doors part ii
TRANSCRIPT
Flad Architects Page 1 of 2 Flad Code Forum Notes : 21 July 2016
Flad Code Forum Notes 21 July 2016 1. Code Forums
a. Notes of past code forums are posted at : i. Flad Home Page / Resources / Codes / Forums / Year / Date of Forum.
b. This Code Forum : Doors : An Open and Shut Case (Part II) c. Additional information is contained in attached power point slides : PP-pages.
Doors : An Open and Shut Case (Part II) – Refer to PP-01 through PP-65 2. Fire Doors (FD) : PP-03 through PP-35
a. Fire-Resistance Ratings (FRR) : Assemblies + Systems + Opening Protectives i. Fire Doors = Opening Protectives
b. Fire Walls + Fire Barriers + Fire Partitions = FRR Assemblies i. All openings in FRR Assemblies must have protected openings (e.g. Fire Doors)
c. “Opening Protection” References d. Section 716 Opening Protectives
i. Fire Doors/Shutters/Windows in FRR Assemblies (1) Interior/Exterior walls required to be rated based on being load bearing are NOT
required to have protective openings. ii. Testing Standards
(1) Opening Protectives : NFPA 252/257 (2) Assemblies + Systems : ASTM E119/UL 263
iii. Classification Marks : fire door labels e. Use correct annotation
i. “1-Hour Wall” is incomplete A what is the wall’s purpose? ii. Wall’s purpose determines the FRR of the door
(1) 1FB (1-Hour Fire Barrier) requires a 0.75 hr door (2) 1FB in a Stairway requires a 1.0 hr door
iii. Why are FRR of doors < FRR of walls? (1) Combustible materials are kept away from these openings
f. IBC Table 716.5 i. Opening Fire Protection Assemblies, Ratings and Marking
(1) Fire-Resistance Rating (FRR) (a) Building element, component or assembly (b) ASTM E 119
(2) Fire Protection Rating (FPR) (a) Opening Protectives (b) NFPA 252 or UL 10C
g. Fire Door Types i. Side-hinged or pivoted swinging doors ii. Swinging elevator iii. Bottom and side-hinged chute intake doors iv. Top-hinged chute discharge doors
3. Smoke Doors (SD) : PP-36 through PP-45 a. No Hose Stream for SDs required in Corridors and Smoke Barriers (SB) b. No rating for SDs in Corridors in I-2 (Hospitals) c. Types of SD
i. Type 1 : Limit the transfer of smoke ii. Type 2 : Doors in smoke partitions iii. Type 3 : Doors in smoke barriers
Flad Architects Page 2 of 2 Flad Code Forum Notes : 21 July 2016
iv. Type 4 : Fire door assemblies in corridors and smoke barriers v. Type 5 : Doors in exit enclosures and exit passageways
4. Hardware for FD : PP-46 through PP-60 a. Self-closing
i. Doors that, when opened and released, return to the closed position. b. Automatic-closing
i. A device that causes the door or window to close when activated by a fusible link or detector.
c. Smoke-activated doors i. (11) conditions where doors must be automatic-closing by smoke detector actuation
d. Latching i. FDs require active latch bolt that will secure the door when it is closed.
5. Resources : PP-61 through PP-63 a. iDigHardware.com
T:\twyatt\Code\Code Forums\2016 0721\2016 0721 Code Forum Notes.docx
F L A D C O D E F O R U M
D O O R SAn Open and Shut Case
(Part II)
07/21/2016 Flad Code Forum : Doors (Part II) 1
O U T L I N E
PART ONE
I. References
II. Types of Doors
III. Size of Doors
IV. Elevation & Arrangement
V. Maneuvering
PART TWO
I. Fire Doors
I. Opng Protection
II. Testing
III. FRR Walls
II. Smoke Doors
III. Hardware (FD)
07/21/2016 Flad Code Forum : Doors (Part II) 2
Fire-Resistance Ratings (FRR)
• Assemblies– Beams, floors, roofs, columns, and walls and
partitions.
• Systems– Construction joint systems, through-penetration
firestop systems, electrical circuit protective systems and duct assemblies.
• Opening Protectives– Dampers, fire doors, glazing and related equipment.
– Used to protect openings in fire-resistance-rated assemblies.
07/21/2016 Flad Code Forum : Doors (Part II) 4
FRR Assemblies
• FIRE WALL. A fire-resistance-rated wall having
protected openings, which restricts the spread of
fire …
• FIRE BARRIER. A fire-resistance-rated wall
assembly of materials designed to restrict the
spread of fire in which continuity is maintained.
• FIRE PARTITION. A vertical assembly of materials
designed to restrict the spread of fire in which
openings are protected.
07/21/2016 Flad Code Forum : Doors (Part II) 5
“Opening” Definitions
• IBC does not define “Opening”
– “Opening” = (813) references in IBC
– “Opening Protection” = (85) references in IBC
• “The act or an instance of becoming open or being made to open.”
• “An open space serving as a passage or gap.”
• “An unfilled job or position; a vacancy.”
• “A breach or aperture.” = Doors & Windows
07/21/2016 Flad Code Forum : Doors (Part II) 6
“Opening Protection” References
• EXIT PASSAGEWAY. An exit component that is separated from other interior spaces of a building or structure by fire-resistance-rated construction and opening protectives …
• FIRE PROTECTION RATING. The period of time that an opening protective will maintain the ability to confine a fire as determined by tests prescribed in Section 715. Ratings are stated in hours or minutes.
• SELF-CLOSING. As applied to a fire door or other opening protective, means equipped with an device that will ensure closing after having been opened.
07/21/2016 Flad Code Forum : Doors (Part II) 7
“Opening Protection” References
SECTION 909 SMOKE CONTROL SYSTEMS
909.5 Smoke barrier construction
909.5.2 Opening protection.
Openings in smoke barriers shall be protected by automatic-closing devices actuated by the
required controls for the mechanical smoke control system. Door openings shall be protected by
fire door assemblies complying with Section 716.5.3.
Exceptions:
3. In Group I-2, where such doors are installed across corridors, a pair of opposite-swinging doors
without a center mullion shall be installed having vision panels with fire protection-rated glazing
materials in fire protection-rated frames, the area of which shall not exceed that tested. The
doors shall be close-fitting within operational tolerances and shall not have undercuts, louvers or
grilles. The doors shall have head and jamb stops, astragals or rabbets at meeting edges and shall
be automatic-closing by smoke detection in accordance with Section 716.5.9.3. Positive-latching
devices are not required.
07/21/2016 Flad Code Forum : Doors (Part II) 9
“Opening Protection” References
1022.4 Openings.
Interior exit stairway and ramp opening
protectives shall be in accordance with the
requirements of Section 716.
3002.1.1 Opening protectives.
Openings in hoistway enclosures shall be
protected as required in Chapter 7.
07/21/2016 Flad Code Forum : Doors (Part II) 10
716 Opening Protectives
• 716.5 Fire door and shutter assemblies
• 716.6 Fire-protection-rated glazing
– “Fire windows” = Assembly
– Includes glass-block assemblies
• Fire Doors/Shutters/Windows
– Installed in Fire-Resistance-Rated (FRR) assemblies :
• Fire Walls (FW), Fire Barriers (FB) & Fire Partitions (FP)
• Exterior Walls (EW) required to be rated
– NOT for rated EWs because of load-bearing requirements
07/21/2016 Flad Code Forum : Doors (Part II) 11
716 Opening Protectives
• Fire Doors/Shutters/Glazing
– NFPA 252
– NFPA 257
– UL-10A
– UL-14B
– UL-14C
• FRR Bldg Construction
– ASTM E 119
– UL 263
07/21/2016 Flad Code Forum : Doors (Part II) 12
Fire Doors/Shutters/Glazing
• NFPA 252– Standard Methods of Fire Tests of Door Assemblies
• NFPA 257– Standard on Fire Test for Window and Glass Block
Assemblies
• UL-10A– Standard for Tin-Clad Fire Doors
• UL-14B– Standard for Sliding Hardware for Standard,
Horizontally Mounted Tin-Clad Fire Doors
• UL-14C– Standard for Swinging Hardware for Standard Tin-
Clad Fire Doors Mounted Singly and in Pairs
07/21/2016 Flad Code Forum : Doors (Part II) 13
ASTM E119
Fire Tests of Building Constructions• Widely accepted test standard.
– Mock up of the entire assembly is built against the gas furnace and burned.
– Assembly must prevent the passage of open flames and heated gases into the protected side for the predetermined time.
07/21/2016 Flad Code Forum : Doors (Part II) 14
• What it does– Benchmark to measure the fire resistance
of building assemblies
• What it does NOT do– Does not predict fire performance of
structural connections
– Does not predict durability of fire-resistance materials
UL 263Fire Tests of Building Construction and Materials
• Fire-rating certifications based upon test method and acceptance criteria.
• Ratings are expressed in minutes or hours – 20/45/60/90/120/180 minutes
• Applicable to – Floor-ceilings
– Roof-ceilings
– Beams
– Columns
– Walls and partitions
07/21/2016 Flad Code Forum : Doors (Part II) 15
UL 263Fire Tests of Building Construction and Materials
• Access-type Fire Doors (GSOT)
• Bullet-resisting-type Fire Doors (GSOX)
• Chute-type Fire Doors (GSPR)
• Curtain-type Fire Doors (GSQX)
• Dumbwaiter-type Fire Doors (GSRV)
• Freight-elevator-type Fire Doors (GSST)
• Freight-elevator-type Fire Door Retrofit Parts (GSSZ)
• Passenger-elevator-type Fire Doors (GSUX)
• Rolling Steel Fire Doors (GSVV)
• Service-counter-type Fire Doors (GSWT)
• Sliding-type Fire Doors (GSXV)
• Special-purpose Fire Doors (GSXZ)
• Swinging-type Fire Doors (GSYX)
• Finishers of Fire Doors (GSZC)
• Swinging-type Fire Door Retrofit Parts (GSZG)
• Swinging-type Fire Doors, Positive-pressure Tested (GSZN)
07/21/2016 Flad Code Forum : Doors (Part II) 16
UL 263Fire Tests of Building Construction and Materials
• Access-type Fire Doors (GSOT)– single-swinging steel doors with frames
• Rolling Steel Fire Doors (GSVV)– Interlocking galvanized or stainless steel slats, bottom bar, wall guides, barrel assembly,
automatic-release device, governor, and counterbalance mechanism
• Swinging-type Fire Doors (GSYX)– doors swinging in pairs in the same direction and double-egress doors swinging in opposite
directions
• Swinging-type Fire Doors, Positive-pressure Tested (GSZN)– Category A Doors
• A fire door that does not require the addition of other components, such as edge seals, to comply with positive-pressure requirements.
• It also includes doors that have been prepared with edge seals in the manufacturing process.
– Category B Doors• A fire door that requires the addition of an edge seal to comply with the positive-pressure
requirements.
• Sliding-type Fire Doors (GSXV)– Composite, hollow-metal, metal-clad, sheet-metal and tin-clad
07/21/2016 Flad Code Forum : Doors (Part II) 17
UL 263 - Classification Marks
3 h ratings (180m)"Fire Door for Opening in Fire Wall“
"A"
1-1/2 h (90m) and 1 h (60m)"Fire Door for Opening in Vertical Shaft“
"B"
3/4 h (45m)“Corridor and Room Partition“
"C"
1-1/2 h (90m)"Fire Door for Opening in Exterior Wall,“
"Fire Shutter for Opening in Exterior Wall“
"D"
3/4 h (45m)"Fire Door for Opening to Exterior Fire Escape“
"E"
07/21/2016 Flad Code Forum : Doors (Part II) 18
UL 263 - Classification Marks
• Temperature-Rise Rating
– Temperature rise developed on the unexposed surface of the door after the first 30 min of fire exposure.
• 250°F, 450°F or 650°F
– Doors with glass lights >100 sq in. are not eligible for a temperature-rise rating.
07/21/2016 Flad Code Forum : Doors (Part II) 19
Labeling Fire Doors
• Why?– IBC 716.5.7 Labeled protective assemblies.
• Fire door assemblies shall be labeled by an approved agency. The labels shall comply with NFPA 80, and shall be permanently affixed to the door or frame.
• Approved agency : established and recognized agency regularly engaged in conducting tests or furnishing inspection services when such agency has been approved."
• Who?– Initial : Manufacturer
– Field (Re-label) : Accredited agent
• Frames– Required to have a label
– Fire protection rating not required
07/21/2016 Flad Code Forum : Doors (Part II) 20
UL : Fire Door Assemblies and Fire
Window Assemblies
Opening Protective No. AA-#-### where :
• "AA" = Type of opening protective
• "#" = Wall type in which the opening
protective is installed
• "###" = Sequential identification number
07/21/2016 Flad Code Forum : Doors (Part II) 21
"AA" = Type of opening protective
AC - Access doors
BR - Bullet-resisting-type fire door assemblies
CH - Chute-type fire door assemblies
CU - Curtain-type fire door assemblies
DW - Dumbwaiter-type fire door assemblies
FE - Freight elevator fire door assemblies
PE - Passenger elevator fire door assemblies
RS - Rolling steel fire door assemblies
SC - Service-counter-type fire door assemblies
SL - Sliding-type fire door assemblies
SA - Special-purpose-type fire door assemblies
SN - Swinging-type fire door assemblies – (ANSI/UL 10B, "Fire Tests of Door Assemblies")
SP - Swinging-type fire door assemblies – (ANSI/UL 10C, "Positive Pressure Fire Tests of Door Assemblies")
WA - Window assemblies
07/21/2016 Flad Code Forum : Doors (Part II) 22
Correct Annotation
“1-Hour Wall”
The FRR of a wall is only
part of the equation.
What is the PURPOSE of
the wall?
FW, FB, FP, SB, SP, HA ???
“Cement Pond”
Cement is part of the
admixture to make
concrete.
07/21/2016 Flad Code Forum : Doors (Part II) 23
PURPOSE of the FRR Wall
Assembly Door Rating
4 FW/FB 3.0
3 FW/FB 3.0
2 FW/FB 1.5
1 FB 0.75
Stair/Exit Passageway/Shaft
2FB 1.5
1FB 1.0
Assembly Door Rating
1FP 0.75
0.5FP 0.33
Corridor FPs
1FP 0.33
0.5FP 0.33
1SB 0.33
07/21/2016 Flad Code Forum : Doors (Part II) 24
PURPOSE of the FRR Wall
• Area of fire door assembly openings is limited to 156 sf unless the buildings on each side of the Fire Wall are sprinklered throughout.
• Aggregate width of openings on any floor level cannot exceed 25% of the overall length of the Fire Wall.
07/21/2016 Flad Code Forum : Doors (Part II) 25
NFPA 80 : Annex K
K.4 Despite the provision of protection specified in this standard, walls with openings have less fire resistance than unpierced walls.
Fire doors, shutters, and fire windows are designed to protect an opening under normal conditions of use, with a clear space on both sides of the opening.
Where the opening is not used and combustible material is piled against the door, window, or shutter, the designed protection cannot be expected. For that reason, combustible material should be kept well away from openings.
Where a door or window opening is no longer in use, the opening should be closed, with construction having a fire resistance rating equivalent to that of the wall.
07/21/2016 Flad Code Forum : Doors (Part II) 26
Performance Requirements
• Fire Protection Ratings : Table 716.5
• Max Temperature Increase
– Unexposed side < 450 degrees F after 30 minutes
– Section 716.5.5
• Doors in FPs (Corridors) & Doors in SBs
– Meet smoke & draft control : UL 1784
– Section 716.5.3.1
07/21/2016 Flad Code Forum : Doors (Part II) 27
IBC TABLE 716.5OPENING FIRE PROTECTION ASSEMBLIES, RATINGS AND MARKING
07/21/2016 Flad Code Forum : Doors (Part II) 28
IBC TABLE 716.5OPENING FIRE PROTECTION ASSEMBLIES, RATINGS AND MARKING
07/21/2016 Flad Code Forum : Doors (Part II) 29
IBC TABLE 716.5OPENING FIRE PROTECTION ASSEMBLIES, RATINGS AND MARKING
07/21/2016 Flad Code Forum : Doors (Part II) 30
Non-corridor walls : Dwelling Unit/Sleeping Unit separation walls,
Tenant separation walls in malls, Elevator Lobby separation walls.
IBC TABLE 716.5OPENING FIRE PROTECTION ASSEMBLIES, RATINGS AND MARKING
FIRE-RESISTANCE RATING.
The period of time a building element, component or assembly maintains the ability
to confine a fire, continues to perform a given structural function, or both, as
determined by the tests, or the methods based on tests, prescribed in Section 703.
(ASTM E 119)
FIRE PROTECTION RATING.
The period of time that an opening protective will maintain the ability to confine a fire
as determined by tests prescribed in Section 715. Ratings are stated in hours or
minutes.
(NFPA 252 or UL 10C)
Installing fire-resistance-rated glazing in a fire-protection-rated frame is not sufficient when a fire-resistance-rated assembly is required – the materials must be successfully tested as an assembly.
07/21/2016 Flad Code Forum : Doors (Part II) 31
716.5 Fire door and shutter assemblies
Approved fire door and fire shutter assemblies shall be
constructed of any material or assembly of component
materials that conforms to the test requirements of Section
716.5.1, 716.5.2 or 716.5.3 and the fire protection rating
indicated in Table 716.5.
Fire door frames with transom lights, sidelights or both shall
be permitted in accordance with Section 716.5.6.
Fire door assemblies and shutters shall be installed in
accordance with the provisions of this section and NFPA 80.
07/21/2016 Flad Code Forum : Doors (Part II) 32
FD Assembly Types
• Side-hinged or pivoted swinging doors
– Section 716.5.1
– Testing : NFPA 252 or UL 10C
• Other Types
– Section 716.5.2
• Swinging elevator
• Bottom and side-hinged chute intake doors
• Top-hinged chute discharge doors
– Testing : NFPA 252 or UL 10B
07/21/2016 Flad Code Forum : Doors (Part II) 35
IBC TABLE 716.5OPENING FIRE PROTECTION ASSEMBLIES, RATINGS AND MARKING
07/21/2016 Flad Code Forum : Doors (Part II) 37
UL 1784, Air Leakage Tests of Door AssembliesLimit for air infiltration is 3 cfm per square foot or less
as tested at a pressure of 0.10 inch of water (0.02
m3/(s · m2) or less as tested at a pressure of 0.02 kPa)
FD Assembly Types
• F/S Door Assemblies in Corridors & Smoke Barriers
– Section 716.5.3
– Testing : NFPA 252 or UL 10C (No Hose Stream)
07/21/2016 Flad Code Forum : Doors (Part II) 38
FD Assembly Types
• F/S Door Assemblies in Corridors & Smoke
Barriers
– Section 716.5.3 : 20 Minutes (0.33 Hours)
– Exceptions
1. Viewports 1” diameter
2. Corridor door assemblies in I-2 = NO Rating
3. Corridor door assemblies in Multiplex = NO Rating
4. Horiz Sliders in SB in I-3
07/21/2016 Flad Code Forum : Doors (Part II) 39
Types of Smoke Doors
1. Doors required to provide an effective barrier
to limit the transfer of smoke
2. Doors in smoke partitions
3. Doors in smoke barriers
4. Fire door assemblies in corridors and smoke
barriers
5. Doors in exit enclosures and exit
passageways
07/21/2016 Flad Code Forum : Doors (Part II) 40
Type 1
Doors required to provide an effective barrier to
limit the transfer of smoke
– Typical Location
• Smoke partition corridor doors in Group I-2
– Fire Rating Required? No
– Closer Required? No
– Latch Required? Yes
– Gasketing Required? No
07/21/2016 Flad Code Forum : Doors (Part II) 41
Type 2
Doors in smoke partitions– Typical Locations
• Atrium enclosures with automatic sprinklers on both sides of the glass
• I-2 care suites
• Elevator lobby in a sprinklered building
– Fire Rating Required? No
– Closer Required?• Yes (atrium & elev lobby)
• No (I-2 care suites)
– Latch Required?• Yes (I-2 care suites & elev lobby)
• No (atrium )
– Gasketing Required?• Yes (elev lobby)
• No (atrium & I-2 care suites)
07/21/2016 Flad Code Forum : Doors (Part II) 42
Type 3
Doors in smoke barriers– Typical Locations
• Underground Buildings
• I-2 occupancies : Cross corridor double-egress doors
• I-3 occupancies
• I-1, Condition 2
• Ambulatory Care Facilities
– Fire Rating Required? No• Vision panels with fire-protection-rated glazing materials in fire-protection-rated frames
– Closer Required? Yes• Automatic-closing by smoke detection
– Latch Required? No
– Gasketing Required? No• Astragals or rabbets at the meeting edges
• Doors must be close-fitting within operational tolerances
• Maximum allowable undercut is 3/4”
• Doors must not have louvers or grilles.
• Frame stops are required at the head and jambs.
07/21/2016 Flad Code Forum : Doors (Part II) 43
Type 4
Fire door assemblies in corridors and smoke barriers
Typical Locations
• Corridors and smoke barriers with a fire-resistance rating
– Fire Rating Required? Yes
• Vision panels with fire-protection-rated glazing materials in fire-protection-rated frames
– Closer Required? Yes
• Self- or Automatic-closing
– Latch Required? Yes
– Gasketing Required? Yes
• Meet the requirements for a smoke and draft control assembly tested in accordance with UL 1784 (maximum air leakage)
07/21/2016 Flad Code Forum : Doors (Part II) 44
Type 5
Doors in exit enclosures and exit passagewaysTypical Locations
• Stair doors required to be fire-rated, and doors within the exit passageway connecting the stair to the exit discharge.
– Fire Rating Required? Yes• Temperature-rise in non-sprinkled buildings
– Closer Required? Yes• Self- or Automatic-closing
– Latch Required? Yes
– Gasketing Required? No (but …)• Gasketing and a door bottom/sweep may be necessary in
order to maintain stair pressurization
07/21/2016 Flad Code Forum : Doors (Part II) 45
Hardware : Fire Doors
716.5.9 Door closing.
Fire doors shall be self- or automatic-closing in accordance with this section.
Self-closing chute intake doors shall not fail in a “door open” position in the event of a closer failure.
Exceptions:
1. Fire doors located in common walls separating sleeping units in Group R-l shall be permitted without automatic- or self-closing devices.
2. The elevator car doors and the associated hoistway enclosure doors at the floor level designated for recall in accordance with Section 3003.2 shall be permitted to remain open during Phase I emergency recall operation.
07/21/2016 Flad Code Forum : Doors (Part II) 47
716.5.9 Door closing
Self-closing
– NFPA 80
• Doors that, when opened and released, return to the closedposition.
• Closing mechanism shall not have a hold-open feature.
• Examples
– Closers
– Spring Hinges
– Gravity
07/21/2016 Flad Code Forum : Doors (Part II) 48
716.5.9 Door closing
Automatic-closing
– NFPA 80
• A device that causes the door or window to close when activated by a fusible link or detector.
• Desirable that when buildings are unoccupied, these doors are closed.
• Examples
– A labeled, fail-safe door holder/release device
– Hold-open mechanism
07/21/2016 Flad Code Forum : Doors (Part II) 49
716.5.9 Door closing
Automatic-closing
– NFPA 80 : Fusible link or Detector?
716.5.9.3 Smoke-activated doors.
Automatic-closing doors installed in the following
locations shall be automatic-closing by the
actuation of smoke detectors … or by loss of
power to the smoke detector or hold-open device.
07/21/2016 Flad Code Forum : Doors (Part II) 50
716.5.9.3 Smoke-activated doors
1. Doors installed across a corridor.
2. Doors that protect openings in exits or corridors required to be of fire-resistance-rated construction.
3. Doors that protect openings in walls that are capable of resisting the passage of smoke in accordance with Section 509.4. (Incidental Use Areas)
4. Doors installed in smoke barriers in accordance with Section 709.5.
5. Doors installed in fire partitions in accordance with Section 708.6.
6. Doors installed in a fire wall in accordance with Section 706.8.
7. Doors installed in shaft enclosures in accordance with Section 713.7.
8. Doors installed in refuse and laundry chutes and access and termination rooms in accor-dance with Section 713.13. Automatic-closing chute intake doors installed in refuse and laun-dry chutes shall also meet the requirements of Sections 716.5.9 and 716.5.9.1.1.
9. Doors installed in the walls for compartmentation of underground buildings in accordance with Section 405.4.2.
10.Doors installed in the elevator lobby walls of underground buildings in accordance with Section 405.4.3.
11.Doors installed in smoke partitions in accordance with Section 710.5.2.3.
07/21/2016 Flad Code Forum : Doors (Part II) 51
716.5.9.3 Smoke-activated doors
1. Doors installed across a corridor.
2. Doors that protect openings in exits or corridors required to be of fire-resistance-rated construction.
3. Doors that protect openings in walls that are capable of resisting the passage of smoke in accordance with Section 509.4. (Incidental Use Areas)
4. Doors installed in smoke barriers in accordance with Section 709.5.
5. Doors installed in fire partitions in accordance with Section 708.6.
6. Doors installed in a fire wall in accordance with Section 706.8.
7. Doors installed in shaft enclosures in accordance with Section 713.7.
8. Doors installed in refuse and laundry chutes and access and termination rooms in accor-dance with Section 713.13. Automatic-closing chute intake doors installed in refuse and laun-dry chutes shall also meet the requirements of Sections 716.5.9 and 716.5.9.1.1.
9. Doors installed in the walls for compartmentation of underground buildings in accordance with Section 405.4.2.
10.Doors installed in the elevator lobby walls of underground buildings in accordance with Section 405.4.3.
11.Doors installed in smoke partitions in accordance with Section 710.5.2.3.
07/21/2016 Flad Code Forum : Doors (Part II) 53
Hardware : Fire Doors
716.5.9.1 Latch required.
Unless otherwise specifically permitted, single
fire doors and both leaves of pairs of side-
hinged swinging fire doors shall be provided
with an active latch bolt that will secure the
door when it is closed.
07/21/2016 Flad Code Forum : Doors (Part II) 58
716.5.9.1 Latch required
07/21/2016 Flad Code Forum : Doors (Part II) 59
Fire doors must be positively latched in order to withstand the pressures created
by the fire and compartmentalize the building to prevent the spread of smoke,
flames, and gases.
Active latch bolt = latch bolt of a lockset or fire exit hardware
Fire Door Hardware (UL)
GWGR . Guide Info
• Accessories for Single-point Locks and Latches and Fire-exit Hardware (GWVW)
• Auxiliary Locks (GWXT)
• Door Hinges (GWZQ)
• Electric Strikes (GXAY)
• Fire-exit Hardware (GXHX)
• Flush and Surface Bolts, Automatic Type (GXOW)
• Flush and Surface Bolts, Manual Type (GXSR)
• Flush and Surface Bolts, Self-latching Type (GXVV)
• Single-point Locks and Latches (GYJT)
• Electrically Controlled Single-point Locks and Latches (GYQS)
• Two- and Three-point Locks and Latches (GYXR)
• Elevator Fire Door Hardware, Passenger (GZKZ)
• Fire Door Hardware (GZYX)
• Fire Door Viewers (HAAU)
07/21/2016 Flad Code Forum : Doors (Part II) 60
iDigHardware.com
Articles published in industry journals
• Doors & Hardware
• Construction Specifier
• Life Safety Digest
• Locksmith Ledger
Topics
• Intro to Codes
• Accessibility
• Egress and Life Safety
• Electrified Hardware
• Fire Door Assemblies
• Health Care Facilities
• Safety Glazing
• School Security
• Miscellaneous
07/21/2016 Flad Code Forum : Doors (Part II) 62
Future (Possible) Topics
• Special Doors
– Revolving
– Gates
– Turnstiles
• Glazing
– Fire Windows
– Glazing in Fire Doors
• Door Hardware
– Locks & Latches
– Bolt Locks
– Panic Hardware
– Electromagnetic Locks
– Special Locking in I-2
– Delayed Egress
– Access Controlled Egress
07/21/2016 Flad Code Forum : Doors (Part II) 64