direct digital dbt, %rh, and condensate control for a doas-crcp system ashrae winter meeting symp....

24
Direct Digital DBT, %RH, and Condensate Control for a DOAS-CRCP system ASHRAE Winter Meeting Symp. 3, Orlando-Feb. 6, 2005 Stanley A. Mumma, Ph.D., P.E. & Jae-Weon Jeong, Ph.D. Architectural Engineering Department Penn State University, @ Univ. Park, PA [email protected]; [email protected] http:// doas- radiant.psu.edu

Upload: matilda-stokes

Post on 01-Jan-2016

215 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Direct Digital DBT, %RH, and Condensate Control for a DOAS-CRCP system ASHRAE Winter Meeting Symp. 3, Orlando-Feb. 6, 2005 Stanley A. Mumma, Ph.D., P.E

Direct Digital DBT, %RH, and Condensate

Control for a DOAS-CRCP system

ASHRAE Winter Meeting Symp. 3, Orlando-Feb. 6, 2005

Stanley A. Mumma, Ph.D., P.E. &Jae-Weon Jeong, Ph.D.

Architectural Engineering DepartmentPenn State University, @ Univ. Park, PA

[email protected]; [email protected]:// doas-radiant.psu.edu

Page 2: Direct Digital DBT, %RH, and Condensate Control for a DOAS-CRCP system ASHRAE Winter Meeting Symp. 3, Orlando-Feb. 6, 2005 Stanley A. Mumma, Ph.D., P.E

Presentation Outline• First thoughts when considering

DOAS-CRCP control.• DOAS-CRCP design philosophy.• Summary of the design issues you

may wish to consider.• Field experience with single zone

controls.• Extension to multi-zone applications

designed with a DOAS supply air temperature equal to the required design SA DPT. Why you ask!

Page 3: Direct Digital DBT, %RH, and Condensate Control for a DOAS-CRCP system ASHRAE Winter Meeting Symp. 3, Orlando-Feb. 6, 2005 Stanley A. Mumma, Ph.D., P.E

First Thoughts about control?

Nyquist Plots

Bodi PlotsZ and Laplace Transforms

Stability and dynamic response

SchematicsPoints li

st

Sequence of operation

BACnet

Page 4: Direct Digital DBT, %RH, and Condensate Control for a DOAS-CRCP system ASHRAE Winter Meeting Symp. 3, Orlando-Feb. 6, 2005 Stanley A. Mumma, Ph.D., P.E

DOAS-CRCP Design Concept

20-70% less OA,

DOAS Unit W/ Energy Recovery

Cool/Dry Supply

Parallel Sen. Radiant Cooling

System

High Induction Diffuser

Building With

Sensible and Latent

cooling decoupled

Page 5: Direct Digital DBT, %RH, and Condensate Control for a DOAS-CRCP system ASHRAE Winter Meeting Symp. 3, Orlando-Feb. 6, 2005 Stanley A. Mumma, Ph.D., P.E

Issues that impact Control• Thermal comfort, temperature and

humidity control.• DOAS SAT, neutral or cold.• Envelope, Internal generation (high

or low occ. Density), & Geo. Loc.• Std. 62, and IAQ.• ADPI with low to very low air flow.• Condensation control.• Instrumentation for control and

monitoring.• Controlled devices.• Desire for BACnet compatibility &

Web Access.• Control hardware and software.

Page 6: Direct Digital DBT, %RH, and Condensate Control for a DOAS-CRCP system ASHRAE Winter Meeting Symp. 3, Orlando-Feb. 6, 2005 Stanley A. Mumma, Ph.D., P.E

Schematic & Control Points: Single Zone DOAS-CRCP System

Page 7: Direct Digital DBT, %RH, and Condensate Control for a DOAS-CRCP system ASHRAE Winter Meeting Symp. 3, Orlando-Feb. 6, 2005 Stanley A. Mumma, Ph.D., P.E

2. Occupied-Unoccupied Control

Page 8: Direct Digital DBT, %RH, and Condensate Control for a DOAS-CRCP system ASHRAE Winter Meeting Symp. 3, Orlando-Feb. 6, 2005 Stanley A. Mumma, Ph.D., P.E

3. Enthalpy Wheel Control

Page 9: Direct Digital DBT, %RH, and Condensate Control for a DOAS-CRCP system ASHRAE Winter Meeting Symp. 3, Orlando-Feb. 6, 2005 Stanley A. Mumma, Ph.D., P.E

4. Chiller Control

Page 10: Direct Digital DBT, %RH, and Condensate Control for a DOAS-CRCP system ASHRAE Winter Meeting Symp. 3, Orlando-Feb. 6, 2005 Stanley A. Mumma, Ph.D., P.E

5. Cooling Coil Control

Page 11: Direct Digital DBT, %RH, and Condensate Control for a DOAS-CRCP system ASHRAE Winter Meeting Symp. 3, Orlando-Feb. 6, 2005 Stanley A. Mumma, Ph.D., P.E

6. CRCP Control

Page 12: Direct Digital DBT, %RH, and Condensate Control for a DOAS-CRCP system ASHRAE Winter Meeting Symp. 3, Orlando-Feb. 6, 2005 Stanley A. Mumma, Ph.D., P.E

7. Thermodynamic Calculations

Page 13: Direct Digital DBT, %RH, and Condensate Control for a DOAS-CRCP system ASHRAE Winter Meeting Symp. 3, Orlando-Feb. 6, 2005 Stanley A. Mumma, Ph.D., P.E

Extension to Multi-Zone Facility• Case 1, Low Occupancy Density Facilities

such as Offices. – Maintain low SAT, i.e. EW with CC.– Modulate the panel inlet water Temperature

rather than flow as in the single zone.– Space DPT sensing not required, provided

DOAS supply conditions maintained, but condensation sensing is still needed in some perimeter spaces.

– If movable sash facility, sash position sensing is required.

Page 14: Direct Digital DBT, %RH, and Condensate Control for a DOAS-CRCP system ASHRAE Winter Meeting Symp. 3, Orlando-Feb. 6, 2005 Stanley A. Mumma, Ph.D., P.E

Extension to Multi-Zone Facility• Case 2, High Occupancy Density Facilities

such as schools. – Maintain low design SAT with capability of

central “free” reheat, i.e. EW-CC-SW.– A critical space reset control will be discussed

next. The intent is to minimize terminal reheat energy use.

Page 15: Direct Digital DBT, %RH, and Condensate Control for a DOAS-CRCP system ASHRAE Winter Meeting Symp. 3, Orlando-Feb. 6, 2005 Stanley A. Mumma, Ph.D., P.E

Paper Figure 3

Space 1 of nDBT, %RH

EW--CC-- SWCRCP

ReHt

Is Terminal Reheat allowed? Yes!!!

See ASHRAE Std. 90.1- 2004; Sec. 6.5.2.1 “If the

air reheated does not exceed that required to

meet ASHRAE Std. 62.1”

Page 16: Direct Digital DBT, %RH, and Condensate Control for a DOAS-CRCP system ASHRAE Winter Meeting Symp. 3, Orlando-Feb. 6, 2005 Stanley A. Mumma, Ph.D., P.E

SpaceDBT, %RH

EW--CC-- SWCRCP

ReHt

Operate the EW when

OA h > RA h, otherwise off

OA

h

RA h,

Page 17: Direct Digital DBT, %RH, and Condensate Control for a DOAS-CRCP system ASHRAE Winter Meeting Symp. 3, Orlando-Feb. 6, 2005 Stanley A. Mumma, Ph.D., P.E

SpaceDBT, %RH

EW--CC-- SWCRCP

ReHt

Modulate the CC CV so

no space %RH > 55%or

no space DBT > 75

CC CV

Page 18: Direct Digital DBT, %RH, and Condensate Control for a DOAS-CRCP system ASHRAE Winter Meeting Symp. 3, Orlando-Feb. 6, 2005 Stanley A. Mumma, Ph.D., P.E
Page 19: Direct Digital DBT, %RH, and Condensate Control for a DOAS-CRCP system ASHRAE Winter Meeting Symp. 3, Orlando-Feb. 6, 2005 Stanley A. Mumma, Ph.D., P.E

SpaceDBT, %RH

EW--CC-- SWCRCP

ReHt

Modulate the SW speed to hold at least one CRCPCV wide open

CR

CP

CV

Page 20: Direct Digital DBT, %RH, and Condensate Control for a DOAS-CRCP system ASHRAE Winter Meeting Symp. 3, Orlando-Feb. 6, 2005 Stanley A. Mumma, Ph.D., P.E
Page 21: Direct Digital DBT, %RH, and Condensate Control for a DOAS-CRCP system ASHRAE Winter Meeting Symp. 3, Orlando-Feb. 6, 2005 Stanley A. Mumma, Ph.D., P.E

SpaceDBT, %RH

EW--CC-- SWCRCP

ReHt

Modulate the CRCP CV & the ReHt CV in sequence to

maintain the Space DBT @ 75F

CR

CP

CV

ReH

t C

V

Page 22: Direct Digital DBT, %RH, and Condensate Control for a DOAS-CRCP system ASHRAE Winter Meeting Symp. 3, Orlando-Feb. 6, 2005 Stanley A. Mumma, Ph.D., P.E
Page 23: Direct Digital DBT, %RH, and Condensate Control for a DOAS-CRCP system ASHRAE Winter Meeting Symp. 3, Orlando-Feb. 6, 2005 Stanley A. Mumma, Ph.D., P.E

Conclusions• The single zone DOAS-CRCP system has been

operating superbly now for over 3 years with the controls presented here.

• Without a single incidence of condensation.• Maintenance free.• Based upon that experience, the control was

extended to a multi-zone building utilizing low SAT. A CRITICAL ZONE DBT AND DPT RESET SCHEME

• The many interacting local control loops in the reset control will require care (slow response) to avoid hunting.

Page 24: Direct Digital DBT, %RH, and Condensate Control for a DOAS-CRCP system ASHRAE Winter Meeting Symp. 3, Orlando-Feb. 6, 2005 Stanley A. Mumma, Ph.D., P.E