DRAWN:
CHECKED:
NO. DATE
DESIGNED:
SCALE
REVISION
FAIRFAX WATER
PLANNING & ENGINEERING
DIVISION
FAIRFAX WATER
PLANNING & ENGINEERING DIVISION
8560 ARLINGTON BOULEVARD
FAIRFAX, VA 22031
RhinoFire Protection Engineering, PLLC
Newington Maintenance Facility
002
----
----
----
-----------
CPT
PAM
FAE
----
----
----
----TITLE SHEET
NEWINGTON FIRE ALARM SYSTEM REPLACEMENT
5-Jun-20
0650
8570 Executive Park Avenue ~ Fairfax ~ Virginia ~ 22031
Newington Fire Alarm System ReplacementFairfax Water Authority Project No. 0650, Division 002
8001 Cinder Bed Road ~ Lorton ~ Virginia ~ 22079
DRAWING INDEX
SHT.
NO.DWG. NO. DESCRIPTION
TITLE SHEET
FIRE ALARM COVER SHEET
FA FIRST FLOOR NEW WORK FIRE ALARM PLAN - PART A
FA FIRST FLOOR NEW WORK FIRE ALARM PLAN - PART B
FA SECOND FLOOR NEW WORK FIRE ALARM PLAN - PARTIAL
FA FIRE ALARM DETAILS
FA FIRE ALARM MATRIX AND RISER DIAGRAM
PROJECT LOCATION MAPSCALE: N/A
NE
WIN
GT
ON
FIR
E A
LA
RM
SY
ST
EM
RE
PLA
CE
ME
NT
8001 C
IND
ER
BE
D R
OA
D, LO
RT
ON
, V
AJU
NE
20
20
10
0%
DE
SIG
N
DR
AW
ING
SP
0650-0
02
06/10/2020
DRAWN:
CHECKED:
NO. DATE
DESIGNED:
SCALE
REVISION
FAIRFAX WATER
PLANNING & ENGINEERING
DIVISION
FAIRFAX WATER
PLANNING & ENGINEERING DIVISION
8560 ARLINGTON BOULEVARD
FAIRFAX, VA 22031
RhinoFire Protection Engineering, PLLC
Newington Maintenance Facility
002
----
----
----
-----------
FAE
PAM
PAM
----
----
----
----GENERAL NOTES, LEGEND & ABBREVIATIONSNEWINGTON FIRE ALARM SYSTEM REPLACEMENT
5-Jun-20
0650
FIRE ALARM GENERAL NOTES1. SCOPE OF WORK INCLUDES PROVIDING A NEW ANALOG ADDRESSABLE FIRE ALARM AND VOICE EVACUATION FIRE ALARM SYSTEM
THROUGHOUT THE BUILDING FOR THE RENOVATION OF THE FIRE ALARM SYSTEM. ALL ENGINEERING DESIGN WORK AND
INSTALLATION SHALL CONFORM WITH THE VIRGINIA CONSTRUCTION CODE (VCC) 2015 EDITION, NFPA STANDARDS NOS. 70 (2014
EDITION), 72 (2013 EDITION), AND OTHER CODES AND STANDARDS INDICATED IN THESE DRAWINGS AND SPECIFICATIONS. THE
SCOPE INCLUDES BUT IS NOT LIMITED TO A NEW FIRE ALARM CONTROL PANEL/ MODULES/ POWER SUPPLIES/AMPLIFIERS,
SPRINKLER SYSTEM SUPERVISION, MANUAL PULL STATIONS, SYSTEM SMOKE/HEAT DETECTORS, DUCT DETECTORS, HORN AND
STROBES FOR OCCUPANT NOTIFICATION, WIRING, CONDUIT AND ALL OTHER ASSOCIATED LABOR, EQUIPMENT AND MATERIALS,
SOFTWARE, AND PROGRAMMING WHETHER MENTIONED OR NOT, FOR A COMPLETE FIRE ALARM SYSTEM COMPLYING WITH THE
APPLICABLE PROVISIONS OF THE CODES OF REFERENCE.
2. SITE VERIFY THE LOCATION OF SMOKE AND FIRE RATED WALLS. ALL PENETRATIONS IN RATED WALLS SHALL BE FIRE STOPPED IN
ACCORDANCE WITH THE PROJECT SPECIFICATIONS. ALL FLOOR PENETRATIONS SHALL BE FIRE STOPPED IN ACCORDANCE WITH
PROJECT SPECIFICATIONS. ALL FLOORS SHALL BE CONSIDERED 2-HOUR RATED FLOORS, UNO.
3. COORDINATE WALL AND CEILING DEVICE LOCATIONS WITH EXISTING CONDITIONS.
4. FIELD VERIFY THE LOCATION OF DUCT SMOKE DETECTORS FOR MECHANICAL EQUIPMENT AND SMOKE DAMPERS. PROVIDE
ADDRESSABLE INTERFACE AND ADDRESSABLE RELAYS AS NEEDED TO MONITOR DUCT SMOKE DETECTORS AND SHUT DOWN THE
ASSOCIATED HVAC EQUIPMENT BY THE FIRE ALARM SYSTEM.
5. CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING ADDITIONAL DEVICES, POWER SUPPLY AND AMPLIFIER AS NECESSARY TO
SUPPLY THE NOTIFICATION DEVICES TO COMPLY WITH APPLICABLE CODES, AND SPECIFICATIONS.
6. THE CONTRACTOR SHALL FIELD VERIFY THE LOCATION OF ALL SYSTEM COMPONENTS. CONTRACTOR(S) SHALL REPORT ANY
DISCREPANCIES WITH THESE DRAWINGS OR CONFLICTS BETWEEN THE SPECIFICATIONS AND DRAWINGS TO THE OWNER'S
ATTENTION IMMEDIATELY. THE CONTRACTOR(S) SHALL NOT PROCEED WITH ANY WORK, EXCEPT AT THEIR OWN RISK, UNTIL
CLARIFICATIONS OF THE CONFLICTS ARE ISSUED TO THE CONTRACTOR(S) BY THE OWNER.
7. CONTRACTOR SHALL BE RESPONSIBLE FOR AVOIDING ALL CONFLICTS WITH LIGHTING FIXTURES, DIFFUSERS, GRILLS, DUCTS,
STRUCTURAL MEMBERS, PIPING, AND OTHER OBSTRUCTIONS ENCOUNTERED.
8. THE FIRE ALARM SYSTEM AND CONTROL PANEL SHALL BE NOTIFIER SYSTEM. THE FACP SHALL BE PRIMARILY MONITORED BY THE
EXISTING DIGITAL ALARM COMMUNICATION TRANSMITTERS UTILIZING TELEPHONE LINES.
9. ALL WIRING AND CIRCUITS SHALL BE PROVIDED IN ELECTRICAL METALLIC TUBING AND CONDUIT CONCEALED ABOVE THE CEILING
OR BEHIND THE WALLS. MINIMUM TRADE SIZE 3/4 INCHES. NO CIRCUITS SHALL BE SUPPORTED FROM THE SPRINKLER PIPING OR
DUCTWORK. ALL CONDUIT SHALL USE COMPRESSION TYPE CONNECTORS.
10. PROVIDE THE FOLLOWING CIRCUITS:
· INTERCONNECTED RISER LOOP OR NETWORK (CLASS X)
· INITIATING DEVICE CIRCUITS (CLASS B)
· SIGNALING LINE CIRCUIT FOR EACH FLOOR (CLASS B)
· SIGNALING LINE CIRCUIT FOR NETWORK (CLASS B)
· NOTIFICATION APPLIANCES (CLASS B)
11. PROVIDE ADDRESSABLE SIGNALING LINE CIRCUITS (SLC) TO MONITOR FIRE ALARM DEVICES, SPRINKLER SYSTEM WATER FLOW
AND SUPERVISORY DEVICES. PROVIDE NEW ADDRESSABLE SLC TYPE CIRCUITS FOR NOTIFICATION APPLIANCES TO MONITOR AND
CONTROL NOTIFICATION DEVICES. PROVIDE ALL EQUIPMENT, SOFTWARE, ACCESSORIES WHETHER MENTIONED OR NOT,
INCLUDING SMOKE, AND HEAT SENSORS, ADDRESSABLE INTERFACE AND RELAY DEVICES, TERMINAL CABINETS, CONDUIT, WIRE,
POWER SUPPLIES, JUNCTION BOXES, FASTENERS, HANGERS, ETC.
12. PROVIDE REQUIRED REMOTE POWER SUPPLIES FOR NOTIFICATION CIRCUITS. ALL POWER SUPPLIES PANELS SHALL BE PROVIDED
WITH AN ADJACENT SMOKE DETECTOR WITHIN 5 FT FROM THE PANEL.
EACH REMOTE POWER SUPPLY SHALL BE SUPERVISED FOR POWER FAULT, GROUND FAULT, AND CIRCUIT FAULT.
PULL STATIONS ARE TO BE DOUBLE-ACTION, INSTALLED WITH OPERATING LEVER MOUNTED AT 48" AFF AND WITHIN 5' OF THE
EXITS.
FIRE ALARM CONTRACTOR SHALL MAKE ALL ELECTRICAL CONNECTIONS TO THE SYSTEM OR EQUIPMENT SUPERVISED BY THE
EXISTING FIRE ALARM SYSTEM INCLUDING WATERFLOW SWITCHES, TAMPER SWITCHES, EMERGENCY GENERATOR MONITORING,
DUCT SMOKE DETECTORS, ELEVATOR RECALL AND POWER SHUTDOWN.
AUDIBLE (HORNS) AND VISUAL (STROBES) NOTIFICATION DEVICES SHALL BE PROVIDED THROUGHOUT THE BUILDING IN
ACCORDANCE WITH NFPA 72 AND ADA-AG REQUIREMENTS.
ALL STROBES ARE RATED 15CD, UNO. INSTALL ALL NEW WALL MOUNTED STROBES WITH THE ENTIRE DEVICE BETWEEN 80"-96" AFF.
AUDIBLE NOTIFICATION DEVICES (HORNS) SHALL BE PROVIDED THROUGHOUT THE HABITABLE SPACES TO ACHIEVE A MINIMUM OF
15 dBA ABOVE AVERAGE AMBIENT SOUND PRESSURE LEVEL (SPL) AND 5 DBA ABOVE AMBIENT PEAK SPL.
CEILING MOUNTED FIRE ALARM DEVICES SHALL BE INSTALLED CENTER OF TILE IN AREAS WITH 2' X 2' SUSPENDED CEILING TILES.
DEVICES SHALL BE INSTALLED IN QUARTER OR CENTER OF TILE IN AREAS WITH 2' X 4' SUSPENDED CEILING TILES.
PROVIDE FIRE ALARM NOTIFICATION DEVICES WITH CLEAR LENS AND RED BASE MARKED "ALARM".
MATERIALS AND EQUIPMENT SHALL BE NEW.
ELECTRICAL CONTROL PANELS, EQUIPMENT, MATERIALS, AND DEVICES PROVIDED OR INSTALLED AS WORK OF THIS PROJECT
SHALL BEAR UL LABEL, OR IF UL LABEL IS NOT AVAILABLE, THE ITEM SHALL BE TESTED AND LABELED BY A NATIONALLY
RECOGNIZED TESTING AGENCY ACCEPTABLE TO AUTHORITIES HAVING JURISDICTION AND IN ACCORDANCE WITH NEC.
ALL EQUIPMENT SHALL BE INSTALLED PER THE LISTING AND MANUFACTURERS INSTALLATION INSTRUCTIONS.
ALL NECESSARY WALL AND FLOOR PENETRATIONS SHALL BE CORE-DRILLED. ALL PENETRATIONS IN WALLS, CEILING, AND FLOORS
SHALL BE SEALED TO THE FULL THICKNESS OF THE PENETRATION WITH APPROVED FIRE STOPPING MATERIAL OF EQUAL.
STAIRWAYS, SHAFT ENCLOSURES, AND FLOOR SLABS ARE TO BE CONSIDERED 2-HOUR FIRE RESISTIVE RATED CONSTRUCTION.
SEE DETAIL SHEET FA FOR FIRE ALARM OPERATING SEQUENCE.
PROVIDE FULL TESTING PER NFPA 72 AND PROVIDE A RECORD OF COMPLETION FORM AFTER THE SYSTEM IS COMPLETED AND
TESTED, WITHOUT ADDITION TO THE CONTRACT SUM.
SUBMIT SHOP DRAWINGS AND PRODUCT DATA FOR EACH MATERIAL AND ITEM OF EQUIPMENT, INCLUDING RISER DIAGRAM AND
PANEL DRAWINGS.
EXISTING FIRE ALARM SYSTEM WILL BE REPLACED BY ZONES/CIRCUITS TO BE CONNECTED TO THE NEW FIRE ALARM CONTROL
PANEL. OTHER ZONES/CIRCUITS OF THE SYSTEM NOT YET REPLACED MUST REMAIN OPERATIONAL UNTIL THEY HAVE BEEN
REPLACED AND TESTED. PATCH AND PAINT WALLS AS NEEDED TO MATCH SURROUNDING SURFACES. VERIFY COLOR AND FINISH
WITH OWNER.
REUSE EXISTING CONDUIT WHERE FEASIBLE.
LEGENDPULL STATION
DUCT DETECTOR
SMOKE DETECTOR
HEAT DETECTOR
HORN / STROBE
STROBE - WALL MOUNT
ADDRESSABLE INTERFACE
ADDRESSABLE RELAY
FLOW SWITCH
TAMPER SWITCH
REMOTE LED FOR DUCT SMOKE DETECTOR
FLOOR CONTROL ASSEMBLY
FIRE ALARM ANNUNCIATOR
FIRE ALARM CONTROL PANEL
FIRE ALARM TERMINAL CABINET
DIGITAL ALARM COMMUNICATOR TRANSMITTER
BATTERY CABINET
EXISTING DEVICE TO BE DEMOLISHED, UNO
EXISTING DEVICE TO REMAIN - R = EXISTING TO REMAIN
NEW DEVICE
KEYNOTE
ABBREVIATIONSAMP
ABOVE
ARCHITECT/ENGINEER (OF RECORD)
AMERICAN NATIONAL STANDARDS INSTITUTE
AUTOMATIC SPRINKLER
AMERICAN WIRE GAGE
BUILDING
BOTTOM OF BEAM
BOTTOM OF JOIST
CEILING
CANDELA
CLOSET
CONCRETE MASONRY UNIT
COMMUNICATIONS
CONTINUED
CORRIDOR
DRY SPRINKLER
EXISTING DEVICE
EXTENDED COVERAGE SPRINKLER
ELECTRIC
END OF LINE RESISTOR
ELEVATOR TERMINAL CABINET
EXISTING
FIRE ALARM CONTROL PANEL
FIRE DEPARTMENT CONNECTION
GALLONS PER MINUTE
HEATING VENTILATION AND AIR CONDITIONING
INCH
JANITOR'S CLOSET
LAY-IN ACOUSTICAL TILE
LIGHT EMITTING DIODE
MACHINE
MECHANICAL ROOM
MINERAL INSULATED
MASS NOTIFICATION SYSTEM
MANUAL PULL STATION
NOTIFICATION APPLIANCE CIRCUIT
NATIONAL FIRE PROTECTION ASSOCIATION
NUMBER
NUMBERS
NATIONAL PIPE THREAD
NOT TO SCALE
OPENING
OUTSIDE STEM AND YOKE
PHASE
PIPE SHAFT
POUNDS PER SQUARE INCH
QUICK RESPONSE
ROOM
SPRINKLER
STANDARD SPRAY UPRIGHT
STANDPIPE
SQUARE FOOT
SURGE PROTECTION DEVICE
STORAGE
TERMINAL CABINET
TOP OF JOIST
UNLESS NOTED OTHERWISE
VOLTS ALTERNATING CURRENT
WEATHER PROOF
WITH
A
ABV
A/E
ANSI
A/S
AWG
BLDG
BOB
BOJ
C
CD
CLO
CMU
COM
CONT
CORR
DS
E
EC
ELEC
EOLR
ETC
EXIST
FACP
FDC
GPM
HVAC
IN
J.C.
LAT
LED
MACH
MECH
MI
MNS
MPS
NAC
NFPA
NO.
NOS.
NPT
NTS
OPG
OS&Y
P
P.C.
PSI
QR
RM
SPKLR
SSU
STDP
SF
SPD
STO
TC
TOJ
UNO
VAC
WP
W/
FACP
F
AI
S
S
AR
WF
VS
FAA
FATC
FCA
DACT
X
RX
X
#
RL
BATT
EXISTING FIRE ALARM ZONES
FIRST FLOOR SECOND FLOOR
ZONE A ZONE B ZONE C ZONE D
NOTE: EXISTING FIRE ALARM ZONES PER AS-BUILT
DRAWINGS, TO BE FIELD VERIFIED. SHOWN FOR REFERENCE
ONLY.
06/10/2020
DE
FG
CA
B
2 31 8 97654 10 11 12 13 14 15
FFF
F F
F
FATC FACP
AI AI
F
S
F
F
F
F
F
VS
R
WFR
WF R
F
AI
F
RB
AT
T FACP
F
110cd
F
110cd
75cd
15cd
15cd
F
15cd
F F
15cd15cd
15cd
15cd
75cd
15cd
F
15cd
SE
F
WP75cd
15cd
15cd
15cd
S
30cd
F
75cd
110cd
FF
F
75cd
AI
15cd
AI
AI
F
110cd
75cd
F
15cd
30cd
15cd
F
AIAI AI
75cd
SHV4
RTU-4
F
EXPLOSION PROOF
SHV4
EXISTING CONDUIT AT CEILING
EXISTING CONDUIT AT CEILING
16'-9" AFF
RRL
RRL
15cd
AI
30cd
AI
AI
AI
AI
AI
AI
VSR
WP30cd
15cd
S
S
SS
SS
110cd
110cd
15cd
VSR
DACT R
VS
R
AI
VSR
WFR
AI AI
AIAI
3/32"=1'-0"
FIRST FLOOR NEW WORK FIRE ALARM PLAN - PART A1FA2
KEY PLAN
3/32"=1'-0
0 2' 4' 8' 16'
KEY NOTES
1. EXISTING DACT TO REMAIN.
2. PROVIDE NEW FIRE ALARM CONTROL PANEL, TO BE LOCATED ABOVE
EXISTING BATTERY CABINET.
3. LOCATE SMOKE DETECTOR NO MORE THAN 12" FROM CEILING.
4. PROVIDE ADDRESSABLE INTERFACE TO MONITOR MANUAL PULL STATION
INSIDE THE BATTERY ROOM.
5. EXISTING REMOTE LED FOR DUCT SMOKE DETECTOR TO REMAIN.
6. PROVIDE NEW ADDRESSABLE INTERFACES TO CONNECT WATER FLOW AND
TAMPER SWITCHES TO THE NEW FACP AT THE BEGINNING OF THE
RENOVATION, TO BE ACTIVE DURING THE ENTIRE RENOVATION.
7. PROVIDE TEMPORARY HORN/STROBES IN MAIN CORRIDOR TO BE IN
SERVICE DURING ENTIRE FIRE ALARM RENOVATION.
8. PROVIDE ADDRESSABLE INTERFACES TO MONITOR GENERATOR RUN AND
FAULT
1
2
DRAWN:
CHECKED:
NO. DATE
DESIGNED:
SCALE
REVISION
FAIRFAX WATER
PLANNING & ENGINEERING
DIVISION
FAIRFAX WATER
PLANNING & ENGINEERING DIVISION
8560 ARLINGTON BOULEVARD
FAIRFAX, VA 22031
RhinoFire Protection Engineering, PLLC
Newington Maintenance Facility
002
----
----
----
-----------
FAE
PAM
PAM
----
----
----
----FIRST FLOOR NEW WORK PLAN - PART A
NEWINGTON FIRE ALARM SYSTEM REPLACEMENT
5-Jun-20
0650
3
FA5
1
4
5
6
7
7
8
06/10/2020
HJ
KM
L
F
S
S
FA
AR
F
F
F
110cd 110cd
F
75cd
15cd15cd
15cd110cd
F
15cd
15cd
15cd
30cd
15cd
75cd
30cd
15cd
15cd
75cd
15cd
SRTU-3
S
RTU-3
F
30cd
75cd
F
110cd
F F
SR HV3
EXISTING CONDUIT AT CEILINGEXISTING CONDUIT AT CEILING
RRL
75cd
RRL
SR HV3
WP
75cd
2 31 8 97654 10 11 12 13 14 15
3/32"=1'-0"
FIRST FLOOR NEW WORK FIRE ALARM PLAN - PART B1FA3
KEY NOTES
1. EXISTING FAA TO REMAIN. CONNECT TO THE NEW FIRE ALARM CONTROL PANEL RIGHT
BEFORE NEW FIRE ALARM SYSTEM ACCEPTANCE TESTING.
2. EXISTING REMOTE LED FOR DUCT SMOKE DETECTOR TO REMAIN.
3. PROVIDE TEMPORARY HORN/STROBES IN MAIN CORRIDOR TO BE IN SERVICE DURING
ENTIRE FIRE ALARM RENOVATION.
1
KEY PLAN
3/32"=1'-0
0 2' 4' 8' 16'DRAWN:
CHECKED:
NO. DATE
DESIGNED:
SCALE
REVISION
FAIRFAX WATER
PLANNING & ENGINEERING
DIVISION
FAIRFAX WATER
PLANNING & ENGINEERING DIVISION
8560 ARLINGTON BOULEVARD
FAIRFAX, VA 22031
RhinoFire Protection Engineering, PLLC
Newington Maintenance Facility
002
----
----
----
-----------
FAE
PAM
PAM
----
----
----
----FIRST FLOOR NEW WORK PLAN - PART B
NEWINGTON FIRE ALARM SYSTEM REPLACEMENT
5-Jun-20
0650
2
2
3
06/10/2020
2 31 8 97654 10 11 12 13 14
F
S
S
AI
S
S S
F
15cd
F
F
S
S
SS
SHV2
WFR
VSR
FCA
F
15cd
F
15cd
15cd
F
SE
SE
75cd
75cd
F
S
S
HV3
S
AHU-1
AI AI
S
HV3
SHV1
SHV1
6'-0" AFF
AT ROOF LEVEL
SMOKE DETECTORS AT UNITS
HV2
RRL
EE
AI AI AI AI
RTU-2
RRL
RTU-6
RRL
S
RTU-6
AI
VSR
S
RTU-6
SS
S
RTU-2
S
RTU-2
RRL
75cd75cd
VSR
RRL
DE
FG
HJ
CA
B
3/32"=1'-0"
SECOND FLOOR NEW WORK FIRE ALARM PLAN - PARTIAL1FA4
KEY PLAN
3/32"=1'-0
0 2' 4' 8' 16'DRAWN:
CHECKED:
NO. DATE
DESIGNED:
SCALE
REVISION
FAIRFAX WATER
PLANNING & ENGINEERING
DIVISION
FAIRFAX WATER
PLANNING & ENGINEERING DIVISION
8560 ARLINGTON BOULEVARD
FAIRFAX, VA 22031
RhinoFire Protection Engineering, PLLC
Newington Maintenance Facility
002
----
----
----
-----------
FAE
PAM
PAM
----
----
----
----SECOND FLOOR NEW WORK PLAN
NEWINGTON FIRE ALARM SYSTEM REPLACEMENT
5-Jun-20
0650
KEY NOTES
1. REPLACE EXISTING HEAT DETECTOR NEAR SPRINKLER FOR ELEVATOR
SHUNT TRIP ACTIVATION.
2. EXISTING REMOTE LED FOR DUCT SMOKE DETECTOR TO REMAIN.
1
2 2 2
06/10/2020
FATC
DEMOLISH
FACP
DEMOLISH
FACP
NEW
BATTERY
ENCLOSURE
EXISTING TO
REMAIN
2'-1034"
1' 1'-5"
2'-6"
FIRST FLOOR
ELECTRIC / TELECOMM ROOM
DACT
EXISTING
TO
REMAIN
ELECTRIC / TELECOMM ROOM1FA5
DRAWN:
CHECKED:
NO. DATE
DESIGNED:
SCALE
REVISION
FAIRFAX WATER
PLANNING & ENGINEERING
DIVISION
FAIRFAX WATER
PLANNING & ENGINEERING DIVISION
8560 ARLINGTON BOULEVARD
FAIRFAX, VA 22031
RhinoFire Protection Engineering, PLLC
Newington Maintenance Facility
002
----
----
----
-----------
FAE
PAM
PAM
----
----
----
----DETAILS
NEWINGTON FIRE ALARM SYSTEM REPLACEMENT
5-Jun-20
0650
SMOKE DETECTOR2FA5
PULL STATION & HORN / STROBE MOUNTING DETAIL3FA5
HORN/STROBE, MALL-MOUNTED4FA5
06/10/2020
FIRE ALARM OPERATING MATRIX1FA6
FIRE ALARM RISER DIAGRAM2FA6
MANUAL PULL STATION
AREA SMOKE DETECTOR
WIRING FAULT, SYSTEM TROUBLE,COMMUNICATION FAULT
DEVICE IND
ICA
TE
ST
AT
US
ON
FA
CP
& R
EM
OT
E A
NN
UN
CIA
TO
R(N
OT
E 1
)
INT
IMA
TE
ALA
RM
ST
AT
US
INT
IMA
TE
TR
OU
BL
E S
TA
TU
S
INT
IMA
TE
SU
PE
RV
ISO
RY
ST
AT
US
TR
AN
SM
IT S
YS
TE
M S
TA
TU
S S
IGN
AL
TO
CE
NT
RA
L S
TA
TIO
N(N
OT
E 2
)
AC
TIV
AT
E F
IRE
ALA
RM
NO
TIF
ICA
TIO
N D
EV
ICE
S(N
OT
E 3
)
X
ACTION
ELEVATOR LOBBY SMOKE DETECTOR(PRIMARY RECALL FLOOR)
ELEVATOR LOBBY SMOKE DETECTOR(OTHER THAN PRIMARY RECALL FLOOR)
ELEVATOR SHAFT FLOW SWITCH
NOTES:1. REFER TO PROJECT SPECIFICATIONS FOR FACP AND REMOTE ANNUNCIATOR DISPLAY REQUIREMENTS.
2. FIRE ALARM STATUS WILL BE TRANSMITTED VIA EXISTING 2 PAIRS OF TELEPHONE LINES IN DACT TO CENTRALMONITORING STATION SYSTEM.
3. INCLUDING HORNS, HORN/STROBES, AND STROBES. INCLUDES EXTERIOR HORN/STROBE; EXTERIOR SPEAKER/STROBESHALL BE PROGRAMMED AS NON-SILENCEABLE.
4. ELEVATOR LOBBY SMOKE DETECTOR SHALL DISPLAY AS "SMOKE DETECTOR" ON ALARM STATUS REPORT (ON FACPDISPLAY, REMOTE ANNUNCIATOR PANEL DISPLAY, AND IN SYSTEM MEMORY).
ELEVATOR SHAFT HEAT DETECTOR
DUCT SMOKE DETECTOR
RE
CA
LL
EL
EV
AT
OR
TO
PR
IMA
RY
RE
CA
LL
FL
OO
R (
FIR
ST
FL
OO
R)
RE
CA
LL
EL
EV
AT
OR
TO
SE
CO
ND
AR
Y F
LO
OR
(S
EC
ON
D F
LO
OR
)
AC
TIV
AT
E "
FIR
EM
AN
'S H
AT
" (S
TE
AD
Y)
AC
TIV
AT
E "
FIR
EM
AN
'S H
AT
" (F
LA
SH
ING
)
SH
UT
DO
WN
AIR
-HA
ND
LIN
G U
NIT
SH
UN
T T
RIP
EL
EV
AT
OR
(N
O T
IME
DE
LA
Y)
NOTES
NOTE 4
NOTE 4
X X X
X X X X
X X X X X X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X X X
X X X
X X
X
GENERATOR RUN
GENERATOR TROUBLE
X
X
X X
X X
FACP SS
FIRST FLOOR
SECOND FLOOR
DRAWN:
CHECKED:
NO. DATE
DESIGNED:
SCALE
REVISION
FAIRFAX WATER
PLANNING & ENGINEERING
DIVISION
FAIRFAX WATER
PLANNING & ENGINEERING DIVISION
8560 ARLINGTON BOULEVARD
FAIRFAX, VA 22031
RhinoFire Protection Engineering, PLLC
Newington Maintenance Facility
002
----
----
----
-----------
FAE
PAM
PAM
----
----
----
----MATRIX AND RISER DIAGRAM
NEWINGTON FIRE ALARM SYSTEM REPLACEMENT
5-Jun-20
0650
ROOF
RDACT
FAA
SE
S
AIAI
WFVS
F
SE
SAIAI
WFVS
F
S
RL
FACP
NEW CONTROL PANEL TO BE CONNECTED TO THE EXISTINGCONTROL PANEL DURING THE RENOVATION. THE CONTROLPANEL WILL BE DISCONNECTED AFTER COMPLETION OFRENOVATION AND TESTING OF THE NEW FIRE ALARMCONTROL PANEL.
SS
KEY NOTES
1. SLC LOOPS SHALL BE CLASS B. SLC CIRCUITS FOR ACTIVATION OF REMOTE FIRE ALARM POWER SUPPLIES SHALL BE CLASS B.
2. NAC CIRCUITS SHALL BE CLASS B FOR EACH FLOOR; PROVIDE EXTERIOR, WEATHERPROOF DEVICES FOR ROOFTOP.
3. CIRCUIT WIRING SHALL BE AS FOLLOWS:
· ADDRESSABLE SIGNALING LINE CIRCUITS (SLC):
#18 AWG, STRANDED COPPER CONDUCTORS, TWISTED/SHIELDED PAIR, TYPE FPL, MARKED "POWER LIMITED FIRE PROTECTIVE
SIGNALING CIRCUIT CABLE" AND UL-LISTED FOR THIS INTENDED PURPOSE.
· NOTIFICATION APPLIANCE CIRCUITS (NAC):
#14 AWG, THHN-THWN INSULATED, 600 VAC SOLID COPPER CONDUCTORS.
· 24 VDC POWER CIRCUITS:
#14 AWG, THHN-THWN INSULATED, 600 VAC SOLID COPPER CONDUCTORS.
· 120 VAC POWER CIRCUITS:
#12 AWG, THHN-THWN INSULATED, 600 VAC SOLID COPPER CONDUCTORS.
· ISOLATE SLC'S FROM NAC'S AND 24 VDC POWER PER MANUFACTURER'S RECOMMENDATIONS (I.E. MAY REQUIRE SEPARATE
CONDUIT FOR LOADS GREATER THAN 2 AMPS).
4. ACTIVATION OF ELEVATOR MACHINE ROOM OR ELEVATOR SHAFT FLOW SWITCH NEAR SPRINKLER HEADS IN THESE AREAS SHALL
INITIATE ELEVATOR SHUNT TRIP WITH NO TIME DELAY.
5. PROVIDE ADDRESSABLE INTERFACE FOR SUPERVISION OF EMERGENCY GENERATOR.
6. PROVIDE DUCT DETECTORS. FIELD VERIFY FOR EXACT QUANTITIES AND LOCATIONS.
7. PROVIDE NEW ADDRESSABLE INTERFACES TO CONNECT WATER FLOW AND TAMPER SWITCHES TO THE NEW FACP AT THE
BEGINNING OF THE RENOVATION, TO BE ACTIVE DURING THE ENTIRE RENOVATION.
8. PROVIDE TEMPORARY HORN/STROBES IN MAIN CORRIDOR TO BE IN SERVICE DURING THE ENTIRE RENOVATION.
1 2 3 4 5 6
7
8
WATER FLOW SWITCH X X X X
WP
06/10/2020