dim_sa_e
TRANSCRIPT
-
7/28/2019 DIM_SA_e
1/2
Page 1 of 2
Signal amplier
Fitting instructions
DIM SA
BA
C
H
D
Description Function and application
The signal amplier DIM SA in combination with 1...10V control
units is used for the control of electronic ballasts (ECG) with a
1...10V interface.
The following applications are available, depending on the con-
nection (see the connection diagram):
Increase in the number of electronic ballasts and luminaires
that can be connected to the control unit.
Increase in the permissible control line length.
Conguration of lighting with daylight-dependent control or
daylight- and motion-dependent control (in combination with
a suitable light sensor or light and motion sensor).
Connections
The signal amplier has the following connections:
Power supply (A)
110V input (B)
110V output (C)
Installation Safety instructions
The signal amplier must only be installed and put into opera-
tion by a qualied electrician. The applicable safety regulations
and accident prevention regulations must be observed.
WARNING!
Exposed, live cables.
Danger of electric shock!
Only work on the signal amplier when it is
de-energised.
CAUTION!
Destruction of the signal amplier and other devices
through incorrect mounting!
Do not connect the control outputs of multiple
signal ampliers in parallel.
Only use ballasts with a 1...10V interface.
Do not exceed the maximum number of connect-
able components.
Only supply signal ampliers with an AC operat-
ing voltage, especially in networks with UPSsystems.
Connecting the signal amplier
D Increase in the number of electronic ballasts and lumi-
naires that can be connected to the control unit (H)
Connect the control output of the control unit with the
1...10V inputs of the signal amplier.
Connect the 1...10V outputs of the signal amplier with
the 1...10V control inputs of the electronic ballast.
Note:
Ensure that the conguration is symmetric:
As far as possible, distribute the number of electronicballasts evenly among the signal ampliers.
Connect all electronic ballasts to the signal ampliers if
possible. If some of the electronic ballasts are connected
directly to the control unit, dim settings and dim speeds
may vary within the system.
-
7/28/2019 DIM_SA_e
2/2
Page 2 of 2
OSRAM GmbH
Kunden Service Center
Customer-Service-Center (CSC)
Steinerne Furt 62
86167 Augsburg
Germany
Tel : +49 (0) 1803 677 - 200
(kostenpichtig / charges apply)
Fax.: +49 (0) 1803 677 - 202
www.osram.com
www.osram.de
400832109709584008321097095
IV 2009
DIM_SA_ma0904en_we1.01.indd
Installation (cont.)
H
The EMC requirements to EN 61547, EN 61347-11 and
EN 55015 are fullled.
Conformity with the relevant EU directives is
conrmed by the CE symbol.
E
F
G
Appendix Technical data
Operating voltage 230 V; 50-60 Hz (no DC operat ion)
Supply connection L, N, PE
Power consumption Approx. 2 W
Load capacity 110V input:
max. 1.5 mA 110V output:
max. 100 mA or 100 OSRAM
110V ECG
Protection class I
Protection type IP 20
Operating temperature 0 C +50 C
Dimensions
(L x W x H)
189 x 30 x 28 mm
Hole distance for
mounting
180 mm
E Increase in the permissible control line length of the
control unit (H)
Maximum line length between the distributors of the
signal ampliers: 300 m.
F Conguration of lighting with daylight-dependent con-
trol
Suitable light sensor: DIM MICO
G Conguration of lighting with daylight- and motion-
dependent control
Suitable light and motion combination sensor: DIM MULTI