    Signal amplier

    Fitting instructions

    DIM SA

    BA

    C

    H

    D

    Description Function and application

    The signal amplier DIM SA in combination with 1...10V control

    units is used for the control of electronic ballasts (ECG) with a

    1...10V interface.

    The following applications are available, depending on the con-

    nection (see the connection diagram):

    Increase in the number of electronic ballasts and luminaires

    that can be connected to the control unit.

    Increase in the permissible control line length.

    Conguration of lighting with daylight-dependent control or

    daylight- and motion-dependent control (in combination with

    a suitable light sensor or light and motion sensor).

    Connections

    The signal amplier has the following connections:

    Power supply (A)

    110V input (B)

    110V output (C)

    Installation Safety instructions

    The signal amplier must only be installed and put into opera-

    tion by a qualied electrician. The applicable safety regulations

    and accident prevention regulations must be observed.

    WARNING!

    Exposed, live cables.

    Danger of electric shock!

    Only work on the signal amplier when it is

    de-energised.

    CAUTION!

    Destruction of the signal amplier and other devices

    through incorrect mounting!

    Do not connect the control outputs of multiple

    signal ampliers in parallel.

    Only use ballasts with a 1...10V interface.

    Do not exceed the maximum number of connect-

    able components.

    Only supply signal ampliers with an AC operat-

    ing voltage, especially in networks with UPSsystems.

    Connecting the signal amplier

    D Increase in the number of electronic ballasts and lumi-

    naires that can be connected to the control unit (H)

    Connect the control output of the control unit with the

    1...10V inputs of the signal amplier.

    Connect the 1...10V outputs of the signal amplier with

    the 1...10V control inputs of the electronic ballast.

    Note:

    Ensure that the conguration is symmetric:

    As far as possible, distribute the number of electronicballasts evenly among the signal ampliers.

    Connect all electronic ballasts to the signal ampliers if

    possible. If some of the electronic ballasts are connected

    directly to the control unit, dim settings and dim speeds

    may vary within the system.

  • 7/28/2019 DIM_SA_e

    2/2

    Page 2 of 2

    OSRAM GmbH

    Kunden Service Center

    Customer-Service-Center (CSC)

    Steinerne Furt 62

    86167 Augsburg

    Germany

    Tel : +49 (0) 1803 677 - 200

    (kostenpichtig / charges apply)

    Fax.: +49 (0) 1803 677 - 202

    www.osram.com

    www.osram.de

    400832109709584008321097095

    IV 2009

    DIM_SA_ma0904en_we1.01.indd

    Installation (cont.)

    H

    The EMC requirements to EN 61547, EN 61347-11 and

    EN 55015 are fullled.

    Conformity with the relevant EU directives is

    conrmed by the CE symbol.

    E

    F

    G

    Appendix Technical data

    Operating voltage 230 V; 50-60 Hz (no DC operat ion)

    Supply connection L, N, PE

    Power consumption Approx. 2 W

    Load capacity 110V input:

    max. 1.5 mA 110V output:

    max. 100 mA or 100 OSRAM

    110V ECG

    Protection class I

    Protection type IP 20

    Operating temperature 0 C +50 C

    Dimensions

    (L x W x H)

    189 x 30 x 28 mm

    Hole distance for

    mounting

    180 mm

    E Increase in the permissible control line length of the

    control unit (H)

    Maximum line length between the distributors of the

    signal ampliers: 300 m.

    F Conguration of lighting with daylight-dependent con-

    trol

    Suitable light sensor: DIM MICO

    G Conguration of lighting with daylight- and motion-

    dependent control

    Suitable light and motion combination sensor: DIM MULTI