 J OSL YN Manufacturing Co. Arresters Distribution Arresters Durability Riser Pole and Heavy Duty Distribution Class arresters have been called upon to serve in the most demanding of applications. Typically unshielded, ov erhead lines can produce some of the most severe lightning surges on the power system. Joslyn distribution arresters are designed to meet the demands of protecting underground and overhead equipment, respectively. Tested in accordance with the latest industry standard, ANSI/IEEE C62.11-1999 for Heavy Duty metal oxide arresters, Joslyn distribution arresters withstand the following minimum design tests: High Curr ent-Short Dur ation: 2 curr ent surg es of 100kA magnitude and 4/10 microsecond duration. Low Current-Long Duration: 20 current sur ges with 2000 micro-second duration and 400 amperes magnitude discharged through ‘ZRP’ and 250 amperes magnitude discharged through ‘ZHP’. Duty Cycl e: 20 dischar ges with a current su rge o f 10kA magnitude and 8/20 microsecond wave shape follo wed by 2 discharges with a current surge of 40kA magnitude. • Follo wing each o f these tests , the arrester s remain thermal ly stable and the discharge voltage change at the classifying current is less than 10%. For more details on procedures and results, request the product specific Certified D esign Test Report.  Insulating Bracket Joslyn’s polymer housed arresters are assembled complete with a molded glass reinforced polyester insulating bracket with greatly increased strength. This polyester bracket provides insulation between the arrester and ground after the ground lead disconnect has operated in the unlikely event of arrester failure. This bracket will accommodate a 1/2 inch carriage bolt on the crossarm bracket. Joslyn recommends that no more than 40 foot-pounds of torque be applied when installing the arrester on the crossarm mounting bolt. The bracket also uses a contamination deterrent crest down the centerline of the body of the bracket. This crest facilitates self-washing of contamination with rainwater. This feature reduces the risk of any contaminant build up on the top of the bracket between the skirts. ©2004 Joslyn Manufacturing Co. • 9200 W. Fullerton Avenue • Franklin Park, IL 60131 • www.joslynmfg.com Phone: 800-4-JOSLYN (800-456-7596) or 773-625-1500 • Fax 800-443-7380 or 773-625-0090 AR-13

Upload: electrification

Post on 02-Jun-2018

230 views

Category:

Documents


1 download

TRANSCRIPT

Page 1: Distribution Lightning Arrester

8/10/2019 Distribution Lightning Arrester

http://slidepdf.com/reader/full/distribution-lightning-arrester 1/10

Page 2: Distribution Lightning Arrester

8/10/2019 Distribution Lightning Arrester

http://slidepdf.com/reader/full/distribution-lightning-arrester 2/10

Distribution Arresters (continued)

Arresters JOSLYNManufacturing Co.

©2004 Joslyn Manufacturing Co. • 9200 W. Fullerton Avenue • Franklin Park, IL 60131 • www.joslynmfg.comPhone: 800-4-JOSLYN (800-456-7596) or 773-625-1500 • Fax 800-443-7380 or 773-625-0090AR-14

Terminal ConnectionsDistribution arrester line terminals utilize a stainless steel

four cornered “Star Clamp” for maximum conductor rangeand speed of installation. The ground terminals utilize astainless steel “U clamp”. Both connectors securely clampaluminum or copper conductors from No. 10 solid through2/0 stranded. Joslyn specifies that no more than 20 foot-pounds of torque be applied to the line and groundterminals.

Transformer ProtectionThe level of protection an arrester can provide will decreasewhen utilizing long connecting leads (line and ground side).This is due to the inductive voltage drop which is added to

the discharge voltage of the arrester. Mounting an arresterdirectly to the transformer will yield excellent protectivemargins from a combination of controlled lead length andlow discharge voltages.

Available OptionsFor options, see Catalog Selection Guides (page AR-19 thru

22) and Accessories (page AR-26 and 27).

Fault-Current Withstand TestsFault-current testing, also known as short circuit testing,demonstrates an arrester failure based on the most probablefailure modes over a range of fault currents. Two failuremodes are tested: 1) a fuse wire runs along the side of theinternal valve elements to simulate and internal flashover(moisture or collar failure), 2) overvoltage the arrester untilthe resistive elements fail to simulate a system overvoltageexceeding the unit’s TOV capability.

ANSI/IEEE C62.11 1999, specifies the test procedures andacceptance criteria for fault-current tests on distributionsurge arresters. Joslyn’s arresters passed the fuse wire andovervoltage fault-current testing at the current levels anddurations listed in the applicable Fault-Current Data Tables.Conformance was shown by oscillograph recordings of current magnitude and duration conducted through thearresters. All units passed the acceptance criteria.

Initial venting and arcing. Continued arcing. Following the severe fault, the arrester remainedintact.

Page 3: Distribution Lightning Arrester

8/10/2019 Distribution Lightning Arrester

http://slidepdf.com/reader/full/distribution-lightning-arrester 3/10

JOSLYNManufacturing Co. Arresters

Distribution Arresters (continued)

Zforce™ ‘ZNP’, ‘ZHP’ and ‘ZRP’ ArrestersPatent No. 5,923,518

‘ZNP’ (5kA Normal Duty Polymer, Rated 9, 10 & 18kV)‘ZHP’ (10kA Heavy Duty Polymer, Rated 3kV-36kV)‘ZRP’ (10kA Riser Pole Polymer, Rated 3kV-36kV)

Fault Current Withstand TestsFault current testing, also known as short circuit testing,demonstrates an arrester failure based on the most probablefailure modes over a range of fault currents. Two failure modesare tested:

• A fuse wire runs along the side of the internal and valveelements to simulate an internal flashover (moisture orcollar failure).

©2004 Joslyn Manufacturing Co. • 9200 W. Fullerton Avenue • Franklin Park, IL 60131 • www.joslynmfg.comPhone: 800-4-JOSLYN (800-456-7596) or 773-625-1500 • Fax 800-443-7380 or 773-625-0090 AR

‘ZNP’ Fault Current Data ‘ZHP’ & ‘ZRP’ Fault Current DataFault Circuit Fault Duration Fault Circuit Fault Duration

Test Type (kA rms) (SEC) Test Type (kA rms) (SEC)

Fuse Wire 10.1 0.202 Fuse Wire 20.0 0.2110.1 0.212 20.0 0.21

Overvoltage 10.1 0.21 Overvoltage 20.0 0.20910.1 0.206 20.0 0.209

5.27 0.207 10.1 0.2095.27 0.207 10.1 0.2110.608 1.009 0.708 1.0120.608 1.011 0.708 1.014

• Overvoltage the arrester until the resistive elements fail tosimulate a system overvoltage exceeding the units TOV

capability.

ANSI/IEEE C62.11-1999, specifies the test procedures andacceptance criteria for fault current tests on distributionsurge arresters. Joslyn’s Zforce™ arresters passed the fusewire and overvoltage fault-current testing at the currentlevels and durations listed in the applicable Fault-CurrentData Tables. Conformance was shown by oscillographrecordings of current magnitude and duration conductedthrough the arresters. All units passed the acceptancecriteria.

Page 4: Distribution Lightning Arrester

8/10/2019 Distribution Lightning Arrester

http://slidepdf.com/reader/full/distribution-lightning-arrester 4/10

Distribution Arresters (continued)

ZFORCE ZNP™(5kA Normal Duty Polymer)

Physical DataCreepage 1 Strike A B C D Weight2

kV Inch mm Inch mm Inch mm Inch mm Inch mm Inch mm Lbs. kg Std. Pkg.

9 15.04 382 7.69 195 8.83 224 4.00 102 7.71 195 3.93 100 2.9 1.32 510 17.41 442 8.00 203 9.14 232 4.00 102 8.02 204 3.93 100 3.0 1.36 518 26.59 675 11.23 285 12.23 311 4.00 102 11.16 283 5.43 138 4.8 2.18 5

Protective Characteristics

Voltage MCOV Max. Equiv. Max. Switch. Max. Discharge Voltage (kV Crest) Using an 8/20 µs Current ImpulseRating (Ur) (Uc) 3 FOW4 Surge6 1.5 2.5 3.0 5.0 10 20 40

(kVrms) (kVrms) (kV Crest) (kV Crest) kA kA kA kA kA kA kA9 7.65 29.9 23.7 25.4 26.2 26.6 28.2 30.5 33.8 39.9

10 8.4 32.9 26.3 28.1 29.2 29.6 31.3 33.9 37.4 43.918 15.3 59.7 47.4 50.7 52.3 53.1 56.4 61.0 67.5 79.7

Arresters JOSLYNManufacturing Co.

©2004 Joslyn Manufacturing Co. • 9200 W. Fullerton Avenue • Franklin Park, IL 60131 • www.joslynmfg.comPhone: 800-4-JOSLYN (800-456-7596) or 773-625-1500 • Fax 800-443-7380 or 773-625-0090AR-16

INSULATED BRACKET DATAArrester Creepage E F G (Radius)Rating Skirts(kV) inch mm inch mm inch mm inch mm

3–15 4.6 117 3 1.875 47.62 2.70 66.58 1.312 33.3418–36 9.16 232 6 2.13 54.10 2.95 74.93 1.656 42.06

OPTIONAL BIRDGUARD

Page 5: Distribution Lightning Arrester

8/10/2019 Distribution Lightning Arrester

http://slidepdf.com/reader/full/distribution-lightning-arrester 5/10

JOSLYNManufacturing Co. Arresters

Distribution Arresters (continued)

ZFORCE ZHP™(10kA Heavy Duty Polymer)

Physical DataCreepage 1 Strike A B C D Weight2

kV Inch mm Inch mm Inch mm Inch mm Inch mm Inch mm Lbs. kg Std. Pk3 7.96 202 5.47 139 6.52 166 4.30 109 5.40 137 3.93 100 2.3 1.05 56 11.94 303 6.02 153 7.66 195 4.30 109 6.54 166 3.93 100 3.0 1.37 59 15.92 404 7.76 197 8.80 224 4.30 109 7.68 195 3.93 100 3.6 1.64 5

10 18.28 464 8.21 209 9.14 232 4.30 109 8.02 204 3.93 100 3.7 1.68 512 19.90 506 8.91 226 9.94 253 4.30 109 8.82 224 3.93 100 4.2 1.91 515 23.84 606 10.01 254 11.09 282 4.30 109 10.02 254 3.93 100 4.9 2.23 518 27.87 708 11.40 290 12.23 311 4.30 109 11.16 283 5.43 138 5.9 2.68 521 31.85 809 12.54 319 13.37 340 4.30 109 12.30 312 5.43 138 6.5 2.96 524 35.83 910 13.69 348 14.51 369 4.30 109 13.44 341 5.43 138 7.1 3.23 527 39.92 1014 14.52 369 15.66 398 4.30 109 14.59 371 5.43 138 7.8 3.52 530 43.90 1115 15.51 394 16.78 426 4.30 109 15.71 399 5.43 138 8.4 3.80 1*

36 51.95 1320 17.79 452 19.13 486 4.30 109 18.06 459 5.43 138 9.6 4.38 1*

Protective Characteristics

Voltage MCOV Max. Equiv. Max. Switch. Max. Discharge Voltage (kV Crest) Using an 8/20 µs Current ImpulseRating (Ur) (Uc) 3 FOW5 Surge6 1.5 2.5 3.0 5.0 10 20 40

(kVrms) (kVrms) (kV Crest) (kV Crest) kA kA kA kA kA kA k3 2.55 10.4 7.8 8.5 8.8 8.9 9.3 9.9 10.9 12.46 5.1 20.7 15.5 16.9 17.5 17.7 18.6 19.8 21.8 24.79 7.65 31.0 23.3 25.4 26.2 26.6 27.9 29.7 32.7 37.0

10 8.4 34.5 25.9 28.2 29.1 29.5 31.0 33.0 36.3 41.112 10.2 41.3 31.0 33.8 34.9 35.4 37.2 39.6 43.5 49.315 12.7 51.7 38.8 42.2 43.6 44.2 46.5 49.5 54.4 61.618 15.3 62.0 46.5 50.7 52.3 53.1 55.8 59.4 65.3 73.9

21 17.0 72.3 54.3 59.1 61.0 61.9 65.1 69.3 76.2 86.224 19.5 82.6 62.1 67.6 69.7 70.7 74.4 79.2 87.0 98.527 22.0 92.9 69.9 76.0 78.4 79.6 83.7 89.1 97.9 110.830 24.4 103.3 77.6 84.4 87.1 88.4 93.0 99.0 108.8 123.136 29.0 124.0 93.1 101.3 104.5 106.1 111.5 118.8 130.5 147.7

ZFORCE ZRP™(10kA Riser Pole Polymer)

Physical DataCreepage 1 Strike A B C D Weight2

kV Inch mm Inch mm Inch mm Inch mm Inch mm Inch mm Lbs. kg Std. Pk3 7.96 202 5.47 139 6.52 166 4.30 109 5.40 137 3.93 100 2.3 1.05 56 11.94 303 6.02 153 7.66 195 4.30 109 6.54 166 3.93 100 3.0 1.37 5

9 15.92 404 7.76 197 8.80 224 4.30 109 7.68 195 3.93 100 3.6 1.64 510 18.28 464 8.21 209 9.14 232 4.30 109 8.02 204 3.93 100 3.7 1.68 512 19.90 506 8.91 226 9.94 253 4.30 109 8.82 224 3.93 100 4.2 1.91 515 23.84 606 10.01 254 11.09 282 4.30 109 10.02 254 3.93 100 4.9 2.23 518 27.87 708 11.40 290 12.23 311 4.30 109 11.16 283 5.43 138 5.9 2.68 521 31.85 809 12.54 319 13.37 340 4.30 109 12.30 312 5.43 138 6.5 2.96 524 35.83 910 13.69 348 14.51 369 4.30 109 13.44 341 5.43 138 7.1 3.23 527 39.92 1014 14.52 369 15.66 398 4.30 109 14.59 371 5.43 138 7.8 3.52 530 43.90 1115 15.51 394 16.78 426 4.30 109 15.71 399 5.43 138 8.4 3.80 1*36 51.95 1320 17.79 452 19.13 486 4.30 109 18.06 459 5.43 138 9.6 4.38 1*

©2004 Joslyn Manufacturing Co. • 9200 W. Fullerton Avenue • Franklin Park, IL 60131 • www.joslynmfg.comPhone: 800-4-JOSLYN (800-456-7596) or 773-625-1500 • Fax 800-443-7380 or 773-625-0090 AR

Page 6: Distribution Lightning Arrester

8/10/2019 Distribution Lightning Arrester

http://slidepdf.com/reader/full/distribution-lightning-arrester 6/10

ZFORCE ZRP™(10kA Riser Pole Polymer)

Protective Characteristics

Voltage MCOV Max. Equiv. Max. Switch. Max. Discharge Voltage (kV Crest) Using an 8/20 µs Current ImpulseRating (Ur) (Uc) 3 FOW5 Surge6 1.5 2.5 3.0 5.0 10 20 40

(kVrms) (kVrms) (kV Crest) (kV Crest) kA kA kA kA kA kA kA3 2.55 8.6 6.2 6.8 7.1 7.2 7.5 8.2 9.0 10.36 5.1 17.1 12.4 13.6 14.1 14.3 15.1 16.3 18.1 20.69 7.65 25.7 18.6 20.3 21.2 21.5 22.6 24.5 27.1 30.9

10 8.4 28.5 20.7 22.6 23.5 23.9 25.1 27.2 30.1 34.312 10.2 34.2 24.8 27.1 28.2 28.7 30.1 32.6 36.1 41.215 12.7 42.8 31.1 33.9 35.3 35.9 37.7 40.8 45.2 51.518 15.3 51.3 37.3 40.7 42.3 43.0 45.2 49.0 54.2 61.721 17.0 59.9 43.5 47.5 49.4 50.2 52.7 57.1 63.2 72.024 19.5 68.4 49.7 54.2 56.4 57.4 60.2 65.3 72.2 82.327 22.0 77.0 55.9 61.0 63.5 64.5 67.8 73.4 81.3 92.6

30 24.4 85.5 62.1 67.8 70.5 71.7 75.3 81.6 90.3 102.936 29.0 102.6 74.5 81.4 84.6 86.0 90.4 97.9 108.4 123.5

1. Reduce creepage by 1.45 inches (36.8mm) when ordering without insulating bracket.

2. Does not include metal mounting bracket hardware.

3. MCOV = Maximum Continuous Operating Voltage that may be applied continuously between the terminals of the arrester.

4. The equivalent Front-of-Wave is the maximum discharge voltage for a 5 kA impulse current wave which produces a voltage wave cresting in 0.5 µs.

5. The equivalent Front-of-Wave is the maximum discharge voltage for a 10 kA impulse current wave which produces a voltage wave cresting in 0.5 µs.

6. Based on a switching surge current impulse of 45x90 µs, 500 amperes.

* Single pack modifier required for 30 kV and 36 kV ratings.

Temporary Overvoltage—’ZNP’, ‘ZHP’ and ‘ZRP’ Arresters

Arresters JOSLYNManufacturing Co.

©2004 Joslyn Manufacturing Co. • 9200 W. Fullerton Avenue • Franklin Park, IL 60131 • www.joslynmfg.comPhone: 800-4-JOSLYN (800-456-7596) or 773-625-1500 • Fax 800-443-7380 or 773-625-0090AR-18

Distribution Arresters (continued)

O v e r v o

l t a g e

p e r

U n

i t o f A r r e s

t e r

M C O V ( U c

)

Duration ZNP ZHP ZRP(seconds) Voltage P.U. of MCOV (Uc)

0.02 1.77 1.80 1.54

0.10 1.70 1.73 1.481.00 1.61 1.63 1.4010 1.52 1.54 1.31

100 1.47 1.47 1.261000 1.42 1.43 1.22

Page 7: Distribution Lightning Arrester

8/10/2019 Distribution Lightning Arrester

http://slidepdf.com/reader/full/distribution-lightning-arrester 7/10

JOSLYNManufacturing Co. Arresters

©2004 Joslyn Manufacturing Co. • 9200 W. Fullerton Avenue • Franklin Park, IL 60131 • www.joslynmfg.comPhone: 800-4-JOSLYN (800-456-7596) or 773-625-1500 • Fax 800-443-7380 or 773-625-0090 AR

Distribution Arresters (continued)

#S - Single Pack Modifier (Requiredfor 30kV and 36kV ratings.)Standard package is 5 unlessotherwise specified.

#P - OEM Bulk Packaging

* Top/Bottom Terminal: Fits wire ranges foraluminum or copper conductors from No. 10solid (3.0mm dia.) through 2/0 stranded(11.0mm dia.)

Page 8: Distribution Lightning Arrester

8/10/2019 Distribution Lightning Arrester

http://slidepdf.com/reader/full/distribution-lightning-arrester 8/10

Arresters JOSLYNManufacturing Co.

©2004 Joslyn Manufacturing Co. • 9200 W. Fullerton Avenue • Franklin Park, IL 60131 • www.joslynmfg.comPhone: 800-4-JOSLYN (800-456-7596) or 773-625-1500 • Fax 800-443-7380 or 773-625-0090AR-20

Distribution, 5kA Dead Front Elbow Arresters

“ZE” SeriesRated 3-27kV

The type “ZE” arrester incorporates surge protection in aone-piece, shielded elbow housing. It permits arresterinstallation on standard separable connector bushings,maintaining the dead front concept.

Performance

The type “ZE” arrester was developed specifically forprotection of underground distribution systems. It isinstalled at the open point of the underground system toprevent voltage wave doubling. When also installed at anintermediate point, voltage reflections from the open pointarrester are harmlessly discharged. The housing, made of peroxide cured EPDM rubber, is totally shielded with amolded conductive EPDM jacket to maintain the dead frontconcept. The one-piece construction requires no fieldassembly. The “ZE” dead front elbow arrester is approved byREA.

Durability

The “ZE” elbow arrester consistently withstands the

following minimum design tests:

• High Current-Short Duration: 2 current surges of 40kAmagnitude.

• Low Current-Long Duration: 20 current surges of 75amperes magnitude and 2000 microsecond duration.

• Duty Cycle: 22 discharges with a current surge of 5kAmagnitude and 8/20 microsecond wave shape.

• Following each of these tests, the “ZE” arrester remainsthermally stable and the discharge voltage increase atrated current is less than 10%.

Reliability

Rigid control standards insure that all material conforms toexacting engineering specifications. Each finished arrester issubjected to electrical tests to determine reference voltage,total leakage current and corona levels.

Application

The type “ZE” arrester rated voltage designates the 60Hzvoltage applied across the arrester terminals during the dutycycle test. In addition, the type “ZE” arrester MaximumContinuous Operating Voltage (MCOV) designates themaximum power frequency voltage that may be continuouslyapplied across the arrester in service. Selection of theappropriate type “ZE” rating is made on the basis that themaximum continuous line-to-ground voltage on the systemdoes not exceed the MCOV of the arrester.

The 10kV, 18kV and 27kV rated arresters are designed forapplication on nominal 15kV, 25kV and 35kV UD systems,respectively. The three ratings include standard ANSI/IEEE386 separable connector interface designs that arecompatible with major interface suppliers at each voltagelevel. Consult Joslyn for your specific requirements.

Permanent Markings

For permanent identification, the “ZE” arrester has moldedinto the housing “JOSLYN ZE ELBOW ARRESTER”. Stampedinto the stainless steel cover are “JOSLYN ZE ARRESTER”,arrester rated voltage, and date of manufacture. In additionto the above, a label contains all other information includingcatalog number and both rated voltage and MCOV rating.

Distribution Arresters (continued)

Page 9: Distribution Lightning Arrester

8/10/2019 Distribution Lightning Arrester

http://slidepdf.com/reader/full/distribution-lightning-arrester 9/10

JOSLYNManufacturing Co. Arresters

©2004 Joslyn Manufacturing Co. • 9200 W. Fullerton Avenue • Franklin Park, IL 60131 • www.joslynmfg.comPhone: 800-4-JOSLYN (800-456-7596) or 773-625-1500 • Fax 800-443-7380 or 773-625-0090 AR

Temporary Overvoltage—‘ZE’ Arresters

PROTECTIVE CHARACTERISTICS

Maximum Maximum Discharge Voltage (kV Crest) UsingVoltage Equivalent An 8/20 µsec Current WaveRating MCOV F.O.W.*

(kV-RMS) (kV-RMS) (kV-Crest) 1.5kA 3kA 5kA 10kA 203 2.55 10.0 8.5 8.8 9.3 10.2 12.96 5.1 20.1 17.0 17.6 18.6 20.4 25.8

10 8.4 30.5 28.0 29.0 30.7 33.7 42.612 10.2 40.2 34.0 35.2 37.2 40.8 51.618 15.3 60.3 51.0 52.8 55.8 61.2 77.424 19.5 80.4 68.0 70.4 74.4 81.6 103.227 22.0 90.5 76.5 79.2 83.7 91.8 116.1

Distribution Arresters (continued)

O v e r v o

l t a g e

p e r

U n

i t o f

A r r e s

t e r

M C O V ( U c

)

Page 10: Distribution Lightning Arrester

8/10/2019 Distribution Lightning Arrester

http://slidepdf.com/reader/full/distribution-lightning-arrester 10/10

Arresters JOSLYNManufacturing Co.

©2004 Joslyn Manufacturing Co. • 9200 W. Fullerton Avenue • Franklin Park, IL 60131 • www.joslynmfg.comPhone: 800-4-JOSLYN (800-456-7596) or 773-625-1500 • Fax 800-443-7380 or 773-625-0090AR-22

Distribution Arresters (continued)

PHYSICAL DATA—‘ZE’ Arresters

DimensionsApprox.

kV A B C D E Elbow ShippingCatalog No. Rating (in.) (mm) (in.) (mm) (in.) (mm) (in.) (mm) (in.) (mm) Interface* Weight8132B0003J001 3 7.0 177.8 4.6 116.8 8.1 205.7 7.7 195.6 2.9 73.7 15kV 3.0 1.48132B0006J001 6 7.0 177.8 4.6 116.8 8.1 205.7 7.7 195.6 2.9 73.7 15kV 3.0 1.48132B0010J001 10 7.0 177.8 4.6 116.8 8.1 205.7 7.7 195.6 2.9 73.7 15kV 3.5 1.68132B1010J001 10 7.0 177.8 4.6 116.8 10.1 256.5 7.7 195.6 2.9 73.7 25kV 3.5 1.68132B0012J001 12 8.3 210.8 5.9 149.9 8.1 205.7 7.7 195.6 2.9 73.7 15kV 4.0 1.88132B0018J001 18 10.0 254.0 7.6 193.0 10.1 256.5 7.7 195.6 2.9 73.7 25kV 4.7 2.18132B2024J001 24 13.3 337.8 10.3 261.6 12.6 320.0 10.1 256.5 4.0 101.6 35kV 2 5.2 2.48132B1027J001 27 13.4 340.4 11.0 279.4 10.1 256.5 7.7 195.6 2.9 73.7 35kV 1 6.4 2.98132B2027J001 27 14.5 368.3 11.5 292.1 12.6 320.0 10.1 256.5 4.0 101.6 35kV 2 8.5 3.9

* Compatible with standard ANSI/IEEE 386 interface designs1 Small 35kV Interface, 21.1/36kV Figure 7 of ANSI/IEEE 386, 1995.2 Large 35kV Interface, 21.1/36.6kV Figure 8 of ANSI/IEEE 386, 1995.

ProbesStandard load break probes are shipped assembled with each unit.

Ground Cable (Included)Size: #5 Stranded Copper Wire Length: 37 Inches

LubricantEach arrester is shipped with a packet of silicone grease, wiping cloth and instruction sheet.

Standard PackagingOne per box.