diversified air systems,inc. firetrace technology

9
03/23/22 1 Diversified Air Systems,Inc. Firetrace Technology Call today: 800-264-8958

Upload: satinka-herrera

Post on 31-Dec-2015

33 views

Category:

Documents


0 download

DESCRIPTION

Diversified Air Systems,Inc. Firetrace Technology. Call today: 800-264-8958. What is Firetrace?. Suppression for the “micro-environment” Pneumatic heat detection Fire suppression system “Total flooding” OR “Local application” Detection and suppression at the ignition point. - PowerPoint PPT Presentation

TRANSCRIPT

Page 1: Diversified Air Systems,Inc. Firetrace Technology

04/19/23 1

Diversified Air Systems,Inc.Firetrace Technology

Call today: 800-264-8958

Page 2: Diversified Air Systems,Inc. Firetrace Technology

04/19/23 2

What is Firetrace?• Suppression for the

“micro-environment”• Pneumatic heat

detection • Fire suppression

system• “Total flooding” OR

“Local application” • Detection and

suppression at the ignition point

Page 3: Diversified Air Systems,Inc. Firetrace Technology

04/19/23 3

“It’s All About the ………………TUBE”

• Linear, pneumatic flame detection• Bursts at 212°F (100°C)• Tubing can be the detector & the piping

network • Tubing is durable and flexible• Tubing is not conductive or corrosive• Good for harsh chemical environments

Page 4: Diversified Air Systems,Inc. Firetrace Technology

04/19/23 4

Direct System

Direct Low Pressure System

Page 5: Diversified Air Systems,Inc. Firetrace Technology

04/19/23 6

• Commercial Name : FT 1992 Thermoplas

• Physical Appearance: 6mm OD red tube

• Change in Physical state: Melts @ 194 C (381.2 F)

• Bulk Density : 17g / meter (5.18g/ft)

• Dielectric Strength: (DIN 53481)kV/mm dry 40

• Thermal Decomposition: Above 300 C (572 F)

• Temperature at Burst: 100-115 C @ 150 psi

(212-239 F @ 150 psi)

Characteristics of the Firetrace Detection Tubing

Page 6: Diversified Air Systems,Inc. Firetrace Technology

04/19/23 7

The “Burst”

Page 7: Diversified Air Systems,Inc. Firetrace Technology

04/19/23 8

Max 3.3 ft / layer

• Tubing is used as a detector and delivery of agent from cylinder

• Valve is a X-over only to allow for connection of the tubing to cylinder

• 4 ports on this valve for gauge, P/S, Ball Valve and cylinder

• Discharge time is limited due to the x-sectional area of the ball valve orifice.

Direct Low Pressure (DLP) System

Page 8: Diversified Air Systems,Inc. Firetrace Technology

04/19/23 9

DLP (Direct Low Pressure) System

Page 9: Diversified Air Systems,Inc. Firetrace Technology

04/19/23 10

OPTIONS

PRESSURE SWITCH

• Monitors pressure in the tubing and in cylinder

• Can use one on cylinder and as many as needed on tubing network

• Used for:• Building alarm tie-in• Power lock-out or shunt trip• Fan/damper control• Auxiliary controls