1
Power Factor Correction Capacitors
Selection & Applications Of Power Factor Correction Capacitor For Industrial and Large Commercial Users Ben Banerjee
Power Quality Solution Group
![Page 2: 1 Power Factor Correction Capacitors Selection & Applications Of Power Factor Correction Capacitor For Industrial and Large Commercial Users Ben Banerjee](https://reader035.vdocuments.us/reader035/viewer/2022062404/5514aa9b550346ea6e8b5e35/html5/thumbnails/2.jpg)
2
Agenda
• Power Factor Fundamental
• The Need for Power Factor Correction
• Effects of Harmonics: TPF & DPF
• Correction Alternatives & Capacitor Locations
• PF Rate, Capacitor Sizing, & ROI
• Capacitor Applications To Motors
• Capacitor Switching Equipment
• Other Application Issues
* Steady State VAR Correction
* Dynamic VAR Correction
• Standards & Codes
![Page 3: 1 Power Factor Correction Capacitors Selection & Applications Of Power Factor Correction Capacitor For Industrial and Large Commercial Users Ben Banerjee](https://reader035.vdocuments.us/reader035/viewer/2022062404/5514aa9b550346ea6e8b5e35/html5/thumbnails/3.jpg)
3
04/10/23
Power Quality Correction
Power Factor Power Factor FundamentalsFundamentals
![Page 4: 1 Power Factor Correction Capacitors Selection & Applications Of Power Factor Correction Capacitor For Industrial and Large Commercial Users Ben Banerjee](https://reader035.vdocuments.us/reader035/viewer/2022062404/5514aa9b550346ea6e8b5e35/html5/thumbnails/4.jpg)
4
04/10/23
Power Quality Correction
Most plant loads are Most plant loads are InductiveInductive and require a and require a magnetic fieldmagnetic field to to operate:operate:
MotorsMotors TransformersTransformers Florescent lightingFlorescent lighting
The magnetic field is necessary, but produces The magnetic field is necessary, but produces no useful workno useful work The utility must supply the power to produce the magnetic The utility must supply the power to produce the magnetic
field field andand the power to produce the useful work: You pay for all the power to produce the useful work: You pay for all of it!of it!
These two types of current are the These two types of current are the ACTIVEACTIVE and and REACTIVEREACTIVE componentscomponents
ACTIVE & REACTIVE POWERSACTIVE & REACTIVE POWERS
![Page 5: 1 Power Factor Correction Capacitors Selection & Applications Of Power Factor Correction Capacitor For Industrial and Large Commercial Users Ben Banerjee](https://reader035.vdocuments.us/reader035/viewer/2022062404/5514aa9b550346ea6e8b5e35/html5/thumbnails/5.jpg)
5
Power Factor Fundamental
• Definitions:
– Working /Active Power: Normally measured in kilowatts (kW). It does the "work" for the system--providing the motion, torque, heat, or whatever else is required.
– Reactive Power: Normally measured in kilovolt-amperes-reactive (kVAR), doesn't do useful "work." It simply sustains the electromagnetic field.
– Apparent Power: Normally measured in kilovolt-amperes (kVA). Working Power and Reactive Power together make up apparent power.
![Page 6: 1 Power Factor Correction Capacitors Selection & Applications Of Power Factor Correction Capacitor For Industrial and Large Commercial Users Ben Banerjee](https://reader035.vdocuments.us/reader035/viewer/2022062404/5514aa9b550346ea6e8b5e35/html5/thumbnails/6.jpg)
6
Power Factor:The Beer Analogy
Mug Capacity = Apparent Power (KVA)
Foam = Reactive Power (KVAR)
Beer = Real Power (kW)
Power Factor = Beer (kW)
Mug Capacity (KVA)
Capacitors provide the Foam (KVAR), freeing up Mug Capacity so you don’t have to buy a bigger mug and/or so you can pay less for your beer !
kVARReactivePower
kWActivePower
kVAApparentPower
![Page 7: 1 Power Factor Correction Capacitors Selection & Applications Of Power Factor Correction Capacitor For Industrial and Large Commercial Users Ben Banerjee](https://reader035.vdocuments.us/reader035/viewer/2022062404/5514aa9b550346ea6e8b5e35/html5/thumbnails/7.jpg)
7
Power Factor : A measure of efficiency. The ratio of Active Power (output) to Total Power (input)
A power factor reading close to 1.0 means that electrical power is being utilized effectively, while a low power factor indicates poor utilization of electrical power.
Total Power (kVA)
Active Power (kW) Power Factor = Active (Real) Power Total Power
= kW kVA
= Cosine (θ) = DISPLACEMENT POWER FACTOR
ReactivePower(KVAR)
Power Factor Fundamental
![Page 8: 1 Power Factor Correction Capacitors Selection & Applications Of Power Factor Correction Capacitor For Industrial and Large Commercial Users Ben Banerjee](https://reader035.vdocuments.us/reader035/viewer/2022062404/5514aa9b550346ea6e8b5e35/html5/thumbnails/8.jpg)
Division - Name - Date - Language 8
LEADING AND LAGGING
G LIC
IL
ILOAD
IR
IR V
IC
KW
KVARL
KVARC
![Page 9: 1 Power Factor Correction Capacitors Selection & Applications Of Power Factor Correction Capacitor For Industrial and Large Commercial Users Ben Banerjee](https://reader035.vdocuments.us/reader035/viewer/2022062404/5514aa9b550346ea6e8b5e35/html5/thumbnails/9.jpg)
9
LEADING AND LAGGING
KVAR (LAG)
KVAR (LAG)
KW
KW
INDUCTION MOTOR
G
L
OVER-EXCITED
SYN. MOTOR
G
L
KVAR (LEAD)KW
KVAR (LEAD)KW
![Page 10: 1 Power Factor Correction Capacitors Selection & Applications Of Power Factor Correction Capacitor For Industrial and Large Commercial Users Ben Banerjee](https://reader035.vdocuments.us/reader035/viewer/2022062404/5514aa9b550346ea6e8b5e35/html5/thumbnails/10.jpg)
10
Typical Uncorrected Power Factor
By Industry PowerFactor
By Operation PowerFactor
Auto parts 75-80 Air compressor:Brewery 76-80 External motors 75-80Cement 80-85 Hermetic motors 50-80Chemical 65-75 Metal working:Coal mine 65-80 Arc welding 35-60Clothing 35-60 Arc welding with
standard capacitors40-60
Electroplating 65-70 Resistance welding 40-60Foundry 75-80 Machining 40-65Forge 70-80 Melting:Hospital 75-80 Arc furnace 75-90Machinemanufacturing
60-65 Inductance furnace60Hz
100
Metalworking 65-70 Stamping:Office building 80-90 Standard speed 60-70Oil-field pumping 40-60 High speed 45-60Paintmanufacturing
55-65 Spraying 60-65
Plastic 75-80 Weaving:Stamping 60-70 Individual drive 60Steelworks 65-80 Multiple drive 70Textile 65-75 Brind 70-75Tool, die, jig 60-65
From IEEE Std 141-1993
(Use only as a Guide)
![Page 11: 1 Power Factor Correction Capacitors Selection & Applications Of Power Factor Correction Capacitor For Industrial and Large Commercial Users Ben Banerjee](https://reader035.vdocuments.us/reader035/viewer/2022062404/5514aa9b550346ea6e8b5e35/html5/thumbnails/11.jpg)
11
WHY DO WE CARE ABOUT POWER FACTOR
![Page 12: 1 Power Factor Correction Capacitors Selection & Applications Of Power Factor Correction Capacitor For Industrial and Large Commercial Users Ben Banerjee](https://reader035.vdocuments.us/reader035/viewer/2022062404/5514aa9b550346ea6e8b5e35/html5/thumbnails/12.jpg)
NAOD – PQCG US – May 16, 2007 - English 12
MOTOR LOAD CHARACTERISTICS
![Page 13: 1 Power Factor Correction Capacitors Selection & Applications Of Power Factor Correction Capacitor For Industrial and Large Commercial Users Ben Banerjee](https://reader035.vdocuments.us/reader035/viewer/2022062404/5514aa9b550346ea6e8b5e35/html5/thumbnails/13.jpg)
13
Why do we care about Power Factor?
• In Industrial Facilities, Mostly Induction Motor loads
• Energy Efficient Motors not optimized for PF • Low power factor is caused by oversized or
lightly loaded induction motors • Low power factor results in:
– Poor electrical efficiency!– Higher utility bills **– Lower system capacity– On the Supply Side, Generation Capacity & Line
Losses
• Power Factor Correction Capacitors (PFCC) provide an economical means for improving Energy utilization
![Page 14: 1 Power Factor Correction Capacitors Selection & Applications Of Power Factor Correction Capacitor For Industrial and Large Commercial Users Ben Banerjee](https://reader035.vdocuments.us/reader035/viewer/2022062404/5514aa9b550346ea6e8b5e35/html5/thumbnails/14.jpg)
14
04/10/23
Power Quality Correction
In this example, demand In this example, demand was reduced to 8250 kVA was reduced to 8250 kVA from 10000 kVA.from 10000 kVA.
1750KVA Transformer 1750KVA Transformer Capacity Release.Capacity Release.
The power factor was The power factor was improved from 80% to improved from 80% to 97%97%
Before AfterWhy do we install Capacitors?Why do we install Capacitors?
![Page 15: 1 Power Factor Correction Capacitors Selection & Applications Of Power Factor Correction Capacitor For Industrial and Large Commercial Users Ben Banerjee](https://reader035.vdocuments.us/reader035/viewer/2022062404/5514aa9b550346ea6e8b5e35/html5/thumbnails/15.jpg)
15
Harmonics
• Displacement Power Factor
• Total Power Factor
• Effects of Harmonics on Capacitors
![Page 16: 1 Power Factor Correction Capacitors Selection & Applications Of Power Factor Correction Capacitor For Industrial and Large Commercial Users Ben Banerjee](https://reader035.vdocuments.us/reader035/viewer/2022062404/5514aa9b550346ea6e8b5e35/html5/thumbnails/16.jpg)
16
04/10/23
Power Quality Correction
v i
Until recently, most electrical equipment Until recently, most electrical equipment drew current in a “drew current in a “linearlinear” fashion:” fashion:
Today, many electrical loads draw Today, many electrical loads draw current in acurrent in a “ “non-linearnon-linear” fashion:” fashion:
• Current (i) is periodic, but not “sinusoidal”vi
• Current (i) & Voltage (v) are both “Sinusoidal”
Linear vs Non-LinearLinear vs Non-Linear
![Page 17: 1 Power Factor Correction Capacitors Selection & Applications Of Power Factor Correction Capacitor For Industrial and Large Commercial Users Ben Banerjee](https://reader035.vdocuments.us/reader035/viewer/2022062404/5514aa9b550346ea6e8b5e35/html5/thumbnails/17.jpg)
17
• Computers
• Fax Machines
• Copiers
M • Variable Frequency Drives
• Electronic Ballasts
• Almost anything electronic
What produces “Non-linear” Current?
![Page 18: 1 Power Factor Correction Capacitors Selection & Applications Of Power Factor Correction Capacitor For Industrial and Large Commercial Users Ben Banerjee](https://reader035.vdocuments.us/reader035/viewer/2022062404/5514aa9b550346ea6e8b5e35/html5/thumbnails/18.jpg)
18
04/10/23
Power Quality Correction
Distorted Wave =f1 + f3 + f5 + f7
0
0.5
1
1 3 5 7 9 1 1
0
0.5
1
1 3 5 7 9 1 1
0
0.5
1
1 3 5 7 9 1 1
0
0.5
1
1 3 5 7 9 1 1
0
0.5
1
1 3 5 7 9 1 1
f1 = 60 Hz
f3 = 3 x 60hz =180 hz
f5 = 5 x 60 hz =300 hz
f7 = 7 x 60 hz =420 hz
f1
f3
+
f5
+
f7
+
=
60 Hz
180 Hz
300 Hz
420 Hz
Time Domain Frequency Domain
Time vs FrequencyTime vs Frequency
![Page 19: 1 Power Factor Correction Capacitors Selection & Applications Of Power Factor Correction Capacitor For Industrial and Large Commercial Users Ben Banerjee](https://reader035.vdocuments.us/reader035/viewer/2022062404/5514aa9b550346ea6e8b5e35/html5/thumbnails/19.jpg)
19
04/10/23
Power Quality Correction
TTotal otal HHarmonic armonic CCurrent urrent DDistortionistortion
Is Same AsIs Same As
TTotal otal DDemand emand DDistortionistortion (TDD) (TDD)
I I I
I
I
ITDD
h2
2
4
1 1
100 100
%
h2
2 I
32
%
2
![Page 20: 1 Power Factor Correction Capacitors Selection & Applications Of Power Factor Correction Capacitor For Industrial and Large Commercial Users Ben Banerjee](https://reader035.vdocuments.us/reader035/viewer/2022062404/5514aa9b550346ea6e8b5e35/html5/thumbnails/20.jpg)
20
04/10/23
Power Quality Correction
Total or True Power Factor (TPF)Total or True Power Factor (TPF)
TPF = (DPF) x (Harm Coefficient)
DPF =KW
KVA= Cos
Harm Coefficient = 1
1 + TDD2
TPF = Total or true power factor
DPF = Displacement power factor
Harm coefficient = Harmonic power factor = Cos
![Page 21: 1 Power Factor Correction Capacitors Selection & Applications Of Power Factor Correction Capacitor For Industrial and Large Commercial Users Ben Banerjee](https://reader035.vdocuments.us/reader035/viewer/2022062404/5514aa9b550346ea6e8b5e35/html5/thumbnails/21.jpg)
Total Power Factor Example
• VFD ( Six Pulse )• DPF = .95• TDD = 90% ( No Line Reactor)
Harm coefficient =
• TPF = .95 x .7433 = .7061
1
1 + .92= .7433
![Page 22: 1 Power Factor Correction Capacitors Selection & Applications Of Power Factor Correction Capacitor For Industrial and Large Commercial Users Ben Banerjee](https://reader035.vdocuments.us/reader035/viewer/2022062404/5514aa9b550346ea6e8b5e35/html5/thumbnails/22.jpg)
22
04/10/23
Power Quality Correction
VFD
Caps at Motors or at SWBD / MCC:Caps at Motors or at SWBD / MCC:Disadvantage:Disadvantage: If Drives are present If Drives are present anywhereanywhere, the harmonic currents , the harmonic currents
they produce can flow back to the point of they produce can flow back to the point of lowest lowest impedanceimpedance: : the capacitorthe capacitor!!
This will cause premature failure of the capacitor.This will cause premature failure of the capacitor.
MM M M M
Applying Capacitors:Applying Capacitors:
![Page 23: 1 Power Factor Correction Capacitors Selection & Applications Of Power Factor Correction Capacitor For Industrial and Large Commercial Users Ben Banerjee](https://reader035.vdocuments.us/reader035/viewer/2022062404/5514aa9b550346ea6e8b5e35/html5/thumbnails/23.jpg)
23
How Harmonics Affect Capacitors
• Capacitors are naturally a low impedance to high frequencies:– Caps absorb harmonics
– Caps do not generate harmonics
• As capacitor absorbs harmonics, the capacitor heats up– Reduced life expectancy
• Voltage harmonics stress the capacitor dielectric– Reduced life expectancy
• Parallel combination of capacitors with motor or transformer can cause resonance condition
![Page 24: 1 Power Factor Correction Capacitors Selection & Applications Of Power Factor Correction Capacitor For Industrial and Large Commercial Users Ben Banerjee](https://reader035.vdocuments.us/reader035/viewer/2022062404/5514aa9b550346ea6e8b5e35/html5/thumbnails/24.jpg)
24
The installation of standard capacitors can magnify harmonic currents on the network
Resonance
![Page 25: 1 Power Factor Correction Capacitors Selection & Applications Of Power Factor Correction Capacitor For Industrial and Large Commercial Users Ben Banerjee](https://reader035.vdocuments.us/reader035/viewer/2022062404/5514aa9b550346ea6e8b5e35/html5/thumbnails/25.jpg)
25
• Resonance:
X flL 2
Xfc
C 1
2
XL
XC
Z
Resonancefr fX
X
L
C 1
fr
( XL-Xc )
How Harmonics Affect Capacitors:
![Page 26: 1 Power Factor Correction Capacitors Selection & Applications Of Power Factor Correction Capacitor For Industrial and Large Commercial Users Ben Banerjee](https://reader035.vdocuments.us/reader035/viewer/2022062404/5514aa9b550346ea6e8b5e35/html5/thumbnails/26.jpg)
26
Magnification of Harmonic Current when Standard Capacitor are Added to the Network
Resonant Point likely to amplify dominant harmonic (typically 5th)
Capacitor Resonance
![Page 27: 1 Power Factor Correction Capacitors Selection & Applications Of Power Factor Correction Capacitor For Industrial and Large Commercial Users Ben Banerjee](https://reader035.vdocuments.us/reader035/viewer/2022062404/5514aa9b550346ea6e8b5e35/html5/thumbnails/27.jpg)
27
• De-tuning a network:– “Force” the resonant point away from naturally occurring
harmonics
Ih5
I<h5>
Z
f
A
f5f3 f7 f9f1
4.2 Harmonic (252 Hz)
We control the impedance of these two elements
Power Factor Correction With Harmonics:
![Page 28: 1 Power Factor Correction Capacitors Selection & Applications Of Power Factor Correction Capacitor For Industrial and Large Commercial Users Ben Banerjee](https://reader035.vdocuments.us/reader035/viewer/2022062404/5514aa9b550346ea6e8b5e35/html5/thumbnails/28.jpg)
28
UTILITY RATE & PFCC
![Page 29: 1 Power Factor Correction Capacitors Selection & Applications Of Power Factor Correction Capacitor For Industrial and Large Commercial Users Ben Banerjee](https://reader035.vdocuments.us/reader035/viewer/2022062404/5514aa9b550346ea6e8b5e35/html5/thumbnails/29.jpg)
29
If the consumer does not correct the power factor, the utility may have to Build more power plants Install New/ Large transformers Use larger utility cables/ Wires, Switchgear,etc.
Many different rate structures across the country. Typically, penalties are imposed for PF < 95%. Thousands of Customers across the country are currently unaware that they are being penalized for low power factor!!!
Most utilities penalize for bad Power Factor...
![Page 30: 1 Power Factor Correction Capacitors Selection & Applications Of Power Factor Correction Capacitor For Industrial and Large Commercial Users Ben Banerjee](https://reader035.vdocuments.us/reader035/viewer/2022062404/5514aa9b550346ea6e8b5e35/html5/thumbnails/30.jpg)
30
How do utilities charge for Power Factor?
• Utilities recoup the cost of providing reactive power in different ways….. – kVA billing: utility measures and bills every ampere of
current including reactive current.
– kW demand billing with Power factor adjustment: utility charges according to kW demand and adds a surcharge for power factor, typically in the form of a multiplier applied to kW demand.
– kVAR Reactive Demand charge: A direct charge for use of magnetizing power. (example:$ 4.50/kVAR)
Two utilities recently introduced substantial Power Factor Penalties TXU (Texas) $3.50 - $5.50 per kW Demand to 95% pf TVA (Tennessee) $1.46 per kVAR lagging, $1.14 per
kVAR leading (April 1, 2004)
![Page 31: 1 Power Factor Correction Capacitors Selection & Applications Of Power Factor Correction Capacitor For Industrial and Large Commercial Users Ben Banerjee](https://reader035.vdocuments.us/reader035/viewer/2022062404/5514aa9b550346ea6e8b5e35/html5/thumbnails/31.jpg)
MOST COMMON POWER FACTOR RATE CLAUSE
BILLING KW DEMAND =
ACTUAL KW DEMAND X BASE PF/ ACTUAL PF
![Page 32: 1 Power Factor Correction Capacitors Selection & Applications Of Power Factor Correction Capacitor For Industrial and Large Commercial Users Ben Banerjee](https://reader035.vdocuments.us/reader035/viewer/2022062404/5514aa9b550346ea6e8b5e35/html5/thumbnails/32.jpg)
Penalty Calculation From Utility Bills In TX
BILLING DEMAND (apfa) = KW2 & ACTUAL DEMAND = KW1
Due to PF Adjustment, KW2 > KW1
*Distribution System Charge = (KW2-KW1) x $3.55 / apfa = M1
*Nuclear Decommission Charge = ( KW2-KW1) x $0.044/apfa = M2
*Transition Charge-1 = (KW2-KW1) x $0.177/ apfa = M3
*Transition Charge-2 = (KW2-KW1) x $0.272 / apfa = M4
*Transmission Service Charge = (KW2-KW1) x $1.19 / apfa = M5
*Transmission Cost Recov Factor = (KW2-KW1) x $0.27103 /apfa =M6
Total / Month = M1+M2+M3+M4+M5+M6 = $ / Month
![Page 33: 1 Power Factor Correction Capacitors Selection & Applications Of Power Factor Correction Capacitor For Industrial and Large Commercial Users Ben Banerjee](https://reader035.vdocuments.us/reader035/viewer/2022062404/5514aa9b550346ea6e8b5e35/html5/thumbnails/33.jpg)
33
CAPACITOR LOCATION & TYPE
![Page 34: 1 Power Factor Correction Capacitors Selection & Applications Of Power Factor Correction Capacitor For Industrial and Large Commercial Users Ben Banerjee](https://reader035.vdocuments.us/reader035/viewer/2022062404/5514aa9b550346ea6e8b5e35/html5/thumbnails/34.jpg)
34
04/10/23
Power Quality Correction
Three Options for Applying Power Factor Three Options for Applying Power Factor Capacitors:Capacitors:A) Fixed capacitors @ individual motors or @ MCCA) Fixed capacitors @ individual motors or @ MCC
B) Automatic Banks at Main Switch BoardB) Automatic Banks at Main Switch Board
C) De-tuned Automatic Capacitor Bank at Main Switch BoardC) De-tuned Automatic Capacitor Bank at Main Switch Board
M M M M M
A B C A
Harmonic Source e.g. Variable Speed Drive
Capacitor LocationsCapacitor Locations
![Page 35: 1 Power Factor Correction Capacitors Selection & Applications Of Power Factor Correction Capacitor For Industrial and Large Commercial Users Ben Banerjee](https://reader035.vdocuments.us/reader035/viewer/2022062404/5514aa9b550346ea6e8b5e35/html5/thumbnails/35.jpg)
35
Fixed Capacitors - Low Voltage
• Main Benefit– pf correction
• Side Benefit– voltage support
– Small I2R reduction
• Usage– Correcting pf on individual loads such as motors
• Disadvantages– Overcompensation (correct past unity)
– Not to be used on non-linear loads
– Unable to track minute by minute load changes occurring on non-compensated feeders
![Page 36: 1 Power Factor Correction Capacitors Selection & Applications Of Power Factor Correction Capacitor For Industrial and Large Commercial Users Ben Banerjee](https://reader035.vdocuments.us/reader035/viewer/2022062404/5514aa9b550346ea6e8b5e35/html5/thumbnails/36.jpg)
36
Standard Automatic Capacitor Systems
• Main Benefit– pf correction
• Side Benefit– voltage support
– Small I2R reduction
• Usage– Correcting pf on entire
MCC’s or substations
• Application alert– Not to be used on non-
linear loads
![Page 37: 1 Power Factor Correction Capacitors Selection & Applications Of Power Factor Correction Capacitor For Industrial and Large Commercial Users Ben Banerjee](https://reader035.vdocuments.us/reader035/viewer/2022062404/5514aa9b550346ea6e8b5e35/html5/thumbnails/37.jpg)
37
Automatic Cap. Bank with a reactors in series
Reactors tuned to 4.2 or 4.4
Use where Non-Linear Loads less than 50% of total loads.
Anti-Resonant Automatic Cap. Bank
![Page 38: 1 Power Factor Correction Capacitors Selection & Applications Of Power Factor Correction Capacitor For Industrial and Large Commercial Users Ben Banerjee](https://reader035.vdocuments.us/reader035/viewer/2022062404/5514aa9b550346ea6e8b5e35/html5/thumbnails/38.jpg)
38
For sensitive networks
Similar to Anti-resonant Automatic Capacitor System except solid state switching
Reactor tuned to 4.2 or 4.4 Response time < 5
sec Use where Non-
Linear Loads < 50% of Total Loads.
Transient Free De-Tuned Automatic Cap. Banks
![Page 39: 1 Power Factor Correction Capacitors Selection & Applications Of Power Factor Correction Capacitor For Industrial and Large Commercial Users Ben Banerjee](https://reader035.vdocuments.us/reader035/viewer/2022062404/5514aa9b550346ea6e8b5e35/html5/thumbnails/39.jpg)
39
Fuses
SCR-Diode
De-tunedInductor
L1 L2 L3
Electronic Switch –Transient Free
![Page 40: 1 Power Factor Correction Capacitors Selection & Applications Of Power Factor Correction Capacitor For Industrial and Large Commercial Users Ben Banerjee](https://reader035.vdocuments.us/reader035/viewer/2022062404/5514aa9b550346ea6e8b5e35/html5/thumbnails/40.jpg)
40
04/10/23
Power Quality Correction
Rule Of Thumb For PFCC ApplicationsRule Of Thumb For PFCC Applications
* When Non-Linear Loads < 15% Of Total Loads * When Non-Linear Loads < 15% Of Total Loads Select Standard Automatic Cap. BankSelect Standard Automatic Cap. Bank
* When Non-linear Loads >15% But < 50% Of Total Loads* When Non-linear Loads >15% But < 50% Of Total Loads Select Anti-Resonant (Detuned) Auto. Cap. BankSelect Anti-Resonant (Detuned) Auto. Cap. Bank
* When Non-Linear Loads > 50% Of Total Loads* When Non-Linear Loads > 50% Of Total Loads Select Active Harmonics Filter For VAR CorrectionSelect Active Harmonics Filter For VAR Correction
* When Transformer KVA To Cap. KVAR Ratio < 3 * When Transformer KVA To Cap. KVAR Ratio < 3 Select Anti-Resonant ( Detuned) Auto. Cap. BankSelect Anti-Resonant ( Detuned) Auto. Cap. Bank
* When Soft-Starters are present, select Detuned Auto. Cap. Bank* When Soft-Starters are present, select Detuned Auto. Cap. Bank
![Page 41: 1 Power Factor Correction Capacitors Selection & Applications Of Power Factor Correction Capacitor For Industrial and Large Commercial Users Ben Banerjee](https://reader035.vdocuments.us/reader035/viewer/2022062404/5514aa9b550346ea6e8b5e35/html5/thumbnails/41.jpg)
41
ACTIVE FILTER in VAR Correction Mode
![Page 42: 1 Power Factor Correction Capacitors Selection & Applications Of Power Factor Correction Capacitor For Industrial and Large Commercial Users Ben Banerjee](https://reader035.vdocuments.us/reader035/viewer/2022062404/5514aa9b550346ea6e8b5e35/html5/thumbnails/42.jpg)
Division - Name - Date - Language 42
WELDING OPERATIONS LARGE HP MOTOR STARTING PROCESS LOADS (i.e. MIXERS,
CRUSHERS, CHIPPERS, SHREDDERS)
ARC FURNACES
CAUSESCAUSES
Cyclical Loads & Loads With Dynamic VAR Movements
RESULTING INRESULTING IN
VOLTAGE FLICKER VOLTAGE SAGS POOR POWER FACTOR INABILITY TO START MOTORS
![Page 43: 1 Power Factor Correction Capacitors Selection & Applications Of Power Factor Correction Capacitor For Industrial and Large Commercial Users Ben Banerjee](https://reader035.vdocuments.us/reader035/viewer/2022062404/5514aa9b550346ea6e8b5e35/html5/thumbnails/43.jpg)
43
Active Filter (AHF)
• For Power Factor Correction For System where Non-Linear Loads > than 50% of Total Loads.
• When Fast VAR Movements Necessary
• AHF-New breed of power quality product
– Harmonics cancellation
– Power factor correction
– VAR compensation
– Resonance elimination
• Independent or simultaneous modes of operation
![Page 44: 1 Power Factor Correction Capacitors Selection & Applications Of Power Factor Correction Capacitor For Industrial and Large Commercial Users Ben Banerjee](https://reader035.vdocuments.us/reader035/viewer/2022062404/5514aa9b550346ea6e8b5e35/html5/thumbnails/44.jpg)
44
Active Harmonics Filter
• Electronic filtering up to the 50th harmonic
I source I load
Powersource
Non-linearload
ActiveHarmonic
Conditioner
I conditioner
![Page 45: 1 Power Factor Correction Capacitors Selection & Applications Of Power Factor Correction Capacitor For Industrial and Large Commercial Users Ben Banerjee](https://reader035.vdocuments.us/reader035/viewer/2022062404/5514aa9b550346ea6e8b5e35/html5/thumbnails/45.jpg)
45
Hybrid Filters
• Combination of passive & active technologies
+
![Page 46: 1 Power Factor Correction Capacitors Selection & Applications Of Power Factor Correction Capacitor For Industrial and Large Commercial Users Ben Banerjee](https://reader035.vdocuments.us/reader035/viewer/2022062404/5514aa9b550346ea6e8b5e35/html5/thumbnails/46.jpg)
Division - Name - Date - Language 46
6000kVAR, 13.8kV, 60HzFIXED, DE-TUNED
NEMA 3R
MAIN INCOMING INTERFACEWITH CUSTOMER'S NETWORK
15kV HVL LINEUPNEMA 3R
4000kVA, 13.8kV/480VNEMA 3R
5000A, 480V MAINSNEMA 1
2000A, 480VNEMA 1
4x300AACCUSINE
4x300AACCUSINE
4x300AACCUSINE
4x300AACCUSINE
4x300AACCUSINE
4x300AACCUSINE
POWER ZONE HOUSE 1 POWER ZONE HOUSE 2
24X300A ACCUSINE -> 6000kVAR
PASSIVE ACTIVE
MV HVC Banks – General Layout
![Page 47: 1 Power Factor Correction Capacitors Selection & Applications Of Power Factor Correction Capacitor For Industrial and Large Commercial Users Ben Banerjee](https://reader035.vdocuments.us/reader035/viewer/2022062404/5514aa9b550346ea6e8b5e35/html5/thumbnails/47.jpg)
Division - Name - Date - Language 47
HVC Banks – General
HVC
-10000
-5000
0
5000
10000
15000
0 2 4 6 8 10 12 14 16 18
Time in cycles
Var
s L
ead
ing
/Lag
gin
g
Fixed Kvar
Load
Accusine
Result Kvar
Marriage of two technologies Fixed capacitor banks and AHF Auxiliaries: MV/LV SWGR
![Page 48: 1 Power Factor Correction Capacitors Selection & Applications Of Power Factor Correction Capacitor For Industrial and Large Commercial Users Ben Banerjee](https://reader035.vdocuments.us/reader035/viewer/2022062404/5514aa9b550346ea6e8b5e35/html5/thumbnails/48.jpg)
Division - Name - Date - Language 48
WELDING OPERATIONS LARGE HP MOTOR STARTING PROCESS LOADS (i.e. MIXERS,
CRUSHERS, CHIPPERS, SHREDDERS)
ARC FURNACES
APPLICATION OF: HYBRID VAR COMPENSATION
(HVC) DYNAMIC VAR INJECTION ON PER
CYCLE BASIS PASSIVE/ACTIVE SYSTEM
ARRANGEMENT WITH INRUSH OR DE-TUNED
REACTORS CUSTOM-ENGINREERED FOR
SPECIFIC SITE, NETWORK, LOAD CHARACTERISTIC NEEDS
CAUSESCAUSES SOLUTIONSSOLUTIONS
Cyclical Loads & Loads With Dynamic VAR Movements
RESULTING INRESULTING IN
VOLTAGE FLICKER VOLTAGE SAGS POOR POWER FACTOR INABILITY TO START MOTORS
![Page 49: 1 Power Factor Correction Capacitors Selection & Applications Of Power Factor Correction Capacitor For Industrial and Large Commercial Users Ben Banerjee](https://reader035.vdocuments.us/reader035/viewer/2022062404/5514aa9b550346ea6e8b5e35/html5/thumbnails/49.jpg)
49
CAPACITOR APPLICATIONS AT MOTOR TERMINAL
> Motor Overload Protection
> Re-closure Issue – Jogging , Reversing, Inching , Plugging Applications
![Page 50: 1 Power Factor Correction Capacitors Selection & Applications Of Power Factor Correction Capacitor For Industrial and Large Commercial Users Ben Banerjee](https://reader035.vdocuments.us/reader035/viewer/2022062404/5514aa9b550346ea6e8b5e35/html5/thumbnails/50.jpg)
50
Capacitor At Motor Terminal Motor Over Load Protection Issue
![Page 51: 1 Power Factor Correction Capacitors Selection & Applications Of Power Factor Correction Capacitor For Industrial and Large Commercial Users Ben Banerjee](https://reader035.vdocuments.us/reader035/viewer/2022062404/5514aa9b550346ea6e8b5e35/html5/thumbnails/51.jpg)
51
Motor Self-Excitation Voltage Influenced By Capacitor Ratings
![Page 52: 1 Power Factor Correction Capacitors Selection & Applications Of Power Factor Correction Capacitor For Industrial and Large Commercial Users Ben Banerjee](https://reader035.vdocuments.us/reader035/viewer/2022062404/5514aa9b550346ea6e8b5e35/html5/thumbnails/52.jpg)
52
Reclosed Breaker & Net Voltage
![Page 53: 1 Power Factor Correction Capacitors Selection & Applications Of Power Factor Correction Capacitor For Industrial and Large Commercial Users Ben Banerjee](https://reader035.vdocuments.us/reader035/viewer/2022062404/5514aa9b550346ea6e8b5e35/html5/thumbnails/53.jpg)
53
CAPACITOR APPLICATION ISSUES
![Page 54: 1 Power Factor Correction Capacitors Selection & Applications Of Power Factor Correction Capacitor For Industrial and Large Commercial Users Ben Banerjee](https://reader035.vdocuments.us/reader035/viewer/2022062404/5514aa9b550346ea6e8b5e35/html5/thumbnails/54.jpg)
54
04/10/23
Power Quality Correction
Multi-Energy Power System Multi-Energy Power System of the Future ?of the Future ?
Hospital with cogeneration (1.5 MW)
SubstationFeeder
Residential photovoltaic system
(6 kW)
Utility-owned Photovoltaic site
(500 kW)
Small wind turbine (10 kW)
Factory with natural gas fuel cell (100 kW to 5 MW)
Residential Fuel cell (7
kW)Utility-owned wind turbine site (1 MW)
![Page 55: 1 Power Factor Correction Capacitors Selection & Applications Of Power Factor Correction Capacitor For Industrial and Large Commercial Users Ben Banerjee](https://reader035.vdocuments.us/reader035/viewer/2022062404/5514aa9b550346ea6e8b5e35/html5/thumbnails/55.jpg)
55
04/10/23
Power Quality Correction
Cos Ø2= 0.55Cos Ø1= 0.89
1000 KW 3000 KW
1537 KVAR
1537 KVAR
1818 KVA1537 KVA
Utility & Customer Owned Utility & Customer Owned Solar Power System WorkingSolar Power System Working
In Parallel In Parallel
![Page 56: 1 Power Factor Correction Capacitors Selection & Applications Of Power Factor Correction Capacitor For Industrial and Large Commercial Users Ben Banerjee](https://reader035.vdocuments.us/reader035/viewer/2022062404/5514aa9b550346ea6e8b5e35/html5/thumbnails/56.jpg)
56
Key Questions to ask Customer For Capacitor Applications
• Are you being charged for poor power factor by your utility (ask for a copy of their electric bill - kW, kVA, Power Factor)?
• Do you have a large number of drives, rectifiers or other harmonic generating equipment? Do you have nuisance tripping of overloads ?
• Do you have welders, chippers, or other large cyclical loads?
• Do you have problems with voltage sags or “flicker”? How sensitive is your equipment to these power issues?
• Do you have capacity issues on any of your substations?
• Do you have HID lighting or critical processes with low tolerance to “brownouts”?
• Have you been experiencing poor weld quality?
• Do you have Soft Starters in the System?
• Do you have Motors subject to reversing, jogging, inching, or plugging?
![Page 57: 1 Power Factor Correction Capacitors Selection & Applications Of Power Factor Correction Capacitor For Industrial and Large Commercial Users Ben Banerjee](https://reader035.vdocuments.us/reader035/viewer/2022062404/5514aa9b550346ea6e8b5e35/html5/thumbnails/57.jpg)
57
Capacitor Standards
• NEMA CP-1 for Shunt Capacitors
• UL 810 Standard for Capacitors
• NFPA 70, National Electrical Code
• IEEE Standard 399, Power System Analysis
• ANSI / IEEE Standard 18, Shunt Power Capacitors
• IEEE Standard 141, Recommended Practice for Electrical Power Distribution for Industrial Plants
![Page 58: 1 Power Factor Correction Capacitors Selection & Applications Of Power Factor Correction Capacitor For Industrial and Large Commercial Users Ben Banerjee](https://reader035.vdocuments.us/reader035/viewer/2022062404/5514aa9b550346ea6e8b5e35/html5/thumbnails/58.jpg)
58
Other Capacitor Application Issues
NEC & NEMA :
* The Ampacity of Capacitor Circuit Conductors shall not be less than 135% of rated Capacitor Current
* Breaker Rating based on 135% Rated Capacitor Current
* Fuse Rating based on 165% Rated Capacitor Current for Class R Time Delay
* Fusible Switch Rating based on 165% Rated Capacitor Current
![Page 59: 1 Power Factor Correction Capacitors Selection & Applications Of Power Factor Correction Capacitor For Industrial and Large Commercial Users Ben Banerjee](https://reader035.vdocuments.us/reader035/viewer/2022062404/5514aa9b550346ea6e8b5e35/html5/thumbnails/59.jpg)
59
Capacitor Operating Environment Issues
Capacitor When Properly Applied Will Have Long Life.
Conditions that affect the Life of Capacitor:
* Ambient Temp. < 46Deg C or 115Deg F
* Case Temp. of Capacitor < 55Deg C or 131 Deg F
* Shunt Capacitor designed to operate at 110%
Rated Voltage.
* Avoid sustained Over Voltage
* High System Harmonics
![Page 60: 1 Power Factor Correction Capacitors Selection & Applications Of Power Factor Correction Capacitor For Industrial and Large Commercial Users Ben Banerjee](https://reader035.vdocuments.us/reader035/viewer/2022062404/5514aa9b550346ea6e8b5e35/html5/thumbnails/60.jpg)
60
04/10/23
Power Quality Correction
Reduced Power Costs:Reduced Power Costs: Since Capacitors supply reactive power, Since Capacitors supply reactive power, you don’t payyou don’t pay the utility the utility
for itfor it Depending up on location of Cap. Bank, Line Loss can be Depending up on location of Cap. Bank, Line Loss can be
reduced.reduced. You can You can calculatecalculate the savings the savings
Off-load transformersOff-load transformers Defer buying a larger transformer when adding loadsDefer buying a larger transformer when adding loads
Reduce voltage drop at loadsReduce voltage drop at loads Only if capacitors are applied at loadsOnly if capacitors are applied at loads (minimal benefit at best)(minimal benefit at best)
A2
Summary of Benefits:Summary of Benefits:
![Page 61: 1 Power Factor Correction Capacitors Selection & Applications Of Power Factor Correction Capacitor For Industrial and Large Commercial Users Ben Banerjee](https://reader035.vdocuments.us/reader035/viewer/2022062404/5514aa9b550346ea6e8b5e35/html5/thumbnails/61.jpg)
61
04/10/23
Power Quality Correction
Thank You !Thank You ! Questions? Questions?