Download - 303.Testing of Relz100 With f6150-Distpro
-
8/6/2019 303.Testing of Relz100 With f6150-Distpro
1/31
India
Knowledge Is PowerSM
Apparatus Maintenance and Power
Management For Energy Delivery
DOBLE ENGINEERING PVT LTD
TESTING OF RELZ 100 RELAYWITH
F6150 & F6TEST SOFTWAREKAMIN DAVE (RELAY APPLICATION ENGINEER)
-
8/6/2019 303.Testing of Relz100 With f6150-Distpro
2/31
India
Knowledge Is PowerSM
Apparatus Maintenance and Power
Management For Energy Delivery
DOBLE ENGINEERING PVT LTD
RELAY INFORMATION:
Features:Simultaneous phase-phase and phase- earth loop impedance measurement, withindividual numerical measuring elements for each type of fault and each distancezone, ensures fast and reliable fault detection.
Minimum operating time: 13 ms
Typical operating time of impedance measuring function: 28 ms.
Multiprocessor design guarantees high availability together with excellent possibiliesfor combining optional functions.
Numerical filtering and measuring technique ensure correct performance during CTsaturation and CVT transients.
Versatile local human machine communication (HMC) from the relay front paneltogether with two optional serial ports brings REL 100 close to the any user whereverthey may be located (in the substation, in the control centre or in the office).
Basic version of REL 100 includes:three forward and one reverse distance zones with individual setting of reach inreactive and resistive direction as well setting of earth return compensating factor.
switch onto fault protection.
three-phase tripping.
-
8/6/2019 303.Testing of Relz100 With f6150-Distpro
3/31
India
Knowledge Is PowerSM
Apparatus Maintenance and Power
Management For Energy Delivery
DOBLE ENGINEERING PVT LTD
Distance Protection:
----- Typical Operating Time = 28ms
----- Minimum Operating current = 0.2*Ir
----- Reset Time:Forward = 40msReverse = 60ms
----- Tripping mode: Three Phase / Single Phase tripping
----- Number of Zones: 3-forward / 1-reverse
----- Impedance Setting Range at Ir = 1.0AReactive reach = (0.1 150)Ohms/PhaseResistive reach:- Phase Phase = (0.1 150)Ohms/Phase- Phase Loop = (0.1 150)Ohms/Phase
----- Setting range of Timer = (0 10)s
----- Power Swing detection element: (0.1 150)Ohms
-
8/6/2019 303.Testing of Relz100 With f6150-Distpro
4/31
India
Knowledge Is PowerSM
Apparatus Maintenance and Power
Management For Energy Delivery
DOBLE ENGINEERING PVT LTD
RELAY SETTINGS:
CLIENT: RELIANCE ENERGY LTD-DAHANU
SERVICE SETTING:
ZONE:-1- EARTH FAULT UNIT:
R1 = 15.02 OHMX1 = 15.99 OHMKN = 0.59t1 = 0ms
PHASE FAULT UNIT:R1 = 3.85 OHM
X1 = 15.99 OHMt1 = 0ms
ZONE:-2 - EARTH FAULT UNIT:
R2 = 20.4 OHMX2 = 22.41 OHMKN = 1.12t2 = 400ms
PHASE UNIT:
R2 = 4.8 OHMX2 = 22.41 OHM
t2 = 400ms
ZONE:-3 - EARTH FAULT UNIT:
R3 = 23.81 OHMX3 = 43.97 OHMKN = 0.59t3 = 750ms
PHASE UNIT:
R3 = 7.97 OHMX3 = 43.97 OHMt3 = 750ms
-
8/6/2019 303.Testing of Relz100 With f6150-Distpro
5/31
India
Knowledge Is PowerSM
Apparatus Maintenance and Power
Management For Energy Delivery
DOBLE ENGINEERING PVT LTD
STEP:-1SELECT DATABASE OF RELZ100
DOUBLE CLICK ON RELZ100
-
8/6/2019 303.Testing of Relz100 With f6150-Distpro
6/31
India
Knowledge Is PowerSM
Apparatus Maintenance and Power
Management For Energy Delivery
DOBLE ENGINEERING PVT LTD
STEP:-2HOW TO SET RELAY CHARACTERISTIC FOR TEST?
SINGLE CLICK ON RELAY PARAMETERS
-
8/6/2019 303.Testing of Relz100 With f6150-Distpro
7/31
India
Knowledge Is PowerSM
Apparatus Maintenance and Power
Management For Energy Delivery
DOBLE ENGINEERING PVT LTD
STEP:-3OPEN EXISTING DATABASE
-
8/6/2019 303.Testing of Relz100 With f6150-Distpro
8/31
India
Knowledge Is PowerSM
Apparatus Maintenance and Power
Management For Energy Delivery
DOBLE ENGINEERING PVT LTD
STEP:-4Modify your settings in Existing database
Select zone & Press Modify button
SELECT GENERAL & ENTER KN VALUE
-
8/6/2019 303.Testing of Relz100 With f6150-Distpro
9/31
India
Knowledge Is PowerSM
Apparatus Maintenance and Power
Management For Energy Delivery
DOBLE ENGINEERING PVT LTD
STEP:-5READY MADE SHAPES ARE OPEN
-
8/6/2019 303.Testing of Relz100 With f6150-Distpro
10/31
India
Knowledge Is PowerSM
Apparatus Maintenance and Power
Management For Energy Delivery
DOBLE ENGINEERING PVT LTD
STEP:-6SINGLE CLICK ON QUAD 2 SHAPE & ENTER RELAY PARAMETERS
ENTER R VALUE
ENTER X VALUE & PUT ANGLE = 90 DEG.ENTER VALUES OF DIRECTIONAL LINES
PRESS OK BUTTON & SAVE IT.
-
8/6/2019 303.Testing of Relz100 With f6150-Distpro
11/31
India
Knowledge Is PowerSM
Apparatus Maintenance and Power
Management For Energy Delivery
DOBLE ENGINEERING PVT LTD
STEP:-7
ENTER TOLERANCES & CLOSE WINDOW
-
8/6/2019 303.Testing of Relz100 With f6150-Distpro
12/31
India
Knowledge Is PowerSM
Apparatus Maintenance and Power
Management For Energy Delivery
DOBLE ENGINEERING PVT LTD
HOW TO ENTER IN TESTPLAN FOR TEST?
STEP:-1SINGLE CLICK ON TESTPLAN TAB
DOUBLE CLICK ON TEST PLAN
-
8/6/2019 303.Testing of Relz100 With f6150-Distpro
13/31
India
Knowledge Is PowerSM
Apparatus Maintenance and Power
Management For Energy Delivery
DOBLE ENGINEERING PVT LTD
STEP:-2
NOW, TEST PLAN IS OPEN
SELECT Z-CHAR MODULE
-
8/6/2019 303.Testing of Relz100 With f6150-Distpro
14/31
India
Knowledge Is PowerSM
Apparatus Maintenance and Power
Management For Energy Delivery
DOBLE ENGINEERING PVT LTD
STEP:-3
SINGLE CLICK ON TEST ELEMENTS
SELECT FUNCTION NAME
-
8/6/2019 303.Testing of Relz100 With f6150-Distpro
15/31
India
Knowledge Is PowerSM
Apparatus Maintenance and Power
Management For Energy Delivery
DOBLE ENGINEERING PVT LTD
STEP:-4
SELECT TEST METHOD CONSTANT-I, V or Z
-
8/6/2019 303.Testing of Relz100 With f6150-Distpro
16/31
India
Knowledge Is PowerSM
Apparatus Maintenance and Power
Management For Energy Delivery
DOBLE ENGINEERING PVT LTD
STEP:-5
SELECT TRIGGER
SELECT TRIGGER (Say, Open to Close)
-
8/6/2019 303.Testing of Relz100 With f6150-Distpro
17/31
India
Knowledge Is PowerSM
Apparatus Maintenance and Power
Management For Energy Delivery
DOBLE ENGINEERING PVT LTD
STEP:-6
SINGLE CLICK ON TEST LINES
SELECT ANY ONE OPTION FOR TEST;1) RADIAL LINES2) User Drawn Lines
ENTER ANGLE BOUNDARY WITH DELTA STEP
-
8/6/2019 303.Testing of Relz100 With f6150-Distpro
18/31
India
Knowledge Is PowerSM
Apparatus Maintenance and Power
Management For Energy Delivery
DOBLE ENGINEERING PVT LTD
STEP:-7SINGLE CLICK ON TEST TAB
SELECT FAULT TYPE
RIGHT CLICK IN BOX; IT SHOWS ONLINE VECTOR & MEASUREMENT
NOW, APPLY RUN COMMAND FOR TEST.
-
8/6/2019 303.Testing of Relz100 With f6150-Distpro
19/31
India
Knowledge Is PowerSM
Apparatus Maintenance and Power
Management For Energy Delivery
DOBLE ENGINEERING PVT LTD
TESTED CHARACTERISTIC ON AB FAULT
BLUE COLOR SHOWS EXPECTED CHARACTERISTIC
RED & GREEN POINT SHOWS; ACTUAL OPERATING POINTS
Dotted line shows tolerances
-
8/6/2019 303.Testing of Relz100 With f6150-Distpro
20/31
India
Knowledge Is PowerSM
Apparatus Maintenance and Power
Management For Energy Delivery
DOBLE ENGINEERING PVT LTD
TEST RESULTS OF AB FAULT
TEST VOLTAGE & CURRENT
-
8/6/2019 303.Testing of Relz100 With f6150-Distpro
21/31
India
Knowledge Is PowerSM
Apparatus Maintenance and Power
Management For Energy Delivery
DOBLE ENGINEERING PVT LTD
SELECT BC FAULT FOR TEST
SELECT BC FAULT
-
8/6/2019 303.Testing of Relz100 With f6150-Distpro
22/31
India
Knowledge Is PowerSM
Apparatus Maintenance and Power
Management For Energy Delivery
DOBLE ENGINEERING PVT LTD
TESTED CHARACTERISTIC ON BC FAULT
-
8/6/2019 303.Testing of Relz100 With f6150-Distpro
23/31
India
Knowledge Is PowerSM
Apparatus Maintenance and Power
Management For Energy Delivery
DOBLE ENGINEERING PVT LTD
TEST RESULTS OF BC FAULT
-
8/6/2019 303.Testing of Relz100 With f6150-Distpro
24/31
India
Knowledge Is PowerSM
Apparatus Maintenance and Power
Management For Energy Delivery
DOBLE ENGINEERING PVT LTD
SELECT AN FAULT
SELECT AN FAULT
-
8/6/2019 303.Testing of Relz100 With f6150-Distpro
25/31
India
Knowledge Is PowerSM
Apparatus Maintenance and Power
Management For Energy Delivery
DOBLE ENGINEERING PVT LTD
TESTED CHARACTERISTIC OF AN FAULTS
-
8/6/2019 303.Testing of Relz100 With f6150-Distpro
26/31
India
Knowledge Is PowerSM
Apparatus Maintenance and Power
Management For Energy Delivery
DOBLE ENGINEERING PVT LTD
TEST RESULTS OF AN FAULT
-
8/6/2019 303.Testing of Relz100 With f6150-Distpro
27/31
India
Knowledge Is PowerSM
Apparatus Maintenance and Power
Management For Energy Delivery
DOBLE ENGINEERING PVT LTD
(B) TIME TEST:STEP:-1
SELECT Z-TIME MODULE & DOUBLE CLICK ON TIMER TEST
-
8/6/2019 303.Testing of Relz100 With f6150-Distpro
28/31
India
Knowledge Is PowerSM
Apparatus Maintenance and Power
Management For Energy Delivery
DOBLE ENGINEERING PVT LTD
STEP:-2SINGLE CLICK ON TEST POINTS
ADD POINT TO LIST BY MOUSE CLICKING ON R-X PLANE
SELECT FAULT TYPE
-
8/6/2019 303.Testing of Relz100 With f6150-Distpro
29/31
India
Knowledge Is PowerSM
Apparatus Maintenance and Power
Management For Energy Delivery
DOBLE ENGINEERING PVT LTD
STEP:-3SELECT FAULT TYPE (Say, AB)
SELECT FAULT TYPE
SELECT OPTION R-X PLANE
-
8/6/2019 303.Testing of Relz100 With f6150-Distpro
30/31
India
Knowledge Is PowerSM
Apparatus Maintenance and Power
Management For Energy Delivery
DOBLE ENGINEERING PVT LTD
SAME RESULT IN Z-T PLANE
SELECT Z-T PLANE
-
8/6/2019 303.Testing of Relz100 With f6150-Distpro
31/31
India
Knowledge Is PowerSM
Apparatus Maintenance and Power
Management For Energy Delivery
THANK YOUDOBLE ENGINEERING PVT LTD