douglas county pud douglas-rapids 230-kv … 230-kv transmission line supplemental progress report...

21
Douglas County PUD Douglas-Rapids 230-kV Transmission Line Supplemental Progress Report March 14, 2014 Updated Information from Initial Progress Report 1. Douglas County PUD is constructing a new 13-mile, 230-kV transmission line to connect its Douglas Switchyard with its Rapids Switchyard. The conductor will be 1590 ACSR/TW and is expected to have a Summer rating of 589.5 MVA, a Winter rating of 766.8 MVA, an Autumn rating of 687.9 MVA, and a Spring rating of 671.6 MVA. A new 230/115-kV transformer will be installed at Rapids Switchyard with expected ratings of 200 MVA (ONAN) 55° C, 266 MVA (ONAF) 55° C, 333 MVA (ONAF) 55° C, and 373 MVA (ONAF) 65° C. The new 230-kV circuit breakers at Douglas Switchyard and Rapids Switchyard will be rated for 3000 A of continuous current. The new 230-kV breaker disconnect switches at Douglas Switchyard will be rated for 3000 A of continuous current and the 230-kV line disconnect switches at Douglas Switchyard and Rapids Switchyard will be rated for 2000 A of continuous current. 2. The new transmission line is planned to be in operation in April, 2014. 3. The project is currently under construction and is tentatively scheduled for completion in April, 2014. The transmission line is complete, and the remaining work is to finish installing the transformer at Rapids Switchyard. 4. The facility owner’s name is Douglas County PUD (DOPD). The contact for the project is: Jerry Kyle Assistant Manager – Distribution Engineering 1151 Valley Mall Parkway East Wenatchee, WA 98802-4497 (509)881-2234 [email protected] Updated Information from Comprehensive Progress Report 1. See above updated information from the Initial Progress Report. 2. There are no changes to the original one-line and geographic diagrams. 3. A model of the new facility is available in the WECC power flow and stability programs.

Upload: vantuyen

Post on 15-Apr-2018

224 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Douglas County PUD Douglas-Rapids 230-kV … 230-kV Transmission Line Supplemental Progress Report ... of 671.6 MVA. A new 230/115-kV transformer ... from the Initial Progress Report

Douglas County PUD

Douglas-Rapids 230-kV Transmission Line

Supplemental Progress Report

March 14, 2014

Updated Information from Initial Progress Report

1. Douglas County PUD is constructing a new 13-mile, 230-kV transmission line to connect its

Douglas Switchyard with its Rapids Switchyard. The conductor will be 1590 ACSR/TW and is

expected to have a Summer rating of 589.5 MVA, a Winter rating of 766.8 MVA, an Autumn

rating of 687.9 MVA, and a Spring rating of 671.6 MVA. A new 230/115-kV transformer will be

installed at Rapids Switchyard with expected ratings of 200 MVA (ONAN) 55° C, 266 MVA (ONAF)

55° C, 333 MVA (ONAF) 55° C, and 373 MVA (ONAF) 65° C. The new 230-kV circuit breakers at

Douglas Switchyard and Rapids Switchyard will be rated for 3000 A of continuous current. The

new 230-kV breaker disconnect switches at Douglas Switchyard will be rated for 3000 A of

continuous current and the 230-kV line disconnect switches at Douglas Switchyard and Rapids

Switchyard will be rated for 2000 A of continuous current.

2. The new transmission line is planned to be in operation in April, 2014.

3. The project is currently under construction and is tentatively scheduled for completion in April,

2014. The transmission line is complete, and the remaining work is to finish installing the

transformer at Rapids Switchyard.

4. The facility owner’s name is Douglas County PUD (DOPD). The contact for the project is:

Jerry Kyle

Assistant Manager – Distribution Engineering

1151 Valley Mall Parkway

East Wenatchee, WA 98802-4497

(509)881-2234

[email protected]

Updated Information from Comprehensive Progress Report

1. See above updated information from the Initial Progress Report.

2. There are no changes to the original one-line and geographic diagrams.

3. A model of the new facility is available in the WECC power flow and stability programs.

Page 2: Douglas County PUD Douglas-Rapids 230-kV … 230-kV Transmission Line Supplemental Progress Report ... of 671.6 MVA. A new 230/115-kV transformer ... from the Initial Progress Report

4. The Transfer Capability associated with the project will be equal to the System Operating Limit

(SOL), which is based on the Facility Ratings (MVA ratings at the applicable ambient

temperature) of all applicable Facilities. The WECC Comprehensive Project Coordination Review

process suggests that project sponsors can use Subregional Planning Groups to meet its

requirements (“a project sponsor may use TEPPC or a Subregional Planning Group to meet the

requirements of Project Coordination Review in lieu of forming an independent PCRG for their

project.” Douglas PUD is a member of and uses ColumbiaGrid to accomplish its subregional

planning requirements. The ColumbiaGrid planning process has open participation in its general

planning and study team meetings. The Douglas-Rapids project has been reviewed by and has

achieved consensus through this planning process, which included all of the transmission

owners that could be impacted by this project. Project reports are available from ColumbiaGrid

at http://www.columbiagrid.org. The requirements of Project Coordination Review for this

project have been met through the ColumbiaGrid Subregional Planning Group. The impact of

the Douglas-Rapids project on other systems and on existing transfer path ratings has been

studied in the ColumbiaGrid Northern Mid-C Study Group. Douglas PUD complies with all NERC

Reliability Standards and WECC Criteria. The Douglas-Rapids Line facility additions and planned

system operation are in conformance with NERC Standards and WECC System Performance

Criteria. The Douglas-Rapids project will not require obtaining an accepted transmission path

rating.

5. The proposed Transfer Capability rating is based on Douglas PUD’s System Operating Limits.

Douglas PUD’s System Operating Limits are based solely on its Facility Ratings, which, for

transmission circuits and transformers, are determined by ambient temperature conditions.

6. See studies conducted in ColumbiaGrid Northern Mid-C Study Team and Northern Mid-C Joint

Operational Study Team for operating conditions that allow the project to operate within the

guidelines defined in the NERC Reliability Standards and WECC Criteria.

7. See studies conducted in ColumbiaGrid Northern Mid-C Study Team and Northern Mid-C Joint

Operational Study Team for potential impacts to transmission facilities including non-

simultaneous ratings and simultaneous path interactions.

8. To demonstrate Douglas PUD’s compliance with NERC Reliability Standards and WECC Criteria,

the following power flow and stability cases were run by ColumbiaGrid:

a. Summer, 2012

b. Summer, 2013

c. Summer, 2014

d. Summer, 2015

e. Summer, 2019

f. Winter, 2019

Page 3: Douglas County PUD Douglas-Rapids 230-kV … 230-kV Transmission Line Supplemental Progress Report ... of 671.6 MVA. A new 230/115-kV transformer ... from the Initial Progress Report

To demonstrate Douglas PUD’s compliance with NERC Reliability Standards and WECC Criteria,

the following power flow and stability cases were run by Douglas PUD in 2013:

a. Heavy Summer, 2015

b. Heavy Summer, 2019

c. Heavy Winter, 2019

d. Light Autumn, 2022

e. Heavy Summer, 2023

f. Heavy Winter, 2024

9. In addition to the data provided in the Comprehensive Study Report, See Appendix A for power

flow outage results that demonstrate Douglas PUD’s compliance with NERC Reliability Standards

and WECC Criteria.

10. The project is currently under construction and is scheduled for completion in April, 2014. The

transmission line is complete, and the remaining work is to finish installing the transformer at

Rapids Switchyard. This will be accomplished within the next month.

Page 4: Douglas County PUD Douglas-Rapids 230-kV … 230-kV Transmission Line Supplemental Progress Report ... of 671.6 MVA. A new 230/115-kV transformer ... from the Initial Progress Report

Appendix A

Power Flow Outage Results

(attached)

Page 5: Douglas County PUD Douglas-Rapids 230-kV … 230-kV Transmission Line Supplemental Progress Report ... of 671.6 MVA. A new 230/115-kV transformer ... from the Initial Progress Report

2015 Heavy Summer Results

Contingency Name Element Category Value Limit Percent Area Name Assoc. Owner Names NERC Category Comment

Cat B - Transformer - Wells T6 + Cat B - Transmission Circuit - Wells-Douglas Line 1 WELLS B2 (47102) -> DOUGLAS (47031) CKT 1 at WELLS B2 Branch Amp 1759.79 1749.62 100.58 NORTHWEST Douglas PUD C or D Loss of Wells-Foster Creek connection and one of the Wells-Douglas Lines overloads the other Wells-Douglas Line.

Cat B - Transformer - Wells T6 + Cat B - Transmission Circuit - Wells-Douglas Line 2 WELLS B1 (47100) -> DOUGLAS (47031) CKT 1 at WELLS B1 Branch Amp 1759.69 1749.62 100.58 NORTHWEST Douglas PUD C or D Loss of Wells-Foster Creek connection and one of the Wells-Douglas Lines overloads the other Wells-Douglas Line.

Cat B - Transmission Circuit - Douglas-Rocky Reach Line + Cat B - Transmission Circuit - Douglas-Sickler Line VALHALLA (41105) -> COLUMBIA (40259) CKT 1 at VALHALLA Branch Amp 1127.51 1069.86 105.39 NORTHWEST Bonneville Power Admin

Cat B - Transmission Circuit - Douglas-Rocky Reach Line + Cat B - Transmission Circuit - Douglas-Sickler Line VALHALLA (41105) -> COLUMBIA (40259) CKT 2 at VALHALLA Branch Amp 1138.52 1069.86 106.42 NORTHWEST Bonneville Power Admin

Cat B - Transmission Circuit - Douglas-Rocky Reach Line + Cat B - Transmission Circuit - Sickler-Schultz HANNA (47051) -> VALHALLA (41105) CKT 1 at HANNA Branch Amp 1007.38 994.05 101.34 NORTHWEST Douglas PUD C or D Loss of the Douglas-Rocky Reach Tie and the Sickler-Schultz Line causes an overload.

Cat B - Transmission Circuit - Douglas-Rocky Reach Line + Cat B - Transmission Circuit - Sickler-Schultz RAPIDS (47080) -> HANNA (47051) CKT 1 at RAPIDS Branch Amp 1033 1009.11 102.37 NORTHWEST Douglas PUD C or D Loss of the Douglas-Rocky Reach Tie and the Sickler-Schultz Line causes an overload.

Cat B - Transmission Circuit - Douglas-Sickler Line + Cat B - Transmission Circuit - Douglas-Rocky Reach Line VALHALLA (41105) -> COLUMBIA (40259) CKT 1 at VALHALLA Branch Amp 1127.51 1069.86 105.39 NORTHWEST Bonneville Power Admin

Cat B - Transmission Circuit - Douglas-Sickler Line + Cat B - Transmission Circuit - Douglas-Rocky Reach Line VALHALLA (41105) -> COLUMBIA (40259) CKT 2 at VALHALLA Branch Amp 1138.52 1069.86 106.42 NORTHWEST Bonneville Power Admin

Cat B - Transmission Circuit - Douglas-Sickler Line + Cat B - Transmission Circuit - RR-Columbia #1 ROCKYRH1 (46831) -> MCKENZIE (46809) CKT 1 at MCKENZIE Branch Amp 1297.49 1109.01 117 NORTHWEST Chelan PUD

Cat B - Transmission Circuit - Douglas-Sickler Line + Cat B - Transmission Circuit - RR-Columbia #2 ROCKYRH2 (46832) -> COLUMBIA (40261) CKT 1 at ROCKYRH2 Branch Amp 1220.18 1199.88 101.69 NORTHWEST Bonneville Power Admin

Cat B - Transmission Circuit - Douglas-Sickler Line + Cat B - Transmission Circuit - RR-Maple Valley ANDRS CN (46801) -> WINTON (46888) CKT 1 at ANDRS CN Branch Amp 268.95 266.08 101.08 NORTHWEST Chelan PUD

Cat B - Transmission Circuit - Douglas-Sickler Line + Cat B - Transmission Circuit - RR-Maple Valley ROCKYRH1 (46831) -> MCKENZIE (46809) CKT 1 at MCKENZIE Branch Amp 1130.51 1109.01 101.94 NORTHWEST Chelan PUD

Cat B - Transmission Circuit - Douglas-Sickler Line + Cat B - Transmission Circuit - RR-Maple Valley WINTON (46888) -> COLESCRN (46864) CKT 1 at WINTON Branch Amp 267.39 266.08 100.49 NORTHWEST Chelan PUD

Cat B - Transmission Circuit - RR-Columbia #1 + Cat B - Transmission Circuit - Douglas-Sickler Line ROCKYRH1 (46831) -> MCKENZIE (46809) CKT 1 at MCKENZIE Branch Amp 1297.49 1109.01 117 NORTHWEST Chelan PUD

Cat B - Transmission Circuit - RR-Columbia #1 + Cat B - Transmission Circuit - Sickler-Schultz ROCKYRH1 (46831) -> MCKENZIE (46809) CKT 1 at MCKENZIE Branch Amp 1165.54 1109.01 105.1 NORTHWEST Chelan PUD

Cat B - Transmission Circuit - RR-Columbia #2 + Cat B - Transmission Circuit - Douglas-Sickler Line ROCKYRH2 (46832) -> COLUMBIA (40261) CKT 1 at ROCKYRH2 Branch Amp 1220.28 1199.88 101.7 NORTHWEST Bonneville Power Admin

Cat B - Transmission Circuit - RR-Maple Valley + Cat B - Transmission Circuit - Douglas-Sickler Line ANDRS CN (46801) -> WINTON (46888) CKT 1 at ANDRS CN Branch Amp 268.95 266.08 101.08 NORTHWEST Chelan PUD

Cat B - Transmission Circuit - RR-Maple Valley + Cat B - Transmission Circuit - Douglas-Sickler Line ROCKYRH1 (46831) -> MCKENZIE (46809) CKT 1 at MCKENZIE Branch Amp 1130.51 1109.01 101.94 NORTHWEST Chelan PUD

Cat B - Transmission Circuit - RR-Maple Valley + Cat B - Transmission Circuit - Douglas-Sickler Line WINTON (46888) -> COLESCRN (46864) CKT 1 at WINTON Branch Amp 267.39 266.08 100.49 NORTHWEST Chelan PUD

Cat B - Transmission Circuit - Sickler-Schultz + Cat B - Transmission Circuit - Douglas-Rocky Reach Line HANNA (47051) -> VALHALLA (41105) CKT 1 at HANNA Branch Amp 1007.38 994.05 101.34 NORTHWEST Douglas PUD C or D Loss of the Douglas-Rocky Reach Tie and the Sickler-Schultz Line causes an overload.

Cat B - Transmission Circuit - Sickler-Schultz + Cat B - Transmission Circuit - Douglas-Rocky Reach Line RAPIDS (47080) -> HANNA (47051) CKT 1 at RAPIDS Branch Amp 1033 1009.11 102.37 NORTHWEST Douglas PUD C or D Loss of the Douglas-Rocky Reach Tie and the Sickler-Schultz Line causes an overload.

Cat B - Transmission Circuit - Sickler-Schultz + Cat B - Transmission Circuit - RR-Columbia #1 ROCKYRH1 (46831) -> MCKENZIE (46809) CKT 1 at MCKENZIE Branch Amp 1165.49 1109.01 105.09 NORTHWEST Chelan PUD

Cat B - Transmission Circuit - Wells-Douglas Line 1 + Cat B - Transformer - Wells T6 WELLS B2 (47102) -> DOUGLAS (47031) CKT 1 at WELLS B2 Branch Amp 1759.79 1749.62 100.58 NORTHWEST Douglas PUD C or D Loss of Wells-Foster Creek connection and one of the Wells-Douglas Lines overloads the other Wells-Douglas Line.

Cat B - Transmission Circuit - Wells-Douglas Line 1 + Cat B - Transmission Circuit - Wells-Foster Creek Line WELLS B2 (47102) -> DOUGLAS (47031) CKT 1 at WELLS B2 Branch Amp 1759.79 1749.62 100.58 NORTHWEST Douglas PUD C or D Loss of Wells-Foster Creek connection and one of the Wells-Douglas Lines overloads the other Wells-Douglas Line.

Cat B - Transmission Circuit - Wells-Douglas Line 2 + Cat B - Transformer - Wells T6 WELLS B1 (47100) -> DOUGLAS (47031) CKT 1 at WELLS B1 Branch Amp 1759.69 1749.62 100.58 NORTHWEST Douglas PUD C or D Loss of Wells-Foster Creek connection and one of the Wells-Douglas Lines overloads the other Wells-Douglas Line.

Cat B - Transmission Circuit - Wells-Douglas Line 2 + Cat B - Transmission Circuit - Wells-Foster Creek Line WELLS B1 (47100) -> DOUGLAS (47031) CKT 1 at WELLS B1 Branch Amp 1759.69 1749.62 100.58 NORTHWEST Douglas PUD C or D Loss of Wells-Foster Creek connection and one of the Wells-Douglas Lines overloads the other Wells-Douglas Line.

Cat B - Transmission Circuit - Wells-Foster Creek Line + Cat B - Transmission Circuit - Wells-Douglas Line 1 WELLS B2 (47102) -> DOUGLAS (47031) CKT 1 at WELLS B2 Branch Amp 1759.79 1749.62 100.58 NORTHWEST Douglas PUD C or D Loss of Wells-Foster Creek connection and one of the Wells-Douglas Lines overloads the other Wells-Douglas Line.

Cat B - Transmission Circuit - Wells-Foster Creek Line + Cat B - Transmission Circuit - Wells-Douglas Line 2 WELLS B1 (47100) -> DOUGLAS (47031) CKT 1 at WELLS B1 Branch Amp 1759.69 1749.62 100.58 NORTHWEST Douglas PUD C or D Loss of Wells-Foster Creek connection and one of the Wells-Douglas Lines overloads the other Wells-Douglas Line.

Page 6: Douglas County PUD Douglas-Rapids 230-kV … 230-kV Transmission Line Supplemental Progress Report ... of 671.6 MVA. A new 230/115-kV transformer ... from the Initial Progress Report

2019 Heavy Summer Results

Contingency Name Element Category Value Limit Percent Area Name Assoc. Owner Names NERC Category Comment

Cat B - Transformer - Wells T6 + Cat B - Transmission Circuit - Wells-Douglas Line 1 WELLS B2 (47102) -> DOUGLAS (47031) CKT 1 at WELLS B2 Branch Amp 1759.81 1749.62 100.58 NORTHWEST Douglas PUD C or D Loss of Wells-Foster Creek connection and one of the Wells-Douglas Lines overloads the other Wells-Douglas Line.

Cat B - Transformer - Wells T6 + Cat B - Transmission Circuit - Wells-Douglas Line 2 WELLS B1 (47100) -> DOUGLAS (47031) CKT 1 at WELLS B1 Branch Amp 1759.71 1749.62 100.58 NORTHWEST Douglas PUD C or D Loss of Wells-Foster Creek connection and one of the Wells-Douglas Lines overloads the other Wells-Douglas Line.

Cat B - Transmission Circuit - Wells-Douglas Line 1 + Cat B - Transformer - Wells T6 WELLS B2 (47102) -> DOUGLAS (47031) CKT 1 at WELLS B2 Branch Amp 1759.81 1749.62 100.58 NORTHWEST Douglas PUD C or D Loss of Wells-Foster Creek connection and one of the Wells-Douglas Lines overloads the other Wells-Douglas Line.

Cat B - Transmission Circuit - Wells-Douglas Line 1 + Cat B - Transmission Circuit - Wells-Foster Creek Line WELLS B2 (47102) -> DOUGLAS (47031) CKT 1 at WELLS B2 Branch Amp 1759.81 1749.62 100.58 NORTHWEST Douglas PUD C or D Loss of Wells-Foster Creek connection and one of the Wells-Douglas Lines overloads the other Wells-Douglas Line.

Cat B - Transmission Circuit - Wells-Douglas Line 2 + Cat B - Transformer - Wells T6 WELLS B1 (47100) -> DOUGLAS (47031) CKT 1 at WELLS B1 Branch Amp 1759.71 1749.62 100.58 NORTHWEST Douglas PUD C or D Loss of Wells-Foster Creek connection and one of the Wells-Douglas Lines overloads the other Wells-Douglas Line.

Cat B - Transmission Circuit - Wells-Douglas Line 2 + Cat B - Transmission Circuit - Wells-Foster Creek Line WELLS B1 (47100) -> DOUGLAS (47031) CKT 1 at WELLS B1 Branch Amp 1759.71 1749.62 100.58 NORTHWEST Douglas PUD C or D Loss of Wells-Foster Creek connection and one of the Wells-Douglas Lines overloads the other Wells-Douglas Line.

Cat B - Transmission Circuit - Wells-Foster Creek Line + Cat B - Transmission Circuit - Wells-Douglas Line 1 WELLS B2 (47102) -> DOUGLAS (47031) CKT 1 at WELLS B2 Branch Amp 1759.81 1749.62 100.58 NORTHWEST Douglas PUD C or D Loss of Wells-Foster Creek connection and one of the Wells-Douglas Lines overloads the other Wells-Douglas Line.

Cat B - Transmission Circuit - Wells-Foster Creek Line + Cat B - Transmission Circuit - Wells-Douglas Line 2 WELLS B1 (47100) -> DOUGLAS (47031) CKT 1 at WELLS B1 Branch Amp 1759.71 1749.62 100.58 NORTHWEST Douglas PUD C or D Loss of Wells-Foster Creek connection and one of the Wells-Douglas Lines overloads the other Wells-Douglas Line.

Page 7: Douglas County PUD Douglas-Rapids 230-kV … 230-kV Transmission Line Supplemental Progress Report ... of 671.6 MVA. A new 230/115-kV transformer ... from the Initial Progress Report

2019 Heavy Winter Results

Contingency Name Element Category Value Limit Percent Area Name Assoc. Owner Names NERC Category Comment

Cat B - Transformer - East Omak + Cat B - Transformer - Wells T6 FSTR CR (47044) Bus Low Volts 0.53 0.95 NORTHWEST Douglas PUD C or D Loss of connection to Wells and East Omak Transformer causes low voltage.

Cat B - Transformer - East Omak + Cat B - Transformer - Wells T6 NILLES C (47067) Bus Low Volts 0.82 0.95 NORTHWEST Douglas PUD C or D Loss of connection to Wells and East Omak Transformer causes low voltage.

Cat B - Transformer - East Omak + Cat B - Transmission Circuit - Foster Creek-Bridgeport Bar-Brewster Line NILLES C (47067) Bus Low Volts 0.89 0.95 NORTHWEST Douglas PUD C or D Loss of connection to Wells and East Omak Transformer causes low voltage.

Cat B - Transformer - East Omak + Cat B - Transmission Circuit - Okanogan-Goose Lake Line WELLS B2 (47102) -> WELLS (47099) CKT 1 at WELLS B2 Branch MVA 135.61 112 121.08 NORTHWEST Douglas PUD C or D Loss of two generation sources into Okanogan's system causes an overload.

Cat B - Transformer - East Omak + Cat B - Transmission Circuit - Wells-Foster Creek Line FSTR CR (47044) Bus Low Volts 0.53 0.95 NORTHWEST Douglas PUD C or D Loss of connection to Wells and East Omak Transformer causes low voltage.

Cat B - Transformer - East Omak + Cat B - Transmission Circuit - Wells-Foster Creek Line NILLES C (47067) Bus Low Volts 0.82 0.95 NORTHWEST Douglas PUD C or D Loss of connection to Wells and East Omak Transformer causes low voltage.

Cat B - Transformer - Wells T6 + Cat B - Transformer - East Omak FSTR CR (47044) Bus Low Volts 0.53 0.95 NORTHWEST Douglas PUD C or D Loss of connection to Wells and East Omak Transformer causes low voltage.

Cat B - Transformer - Wells T6 + Cat B - Transformer - East Omak NILLES C (47067) Bus Low Volts 0.82 0.95 NORTHWEST Douglas PUD C or D Loss of connection to Wells and East Omak Transformer causes low voltage.

Cat B - Transmission Circuit - Foster Creek-Bridgeport Bar-Brewster Line + Cat B - Transformer - East Omak NILLES C (47067) Bus Low Volts 0.89 0.95 NORTHWEST Douglas PUD C or D Loss of connection to Wells and East Omak Transformer causes low voltage.

Cat B - Transmission Circuit - Okanogan-Goose Lake Line + Cat B - Transformer - East Omak WELLS B2 (47102) -> WELLS (47099) CKT 1 at WELLS B2 Branch MVA 135.59 112 121.07 NORTHWEST Douglas PUD C or D Loss of two generation sources into Okanogan's system causes an overload.

Cat B - Transmission Circuit - Wells-Foster Creek Line + Cat B - Transformer - East Omak FSTR CR (47044) Bus Low Volts 0.53 0.95 NORTHWEST Douglas PUD C or D Loss of connection to Wells and East Omak Transformer causes low voltage.

Cat B - Transmission Circuit - Wells-Foster Creek Line + Cat B - Transformer - East Omak NILLES C (47067) Bus Low Volts 0.82 0.95 NORTHWEST Douglas PUD C or D Loss of connection to Wells and East Omak Transformer causes low voltage.

Cat D - 3 Transmission Circuits - Okanogan-Goose Lake, East Omak Transformer, East Omak-Foster Creek WELLS (47099) -> FSTR CR (47044) CKT 1 at FSTR CR Branch Amp 1233.97 1114.54 110.72 NORTHWEST Douglas PUD D Loss of all other generation sources into Okanogan's system causes an overload.

Cat D - 3 Transmission Circuits - Okanogan-Goose Lake, East Omak Transformer, East Omak-Foster Creek WELLS B2 (47102) -> WELLS (47099) CKT 1 at WELLS B2 Branch MVA 254.98 112 227.66 NORTHWEST Douglas PUD D Loss of all other generation sources into Okanogan's system causes an overload.

Cat D - 3 Transmission Circuits - Okanogan-Goose Lake, East Omak Transformer, East Omak-Foster Creek FSTR CR (47044) Bus Low Volts 0.76 0.95 NORTHWEST Douglas PUD D Loss of all other generation sources into Okanogan's system causes low voltage.

Cat D - 3 Transmission Circuits - Okanogan-Goose Lake, East Omak Transformer, East Omak-Foster Creek WELLS (47099) Bus Low Volts 0.87 0.95 NORTHWEST Douglas PUD D Loss of all other generation sources into Okanogan's system causes low voltage.

Cat D - Common ROW - Sickler-Schultz, Douglas-Rapids, RR-Columbia #1, RR-Maple Valley, RR-Columbia #2 DOUGLAS (47031) -> DOUGLAS (47029) CKT 1 at DOUGLAS Branch MVA 193.05 190 101.61 NORTHWEST Douglas PUD D Common corridor outage causes an overload.

Cat D - Common ROW - Sickler-Schultz, Douglas-Rapids, RR-Columbia #1, RR-Maple Valley, RR-Columbia #2, RR-Cascade DOUGLAS (47031) -> DOUGLAS (47029) CKT 1 at DOUGLAS Branch MVA 218.32 190 114.91 NORTHWEST Douglas PUD D Common corridor outage causes an overload.

Page 8: Douglas County PUD Douglas-Rapids 230-kV … 230-kV Transmission Line Supplemental Progress Report ... of 671.6 MVA. A new 230/115-kV transformer ... from the Initial Progress Report

2022 Light Autumn Results

Contingency Name Element Category Value Limit Percent Area Name Assoc. Owner Names NERC Category Comment

Cat B - Transmission Circuit - Wells-Douglas Line 1 + Cat B - Transmission Circuit - Wells-Douglas Line 2 WELLS B2 (47102) -> WELLS (47099) CKT 1 at WELLS Branch MVA 141.82 112 126.63 NORTHWEST Douglas PUD C or D Modeling Error. Actual gen reduction scheme at Wells would drop to only one unit in service, thus eliminating this violation.

Cat B - Transmission Circuit - Wells-Douglas Line 2 + Cat B - Transmission Circuit - Wells-Douglas Line 1 WELLS B2 (47102) -> WELLS (47099) CKT 1 at WELLS Branch MVA 141.82 112 126.63 NORTHWEST Douglas PUD C or D Modeling Error. Actual gen reduction scheme at Wells would drop to only one unit in service, thus eliminating this violation.

Cat D - Common ROW - Wells-Douglas Lines WELLS B2 (47102) -> WELLS (47099) CKT 1 at WELLS Branch MVA 141.82 112 126.63 NORTHWEST Douglas PUD D Modeling Error. Actual gen reduction scheme at Wells would drop to only one unit in service, thus eliminating this violation.

Cat D - Switching Station - Douglas 230 WELLS B2 (47102) -> WELLS (47099) CKT 1 at WELLS Branch MVA 141.82 112 126.62 NORTHWEST Douglas PUD D Modeling Error. Actual gen reduction scheme at Wells would drop to only one unit in service, thus eliminating this violation.

Page 9: Douglas County PUD Douglas-Rapids 230-kV … 230-kV Transmission Line Supplemental Progress Report ... of 671.6 MVA. A new 230/115-kV transformer ... from the Initial Progress Report

2023 Heavy Summer Results

Contingency Name Element Category Value Limit Percent Area Name Assoc. Owner Names NERC Category Comment

Cat B - Transformer - Wells T6 + Cat B - Transmission Circuit - Wells-Douglas Line 1 WELLS B2 (47102) -> DOUGLAS (47031) CKT 1 at WELLS B2 Branch Amp 1759.82 1749.62 100.58 NORTHWEST Douglas PUD C or D Loss of Wells-Foster Creek connection and one of the Wells-Douglas Lines overloads the other Wells-Douglas Line.

Cat B - Transformer - Wells T6 + Cat B - Transmission Circuit - Wells-Douglas Line 2 WELLS B1 (47100) -> DOUGLAS (47031) CKT 1 at WELLS B1 Branch Amp 1759.72 1749.62 100.58 NORTHWEST Douglas PUD C or D Loss of Wells-Foster Creek connection and one of the Wells-Douglas Lines overloads the other Wells-Douglas Line.

Cat B - Transmission Circuit - Wells-Douglas Line 1 + Cat B - Transformer - Wells T6 WELLS B2 (47102) -> DOUGLAS (47031) CKT 1 at WELLS B2 Branch Amp 1759.82 1749.62 100.58 NORTHWEST Douglas PUD C or D Loss of Wells-Foster Creek connection and one of the Wells-Douglas Lines overloads the other Wells-Douglas Line.

Cat B - Transmission Circuit - Wells-Douglas Line 1 + Cat B - Transmission Circuit - Wells-Foster Creek Line WELLS B2 (47102) -> DOUGLAS (47031) CKT 1 at WELLS B2 Branch Amp 1759.82 1749.62 100.58 NORTHWEST Douglas PUD C or D Loss of Wells-Foster Creek connection and one of the Wells-Douglas Lines overloads the other Wells-Douglas Line.

Cat B - Transmission Circuit - Wells-Douglas Line 2 + Cat B - Transformer - Wells T6 WELLS B1 (47100) -> DOUGLAS (47031) CKT 1 at WELLS B1 Branch Amp 1759.72 1749.62 100.58 NORTHWEST Douglas PUD C or D Loss of Wells-Foster Creek connection and one of the Wells-Douglas Lines overloads the other Wells-Douglas Line.

Cat B - Transmission Circuit - Wells-Douglas Line 2 + Cat B - Transmission Circuit - Wells-Foster Creek Line WELLS B1 (47100) -> DOUGLAS (47031) CKT 1 at WELLS B1 Branch Amp 1759.72 1749.62 100.58 NORTHWEST Douglas PUD C or D Loss of Wells-Foster Creek connection and one of the Wells-Douglas Lines overloads the other Wells-Douglas Line.

Cat B - Transmission Circuit - Wells-Foster Creek Line + Cat B - Transmission Circuit - Wells-Douglas Line 1 WELLS B2 (47102) -> DOUGLAS (47031) CKT 1 at WELLS B2 Branch Amp 1759.82 1749.62 100.58 NORTHWEST Douglas PUD C or D Loss of Wells-Foster Creek connection and one of the Wells-Douglas Lines overloads the other Wells-Douglas Line.

Cat B - Transmission Circuit - Wells-Foster Creek Line + Cat B - Transmission Circuit - Wells-Douglas Line 2 WELLS B1 (47100) -> DOUGLAS (47031) CKT 1 at WELLS B1 Branch Amp 1759.72 1749.62 100.58 NORTHWEST Douglas PUD C or D Loss of Wells-Foster Creek connection and one of the Wells-Douglas Lines overloads the other Wells-Douglas Line.

Page 10: Douglas County PUD Douglas-Rapids 230-kV … 230-kV Transmission Line Supplemental Progress Report ... of 671.6 MVA. A new 230/115-kV transformer ... from the Initial Progress Report

2024 Heavy Winter Results

Contingency Name Element Category Value Limit Percent Area Name Assoc. Owner Names NERC Category Comment

Cat B - Transformer - East Omak + Cat B - Transformer - Wells T6 FSTR CR (47044) Bus Low Volts 0.5 0.95 NORTHWEST Douglas PUD C or D Loss of connection to Wells and East Omak Transformer causes low voltage.

Cat B - Transformer - East Omak + Cat B - Transformer - Wells T6 NILLES C (47067) Bus Low Volts 0.81 0.95 NORTHWEST Douglas PUD C or D Loss of connection to Wells and East Omak Transformer causes low voltage.

Cat B - Transformer - East Omak + Cat B - Transmission Circuit - Foster Creek-Bridgeport Bar-Brewster Line NILLES C (47067) Bus Low Volts 0.89 0.95 NORTHWEST Douglas PUD C or D Loss of connection to Wells and East Omak Transformer causes low voltage.

Cat B - Transformer - East Omak + Cat B - Transmission Circuit - Okanogan-Goose Lake Line WELLS B2 (47102) -> WELLS (47099) CKT 1 at WELLS B2 Branch MVA 140.26 112 125.23 NORTHWEST Douglas PUD C or D Loss of two generation sources into Okanogan's system causes an overload.

Cat B - Transformer - East Omak + Cat B - Transmission Circuit - Wells-Foster Creek Line FSTR CR (47044) Bus Low Volts 0.5 0.95 NORTHWEST Douglas PUD C or D Loss of connection to Wells and East Omak Transformer causes low voltage.

Cat B - Transformer - East Omak + Cat B - Transmission Circuit - Wells-Foster Creek Line NILLES C (47067) Bus Low Volts 0.81 0.95 NORTHWEST Douglas PUD C or D Loss of connection to Wells and East Omak Transformer causes low voltage.

Cat B - Transformer - Wells T6 + Cat B - Transformer - East Omak FSTR CR (47044) Bus Low Volts 0.5 0.95 NORTHWEST Douglas PUD C or D Loss of connection to Wells and East Omak Transformer causes low voltage.

Cat B - Transformer - Wells T6 + Cat B - Transformer - East Omak NILLES C (47067) Bus Low Volts 0.81 0.95 NORTHWEST Douglas PUD C or D Loss of connection to Wells and East Omak Transformer causes low voltage.

Cat B - Transmission Circuit - Foster Creek-Bridgeport Bar-Brewster Line + Cat B - Transformer - East Omak NILLES C (47067) Bus Low Volts 0.89 0.95 NORTHWEST Douglas PUD C or D Loss of connection to Wells and East Omak Transformer causes low voltage.

Cat B - Transmission Circuit - Okanogan-Goose Lake Line + Cat B - Transformer - East Omak WELLS B2 (47102) -> WELLS (47099) CKT 1 at WELLS B2 Branch MVA 140.25 112 125.22 NORTHWEST Douglas PUD C or D Loss of two generation sources into Okanogan's system causes an overload.

Cat B - Transmission Circuit - Wells-Foster Creek Line + Cat B - Transformer - East Omak FSTR CR (47044) Bus Low Volts 0.5 0.95 NORTHWEST Douglas PUD C or D Loss of connection to Wells and East Omak Transformer causes low voltage.

Cat B - Transmission Circuit - Wells-Foster Creek Line + Cat B - Transformer - East Omak NILLES C (47067) Bus Low Volts 0.81 0.95 NORTHWEST Douglas PUD C or D Loss of connection to Wells and East Omak Transformer causes low voltage.

Cat D - 3 Transmission Circuits - Okanogan-Goose Lake, East Omak Transformer, East Omak-Foster Creek WELLS (47099) -> FSTR CR (47044) CKT 1 at FSTR CR Branch Amp 1316.52 1114.54 118.12 NORTHWEST Douglas PUD D Loss of all other generation sources into Okanogan's system causes an overload.

Cat D - 3 Transmission Circuits - Okanogan-Goose Lake, East Omak Transformer, East Omak-Foster Creek WELLS B2 (47102) -> WELLS (47099) CKT 1 at WELLS B2 Branch MVA 270.43 112 241.45 NORTHWEST Douglas PUD D Loss of all other generation sources into Okanogan's system causes an overload.

Cat D - 3 Transmission Circuits - Okanogan-Goose Lake, East Omak Transformer, East Omak-Foster Creek FSTR CR (47044) Bus Low Volts 0.72 0.95 NORTHWEST Douglas PUD D Loss of all other generation sources into Okanogan's system causes low voltage.

Cat D - 3 Transmission Circuits - Okanogan-Goose Lake, East Omak Transformer, East Omak-Foster Creek WELLS (47099) Bus Low Volts 0.84 0.95 NORTHWEST Douglas PUD D Loss of all other generation sources into Okanogan's system causes low voltage.

Cat D - Common ROW - Sickler-Schultz, Douglas-Rapids, RR-Columbia #1, RR-Maple Valley, RR-Columbia #2 DOUGLAS (47031) -> DOUGLAS (47029) CKT 1 at DOUGLAS Branch MVA 200 190 105.26 NORTHWEST Douglas PUD D Common corridor outage causes an overload.

Cat D - Common ROW - Sickler-Schultz, Douglas-Rapids, RR-Columbia #1, RR-Maple Valley, RR-Columbia #2, RR-Cascade DOUGLAS (47031) -> DOUGLAS (47029) CKT 1 at DOUGLAS Branch MVA 224.93 190 118.38 NORTHWEST Douglas PUD D Common corridor outage causes an overload.

Page 11: Douglas County PUD Douglas-Rapids 230-kV … 230-kV Transmission Line Supplemental Progress Report ... of 671.6 MVA. A new 230/115-kV transformer ... from the Initial Progress Report

Douglas County PUD

Rapids-Columbia 230-kV Transmission Line

Supplemental Progress Report

March 14, 2014

Updated Information from Initial Progress Report

1. Douglas County PUD is constructing a new 230-kV transmission line to connect its Rapids

Switchyard with BPA’s Columbia Substation. The conductor will be 1590 ACSR/TW and is

expected to have a Summer rating of 589.5 MVA, a Winter rating of 769.2 MVA, an Autumn

rating of 690.3 MVA, and a Spring rating of 671.2 MVA. The new 230-kV circuit breaker at

Rapids Switchyard will be rated for 3000 A of continuous current. The new 230-kV line

disconnect switch at Rapids Switchyard will be rated for 2000 A of continuous current.

2. The new transmission line is planned to be in operation in January, 2017.

3. The project is currently in the planning and design process. Alternative line routes are being

studied and considered and biological and cultural studies are currently underway. The project

is tentatively scheduled for completion in January, 2017.

4. The facility owner’s name is Douglas County PUD (DOPD). The contact for the project is:

Jerry Kyle

Assistant Manager – Distribution Engineering

1151 Valley Mall Parkway

East Wenatchee, WA 98802-4497

(509)881-2234

[email protected]

Updated Information from Comprehensive Progress Report

1. See above updated information from the Initial Progress Report.

2. There are no changes to the original one-line and geographic diagrams.

3. A model of the new facility is available in the WECC power flow and stability programs.

4. The Transfer Capability associated with the project will be equal to the System Operating Limit

(SOL), which is based on the Facility Ratings (MVA ratings at the applicable ambient

temperature) of all applicable Facilities. The WECC Comprehensive Project Coordination Review

process suggests that project sponsors can use Subregional Planning Groups to meet its

Page 12: Douglas County PUD Douglas-Rapids 230-kV … 230-kV Transmission Line Supplemental Progress Report ... of 671.6 MVA. A new 230/115-kV transformer ... from the Initial Progress Report

requirements (“a project sponsor may use TEPPC or a Subregional Planning Group to meet the

requirements of Project Coordination Review in lieu of forming an independent PCRG for their

project.” Douglas PUD is a member of and uses ColumbiaGrid to accomplish its subregional

planning requirements. The ColumbiaGrid planning process has open participation in its general

planning and study team meetings. The Rapids-Columbia project has been reviewed by and has

achieved consensus through this planning process, which included all of the transmission

owners that could be impacted by this project. Project reports are available from ColumbiaGrid

at http://www.columbiagrid.org. The requirements of Project Coordination Review for this

project have been met through the ColumbiaGrid Subregional Planning Group. The impact of

the Rapids-Columbia project on other systems and on existing transfer path ratings has been

studied in the ColumbiaGrid Northern Mid-C Study Group. Douglas PUD complies with all NERC

Reliability Standards and WECC Criteria. The Rapids-Columbia Line facility additions and

planned system operation are in conformance with NERC Standards and WECC System

Performance Criteria. The Rapids-Columbia project will not require obtaining an accepted

transmission path rating.

5. The proposed Transfer Capability rating is based on Douglas PUD’s System Operating Limits.

Douglas PUD’s System Operating Limits are based solely on its Facility Ratings, which, for

transmission circuits and transformers, are determined by ambient temperature conditions.

6. See studies conducted in ColumbiaGrid Northern Mid-C Study Team and Northern Mid-C Joint

Operational Study Team for operating conditions that allow the project to operate within the

guidelines defined in the NERC Reliability Standards and WECC Criteria.

7. See studies conducted in ColumbiaGrid Northern Mid-C Study Team and Northern Mid-C Joint

Operational Study Team for potential impacts to transmission facilities including non-

simultaneous ratings and simultaneous path interactions.

8. To demonstrate Douglas PUD’s compliance with NERC Reliability Standards and WECC Criteria,

the following power flow and stability cases were run by ColumbiaGrid:

a. Summer, 2012

b. Summer, 2013

c. Summer, 2014

d. Summer, 2015

e. Summer, 2019

f. Winter, 2019

Page 13: Douglas County PUD Douglas-Rapids 230-kV … 230-kV Transmission Line Supplemental Progress Report ... of 671.6 MVA. A new 230/115-kV transformer ... from the Initial Progress Report

To demonstrate Douglas PUD’s compliance with NERC Reliability Standards and WECC Criteria,

the following power flow and stability cases were run by Douglas PUD:

a. Heavy Summer, 2015

b. Heavy Summer, 2019

c. Heavy Winter, 2019

d. Light Autumn, 2022

e. Heavy Summer, 2023

f. Heavy Winter, 2024

9. In addition to the data provided in the Comprehensive Study Report, See Appendix A for power

flow outage results that demonstrate Douglas PUD’s compliance with NERC Reliability Standards

and WECC Criteria.

10. See Appendix B for project milestone schedule that covers the current period through initial

operation of the project.

Page 14: Douglas County PUD Douglas-Rapids 230-kV … 230-kV Transmission Line Supplemental Progress Report ... of 671.6 MVA. A new 230/115-kV transformer ... from the Initial Progress Report

Appendix A

Power Flow Outage Results

(attached)

Page 15: Douglas County PUD Douglas-Rapids 230-kV … 230-kV Transmission Line Supplemental Progress Report ... of 671.6 MVA. A new 230/115-kV transformer ... from the Initial Progress Report

2019 Heavy Summer Results

Contingency Name Element Category Value Limit Percent Area Name Assoc. Owner Names NERC Category Comment

Cat B - Transformer - Wells T6 + Cat B - Transmission Circuit - Wells-Douglas Line 1 WELLS B2 (47102) -> DOUGLAS (47031) CKT 1 at WELLS B2 Branch Amp 1759.81 1749.62 100.58 NORTHWEST Douglas PUD C or D Loss of Wells-Foster Creek connection and one of the Wells-Douglas Lines overloads the other Wells-Douglas Line.

Cat B - Transformer - Wells T6 + Cat B - Transmission Circuit - Wells-Douglas Line 2 WELLS B1 (47100) -> DOUGLAS (47031) CKT 1 at WELLS B1 Branch Amp 1759.71 1749.62 100.58 NORTHWEST Douglas PUD C or D Loss of Wells-Foster Creek connection and one of the Wells-Douglas Lines overloads the other Wells-Douglas Line.

Cat B - Transmission Circuit - Wells-Douglas Line 1 + Cat B - Transformer - Wells T6 WELLS B2 (47102) -> DOUGLAS (47031) CKT 1 at WELLS B2 Branch Amp 1759.81 1749.62 100.58 NORTHWEST Douglas PUD C or D Loss of Wells-Foster Creek connection and one of the Wells-Douglas Lines overloads the other Wells-Douglas Line.

Cat B - Transmission Circuit - Wells-Douglas Line 1 + Cat B - Transmission Circuit - Wells-Foster Creek Line WELLS B2 (47102) -> DOUGLAS (47031) CKT 1 at WELLS B2 Branch Amp 1759.81 1749.62 100.58 NORTHWEST Douglas PUD C or D Loss of Wells-Foster Creek connection and one of the Wells-Douglas Lines overloads the other Wells-Douglas Line.

Cat B - Transmission Circuit - Wells-Douglas Line 2 + Cat B - Transformer - Wells T6 WELLS B1 (47100) -> DOUGLAS (47031) CKT 1 at WELLS B1 Branch Amp 1759.71 1749.62 100.58 NORTHWEST Douglas PUD C or D Loss of Wells-Foster Creek connection and one of the Wells-Douglas Lines overloads the other Wells-Douglas Line.

Cat B - Transmission Circuit - Wells-Douglas Line 2 + Cat B - Transmission Circuit - Wells-Foster Creek Line WELLS B1 (47100) -> DOUGLAS (47031) CKT 1 at WELLS B1 Branch Amp 1759.71 1749.62 100.58 NORTHWEST Douglas PUD C or D Loss of Wells-Foster Creek connection and one of the Wells-Douglas Lines overloads the other Wells-Douglas Line.

Cat B - Transmission Circuit - Wells-Foster Creek Line + Cat B - Transmission Circuit - Wells-Douglas Line 1 WELLS B2 (47102) -> DOUGLAS (47031) CKT 1 at WELLS B2 Branch Amp 1759.81 1749.62 100.58 NORTHWEST Douglas PUD C or D Loss of Wells-Foster Creek connection and one of the Wells-Douglas Lines overloads the other Wells-Douglas Line.

Cat B - Transmission Circuit - Wells-Foster Creek Line + Cat B - Transmission Circuit - Wells-Douglas Line 2 WELLS B1 (47100) -> DOUGLAS (47031) CKT 1 at WELLS B1 Branch Amp 1759.71 1749.62 100.58 NORTHWEST Douglas PUD C or D Loss of Wells-Foster Creek connection and one of the Wells-Douglas Lines overloads the other Wells-Douglas Line.

Page 16: Douglas County PUD Douglas-Rapids 230-kV … 230-kV Transmission Line Supplemental Progress Report ... of 671.6 MVA. A new 230/115-kV transformer ... from the Initial Progress Report

2019 Heavy Winter Results

Contingency Name Element Category Value Limit Percent Area Name Assoc. Owner Names NERC Category Comment

Cat B - Transformer - East Omak + Cat B - Transformer - Wells T6 FSTR CR (47044) Bus Low Volts 0.53 0.95 NORTHWEST Douglas PUD C or D Loss of connection to Wells and East Omak Transformer causes low voltage.

Cat B - Transformer - East Omak + Cat B - Transformer - Wells T6 NILLES C (47067) Bus Low Volts 0.82 0.95 NORTHWEST Douglas PUD C or D Loss of connection to Wells and East Omak Transformer causes low voltage.

Cat B - Transformer - East Omak + Cat B - Transmission Circuit - Foster Creek-Bridgeport Bar-Brewster Line NILLES C (47067) Bus Low Volts 0.89 0.95 NORTHWEST Douglas PUD C or D Loss of connection to Wells and East Omak Transformer causes low voltage.

Cat B - Transformer - East Omak + Cat B - Transmission Circuit - Okanogan-Goose Lake Line WELLS B2 (47102) -> WELLS (47099) CKT 1 at WELLS B2 Branch MVA 135.61 112 121.08 NORTHWEST Douglas PUD C or D Loss of two generation sources into Okanogan's system causes an overload.

Cat B - Transformer - East Omak + Cat B - Transmission Circuit - Wells-Foster Creek Line FSTR CR (47044) Bus Low Volts 0.53 0.95 NORTHWEST Douglas PUD C or D Loss of connection to Wells and East Omak Transformer causes low voltage.

Cat B - Transformer - East Omak + Cat B - Transmission Circuit - Wells-Foster Creek Line NILLES C (47067) Bus Low Volts 0.82 0.95 NORTHWEST Douglas PUD C or D Loss of connection to Wells and East Omak Transformer causes low voltage.

Cat B - Transformer - Wells T6 + Cat B - Transformer - East Omak FSTR CR (47044) Bus Low Volts 0.53 0.95 NORTHWEST Douglas PUD C or D Loss of connection to Wells and East Omak Transformer causes low voltage.

Cat B - Transformer - Wells T6 + Cat B - Transformer - East Omak NILLES C (47067) Bus Low Volts 0.82 0.95 NORTHWEST Douglas PUD C or D Loss of connection to Wells and East Omak Transformer causes low voltage.

Cat B - Transmission Circuit - Foster Creek-Bridgeport Bar-Brewster Line + Cat B - Transformer - East Omak NILLES C (47067) Bus Low Volts 0.89 0.95 NORTHWEST Douglas PUD C or D Loss of connection to Wells and East Omak Transformer causes low voltage.

Cat B - Transmission Circuit - Okanogan-Goose Lake Line + Cat B - Transformer - East Omak WELLS B2 (47102) -> WELLS (47099) CKT 1 at WELLS B2 Branch MVA 135.59 112 121.07 NORTHWEST Douglas PUD C or D Loss of two generation sources into Okanogan's system causes an overload.

Cat B - Transmission Circuit - Wells-Foster Creek Line + Cat B - Transformer - East Omak FSTR CR (47044) Bus Low Volts 0.53 0.95 NORTHWEST Douglas PUD C or D Loss of connection to Wells and East Omak Transformer causes low voltage.

Cat B - Transmission Circuit - Wells-Foster Creek Line + Cat B - Transformer - East Omak NILLES C (47067) Bus Low Volts 0.82 0.95 NORTHWEST Douglas PUD C or D Loss of connection to Wells and East Omak Transformer causes low voltage.

Cat D - 3 Transmission Circuits - Okanogan-Goose Lake, East Omak Transformer, East Omak-Foster Creek WELLS (47099) -> FSTR CR (47044) CKT 1 at FSTR CR Branch Amp 1233.97 1114.54 110.72 NORTHWEST Douglas PUD D Loss of all other generation sources into Okanogan's system causes an overload.

Cat D - 3 Transmission Circuits - Okanogan-Goose Lake, East Omak Transformer, East Omak-Foster Creek WELLS B2 (47102) -> WELLS (47099) CKT 1 at WELLS B2 Branch MVA 254.98 112 227.66 NORTHWEST Douglas PUD D Loss of all other generation sources into Okanogan's system causes an overload.

Cat D - 3 Transmission Circuits - Okanogan-Goose Lake, East Omak Transformer, East Omak-Foster Creek FSTR CR (47044) Bus Low Volts 0.76 0.95 NORTHWEST Douglas PUD D Loss of all other generation sources into Okanogan's system causes low voltage.

Cat D - 3 Transmission Circuits - Okanogan-Goose Lake, East Omak Transformer, East Omak-Foster Creek WELLS (47099) Bus Low Volts 0.87 0.95 NORTHWEST Douglas PUD D Loss of all other generation sources into Okanogan's system causes low voltage.

Cat D - Common ROW - Sickler-Schultz, Douglas-Rapids, RR-Columbia #1, RR-Maple Valley, RR-Columbia #2 DOUGLAS (47031) -> DOUGLAS (47029) CKT 1 at DOUGLAS Branch MVA 193.05 190 101.61 NORTHWEST Douglas PUD D Common corridor outage causes an overload.

Cat D - Common ROW - Sickler-Schultz, Douglas-Rapids, RR-Columbia #1, RR-Maple Valley, RR-Columbia #2, RR-Cascade DOUGLAS (47031) -> DOUGLAS (47029) CKT 1 at DOUGLAS Branch MVA 218.32 190 114.91 NORTHWEST Douglas PUD D Common corridor outage causes an overload.

Page 17: Douglas County PUD Douglas-Rapids 230-kV … 230-kV Transmission Line Supplemental Progress Report ... of 671.6 MVA. A new 230/115-kV transformer ... from the Initial Progress Report

2022 Light Autumn Results

Contingency Name Element Category Value Limit Percent Area Name Assoc. Owner Names NERC Category Comment

Cat B - Transmission Circuit - Wells-Douglas Line 1 + Cat B - Transmission Circuit - Wells-Douglas Line 2 WELLS B2 (47102) -> WELLS (47099) CKT 1 at WELLS Branch MVA 141.82 112 126.63 NORTHWEST Douglas PUD C or D Modeling Error. Actual gen reduction scheme at Wells would drop to only one unit in service, thus eliminating this violation.

Cat B - Transmission Circuit - Wells-Douglas Line 2 + Cat B - Transmission Circuit - Wells-Douglas Line 1 WELLS B2 (47102) -> WELLS (47099) CKT 1 at WELLS Branch MVA 141.82 112 126.63 NORTHWEST Douglas PUD C or D Modeling Error. Actual gen reduction scheme at Wells would drop to only one unit in service, thus eliminating this violation.

Cat D - Common ROW - Wells-Douglas Lines WELLS B2 (47102) -> WELLS (47099) CKT 1 at WELLS Branch MVA 141.82 112 126.63 NORTHWEST Douglas PUD D Modeling Error. Actual gen reduction scheme at Wells would drop to only one unit in service, thus eliminating this violation.

Cat D - Switching Station - Douglas 230 WELLS B2 (47102) -> WELLS (47099) CKT 1 at WELLS Branch MVA 141.82 112 126.62 NORTHWEST Douglas PUD D Modeling Error. Actual gen reduction scheme at Wells would drop to only one unit in service, thus eliminating this violation.

Page 18: Douglas County PUD Douglas-Rapids 230-kV … 230-kV Transmission Line Supplemental Progress Report ... of 671.6 MVA. A new 230/115-kV transformer ... from the Initial Progress Report

2023 Heavy Summer Results

Contingency Name Element Category Value Limit Percent Area Name Assoc. Owner Names NERC Category Comment

Cat B - Transformer - Wells T6 + Cat B - Transmission Circuit - Wells-Douglas Line 1 WELLS B2 (47102) -> DOUGLAS (47031) CKT 1 at WELLS B2 Branch Amp 1759.82 1749.62 100.58 NORTHWEST Douglas PUD C or D Loss of Wells-Foster Creek connection and one of the Wells-Douglas Lines overloads the other Wells-Douglas Line.

Cat B - Transformer - Wells T6 + Cat B - Transmission Circuit - Wells-Douglas Line 2 WELLS B1 (47100) -> DOUGLAS (47031) CKT 1 at WELLS B1 Branch Amp 1759.72 1749.62 100.58 NORTHWEST Douglas PUD C or D Loss of Wells-Foster Creek connection and one of the Wells-Douglas Lines overloads the other Wells-Douglas Line.

Cat B - Transmission Circuit - Wells-Douglas Line 1 + Cat B - Transformer - Wells T6 WELLS B2 (47102) -> DOUGLAS (47031) CKT 1 at WELLS B2 Branch Amp 1759.82 1749.62 100.58 NORTHWEST Douglas PUD C or D Loss of Wells-Foster Creek connection and one of the Wells-Douglas Lines overloads the other Wells-Douglas Line.

Cat B - Transmission Circuit - Wells-Douglas Line 1 + Cat B - Transmission Circuit - Wells-Foster Creek Line WELLS B2 (47102) -> DOUGLAS (47031) CKT 1 at WELLS B2 Branch Amp 1759.82 1749.62 100.58 NORTHWEST Douglas PUD C or D Loss of Wells-Foster Creek connection and one of the Wells-Douglas Lines overloads the other Wells-Douglas Line.

Cat B - Transmission Circuit - Wells-Douglas Line 2 + Cat B - Transformer - Wells T6 WELLS B1 (47100) -> DOUGLAS (47031) CKT 1 at WELLS B1 Branch Amp 1759.72 1749.62 100.58 NORTHWEST Douglas PUD C or D Loss of Wells-Foster Creek connection and one of the Wells-Douglas Lines overloads the other Wells-Douglas Line.

Cat B - Transmission Circuit - Wells-Douglas Line 2 + Cat B - Transmission Circuit - Wells-Foster Creek Line WELLS B1 (47100) -> DOUGLAS (47031) CKT 1 at WELLS B1 Branch Amp 1759.72 1749.62 100.58 NORTHWEST Douglas PUD C or D Loss of Wells-Foster Creek connection and one of the Wells-Douglas Lines overloads the other Wells-Douglas Line.

Cat B - Transmission Circuit - Wells-Foster Creek Line + Cat B - Transmission Circuit - Wells-Douglas Line 1 WELLS B2 (47102) -> DOUGLAS (47031) CKT 1 at WELLS B2 Branch Amp 1759.82 1749.62 100.58 NORTHWEST Douglas PUD C or D Loss of Wells-Foster Creek connection and one of the Wells-Douglas Lines overloads the other Wells-Douglas Line.

Cat B - Transmission Circuit - Wells-Foster Creek Line + Cat B - Transmission Circuit - Wells-Douglas Line 2 WELLS B1 (47100) -> DOUGLAS (47031) CKT 1 at WELLS B1 Branch Amp 1759.72 1749.62 100.58 NORTHWEST Douglas PUD C or D Loss of Wells-Foster Creek connection and one of the Wells-Douglas Lines overloads the other Wells-Douglas Line.

Page 19: Douglas County PUD Douglas-Rapids 230-kV … 230-kV Transmission Line Supplemental Progress Report ... of 671.6 MVA. A new 230/115-kV transformer ... from the Initial Progress Report

2024 Heavy Winter Results

Contingency Name Element Category Value Limit Percent Area Name Assoc. Owner Names NERC Category Comment

Cat B - Transformer - East Omak + Cat B - Transformer - Wells T6 FSTR CR (47044) Bus Low Volts 0.5 0.95 NORTHWEST Douglas PUD C or D Loss of connection to Wells and East Omak Transformer causes low voltage.

Cat B - Transformer - East Omak + Cat B - Transformer - Wells T6 NILLES C (47067) Bus Low Volts 0.81 0.95 NORTHWEST Douglas PUD C or D Loss of connection to Wells and East Omak Transformer causes low voltage.

Cat B - Transformer - East Omak + Cat B - Transmission Circuit - Foster Creek-Bridgeport Bar-Brewster Line NILLES C (47067) Bus Low Volts 0.89 0.95 NORTHWEST Douglas PUD C or D Loss of connection to Wells and East Omak Transformer causes low voltage.

Cat B - Transformer - East Omak + Cat B - Transmission Circuit - Okanogan-Goose Lake Line WELLS B2 (47102) -> WELLS (47099) CKT 1 at WELLS B2 Branch MVA 140.26 112 125.23 NORTHWEST Douglas PUD C or D Loss of two generation sources into Okanogan's system causes an overload.

Cat B - Transformer - East Omak + Cat B - Transmission Circuit - Wells-Foster Creek Line FSTR CR (47044) Bus Low Volts 0.5 0.95 NORTHWEST Douglas PUD C or D Loss of connection to Wells and East Omak Transformer causes low voltage.

Cat B - Transformer - East Omak + Cat B - Transmission Circuit - Wells-Foster Creek Line NILLES C (47067) Bus Low Volts 0.81 0.95 NORTHWEST Douglas PUD C or D Loss of connection to Wells and East Omak Transformer causes low voltage.

Cat B - Transformer - Wells T6 + Cat B - Transformer - East Omak FSTR CR (47044) Bus Low Volts 0.5 0.95 NORTHWEST Douglas PUD C or D Loss of connection to Wells and East Omak Transformer causes low voltage.

Cat B - Transformer - Wells T6 + Cat B - Transformer - East Omak NILLES C (47067) Bus Low Volts 0.81 0.95 NORTHWEST Douglas PUD C or D Loss of connection to Wells and East Omak Transformer causes low voltage.

Cat B - Transmission Circuit - Foster Creek-Bridgeport Bar-Brewster Line + Cat B - Transformer - East Omak NILLES C (47067) Bus Low Volts 0.89 0.95 NORTHWEST Douglas PUD C or D Loss of connection to Wells and East Omak Transformer causes low voltage.

Cat B - Transmission Circuit - Okanogan-Goose Lake Line + Cat B - Transformer - East Omak WELLS B2 (47102) -> WELLS (47099) CKT 1 at WELLS B2 Branch MVA 140.25 112 125.22 NORTHWEST Douglas PUD C or D Loss of two generation sources into Okanogan's system causes an overload.

Cat B - Transmission Circuit - Wells-Foster Creek Line + Cat B - Transformer - East Omak FSTR CR (47044) Bus Low Volts 0.5 0.95 NORTHWEST Douglas PUD C or D Loss of connection to Wells and East Omak Transformer causes low voltage.

Cat B - Transmission Circuit - Wells-Foster Creek Line + Cat B - Transformer - East Omak NILLES C (47067) Bus Low Volts 0.81 0.95 NORTHWEST Douglas PUD C or D Loss of connection to Wells and East Omak Transformer causes low voltage.

Cat D - 3 Transmission Circuits - Okanogan-Goose Lake, East Omak Transformer, East Omak-Foster Creek WELLS (47099) -> FSTR CR (47044) CKT 1 at FSTR CR Branch Amp 1316.52 1114.54 118.12 NORTHWEST Douglas PUD D Loss of all other generation sources into Okanogan's system causes an overload.

Cat D - 3 Transmission Circuits - Okanogan-Goose Lake, East Omak Transformer, East Omak-Foster Creek WELLS B2 (47102) -> WELLS (47099) CKT 1 at WELLS B2 Branch MVA 270.43 112 241.45 NORTHWEST Douglas PUD D Loss of all other generation sources into Okanogan's system causes an overload.

Cat D - 3 Transmission Circuits - Okanogan-Goose Lake, East Omak Transformer, East Omak-Foster Creek FSTR CR (47044) Bus Low Volts 0.72 0.95 NORTHWEST Douglas PUD D Loss of all other generation sources into Okanogan's system causes low voltage.

Cat D - 3 Transmission Circuits - Okanogan-Goose Lake, East Omak Transformer, East Omak-Foster Creek WELLS (47099) Bus Low Volts 0.84 0.95 NORTHWEST Douglas PUD D Loss of all other generation sources into Okanogan's system causes low voltage.

Cat D - Common ROW - Sickler-Schultz, Douglas-Rapids, RR-Columbia #1, RR-Maple Valley, RR-Columbia #2 DOUGLAS (47031) -> DOUGLAS (47029) CKT 1 at DOUGLAS Branch MVA 200 190 105.26 NORTHWEST Douglas PUD D Common corridor outage causes an overload.

Cat D - Common ROW - Sickler-Schultz, Douglas-Rapids, RR-Columbia #1, RR-Maple Valley, RR-Columbia #2, RR-Cascade DOUGLAS (47031) -> DOUGLAS (47029) CKT 1 at DOUGLAS Branch MVA 224.93 190 118.38 NORTHWEST Douglas PUD D Common corridor outage causes an overload.

Page 20: Douglas County PUD Douglas-Rapids 230-kV … 230-kV Transmission Line Supplemental Progress Report ... of 671.6 MVA. A new 230/115-kV transformer ... from the Initial Progress Report

Appendix B

Project Milestone Schedule

Page 21: Douglas County PUD Douglas-Rapids 230-kV … 230-kV Transmission Line Supplemental Progress Report ... of 671.6 MVA. A new 230/115-kV transformer ... from the Initial Progress Report

ID Task

Mode

Task Name Duration Start Finish

1

2 P2 Route Selection 30 days Tue 3/5/13 Mon 4/15/13

3 P3 Permitting Support 671 days Tue 3/5/13 Tue 9/29/15

4 P4 Preliminary Design 70 days Wed 6/25/14 Tue 9/30/14

5 30% Milestone 70 days Wed 6/25/14 Tue 9/30/14

6 P5 Geotechnical 80 days Wed 10/1/14 Tue 1/20/15

7 P6 Detailed Design 240 days Wed 1/21/15 Tue 12/22/15

8 60% Milestone 110 days Wed 1/21/15 Tue 6/23/15

9 90% Milestone 110 days Wed 6/24/15 Tue 11/24/15

10 100% Milestone 20 days Wed 11/25/15Tue 12/22/15

11 P7 Utility Coordination 1021 days Tue 3/5/13 Tue 1/31/17

12 P8 Construction

Support

160 days Wed 6/22/16 Tue 1/31/17

13

14

15

16

17

18

19 NEPA Process 411 days Tue 3/5/13 Tue 9/30/14

20 Preliminary EA 0 days Wed 1/15/14 Wed 1/15/14

21 Section 7 0 days Mon 6/2/14 Mon 6/2/14

22 Section 106 0 days Tue 7/1/14 Tue 7/1/14

23 Final EA Review 0 days Sat 8/30/14 Sat 8/30/14

24 BPA Decision 0 days Tue 9/30/14 Tue 9/30/14

25

26 Douglas PUD Tasks 260 days Wed 10/1/14 Tue 9/29/15

27 Easement

Descriptions

60 days Wed 10/1/14 Tue 12/23/14

28 Property Appraisals 60 days Wed 12/24/14Tue 3/17/15

29 Property Acquisition 120 days Wed 3/18/15 Tue 9/1/15

30 SEPA 260 days Wed 10/1/14 Tue 9/29/15

31 Shoreline Permits 260 days Wed 10/1/14 Tue 9/29/15

32 Other Permits 260 days Wed 10/1/14 Tue 9/29/15

1/15

6/2

7/1

8/30

9/30

FebMarAprMayJun Jul AugSep OctNovDec Jan FebMarAprMayJun Jul AugSep OctNovDec Jan FebMarAprMayJun Jul AugSep OctNovDec Jan FebMarAprMayJun Jul AugSep OctNovDec Jan Feb

2013 2014 2015 2016 2017

Task

Split

Milestone

Summary

Project Summary

External Tasks

External Milestone

Inactive Task

Inactive Milestone

Inactive Summary

Manual Task

Duration-only

Manual Summary Rollup

Manual Summary

Start-only

Finish-only

Deadline

Progress

Page 1

Project: RC

Date: Thu 6/6/13