Download - 3851_1_AS_620B_HW-exchange_S5_to_S7_e
-
7/27/2019 3851_1_AS_620B_HW-exchange_S5_to_S7_e
1/11
Copyright Siemens AG 2007. All Rights Reserved.
SPPA-T2000
AS 620 Hardware exchangeS5 / S7
Instrumentation & Controls
-
7/27/2019 3851_1_AS_620B_HW-exchange_S5_to_S7_e
2/11
Page 2 March-2007 Power Generation / Instrumentation & Controls / PG L5Andreas Lang
Copyright Siemens AG 2007. All Rights Reserved.
AP based on SIMATIC S5
ZG 155 S5-Rack
CPU 948R Processor ModuleCP 1430 Ethernet Communication
ProcessorIM 308C PROFIBUS DP MasterIM 304 Interface Module to FUMIM 324 Redundancy Coupling
AP based on SIMATIC S7Release 8
UR 2-H S7-Rack
CPU 417H Processor ModuleCP 443-1 Ethernet Communication
ProcessorCP 443-5 PROFIBUS DP Master
also used with FUM
SPPA-T2000 Application Processor
Comparison of SIMATIC S5 and SIMATIC S7
-
7/27/2019 3851_1_AS_620B_HW-exchange_S5_to_S7_e
3/11
Page 3 March-2007 Power Generation / Instrumentation & Controls / PG L5Andreas Lang
Copyright Siemens AG 2007. All Rights Reserved.
Redundant AP based on SIMATIC S7
Coupled with Function Modules (FUM)
Redundant AP
(SIMATIC S7)
FUM - subrack
(19 modules)
Field Bus
AP
SIMATIC S7
FUM
typical
2 FUM subracks
FUM
PROFIBUS-DP
FUM
FUM
FUM
FUM
typical
4 FUM subracks
IM 616
max. 6 FUM- subracks per AP allowed
FUM
FUM
typical
2 FUM subracks
Plant Bus
-
7/27/2019 3851_1_AS_620B_HW-exchange_S5_to_S7_e
4/11
Page 4 March-2007 Power Generation / Instrumentation & Controls / PG L5Andreas Lang
Copyright Siemens AG 2007. All Rights Reserved.
SIEMENS TEL ERP ERM XP
AP basedon S5
Monitoring-distribution unit
Monitoringcable
IM 614
Internalcabinet bus
IM 614
IM 614
EU 902 rack
AS 620B HW - Exchange of S5 to S7
TELEPERM XP Cabinet with AP based on S5
TELEPERM XP cabinetwith AP based on S5
-
7/27/2019 3851_1_AS_620B_HW-exchange_S5_to_S7_e
5/11
Page 5 March-2007 Power Generation / Instrumentation & Controls / PG L5Andreas Lang
Copyright Siemens AG 2007. All Rights Reserved.
SIEMENS TELER PER M XP
Monitoringcable
IM 614
Backplane*
IM 614
IM 614
Monitoringdistribution unit
EU 902 rack
AS 620B HW - Exchange of S5 to S7
Removal of all S5 components
Removal of
S5 components
TELEPERM XP cabinet
without AP
*) the change of the backplane depends on the backplane version,FUM rack friom January 2006 onwards require no exchange
AP basedon S5
Internalcabinet bus
-
7/27/2019 3851_1_AS_620B_HW-exchange_S5_to_S7_e
6/11
-
7/27/2019 3851_1_AS_620B_HW-exchange_S5_to_S7_e
7/11
Page 7 March-2007 Power Generation / Instrumentation & Controls / PG L5Andreas Lang
Copyright Siemens AG 2007. All Rights Reserved.
SPPA-T2000
with AP based on S7
AP basedon S7
SIEMENS SPPA-T2000
IM 616
PROFIBUScable
IM 616
IM 616
AS 620B HW - Exchange of S5 to S7
HW - Exchange completed
EU 902 rack
Monitoringcable
-
7/27/2019 3851_1_AS_620B_HW-exchange_S5_to_S7_e
8/11
Page 8 March-2007 Power Generation / Instrumentation & Controls / PG L5Andreas Lang
Copyright Siemens AG 2007. All Rights Reserved.
Plantwith AP based on SIMATIC S5
Release 7.8
PU SU
Web-Client
ES
APSIMATIC S5
APSIMATIC S5
Plant Bus
Terminal Bus
DS
SPPA-T2000
ES/DS-Server for AP based on S7 Release 8.1
Plantwith AP based on SIMATIC S7
Release 8.1
APSIMATIC S7
ES/DS-Server
PU
Plant Bus
APSIMATIC S7
SU
Terminal Bus
Web-Client for ES/DS-Server
-
7/27/2019 3851_1_AS_620B_HW-exchange_S5_to_S7_e
9/11
Page 9 March-2007 Power Generation / Instrumentation & Controls / PG L5Andreas Lang
Copyright Siemens AG 2007. All Rights Reserved.
One Server or PC for all requirements Engineering and Diagnostics
The DS light version can be easily upgraded to the full DS version by purchasing a licenseAll functionalities are already built in to the ES/DS-Server
Integrated Web-Server
Flexible, inexpensive and reliable disk-less Thin Clients (Futro)
ES680 &
DS670 &
Web-Server
Thin Clients for Engineering & Diagnostics (Futro)
Terminal or Multimedia Bus
Plant bus
Sun Fire X4100 x64 Server (Solaris 10)
SPPA-T2000 Engineering and Diagnostics using only
a High Performance Server or PC
-
7/27/2019 3851_1_AS_620B_HW-exchange_S5_to_S7_e
10/11
Page 10 March-2007 Power Generation / Instrumentation & Controls / PG L5Andreas Lang
Copyright Siemens AG 2007. All Rights Reserved.
DS670 based onPCs (SCO 5.4)
For plants w ith an AP based on S7, an ES/DS-Server (SUN Solaris) is mandatory
For plants with an AP based on S5, a SW-Update R 8.1 for the HP 2600 is available
Engineering- and Diagnostics-Terminals based on Thin Clients
SPPA-T2000 R8.1
SPPA-T2000
-
7/27/2019 3851_1_AS_620B_HW-exchange_S5_to_S7_e
11/11