DISSOLVED GAS ANALYSIS
Used to find electrical & thermal fault in
transformer Fault can be found at incipient stage
Remedial measure can be initiated to avoidmajor damage to transformer
FORMATION OF GAS
Degradation of solid & liquid insulation Faults in transformer Gases gets dissolved in oil till saturation
8/8/2019 Dissolve Gas Analysis
http://slidepdf.com/reader/full/dissolve-gas-analysis 2/10
DGA - Tool for Quality Check
DGA - Quality check during procurement of new transformers.
DGA - before & after heat run test or fast transient test or high
voltage test.
Abnormal increase in gas concentration after factory test indicate
manufacturing / design defect in transformer.
Defect can be rectified before shipment & installation at site.
8/8/2019 Dissolve Gas Analysis
http://slidepdf.com/reader/full/dissolve-gas-analysis 3/10
DGA
Extraction
of
gases from oil
Analysing
for
key gases
Interpretation
of
results
Methane
Ethane
Ethylene
Acetylene
Hydrogen
Carbon monoxide
IS ratio
Key gas method
Rogers ratio
Rate of rise of key gas
8/8/2019 Dissolve Gas Analysis
http://slidepdf.com/reader/full/dissolve-gas-analysis 5/10
CHARACTERISTIC TRANSFORMER FAULTS
ELECTRICAL FAULTS
Sl Type of faults & cause Major gases
1 High energy discharge (Arcing) Methane
* SC in winding Hydrogen
* Breakdown between windings Acetylene
* Breakdown through the oil between bare
conductors
2 Low energy discharge (High energy partial Hydrogen
discharge) Acetylene
* Bad contact action of connection to metallic Methane
parts
* Continuous sparking at breaks
* Discharges between selector contacts
8/8/2019 Dissolve Gas Analysis
http://slidepdf.com/reader/full/dissolve-gas-analysis 6/10
CHARACTERISTIC TRANSFORMER FAULTS
THERMAL FAULTS
Sl Type of faults & cause Major gases
1 Thermal fault of low temperature <150oC Hydrogen
* General conductor overheating Methane
Ethylene
2 Thermal fault of medium temp. 300 to 700oC Hydrogen
* Local over heating of core due to circulating Methane
current Ethylene
* Bad contacts
3 Thermal fault of high temperature >700oC Hydrogen
* Loacl over heating of core due to circulating Methane
current Ethylene
* Bad contacts Acetylene
8/8/2019 Dissolve Gas Analysis
http://slidepdf.com/reader/full/dissolve-gas-analysis 7/10
Sampling of transformer oil
SAMPLING CONTAINER
Perfectly cleaned & Dried Free from dust & moisture Airtight Glass or Metal or Plastic cans
SAMPLING POINT
Bottom valve Sample in actual contact with body Forced cooled TR-Circulate pump for 30 min
Sampling under energized condition
8/8/2019 Dissolve Gas Analysis
http://slidepdf.com/reader/full/dissolve-gas-analysis 8/10
SAMPLING
•Equipment
•Test Requisition form•Method
8/8/2019 Dissolve Gas Analysis
http://slidepdf.com/reader/full/dissolve-gas-analysis 9/10
GENERAL PRECAUTIONS
Avoid sampling in rainy or foggy weather
Protect sample from direct light
Avoid moisture & dust contamination
Cotton waste & other fibrous materials
should not be used
Use the sampling containers exclusively for
transformer oil sampling