Download - 46 Calculation

Transcript
  • 8/10/2019 46 Calculation

    1/10

    REL352AN-93L-02

    Phase Comparison Relay REL352 Current Pickup Calculation

    Introduction

    This note describes how to calculate the current pick-up level for different types of faults.

    IT current

    REL352 uses sequence filters to obtain positive, negative and zero sequence currents. These currents arethen combined into one quantity:

    021 021 ICICICIT ++=

    The positive, negative and zero sequence current is computed from the phase currents by the use ofClarkes components based on sample currents that can mathematically be expressed as:

    3

    3

    43.104983.043.134983.015966.0

    3

    43.134983.043.104983.015966.0

    0

    2

    1

    CBA

    CBA

    CBA

    IIII

    IIII

    IIII

    ++=

    ++=

    ++=

    The advantage of using Clarkes components is that they give a close approximation of symmetricalcomponents while not having the need of using complex numbers.

    Note that all sequence component currents are referenced to phase A current.

    General calculation of IT

    Based on input currents and C-settings, the IT current is calculated as follows:

    Settings

    0

    2

    1

    C

    C

    C

    ABBApplication NoteSubstation Automation and Protection Division

  • 8/10/2019 46 Calculation

    2/10

    Phase Comparison Relay REL352 Current Pickup Calculation AN-93L-02

    2

    Input currents

    C

    B

    A

    I

    I

    I

    IT

    3

    )(

    3

    )43.104983.043.134983.015966.0(

    3

    )43.134983.043.104983.015966.0(

    02

    1

    002211

    CBACBA

    CBA

    T

    T

    IIICIIIC

    IIICI

    ICICICI

    +++

    +++

    +++

    =

    =++=

    Example 1a, phase A to ground fault

    With settings

    0.1

    7.0

    1.0

    0

    2

    1

    =

    =

    =

    C

    C

    C

    and input currents

    0

    0

    00.5

    =

    =

    =

    C

    B

    A

    I

    I

    AI

    IT becomes:

    ACCC

    I

    ICICICI

    T

    T

    65.23

    )0.5(

    3

    )15966.00.5(

    3

    )15966.00.5( 021

    002211

    =+

    +

    =

    =++=

  • 8/10/2019 46 Calculation

    3/10

    Phase Comparison Relay REL352 Current Pickup Calculation AN-93L-02

    3

    Example 1b, phase B to ground fault

    With settings

    0.1

    7.0

    1.0

    0

    2

    1

    =

    =

    =

    C

    C

    C

    and input currents

    0

    1200.5

    0

    =

    =

    =

    C

    B

    A

    I

    I

    I

    IT becomes:

    ACCC

    I

    ICICICI

    T

    T

    33.13

    )1200.5(

    3

    )12043.134983.00.5(

    3

    )12043.104983.00.5( 021

    002211

    =

    +

    +

    =

    =++=

    That the IT current is different for a phase B to ground fault compared to phase A to ground is due to thefact that Clarkes symmetrical component computations are made referenced to phase A.

    REL352 Trip Criterion

    REL352 operates when the IT RMS current exceeds the LP setting, assuming that the relay is connected inloop-back or back-to-back (with the same current fed into the two relays):

    thresholdoperatingset

    currentcomposite

    =

    =

    >

    LP

    I

    where

    LPI

    T

    T

    It is also assumed that all other settings (IPL, IGL, ITA1, ITA2) are set so that they do not restrict tripping atthe set LP level.

  • 8/10/2019 46 Calculation

    4/10

    Phase Comparison Relay REL352 Current Pickup Calculation AN-93L-02

    4

    Sometimes, ITA2 is the limiting threshold, and then the operating criterion will be:

    thresholdoperatingset2

    currentcomposite

    2

    =

    =

    >

    ITA

    I

    where

    ITAI

    T

    T

    Pickup calculation

    To determine the theoretical pickup current for different types of fault, we need to determine that the outputfrom the trip criterion exceeds the set operating threshold.

    Set-up in loop-back or back-to-back is assumed so that IR= IL= IT, i.e. the infeed current from both ends areequal in magnitude and in phase. This represents an internal fault.

    In order to determine the required current threshold for operation for different types of faults the expressionsabove for ITand sequence currents need to be entered into the formula, solving the phase current(s).

    Phase A to ground fault

    Input currents

    0

    0

    0

    =

    =

    =

    C

    B

    aA

    I

    I

    AII

    Pickup current phase A

    )15966.015966.0(

    3

    3

    15966.015966.0

    021

    021

    002211

    CCCLPI

    LPICICIC

    LPICICIC

    LPI

    a

    aaa

    T

    ++>

    >++

    >++

    >

  • 8/10/2019 46 Calculation

    5/10

    Phase Comparison Relay REL352 Current Pickup Calculation AN-93L-02

    5

    Phase B to ground fault

    Input currents

    0

    120

    0

    =

    =

    =

    C

    bB

    A

    I

    II

    I

    Pickup current phase B

    )12043.254983.057.15983.0(

    3

    3

    12043.254983.057.15983.0

    021

    021

    002211

    ++>

    >++

    >++

    >

    CCCLPI

    LPICICIC

    LPICICIC

    LPI

    b

    bbb

    T

    Phase C to ground fault

    Input currents

    =

    =

    =

    120

    0

    0

    cC

    B

    A

    II

    I

    I

  • 8/10/2019 46 Calculation

    6/10

    Phase Comparison Relay REL352 Current Pickup Calculation AN-93L-02

    6

    Pickup current phase C

    )12043.224983.043.14983.0(

    3

    3

    12043.224983.043.14983.0

    021

    021

    002211

    ++>

    >++

    >++

    >

    CCCLPI

    LPICICIC

    LPICICIC

    LPI

    c

    ccc

    T

    Phase A to B fault

    Input currents

    0

    180

    0

    =

    =

    =

    C

    abB

    abA

    I

    II

    II

    Pickup current phases A and B

    )]57.45983.015966.0()43.284983.015966.0([

    3

    3

    )57.45983.015966.0()43.284983.015966.0(

    21

    21

    002211

    +++>

    >+++

    >++

    >

    CCLPI

    LPIICIIC

    LPICICIC

    LPI

    ab

    abababab

    T

  • 8/10/2019 46 Calculation

    7/10

    Phase Comparison Relay REL352 Current Pickup Calculation AN-93L-02

    7

    Phase B to C fault

    Input currents

    =

    =

    =

    60

    120

    0

    bcC

    bcB

    A

    II

    II

    I

    Pickup current phases B and C

    )]43.164983.043.254983.0()43.74983.057.15983.0([

    3

    3

    )43.164983.043.254983.0()43.74983.057.15983.0(

    21

    21

    002211

    +++>

    >+++

    >++

    >

    CCLPI

    LIICIIC

    LPICICIC

    LPI

    bc

    bcbcbcbc

    T

    Phase C to A fault

    Input currents

    =

    =

    =

    120

    0

    60

    caC

    B

    caA

    II

    I

    II

  • 8/10/2019 46 Calculation

    8/10

    Phase Comparison Relay REL352 Current Pickup Calculation AN-93L-02

    8

    Pickup current phases C and A

    )]43.224983.075966.0()43.14983.075966.0([

    3

    3

    )43.224983.075966.0()43.14983.075966.0(

    21

    21

    002211

    +++>

    >+++

    >++

    >

    CCLPI

    LPIICIIC

    LPICICIC

    LPI

    ca

    cacacaca

    T

    Three phase ABC fault

    Input currents

    =

    =

    =

    120

    120

    0

    abcC

    abcB

    abcA

    II

    II

    II

    Pickup current phases A, B and C

    43.224983.043.254983.015966.0()43.14983.057.15983.015966.0(

    3

    3

    )43.224983.043.254983.015966.0(

    3

    )43.14983.057.15983.015966.0(

    21

    2

    1

    002211

    +++++>

    >++

    +++

    >++

    >

    CCLPI

    LPIIIC

    IIIC

    LPICICIC

    LPI

    abc

    abcabcabc

    abcabcabc

    T

    Theoretically, there should be no negative sequence current for a three phase fault, but Clarke introduces asmall value. However, the formula for three phase fault pickup current can be simplified by removing the C2term. The error by doing so will result in less than 10% error. Note however, that the below formula gives a10% highertheoretical result (i.e. the actual test current required for operation is lower).

  • 8/10/2019 46 Calculation

    9/10

  • 8/10/2019 46 Calculation

    10/10

    Phase Comparison Relay REL352 Current Pickup Calculation AN-93L-02

    10

    Example 2b, Phase B to ground fault

    With input currents:

    0

    120

    0

    =

    =

    =

    C

    bB

    A

    I

    II

    I

    and settings:

    0.10

    7.02

    1.01

    5.0

    =

    =

    =

    =

    C

    C

    C

    OTH

    the required phase B current becomes:

    63.5)1200.143.254983.07.057.15983.01.0(

    3

    3

    1200.143.254983.07.057.15983.01.0

    002211

    =++

    >

    >++

    >++

    >

    LPI

    LPIII

    LPICICIC

    LPI

    b

    bbb

    T

    That the pickup current is higher for a phase B to ground fault compared to phase A to ground is due to thefact that the symmetrical component computations of IT are made referenced to phase A.

    Contributed by:Solveig WardRevision 0, 03/25/02

    ABB Inc.7036 Snowdrift RoadAllentown, PA 18106800-634-6005 Fax 610-395-1055Email: [email protected]: www.abb.com/substationautomation


Top Related