Accessories
Product overview
Power CablesAvailable in versions with connector at each end or with single connector at one end for connection to Power Supply. 4 Pin connector versions for EtherNet/IP5 Pin connector versions for Modbus TCP
Sensor CablesAvailable in versions with M12 threaded connectors or with quick release Ultra- Lock connectors. Also available are splitter cables to connect 2 sensors to a single I/O port.
Ethernet Communication CablesAvailable in versions with an RJ 45 connector at one end and an M12 connector at other end, or versions with 2- M12 connectors.
(Note: The cable jacket material is approved for both the European and North American markets)
Product overview
Enclosure
PowerSupply
Processor
Ethernet Cable toconnect next module
Power Supply Cablesto additional modules
Splitter Cable to sensors
●Module with cables and accessories
Power Tee
Power Receptacle
Ethernet Cable Adapter
Target markets for IP67 I/O
●Installed Base Customers - Automotive●Machining●Component Assembly●Body Assembly
●Food and Beverage●Bottling●Packaging●Material Handling
●Other●Mining, Minerals, & Metal – Material Handling●Printing●Pulp & Paper – Pulping Paper Machine Wet End
Target markets for IP67 I/O
●Where to use Ethernet IP67 rated I/O Modules● Harsh Environments that include:
● Oil and/or water spray● Extended operating temperature -25 to + 70°C● High vibration and shock
● I/O Modules must or can be mounted directly on equipment● Field devices are located near I/O Modules, no long wire runs● There is no space available for I/O cabinets at location● Need to reduce the cost and time to install the I/O modules ● Field devices selected are available with M12 connectors● Customers are using Ethernet as their industrial communication
network
Product overviewProduct features & specificationsSystem viewCompetitive positionCost comparisonsCustomer values
Product features●Built for operation in harsh environments
● IP67 Rated Module Package, Connectors, and Cables
● Extended Operating Temperature Range -25°C to + 70°C
● Flexible Mounting System
●Benefit● Watertight, can be used in locations with oil and water spray
● Used on plant floor or outdoors
● Mounts directly on equipment – no need for enclosure
●Reduced installed cost – Ethernet Switch● Built-in 2 Port Unmanaged Ethernet Switch with cross-over capability
- allows daisy chain connections for Ethernet with no need for external switches
● Daisy-chain connection for Power Supply
Product features
Processor
Power Supply
Ethernet
Daisy Chainconnection –Up to 10 Modules
Product features●Reduced Installed Cost - M12- Ultra-Lock quick release Connector
● Faster and easier to connect then standard threaded M12
● Easy to connect – even when difficult to access
● Snap on for IP67 sealing of connections
● Standard M12-connectors can also be used on modules
● Reduced Installed Cost – Built-in Display with Control Buttons ● 4-Character LED Display allows diagnosis without additional tools
● Shows Current IP Address
● Displays IP Address Configuration Mode
● Control Buttons for Setting IP Address in Static Mode
● Displays Errors
● Network functions are displayed (e.g. ping)
Product features
Product features●Reduced Installed and Operating Cost – Integrated Web Server
provides the following capabilities● Password Protection for Security
● Module Configuration - IP Address, Module Parameters, and WDT Error behavior
● Module Status Information
● Remote Access and Diagnosis via Web – Interface
● No additional software tool needed for configuration and diagnosis
Product featuresModule diagnosis
Input / Output Input / Output on
Input / Output failed
Input / Output off
Display with information about Ethernet address, IO & watchdog status
Ethernet Port 100MBit Communication
10MBit Communication
Module & Input Power Power present
Power not connected
Output Power Power present
Power not connected
Module specifications
●Common specifications for all modules
Number of I/O Points 16 Digital Points per Module
I/O Configurations 16 Inputs12 Inputs / 4 Outputs 8 Inputs / 8 Outputs16 I/O Points, User configurable
I/O Points per Connectors 2 Points
Power Requirements 24 VDC – Module and Input Power13 to 28 VDC, 8 amp max. Outputs
Input Type Compatible with Contact and 3 wire devices
Input Delay 2.5 ms default, user configurable
Output Current 2 amps per Output, 8 amps per Module
Output Protection Electronic Short Circuit Protection
Max. Switching Frequency 200 Hz
Short Circuit Current 6.5 Amps (typical)
Module specifications●Common specifications for all modules (continued)
Operating Temperature -25°C to + 70°C ( -4° to + 158°F)
Storage Temperature -40°C to + 85°C ( -40° to + 185°F)
Protection IP67 according to IEC 60529
Vibration IEC 60068-2-8
Mechanical Shock 10G, 11 ms, 3 axis
MTBF 100,000 Hours
Power Connectors 7/8 Connectors, 5 pin for Modbus TCP/IP
4 pin for EtherNet/IP
Ethernet Connections M12 and Ultra-Lock Connectors, 4 pin
I/O Connectors M12 and Ultra-Lock Connectors, 5 pin
Product overviewProduct features & specificationsSystem viewCompetitive positionCost comparisonsCustomer values
●Ethernet (Modbus TCP/IP) based control system using a combination of IP67 and IP20 I/O
Ethernet Switch/ M1 Processor
PC/Supervisory System
Advantys ETB IP67 I/Omounted on equipment
Advantys STB IP20 I/Omounted in cabinets
Typical system configuration
Typical system configuration
●Control system topology for EtherNet/IP network
PLC or IPCEtherNet/IP
Switch
Advantys ETB IP67 I/O mounted on equipment
Typical system configuration●Ethernet (Modbus TCP/IP) modules can be used with the following Schneider control systems:
● Quantum system with NOE Ethernet interface
● Premium system with ETY Ethernet interface
● M340 system with NOE Ethernet interface
● Momentum system using M1E Ethernet processors
Typical system configuration●EtherNet/IP modules can be used with the following Schneider control systems along with other control systems:
● Quantum system with NOC Ethernet interface
● Premium system with ETC Ethernet interface
● Rockwell ControlLogix and CompactLogix systems = opportunity at competitive accounts
Typical I/O configuration
●Advantys ETB I/O has the flexibility to be installed in the following configurations:
● Daisy Chain
● Star
● Combination
Typical I/O configuration
●Daisy Chain I/O configuration
● Where to use
Systems with I/O count under 160 I/O points
Installations where I/O blocks are within 5 meters of the next block
Applications where installed cost is an issue
● Advantages
Lower installed cost
Eliminates external switch
Easy to expand system
Simplified troubleshooting and maintenance
● Limitations
Up to 10 modules per Daisy Chain
Disconnecting 1 module will shut down the following modules in the daisy chain
Typical I/O configuration
●Star configuration
● Where to use
Systems with large number of I/O points
Installations where the I/O is not concentrated in one area
Applications where system will be changing, with modules added, disconnected and reconnected to the network
● Advantages
Large number of modules per system (limitation is number of switches)
Flexible module location
● Disadvantages
Higher installed cost, switches
Longer cable runs, adds complexity
Maintenance requires additional effort
●Combination of Star and Daisy Chain configuration●Where to use
Large systems with multiple machine or work areas●Advantages
Segments modules into groups for each area
Simplifies installation and troubleshooting
Has lower installed cost than Star only network●Disadvantages
Most effective for larger systems
Typical I/O configuration
Typical field devices
●Advantys ETB I/O can connect directly to sensors and field devices that are available with M12 connectors and are IP67 rated.
● Schneider Electric Sensors include:
-Osiprox XS6 and XS8 Inductive Sensors
-Osiris XUB Photoelectric Sensors
-PhotoVirtu XUN Teachable Sensors
-VM1 Ultra Sonic Sensors
For the full range of Schneider Electric sensors, please visit our web site: http://www.sensors.com/
Product overviewProduct features & specificationsSystem viewCompetitive positionCost comparisonsCustomer values
Competitive advantages
●Built-in Ethernet Switch Save time and money by eliminating the need for external switches to connect modules
● Integrated Web Server Simplifies Module Configuration & DiagnosticsNo Additional Software Required
●4 Character Display Real Time Ethernet and Diagnostic Information
●Quick Release Connectors Fast connection to communications, and field devices
Competition
Schneider
Advantys ETB1732 Armor
Block PicoNet I/O Cube 67SAI Active
Universal ProFieldbus Box Couplier Box
Fieldline Modular
X 67 System
Ethernet IP X X X X X XModbus TCP/IP X X X X XProfiNet X X XPower Link X XEtherCat X
Types of Modules
Digital Inputs/Outputs X X X X X X X XAnalog Inputs/Outputs X X X X X X
Block X XBlock Modular X X X X X X
Built-in Switch X XBuilt-in Display XM12 Quick release connectors XIntegral Web Server X XExtended Operating Temp X
IP 6x Block and Block Modular I/O Systems
Network Types
Architecture
Features
Product overviewProduct features & specificationsSystem viewCompetitive positionCost comparisonsCustomer values
IP67 I/O cost advantages●Lower installed cost
● No need for cabinet or enclosure
● Plug-in cables for Power, I/O, and Ethernet Communications
● Simplified configuration via Web Pages or HMI Display
Field Sensors and Actuators
Traditional I/O System
I/O Modules
Wiring Duct
Terminal Blocks
Advantys ETB I/O
Total Installed Cost €825.70 €655.00
Installed cost comparison16 I/O points
●Traditional I/O system (IP20) includes the following;● NEMA 4 metal enclosure 16”x12”x8”
● 2 wires per device
● Wiring from I/O module to Terminal blocks
● Wiring from Terminal blocks to Field Devices
● Power Wiring coming from outside 24 VDC Power Supply
● Mounting I/O Module and Terminal Blocks
● Labels for all wires
●Advantys ETB IP67 Rated I/O modules includes the following● Power, Sensor, and Ethernet Cables
● Labor to install 10 threaded type connectors into module
●Not included in the installed cost comparison● I/O Modules, power supply, sensors or actuators
● Labor to mount I/O module or enclosure on machine
Installed cost comparisonAdvantys ETB IP67 vs IP20
●Summary of installed cost for 16 I/O points on Ethernet:
Advantys ETB IP20 I/O
Module cost (net)…….. €216.00 €204.00
Installation cost………. €439.00 €671.70
Total cost €655.00 €809.70 = €170.70 less
26%lower installed cost for Advantys ETB I/O
Installed cost comparison16 I/O points
Advantys ETB Traditional I/OQty. Cost
I/O Module 1 € 20.00 € 20.00Terminal blocks & hardware 1 € 20.00 € 20.00Fittings in cabinet for wiring 1 € 20.00 € 20.00
To Field Devices 16 € 10.00 € 160.00To Terminal Blocks 16 € 8.50 € 136.00Power Wiring 2 € 8.50 € 17.00Wire Lables 34 € 0.05 € 1.70
Enclosure € 205.00Terminal Blocks € 12.00Fittings € 20.00Wire € 10.00
Straight Cables 8 € 12.00 € 96.00Splitter Cables 8 € 27.00 € 216.00Power Cable 1 € 49.00 € 49.00Ethernet Cable 1 € 28.00 € 28.00
Install Cables in Module 10 € 5.00 € 50.00
Total Installed Cost € 439.00 € 621.70 € 182.70 41.62%
Cabling Labor
Difference
Traditional I/O
Wiring Cost Labor
Parts Cost
Sensor Cables
Mounting Labor
Advantys ETB
Product overviewProduct features & specificationsSystem viewCompetitive positionCost comparisonsCustomer values
Customer values●Simple Installation
● I/O mounted directly on equipment eliminates the need for enclosures
● Quick Release Connectors allow fast connection to power, communications, and field devices
● Direct Connection to Ethernet Network without the need for external switches
●Easy to Configure● Built-in Ethernet Switch for Network connections ● Web Pages and Display simplifies integration and
commissioning
●Solution Approach● Can be combined with Schneider PLC’s, sensors, actuators,
drives, and IP20 I/O for a total control system package● Complete solution with cables and accessories