THERE IS LIGHT. AND THERE IS OSRAM.

QUICKTRONIC® DIMMABLE

Technical Guide September 2000

Dimmable high-frequency control gear for fluorescentlamps and compactfluorescent lamps

• Applications

• Instructions for installation in luminaires

• Wiring instructions

• Operating instructions

2046 QT dimm E 26.09.2000 9:34 Uhr Seite 3

Page 2: Dimming 1-10 Osram

2

1246 Quicktr Dimmbar Engl 26.09.2000 9:25 Uhr Seite 2

Page 3: Dimming 1-10 Osram

3

Contents

1. Introduction 41.1 The 1…10 V interface 61.2 How to use this Guide? 71.3 Where can I find what I’m looking for? 8

2. Basic circuits: Manual controllers 102.1 Control via potentiometer 102.2 Systems with up to 50 ECGs with manual control unit DIM MCU 102.3 Systems with switch 12

control or remote control (DIM ICM 10)

3. Basic circuits: Daylight-dependent controllers 183.1 Single-luminaire sensor DIM PICO 193.2 Mini constant unit DIM MICO 213.3 Multisensor DIM MULTI 23

4. Application: Complex or special circuits 284.1 Multi-channel systems with remote control 284.2 Scene controller DIM BEAMIT 314.3 Floor-standing luminaires with DIM MULTI 2 384.4 Choice of manual control or constant lighting control 444.5 Standby modes 454.6 Systems with lighting control system DIM KAD-S 474.7 Signal amplifier DIM SA 504.8 Control via analogue output 524.9 Control using instabus EIB 53

5. Special circuit diagrams, hints and tips 545.1 Circuits with fixed resistors 545.2 Upgrades: leading-edge phase dimmers and signal converter DIM SC 555.3 Cinema control 575.4 Temperature-dependent control 585.5 Combining several controllers 595.6 Placing upper and lower limits on the control voltage 605.7 Incorporating HALOTRONIC 61

6. Installation in luminaires, wiring and operating instructions 626.1 Installation in luminaires 626.2 Wiring instructions 666.3 Operating instructions 686.4 FAQ (frequently asked questions) 696.5 Troubleshooting tips 70

7. Range, lamp combinations 717.1 QUICKTRONIC® DIMMABLE 717.2 Lamps recommended for use with QUICKTRONIC® DIMMABLE 737.3 1…10 V dimming components from OSRAM 74

8. Appendix 778.1 Overview of applications 778.2 1…10 V dimming components from other manufacturers 818.3 ECOS 99 81

9. Index 82

1246 Quicktr Dimmbar Engl 26.09.2000 9:25 Uhr Seite 3

Page 4: Dimming 1-10 Osram

Dimmable lighting systems

Dimmable lighting systems are playing a more and more important role in allareas of application.

The reason is that many of the demands that are placed on lighting systemscan be met more easily and more elegantly with lighting controls. Economyand comfort are the driving forces here.

• Reducing lighting costs

• Raising comfort levels

• Promoting individuality

This has all been made possible thanks to technical developments overrecent years.

Modern dimmable ECGs with 1…10 V interfaces in combination with theappropriate controllers and sensors provide the basis for simple and cost-effective systems.

The right controller for any application

There are very many different ways in which dimmable ECGs can be used.Typical applications include offices and factories with daylight-dependentcontrollers, conference and meeting rooms with situation-dependent lightingand CAD rooms and control rooms with individual adjustment of the lightinglevel.

The heart of the lighting system is a QUICKTRONIC® DIMMABLE ECG with a1…10 V interface. This is controlled with a controller or a sensor. The choiceof the right 1…10 V dimmer components for controlling the lighting leveldepends on the particular application. The requirement profile for thedimmable lighting system must therefore be defined accurately.

4

1. Introduction

Cost savings in office lighting with dimmable ECGs for2 x L 58 W and daylight-dependent lighting control

• Up to 60% lower electricity costs• Short amortisation period• A positive contribution to the140 W

LLG

110 W

ECG

50 W

dimmableECG and

lighting sensor

Savings

60%

100DM

0Extra price

of luminaire

Paybackperiod

2,2 years 10 years

Savingson lightingcosts

350DM

• 2500 hours of operation per year• 20 Pf/kWh

1246 Quicktr Dimmbar Engl 26.09.2000 9:25 Uhr Seite 4

Page 5: Dimming 1-10 Osram

Manual control

Manual control using switches and remote control units, for example, offers ahigh degree of flexibility and can be adapted to the specific needs of the user.The functions of different 1…10 V controllers can be combined for tailor-madelighting control.

Automatic control

Automatic controllers with sensors are ideal for saving on lighting costs. Thelighting level is controlled by light sensors according to the amount of daylightavailable (constant lighting control), so free daylight is used. Energy savings ofup to 60% are possible. Potential savings of 70% and more can be achievedby using sensors with automatic disconnection, motion detectors and timeswitches.

Complex control

A simple link between the 1…10 V interface and the instabus EIB buildingservices control bus can be established via switching/dimming actuators.Computer control is also becoming more and more important.

5

System wattage

1 %

13 % 100 %

20 %

50 %

80 %

100 %

Lum

inou

s flu

x

QUICKTRONICDIMMABLE

®

Power consumption as a function of luminous flux

1246 Quicktr Dimmbar Engl 26.09.2000 9:25 Uhr Seite 5

Page 6: Dimming 1-10 Osram

6

Over the past few years dimmable ECGs with 1…10 V interfaces havebecome standard components in lighting control. These ECGs can bedimmed via a two-wire control line (1…10 V interface).

Properties of the 1…10 V interface:

1. Control is via an interference-proof dc voltage signal of 10V (maximumbrightness; control line open) to 1V (minimum brightness; control lineshort-circuited)

2. The control power is generated by the ECG (maximum current 0.6 mA per ECG)

3. The voltage on the control line is isolated from the power cable but is not at safety extra-low voltage (SELV).

4. ECGs connected to different phases can be dimmed via the samecontroller.

For wiring information see Sections 6.1 and 6.2

In view of the properties of the 1…10 V interface the following points shouldbe borne in mind:

• All the control lines of an ECG installation must be connected with thecorrect polarity (+/–).

• The control line is isolated from the power cable but is not at safety extra-low voltage (SELV). Cables and terminals approved for use with 230 Vmust therefore be used.

• The control voltage can be easily kept within upper and lower limits;controllers can be combined with one another (see 5.5 and 5.6).

• The ECG can be tested for correct operation as follows:

1. Switch on the ECG with the control line open. The lamp must start andoperate at rated voltage.

2. Short-circuit the control line (jumper). The lamp must operate atminimum brightness.

• Each QUICKTRONIC® DIMMABLE can be used as a normal non-dimmableECG if a controller is not connected to the control line.

• Dimmable ECGs are only dimmed via the 1…10 V interface; they areswitched via the power line.

• Check the maximum load capacity of the controller (switching output and1…10 V output).

• The connected controller must be able to accept the current supplied bythe ECG in the control line (current sink) and reduce the control voltage.This requirement is met by suitably dimensioned potentiometers and allOSRAM control components. Normal power supply units, converter cardsand so on do not necessarily have this ability. To check, connect thecontroller, set to lowest brightness and measure the voltage on the controlline. The value should be 1 V or less.

• QUICKTRONIC® DIMMABLE cannot be dimmed via the power line (e.g.with phase control or round control pulses).

1.1 The 1…10 V interface

1246 Quicktr Dimmbar Engl 26.09.2000 9:25 Uhr Seite 6

Page 7: Dimming 1-10 Osram

7

Ic – Uc characteristic(Control current/control voltage)

Control voltage in V

0.6

Con

trol

cur

rent

in m

A

10987654320 1

0.5

0.4

0.3

0.2

0.1

0

Control Voltage U in V

Lum

inou

s flu

x

Φ-Uc characteristic(Luminous flux/control voltage)

1.2 How to use this Guide

Target groups

The new October 1999 edition of the “QUICKTRONIC® DIMMABLE” Guide isan update of the last edition of January 1997 and now includes a largenumber of new system components that are indispensable for modernapplications of dimmable ECGs.

This Guide is intended for everyone who designs, plans, installs or operatesdimmable lighting systems. We have focused on practical considerations.

If you need a quick summary, we recommend that you read the Introduction(Chapter 1) and the chapters on basic circuits (Chapter 2+3).

In these 15 pages you will find everything you need to know about the typicalapplications of lighting controllers. In particular, Section 1.3 will give you agood grounding in dimmable lighting systems.

The part of this Guide intended for lighting professionals (Chapters 4 and 5)provides detailed descriptions of more complex circuits. Practical hints andtips round off the package.

If you so wish, you can skip these two chapters and come back to them later,but you must read Chapter 6. This provides you with all the necessaryinstructions for installing and operating the equipment. Chapters 7 and 8contain information on the ECGs and 1…10 V dimming components. Theyalso contain a number of pointers to help you choose the right controller.

Structure

1246 Quicktr Dimmbar Engl 26.09.2000 9:25 Uhr Seite 7

Page 8: Dimming 1-10 Osram

8

1.3 Where can I find what I’m looking for? Your problem First step

• You know what the lighting system has to do 1.3and you are looking for the right controller 8.1

• You want a summary of the 1…10 V dimming component 7.3from OSRAM

• You are looking for details on particular controllers 7.3

• You want to know whether a particular lamp can be dimmed 7.2

• You want to convince a customer of the benefits Introductionof a dimmable lighting system. 7.1

8.3

• You are having problems with an installed dimmable lighting system 6.5

For the sake of clarity, the following pictograms are used throughout thisGuide:

Manual control using a rotary potentiometer

Manual control using switches

Manual control using scenes

Manual control using a remote control unit

Constant lighting control

Time control

Motion detector or presence sensor

Control using instabus EIB

Control using a PC

Hints and tips

Pictograms

1246 Quicktr Dimmbar Engl 26.09.2000 9:26 Uhr Seite 8

Page 9: Dimming 1-10 Osram

9

The most common applications

Objective Application Controller Basic circuit

Energy costssavings

Increaselighting comfort

Increaseindividuality

Constant lighting control

Constant lighting control + motion detector

Time control

One control point

Multiple control points

Switch + remote control

Scene control withremote control

instabus EIB +PC

DIM PICO

DIM MICO

DIM MULTI

DIM MULTI 2

Automaticstairwell switch

Poti

DIM MCU

DIM ICM 10

DIM ICM 10

DIM BEAMIT

Switching/dimming actuator

PC card

page 19f

page 21f

page 23ff

page 38ff

page 46

page 10

page 10ff

page 12ff

page 12ff

page 31ff

page 53

page 52f

1246 Quicktr Dimmbar Engl 26.09.2000 9:26 Uhr Seite 9

Page 10: Dimming 1-10 Osram

The simplest way of controlling a lighting system is with a suitablydimensioned potentiometer (available in electrical retail outlets). Since thecontrol output of the DIM ECG is generated by the ECG itself, the resistancevalue depends on the number n of connected ECGs. It can be calculatedusing the following formula:

RPoti =100 kΩ log

n

If the calculated value is not in the resistance table the next higher valueshould be used, otherwise the lamps cannot be operated at their full output(note: this over-dimensioning may mean that the potentiometer may not turnthrough a complete rotation for controlling the brightness).

The potentiometer must be designed for an output of Ppot = 2.8 (mW) · n.

A mains switch is also needed to switch the lighting system on and off. Whenconnecting the potentiometer make sure that the full lighting level is reachedwhen the potentiometer is turned to the right.

If more than two ECGs are connected it is normally better to use a DIM MCUmanual control unit.

Floor-standing luminaires, single luminaires

Manual control unit DIM MCU is the standard solution for manual brightnesscontrol from a single control point (e.g. in small to medium size rooms withone door).

A maximum of 50 DIM ECGs can be controlled with on manual control unit.Control with a combination of two or more manual control units is notpossible. If more than one control point is to be installed it is best to equip thesystem with DIM ICM 10 and louvre switches (see 2.3).

Offices, small meeting rooms

10

2.1 Control via potentiometer

Application

2. Basic circuits: Manual controllers

On/Offswitch

NL – +

NL

NL

NL

NL

+

+

+ 4

3

2

1

4321

4321

DIM ECGLamp

Lamp

Lamp

DIM ECG

DIM ECG

Potentiometer

R = 100 kΩ log. n

n: Number of ECGs connected

Control via potentiometer

2.2 Systems with up to 50 ECGs with manual control unit DIMMCU

Application

1246 Quicktr Dimmbar Engl 26.09.2000 9:26 Uhr Seite 10

Page 11: Dimming 1-10 Osram

11

There is a pushbutton integrated in the manual control unit (electricallyisolated from the brightness control). This switching contact is used toactuate relays to switch ECGs together in different circuits or on differentmains phases. A maximum of 10 single-lamp or 5 two-lamp dimmable ECGs can be switched directly in a circuit.

For systems with more than 50 dimmable ECGs see 4.7

The manual control unit is suitable for installation in flush-type boxes with adiameter of 55/60 mm. There are two versions available. DIM MCU P issupplied with a rotary button and cover plate, whereas DIM MCU has neitherof these. In this case, the button and cover plate should be purchasedseparately from the Berker, Gira or Jung range.

Please note:The manual control unit may be destroyed if incorrectly installed.A separate supply voltage is not required for the manual control unit.

Once the system has been installed, switch off all lighting, turn the button onthe manual control unit to the left as far as it will go and adjust the trimmeruntil you can see light.

Switching on/off

NL – +

NL

Manual Control UnitDIM MCU

NL

NL

NL

+

+

+ 4

3

2

1

4321

4321

DIM ECGLamp

Lamp

Lamp

– +

DIM ECG

DIM ECG

Wiring diagram for systemswith a maximum of 10 single-lamp dimmable ECGs or 5 two-lamp dimmable ECGs

Wiring diagram for systems with a maximum of 50 dimmableECGs

Installation

Setting the minimum brightness

NL3

Manual Control UnitDIM MCU

NL

NL

NL

+

+

+ 4

3

2

1

4321

4321

NL

L2

L1

Relais

N – +L3L2L1

Max. 50 DIM ECG

– +

DIM ECG

DIM ECG

DIM ECG

Lamp

Lamp

Lamp

1246 Quicktr Dimmbar Engl 26.09.2000 9:26 Uhr Seite 11

Page 12: Dimming 1-10 Osram

12

2.3 Systems with switch control or remote control(DIM ICM 10)

Most rooms over a certain size have more than one door and thereforerequire more than one control point for the lighting.

DIM ICM 10 is a compact basic control module that provides a convenientway of dimming and switching the QUICKTRONIC® DIMMABLE. The DIM ICM10 can be controlled either with an ordinary commercially available switch or aDIM FB infra-red remote control unit.

The DIM ICM 10 receives the incoming control signals and converts them to1…10 V signals for the dimmable ECG. When it is switched on, the dimmableECG is connected via a floating relay contact to the supply voltage. Fordimming, the 1…10 V output of the DIM ICM 10 then provides the requiredcontrol voltage.

The DIM ICM 10 has a memory function for the last brightness value so when it is switched off at the switch or with the remote control unit and thenswitched back on again it will automatically revert to its last dimmer setting.

80

80

54

60

33

DIM MCU P

54

51

33

4

71

71

Sicherung

DIM MCU

Trim potentio-meter for settingthe minimalbrightness

Technical data for manual control units DIM MCUReference: DIM MCU or DIM MCU P

Dimensions: for flush-type box Ø = 55/60 mm (see dimensional diagram)

Rotary axis: Ø = 4mm, l =14 mm and 6 mm thread

Type of fixing: Claws or screws

Permissible ambient temperature – 20 °C to + 50 °C

Terminals: Screw terminalsPermissible wire cross-section: max. 1.5 mm2

Terminal –: – (control signal)Terminal +: + (control signal)Terminal and Switching contact 230V mains voltageMains connection: Not required

Effects of incorrect wiring230V at control terminal: Fuse defective or total failureReversing +/–: always minimum luminous flux

Control signal range: 1 to 10V DC (voltage source in dimmable ECG)

Load capacity of the manual control Maximum of 40 mA or a maximum of 50 dimmable ECG unit for brightness control: or 16 signal amplifiers DIM SA

Switching contact: 250 V/6 A (10 single-lamp or 5 two-lamp dimmable ECGs)

Fuse: Fine fuse F500/H250

Cover and rotary button: From the Berker (2891), Gira (30900)or Jung (240-10) range, as appropriate

Note: Control with a combination of two or more manual control units is notpossible.

1246 Quicktr Dimmbar Engl 26.09.2000 9:26 Uhr Seite 12

Page 13: Dimming 1-10 Osram

With DIM ICM 10 it is possible to set up a multi-channel lighting system(maximum of 10 channels, see 4.1). The channels are assigned with thechannel selector on the casing.

Meeting rooms, offices, conference rooms, foyers, control rooms, schools

a) Three-switch control

The lighting system is controlled by an ON/OFF switch and a combined louvreswitch combination, consisting of two make contacts.

Pressing the “ON/OFF” switch switches the element on or off; the memoryfunction stores the last brightness value and restores this value when thesystem is switched on again. Pressing the “BRIGHTER” switch when thesystem is switched off causes the module to start at the lowest brightnessvalue; pressing the “DARKER” switch causes the module to start at themaximum brightness value and then adjust either up or down until the endvalue is reached. The combination switch must be connected to the(ON/OFF), (BRIGHTER) and (DARKER) terminals as shown in the diagramabove.

A two-switch arrangement (without the ON/OFF switch) is not possible.

b) Single-switch control

Another option is single-switch control. An ordinary switch can be brieflypressed (< 400 ms) to switch on or off the control gear and therefore theassociated lamps.

If the switch is off and is then pressed for longer (> 400 ms) the moduleautomatically goes into dimmer mode, starting at the lowest brightness valueand continues to increase the brightness level for as long as the switchremains pressed. The process stops when the end value is reached.

If the switch is on and is then pressed for longer (> 400 ms) the module goesto either end value in alternation.

13

Application

Control via a switch

ICM-10

250V10A~

otherswitchesin parallel

OUT

BUS

N

L

1

2

ON/OFF

Three-way switch(detail)

ICM-10

250V10A~ OUT

BUS

N

L

1

2

otherswitchesin parallel

One.way switch(detail)

Wiring diagramfor one-way switch

Wiring diagram for three-way switch

1246 Quicktr Dimmbar Engl 26.09.2000 9:26 Uhr Seite 13

Page 14: Dimming 1-10 Osram

If one-way switches are used only the and terminals need to beconnected. Terminals and remain unconnected.

Ordinary installation cable can be used for the connection from the switchesto the modules. The cable should not be more than 50 m in length. If there ismore than one control point in the room the switch combinations can beconnected in parallel. A mixed combination of one-way and three-way switches is possible.

The infra-red remote control, in combination with the IR receiver, is used forcentral wireless dimming and switching of pushbutton dimmer/IR controlmodule DIM ICM 10. DIM ICM 10 has a connection for the IR receiver that isprotected against polarity reversal. The IR receiver can be installed togetherwith the DIM ICM 10 anywhere in the room.

The infra-red-remote control can be used to control ten lighting channelsindividually or with the common control button. There is an ON/OFF buttonand a BRIGHTER/DARKER button combination for each channel. (The lastrow of buttons enables all the lighting channels installed in a multi-channelsystem to be controlled at the same time).

Because the selected carrier frequency is 455 kHz, data transfer from the IRremote control is not affected by IR interference from fluorescent lamps.

The range of the transmitter is ten meters.

14

Control with IR remote controlDIM FB and IR receiver DIM IE

Optional RCconnection

DIM ECG

DIM ECG

DIM ECG

DIM ECG

Fluorescent lamp

Fluorescent lamp

Fluorescent lamp

Fluorescent lampSwitch

Furtherswitch

ON/OFF

Control with DIM ICM-10 with direct use of the switching contact (for the maximum number of ECGs see Table 1)

1246 Quicktr Dimmbar Engl 26.09.2000 9:26 Uhr Seite 14

Page 15: Dimming 1-10 Osram

Note: The BUS connection is required only in combination with DIM BK 10required (see 4.1).

Table 1

Maximum switching contact loadNo. ECG model10 HF 1x58/230-240 DIM5 HF 2x58/230-240 DIM16 HF 1x36/230-240 DIM8 HF 2x36/230-240 DIM16 HF 1x18/230-240 DIM8 HF 2x18/230-240 DIM20 QT-D/E 1x18/230-240 DIM20 QT-D/E 1x26/230-240 DIM20 QT-T/E 1x32/230-240 DIM10 QT-T/E 1x42/230-240 DIM10 QT-T/E 2x18/230-240 DIM10 QT-T/E 2x26/230-240 DIM10 QT-T/E 2x32/230-240 DIM

15

Maximum permitted load on thepushbutton dimming /IR controlmodule DIM ICM-10

To further channels(DIM ICM 10)

To further DIM ICM-10 units

OptionalRC connection

Lamp

Lamp

Lamp

DIM ECG

DIM ECG

DIM ECG

Contactor

Furtherswitches

switchON/OFF

Control of a maximum of 100 dimmable ECGs with DIM ICM-10

Table 2

Maximum load on the dimmer outputNo. ECG model100 HF ...x.../230-240 DIM100 QT-D/E ...x.../230-240 DIM100 QT-T/E ...x.../230-240 DIM

One DIM SA places the same load on DIM ICM-10 as 3 dimmable ECGs.

1246 Quicktr Dimmbar Engl 26.09.2000 9:26 Uhr Seite 15

Page 16: Dimming 1-10 Osram

16

189 180

28

30

4.5

Technical data for pushbutton dimming/IR control module DIM ICM-10Reference DIM ICM-10

Dimensions: see dimensional diagram

Weight: 180 g

Maximum ambient temperature: 0 °C … + 40 °C

Terminals: Screw terminals for single wires

Maximum cable cross-section: 2.5 mm2

Rated voltage: 220 V (– 10 %) – 240 V (+ 6 %)

Frequency: AC 50 … 60 Hz; DC not permissible: Destroys unit

Switching contact: 230 V/10 A

Power input: 1 – 2 W

Protection class: 1

Maximum cable lengths:to the switches: 50 mto the bus controller: (DIM BK 10) 300 mto the IR receiver: (DIM IE) 10 m

Control signal range:, , (switch): + 15 V; 0 V

Bus: + 10 V; 0 V, digital signalOut: 1…10 V DC; max. 100 mA

Note: Parallel connection of more than one DIM ICM 10 in a control circuit is not possible.

After an interruption in the power supply (emergency lighting, mains voltagefailures) the lamps remain switched off and have to be switched on again byhand; no memory effect.

1246 Quicktr Dimmbar Engl 26.09.2000 9:26 Uhr Seite 16

Page 17: Dimming 1-10 Osram

17

SW

28SW

2113

8 21.1

PG

13.

5

approx.35

Technical data for IR receiver diode DIM IEReference: DIM IE

Dimensions: see dimensional diagram

Type of fixing: Drill hole:Ø = 21 mm (PG 13,5)Material thickness: max. 16 mm

Weight: 30 g

Permissible ambient temperatureOperation: 0 ºC to + 40 ºCStorage: 20 ºC to + 40 ºC

Terminals: 3-pin plug connection with mechanicalpolarity reversal protection

Cable length: 70 cm ready made, Can be extended up to 10 m (2 wires + shielding)

Rated voltage: 5 V DC from DIM ICM-10

Power input: 12.5 mW

Note: The DIM ICM 10, DIM FB and DIM IE components are not compatible with scenecontrol components DIM BEAMIT, DIM IRM and DIM IRE.

186

64

Height:16.5 mm

Technical data for IR remote control DIM FBReference: DIM FB

Dimensions: see dimensional diagram

Weight: 100 g

Permissible ambient temperatureOperation: 0 ˚C ... + 50 ˚CStorage: – 20 ˚C ... + 50 ˚C

Transmitter range: 10 m (no shadowing)

Rated voltage: 6 V DC (battery)4 x 1.5 V (micro)

Battery type: IEC LR 03 (micro)

1246 Quicktr Dimmbar Engl 26.09.2000 9:26 Uhr Seite 17

Page 18: Dimming 1-10 Osram

Saving energy with daylight

18

3. Basic circuits: Daylight-dependent controllers

The sun is the free and inexhaustible source of energy for our planet and also our most powerful source of light. We should make use of what it has tooffer in order to reduce the amount of energy we need to supply and thereforeour costs. And how can we do this? By producing only as much artificial lightas we need to make up what we don’t get from the sun.

A light sensor measures the brightness in the room and controls it with theappropriate dimmable electronic control gear so that a predefined lightinglevel is maintained at all times. This means that not only can energy be savedon sunny days but full use can be made of the available daylight on overcastdays.

Depending on the light sensor and the ECG used, energy savings ofmore than can be achieved.

For a comparison of the various sensors see Section 7.3. Project-specificcost/benefit calculations can be easily produced with the ECOS 99 program(see 8.3)

Obviously, the further into the centre of a room you go, the less daylight isavailable. For this reason, as in this example, each of the three lighting stripson the ceiling can be controlled by its own sensor. This arrangement achieves maximum energy savings since each of the stripsbenefits from constant lighting control.

Annual energy consumption of a 1x58 W luminaire in a typical officeapplication (2300 h), comparison of different control gear. Constant lighting control provides energy savings of 60% even comparedwith efficient 100% ECG operation.

1st Light sensor 2nd Light sensor 3rd Light sensor

Illuminance En

Constant setpoint value

Lighting strip 1 Lighting strip 2 Lighting strip 3

Lighting strip 1

Lighting strip 2

Lighting strip 3

LLG lead-lag circuit

100% ECG operation

Constant lighting control

1246 Quicktr Dimmbar Engl 26.09.2000 9:26 Uhr Seite 18

Page 19: Dimming 1-10 Osram

19

DIM PICO is a simple light sensor for dimmable ECGs with a 1…10 Vinterface for installation in a single luminaire or for applications in individualoffices.

This mini light sensor has a light control function that reduces the amount ofartificial light by approximately 50% measured against the increase in daylight.

The diagram shows how a typical workplace installation works for a lightinglevel of 500 lux.

In large rooms or if strip lighting is installed, use of more than one DIM PICOmay lead to different brightness values on the ceiling. Mini constant unit DIM

MICO is recommended for such applications.

Single luminaires, individual offices

The light sensor should be mounted on the lamp with a T8 clip or a T5 clip asshown in the diagram. One side of the lamp clip has two nipples at the endsso the cable can be routed properly along the side of the fluorescent lamp.The sensor can also be installed in the luminaire with a suitable support to beconstructed by the user.

• The light sensor should be set with the aid of a lux meter with little daylight(evenings, darkened room) in a room furnished for use.

• Turn the casing of the DIM PICO until the aperture is barely open.

• The luminaire should be operated for approx. 30 minutes to ensure that theluminous flux has stabilised.

• Turn the casing to increase the aperture until the unit starts to dim thelamp(s). Turn back the setting slightly so that the luminaire does not start todim too early.

• When making adjustments to the light sensor you should remember thatyour own body will affect the luminous flux that reaches the light sensor.You should therefore stand well away from the sensor to check the finalsetting.

• In the case of luminaires in comparable positions you can copy the settingsfrom one photocell to the next by marking the position of the casing.

• Note: The time constant in the light sensor means that you need to wait afew seconds after each adjustment so that the luminous flux can stabilise.

3.1 Single-luminaire sensor DIM PICO

Application

Installation

Operation

1500

1000

500

500 1000 1500

Work surfacelighting (lux)

Daylight (lux)

Luminous flux fromluminaire

DaylightTotel with DIM PICO

1246 Quicktr Dimmbar Engl 26.09.2000 9:26 Uhr Seite 19

Page 20: Dimming 1-10 Osram

20

Control via DIM PICO

On/offswitch

white

striped

DIM ECG

Maximum of 5 ECGs on the control line

lamp

Leave at least 5 cm free from the end of the lamp.

21.4 mm

Lamp

Technical data for DIM PICO Reference DIM PICO

Output 1…10 V-Signal

Load capacity of the output max. 3 mA (maximum of 5 QUICKTRONIC® DIMMABLE)

Cable length 700 mm

Cable type 2 x 0.5 mm 2 (soldered ends)

Polarity – : striped cable+: white cableNote: Reversing the connections Will not damage the light sensor.

Measurement angle 50°

Ambient temperature 5°C to 55°C

Protection class Class II

Type of protection IP 20

Weight 21 g

Material Makrolon/polycarbonate

Note: In the case of screw terminals, the soldered ends have to be removedto ensure reliable contact.Two plastic clips (for T8 and T5 lamps) are included.

1246 Quicktr Dimmbar Engl 26.09.2000 9:26 Uhr Seite 20

Page 21: Dimming 1-10 Osram

21

3.2 Mini constant unit DIM MICO Mini constant unit DIM MICO is the standard solution for constant lightingcontrol for strip lighting. The control function is built in.

DIM MICO does not need a separate power supply; the control current of theECG is sufficient. The two-pole connection cable is connected directly to the1…10V control input of the dimmable ECG. A trim potentiometer is providedat the side for precise and continuous adjustment of the lighting level.

The mini constant unit can control a maximum of 100 QUICKTRONIC®

DIMMABLE units, thereby eliminating the major weakness of single luminairecontrol, namely the different impressions of brightness on the ceiling.

Groups of luminaires that have the same proportion of daylight (zones ofequal brightness) are controlled by a single DIM MICO. In rooms with striplighting arranged parallel to the window (such as in schools and offices) werecommend using one DIM MICO per strip.

The casing for single-hole mounting opens up a wide range of possibilities.DIM MICO is supplied with a mounting bracket (the mounting bracket canalso be removed) so that it can be clipped directly on the fluorescent lamp (T8 tubular lamp or OSRAM DULUX L).

Strip lighting, individual offices, open-plan offices, schools

• The light sensor should be placed within the room so that it registers boththe artificial light and natural daylight as mixed light.

• The light sensor must be installed so that objects or persons do notmaterially affect the measurements.

- Do not install directly next to a window (minimum angle to the window40°, rule of thumb: l > 0.8 h see diagram)

- The “eye” of the light sensor should not be directly exposed to the lightfrom the luminaires.

- Do not install directly in passageways (in corridors or on doors)

• The light sensor should be set in artificial light (at night).

• Reversing + and – causes the light to be set at its lowest dimmer setting(the ECG is not damaged as a result).

Applications

Installation notes, operation

1246 Quicktr Dimmbar Engl 26.09.2000 9:26 Uhr Seite 21

Page 22: Dimming 1-10 Osram

The mounting bracket of the DIM MICO must not be placed near the lamp electrodes (risk of overheating), nor where a wire coming loose from aterminal could come into contact with it.

22

Installation instructions

Control via DIM MICO

Min. clearance l

Win

dow

Light sensor

Hei

ght a

bove

win

dow

sill

h

Lamp

with mounting bracket with mounting bracket

LampDIM ECG

DIM ECG

DIM ECG

Maximum of 100 ECGs on the control line

On/offswitch

brown

white

Mini constant unit

Lamp

Lamp

Note: Maximum control line length: 100 m

Technical data for mini constant unit DIM MICOReference DIM MICO

Dimensions see dimensional diagram

Weight 100 g (incl. bracket)

Operating temperature 0 ºC to + 45 ºC

Cable length 80 cm cable

Control range 15-800 lux (illuminance at mini constant unit)

Detection angle 90°

Maximum permissible cable length 100m(DIM MICO — ECG)

Output 1…10V control signal

Protection class IP20

Control and load connections see wiring diagrams

Settling time for the control output approx. 20 seconds (depends on the control difference)

Load capacity of the control output 50 mA (approx. 100 ECGs)

Single-hole installation 19 mm dia. hole

1246 Quicktr Dimmbar Engl 26.09.2000 9:26 Uhr Seite 22

Page 23: Dimming 1-10 Osram

Multisensor DIM MULTI is designed for lighting control at workplaces or inrooms. It maintains the light at a constant level. If sufficient daylight is availablethe lighting system is switched off. It has an integrated motion detector sothat the lighting is only switched on if there is at least one person in the room.This is the most efficient form of lighting control and achieves energy savingsof 70% and more.

Strip lighting, individual offices, open-plan offices, schools

There are four different modes of operation:

• Alternative 1: DIM MULTI is used as a standalone unit to switch andcontrol the lighting in one area.

• Alternative 2: More than one DIM MULTI is installed and each is used toswitch and control a separate area; all the units take part in motiondetection.

• Alternative 3: One DIM MULTI switches and controls a relatively largearea; several additional DIM MULTI units are linked together to increase thedetection area.

• Alternative 4: The motion detectors are deactivated (turn the switch to 0).

23

Applications

3.3 Multisensor DIM MULTI

Modes of operation

Alternative 1: • Single office• Only DIM MULTI

Alternative 3: • Open plan office, large area to cover• Shared presence detector• Shared lighting control

Alternative 4: • Single or open plan office• Motion detector inactive• Connect illuminated control switch on supply side

Alternative 2: • Open plan office, large area to cover• Shared presence detector• Separate lighting control

1246 Quicktr Dimmbar Engl 26.09.2000 9:26 Uhr Seite 23

Page 24: Dimming 1-10 Osram

24

The brightness value to be maintained in the room or at the workplace can beset on the multisensor. It detects the level of mixed light (comprising artificiallight and natural daylight) with an integrated brightness sensor and adjuststhe room lighting according to the available daylight. If there is sufficientdaylight it switches the artificial lighting off after a preset delay.

If a presence is no longer detected at the workplace the unit slowly turnsdown the lighting after a preset delay and then switches it off. If someoneenters the room or approaches the workplace the lighting is switched onagain, provided artificial light is required. An additional switch can be used toswitch the lighting on.

The presence detector can be switched off at the unit (O/I switch). Thelighting will remain switched on until sufficient daylight is available and it istherefore no longer required. If the presence detector is deactivated on theunit an illuminated control switch should be connected ahead of it so that thesystem does not switch on again at dusk (Alternative 4).

The motion sensor on the constant light unit has a detection angle of approx.100°, covering an area with a diameter of approx. 7 m in a room with a ceilingheight of 3 m.

If larger rooms or areas are to be monitored, units can be interlinked(alternatives 2+3). Each unit can control the brightness of part of the overallarea. Presence detection is performed jointly however. In this case, it issufficient if one of the units detects movement (alternative 2). The additionalunits may be used simply as motion sensors to increase the detection area orprovide extra cover (alternative 3).

How it works

Detection area and expandingthe presence detectioncapability

3 m

3.5 mDetection field for the motion detector:7 m max.

2.5 m

1246 Quicktr Dimmbar Engl 26.09.2000 9:26 Uhr Seite 24

Page 25: Dimming 1-10 Osram

25

Design, installation andconnection

Installation instructions

The multisensor can be surface mounted on the ceiling (or, with the lamp clipssupplied, on T8 or T5 fluorescent lamps).

If it is to be mounted on the ceiling you can remove the baseplate from theunit and use screws to attach it to the ceiling. You can then use the cablesupplied to connect it to the lamps, or other suitable cables in the base. Thecontrol unit is simply attached.

With the aid of the lamp clips supplied the unit can be installed in luminaireswith a louvre at least 60 mm wide. The appropriate lamp clip is inserted in thebase of the DIM MULTI so that the entire unit can be attached to 26 mm or16 mm fluorescent lamps. The clip must be placed at the start or end of thelamp to avoid an excessive load on the lamp. The unit can be adjusted todifferent depths of the louvre luminaires by pushing in or pulling out the lampclips.

Wherever possible, the constant light unit should be placed directly above theworkplace for which lighting control is needed. The room brightness shouldalways be measured indirectly; light from the room lighting or workplacelighting should not shine directly into the unit. The optical system of thepresence sensor is designed for a room height of between 2.5 m and 3.0 m.In rooms with higher ceilings the detection density of the motion sensor islower.

If possible, the unit should be installed so that the brightness trimmer facesthe window. This ensures that the light sensor is pointing into the room. Avoidplacing the sensor in drafts (near a ventilator for example).

Wiring diagrams:

DIM MULTI as a standalone unit for switching and controlling an area.

Alternative 1

Maximum of 50 ECGs on the control line

DIM ECG

DIM ECG

DIM ECG

Lamp

Lamp

Lamp

Note:If the presence sensor is deactivated an illuminated control switch should beconnected on the supply side

1246 Quicktr Dimmbar Engl 26.09.2000 9:26 Uhr Seite 25

Page 26: Dimming 1-10 Osram

26

Alternative 2

Maximum load capacity of the switching outputs on DIM MULTI

No. ECG model30 HF 1x18/230-240 DIM

30 HF 1x36/230-240 DIM

20 HF 1x58/230-240 DIM

20 HF 2x18/230-240 DIM

20 HF 2x36/230-240 DIM

10 HF 2x58/230-240 DIM

Alternative 3

Alternative 4

Several DIM MULTI units with joint presence detection, each switching andcontrolling a separate area.

One DIM MULTI for switching and controlling a large area; the area forpresence detection is extended with additional units.

Presence detection is inactive (0); a control switch is connected ahead of the unit.

DIM ECGCircuit 1

To furtherDIM MULTIs

DIM ECGCircuit 2

DIM ECGCircuit 1

To furtherDIM MULTIs

On/Off

DIM ECGCircuit 1

1246 Quicktr Dimmbar Engl 26.09.2000 9:26 Uhr Seite 26

Page 27: Dimming 1-10 Osram

27

71

58

71

42

Brightness setting

Presencedetection: active (I) inactive (0)

Adjustable switch-off delay for presencedetection (5 – 30 min)

Technical data for multisensor DIM MULTIReference DIM MULTI

Operating voltage: 230Vac 50/60 Hz, DC not permitted (destroys unit)

Fuse protection: External 16A

Power input: Approx. 1W

Operating temperature: 0°C to +50°C

Adjustable light value: Approx. 50-800 lux (directly on the unit)

Detection angle, mounting height: Approx. 100° (light and presence sensor), 2.5–3m (optimum height for motion detection)

Supply and load connections: L, N, switched L (↑ )

Control connections: +, - (1…10 V of the ECG or transformers), B (parallel connection of the motion sensor)*No safety extra-low voltage (no SELV)

Load capacity at control output: 50 mA (approx. 50 QUICKTRONIC® DIMMABLE units)

Terminal assignment: See wiring diagram – If incorrectly connectedthere is a risk of failure or destruction

Load capacity at switching output: 5 A ohmic load

Settling time of the control output: Approx. 10–30 seconds(depending on the control difference)

Switch-off delay: 1–3 minutes (depending on the control difference)

Absence delay: Adjustable between 5 and 30 minutes

Parallel connection of units: Maximum of 5 units (motion detection)*

Protection class, type of protection: II (total insulation), IP 20

Maximum cable length: 100 m (control lines 0.5mm2,load and supply lines 1.5mm2)

Cable connection: Screw terminals for single-wire or fine-wireconductors 0.3–1.5mm2 (with 1.5m cable).

Design: Plastic housing for installation on ceilings or in louvre luminaires

Dimensions, weight: W x H x D = 58 x 71 x 42mm, approx. 150 g* Connection B can also be used if the connected ECG is on different phases.

1246 Quicktr Dimmbar Engl 26.09.2000 9:26 Uhr Seite 27

Page 28: Dimming 1-10 Osram

4.1 Multi-channel systems with remote control

Multi-channel systems with DIM ICM 10 enable different lighting strips in alarge lighting system to be controlled separately with a single remote control.One DIM ICM 10 is needed per lighting channel.

The channels are assigned to the rows of buttons on the IR remote controlwith the aid of the red channel selector on the DIM ICM 10.

There are three ways with DIM ICM 10 of implementing multi-channel lightingcontrol systems with up to ten channels:

1) The DIM ICM 10 units are interconnected via the DIM BK 10 bussystem

A DIM BK 10 bus controlled with an IR receiver is also installed as the centralcontrol unit. No IR receivers are then needed for the DIM ICM 10 units.

Remote control (multiple)

Bus controller DIM BK 10 receives the signals sent by the remote control viathe IR receiver and forwards the processed signals to the connected DIM ICM10 units. In this arrangement the channels can be controlled not onlyindividually but also together at the push of a button. This group controlfeature is possible with the group switch on the remote control and withswitches connected to the DIM BK 10.

Note: In rooms with alcoves and the like it may be necessary to install anumber of IR receivers to ensure proper infra-red links. This is done byconnecting DIM BK 10 bus controllers in parallel (BUS and connections). Ifyou are installing more than one bus control you should set priorities on theDIM BK 10 to avoid data conflicts (rotary switch: 1 to 10).

28

4. Application: Complex or special circuits

DIM BK10 DIM ICM-10

DIM ICM-10 EVG

EVG

DIM ICM-10

DIM FB

DIM IE

ECG

ECG

1246 Quicktr Dimmbar Engl 26.09.2000 9:26 Uhr Seite 28

Page 29: Dimming 1-10 Osram

2) DIM ICM 10 are installed with one IR receiver each

This multi-channel system consists in principle of a number of independentsingle-channel systems. The wiring is as shown on pages 14f an in the abovewiring diagrams. For a five-channel system, for example, five DIM ICM 10units, five IR receivers and one remote control are needed. Common controlof all the channels cannot be provided with this arrangement, however.

Note: parallel connection of several DIM ICM 10 units in one control circuit isnot possible.

3) Maximum of three channels: several DIM ICM 10 units and one IRreceiver DIM IE

If a maximum of three DIM ICM 10 units are connected to form a multi-channel system there is no need for one of the DIM BK 10 units. The infra-redreceiver IE is connected directly to the DIM ICM 10. Group and individualcontrol are possible.

All the DIM ICM 10 units can be operated with different channel settings. Thesupply voltage to the IR receiver comes from the first DIM ICM 10. The othertwo IE receivers are connected with the IR signal and earth (brown cable andshielding).

29

Multi-channel system with buscontrollers DIM BK 10 and DIMICM 10 (wiring detail)

L1L2L3N

PE

Further switchesfor sum control(optional)

To further channels

Bus controllerDIM BK 10

DIM IE

L

N

BUS

IE

EIN/AUS

(DIM ICM 10)

DIM ICM 10

DIM FB

Combine with wiring diagram from page 15;BUS and must be connected;

, and only if switches are used

Vc whiteIR brownGND shield

Vc whiteIR brownGND shield

DIM ICM 10 #1

DIM ICM 10 #2

DIM ICM 10 #3

IR brown

IR brown

DIM IE

Multi-channel system: three DIM ICM 10 units and one DIM IE

1246 Quicktr Dimmbar Engl 26.09.2000 9:26 Uhr Seite 29

Page 30: Dimming 1-10 Osram

30

Technical data for bus controller DIM BK 10Designation: DIM BK 10

Rated voltage: 230 V; 220 V (-10%) to 240 V (+ 6%)

Frequency: AC 50/60 Hz (DC not permissible: destroys unit)

Power input: 1 W

Voltage pulses : To DIN VDE 0160

Continual overvoltage: Up to 300 Vrms (not normal use)

Behaviour at undervoltage or loss of mains voltage: IR remote control or group control inoperable

Effects of incorrect wiring:230 V at control terminal: Unit destroyedReversing of 4 and 6: Incorrect operation of IR remote controls and

group control

Maximum cable lengths:to switches: 50 mto control modules (BUS connection) 300 m

Control signal range:switches (terminals 1, 2, 3): +15 V; 0 VBUS (terminal 4): +15 V; 0 V, digital signal

Delay for changes in luminous flux approx. t = 5 s100% 1% or 1% 100%

Load capacity of the BK-10 50 DIM ICM 10 units or 9 further bus controllers Can be connected within the permissible cable lengths

Dimensions l x w x h: 53 x 49 x 29 mm

Type of fixing: DIN rail with plastic clip

Weight: 80 g

Terminals: Screw terminals without wire protection

Maximum cable cross-section: 2.5 mm2 (single-wire)

Important: On this model the polarity reversal protected connector providedby the manufacturer must be removed and rewired. OSRAM cannot thereforeundertake any guarantee for this solution. OSRAM cannot supply additionalconnectors.(Source: Horst Göbel, D-67005 Ludwigshafen, Germany).

49

53

29

1246 Quicktr Dimmbar Engl 26.09.2000 9:26 Uhr Seite 30

Page 31: Dimming 1-10 Osram

This scene controller for dimmable ECGs enables up to four lighting groups(channels) to be controlled with a high degree of ease and flexibility. Eachsituation (meeting, PC work, overhead projection, and so on) calls for lightingadapted for the purpose. The various light sources in the room, such asceiling, wall, cove and accent lighting, can be configured with the aid of scenecontrol to create coordinated lighting arrangement that suits the situation.

The small elegant remote control is used to switch any of the four individualchannels on or off and dim them or call up a maximum of four individuallyadjustable lighting scenes.

Halogen lamps can also be included via 1…10 V converters for electronic HT1…10 DIM transformers.

Offices, conference rooms, lecture rooms, exhibition rooms, meeting rooms,restaurants, CAD workplaces

The following three components are needed for scene controller DIM BEAMIT:

DIM BEAMIT 4-channel manual scene transmitterDIM IRM IR module (one DIM IRM per lighting channel)DIM IRE IR eye (one DIM IRE per lighting channel)

It is possible to use one DIM IRE for max. 4 DIM IRM modules.

The manual scene transmitter offers two modes of operation (channel mode,scene mode):

Channel mode (slide switch to Channel setting):

A maximum of four 4 IR modules can be controlled

Button pressed briefly Button held down

ON/OFF Dimmer operates until Max. or Min. is reached *)

*) Direction changes each time

31

4.2 Scene controllerDIM BEAMIT

Applications

System components

Manual scene transmitterDIM BEAMIT

IR eyeDIM IRE

IR moduleDIM IRM

DIM ECG

IR moduleDIM IRM

DIM ECG

IR eyeDIM IRE

IR moduleDIM IRM

HT 1-10 DIM HALOTRONIC

Lamp

Lamp

Lamp

Channel 1

Channel 2

Channel 3

1246 Quicktr Dimmbar Engl 26.09.2000 9:26 Uhr Seite 31

Page 32: Dimming 1-10 Osram

32

Addressing

1. Set the dial (1) under the battery cover on the manual transmitter to Group A (for other settings of the group switch see end of 4.2).

2. Set Group A on the address switch on the IR module and set the addressaccording to the control button you want.

3. Make sure the transmitter is positioned so that there is a line of sight fromthe transmitter to the receiver windows of all the IR receivers to becontrolled. The maximum range of both types of transmitter is 10 m.

Note: When the button is pressed the red LED must light.

Scene mode (slide switch to Scene setting):

The DIM BEAMIT manual scene transmitter can call up four different scenes.Each control button on the transmitter corresponds to a scene.

The 4/OFF button is provided for use with any particular scene or for the “All OFF” command (all units switched off or returned to the starting position).

NOTE: The OFF command is not set up by default; it has to be programmedby hand.

GROUPA B

CDEF

G

A BC

DEFG

1

2

3Scene Channel

1 2

3 4OFF

Rear view, without battery cover. Set to Group A (example)

View of the keypad (Address buttons 1 to 4)

Key:

1 Group switch

2 Control buttons

3 Slide switch

1246 Quicktr Dimmbar Engl 26.09.2000 9:26 Uhr Seite 32

Page 33: Dimming 1-10 Osram

Programming a scene

Set Scene to OFF (ALL OFF)

Calling up a scene(switching on)

Deleting a scene

Plan the scene in advance so it can be programmed without interruption.

1. Move the slide switch (2) to the Scene setting.

2. Press a control button (e.g. 1) for the new scene and hold it down for atleast 4 s (until the red LED flashes continuously). Programming mode is activated.

3. Move the slide switch to Channel (the red LED will continue to flash).

4. Set up the scene: The units involved in the scene you are about to set up should be set tothe required state with the manual transmitter (dimmer setting and/orON/OFF).Example: - Luminaire group 1 with address 1/Group A: ON

- Luminaire group 2 with address 2/Group A: 50%- Luminaire group 3 with address 3/Group A: 30%- Luminaire group 4 with address 4/Group A: OFF

NOTE: For reasons of signal reliability, each channel should be switched onor off at least once. If a control button is not pressed within 30 seconds theprogramming mode will shut down automatically. If units are not set withthe manual scene transmitter this setting must therefore be made within 30 seconds.

5. When the scene has been set up move the slide switch back to Scene.The red LED will go out. The scene is now stored.

6. Stick a label with the programming instructions in the appropriate language(choice of four languages) in the battery cover. NOTE: The scenes are stored with scene numbers in the IR module. Theseare permanently assigned to the buttons (1 to 4/OFF) on the manual scenetransmitter. If more than one manual scene transmitter is used in thesame room a maximum of four identical scenes can be programmedand called up on the individual transmitters.

The procedure is the same as for “Programming a scene”. In step 4, however, all the units involved have to be switched to OFF with the manual transmitter or returned to their basic settings.

Press the relevant scene button briefly to switch on the scenestored for that button.

Individual scene An individual scene can be replaced by setting up a newone over it

All scenes Move slide switch to Scene. Hold down the 4/OFFbutton for at least 10 s. The red LED will flash slowly atfirst and then rapidly. All scenes are now deleted.

33

Programming a scene1 Move slide switch to Scene.

2 Press control button (1 to 4/OFF) for more than 4 s until the red LED flashes

3 Move slide switch to Channel

4 Set up the scene with the manualtransmitter:

5 Move slide switch to Scene (the red LED will go out).

The scene is stored.

Deleting a scenePress control button 4/OFF for more than 10 s (the LED will flash rapidly)

1246 Quicktr Dimmbar Engl 26.09.2000 9:26 Uhr Seite 33

Page 34: Dimming 1-10 Osram

34

IR module DIM IRM IR modules use the 1…10 V interface to control the dimmable ECGs. The IR modules themselves can be controlled from a DIM BEAMIT scenetransmitter or with an external switch on the IR module (see wiring diagram).A number of switches can be connected in parallel. (Note: Only non-illuminated switches can be connected to the switch terminal of the IRmodule, with a switch connection cable no longer than 100 m).

IR module DIM IRM is designed for installation in luminaires.

Switching: IR module DIM IRM uses a relay contact to switch the connectedload (dimmable ECG) on or off. Up to four ECGs can be switched directly.Because of the high peak currents that occur when an ECG is switched on,luminaire groups with five or more ECGs have to be switched via a powerrelay.

Dimming: The DIM IRM module uses the 1…10 V control output to controlthe brightness of the fluorescent lamp. A maximum of 50 ECGs can beconnected. If more than 50 ECGs are to be connected a DIM SA signalamplifier will also be needed.

Addressing: see above

The IR eye is separate from the DIM IRM module. It is used as a receiver forthe infra-red signal from DIM BEAMIT.

To ensure it operates correctly and achieves its intended range of 10 m, theIR eye must have a line of sight to the transmitter and must be placed whereit is shielded as far as possible from other light sources.

A BC

DEFG

1 23

45678

1

2

ADDRESS GROUP

40

178

200

190

Setting the addressing switch

Height: 31

IR eye DIM IRE

Key:

1 addressing switch2 Fine fuse (T 6.3 A)

1246 Quicktr Dimmbar Engl 26.09.2000 9:26 Uhr Seite 34

Page 35: Dimming 1-10 Osram

35

Installation instructions The IR eye must be placed so that it can be reached by the infra-red signal of the IR transmitter. If the connecting cable (2 m) is too short it may beextended to 10 m. This extension cable must have the same number of wires,the same colour of wires and the same insulation thickness as the originalconnecting cable (recommended cross-section: 1.5 mm2). Do not run cablefor the IR eye parallel to the earth conductor.

CAUTION: IR eyes are not suitable for outdoor applications (IP 20).The IR eye must never be connected to the mains.

QUICKTRONICDIM ECG

QUICKTRONICDIM ECG

QUICKTRONICDIM ECG

Switch

LN

L’N

NLT

IR moduleDIM IRM

IR eyeDIM IRE

+–

– +

1…10 V

IR eye

brownblackblue

Earthing via luminaire casing

(mm)

14–

16

10–

13

5–

9

1–

4

ø 46 mm

20 m

m

10 m

m

Installation 1 Drill a 13 mm hole in the suspended ceiling

2 Set the clamping springs of the IR eyeaccording to the ceiling thickness (seediagram)

3 Push the supply cable with the three wireends into the hole

4 Insert the IR eye in the hole and turn to theleft as far as it will go

5 Route the cable to the place where IRmodule DIM IRM is installed.

(To remove the IR eye, turn it to the left andwithdraw it from the hole)

Adjustable clearances (see diagram)1– 4 mm5–9 mm

10–13 mm14–16 mm

Technical data for manual scene transmitter DIM BEAMITReference DIM BEAMIT

Dimensions 80 x 52 x 15 mm

Voltage supply Battery: 1.5 V alkaline (micro, LR 03, AAA, AM4)

Battery life Approx. 2 to 3 years

IR carrier frequency 447.5 kHz

Range Max. 10 m

Coding: 28 possibilities (7 groups of four addresses each)

1246 Quicktr Dimmbar Engl 26.09.2000 9:26 Uhr Seite 35

Page 36: Dimming 1-10 Osram

The components are compatible with all other BEAMIT components suppliedby the Feller company that carry the . symbol.

The above mentioned components are not compatible with systemcomponents DIM ICM 10, DIM FB, DIM IE or DIM BK 10.

36

Technical data for IR module DIM IRMReference DIM IRM

Control output 1…10 V, for a maximum of 50 ECGs, 60 mA (current sink)

Rated voltage 230 – 240 V/50–60 HzDC not permissible

Power range 1000 VA (if five or more ECGs use power relay)

Dimensions 200 x 40 x 31 mm

Hole spacing 190 mm

Type of protection IP 20, dry installation

Temperature range 0 – 55 °C

Intrinsic consumption approx. 0.75 W

Protection Fine fuse T 6.3 A (quartz sand filled)

Coding 56 possibilities (7 groups of eight addresses each)

Switch input Present, any number can be connected in parallel, use non-illuminated switches

A maximum of two IR eyes can be connected to an IR module DIM IRM (parallel connection).IRM module DIM IRM must be supplied permanently with power. The lighting scenes have to be set up again if there is an interruption in power supply lasting morethan 24 hours.CAUTION: Multiple IR modules DIM IRM cannot be connected to one IR eye.

Technical data for IR eye DIM IREReference DIM IRE

IR carrier frequency 447.5 kHz

Dimensions Ø 46 x 20 mm

Thickness of suspended ceiling 1–16 mm

Hole Ø 13 mm

Cable length 2 m, can be extended to 10 m

Type of protection IP 20

1246 Quicktr Dimmbar Engl 26.09.2000 9:27 Uhr Seite 36

Page 37: Dimming 1-10 Osram

37

Troubleshooting

Fault Cause Remedy

Load does not light up No supply voltage Check fuse/fine fuseor react Replace fine fuse with one of

the same type and value (quartz sand filled)

Load defective Check fluorescent lamp and ECG

LED function display on the IR Replace battery in the transmitter does not light when transmitter a button is pressed. The batteryin the IR transmitter is flat.

Fluorescent lamp defective Replace lamp

Incorrect installation Get a qualified electrician to check the installation

The load (lamps etc.) only The IR beam is not hitting the Position the transmitter so thatwork via externals switches IR receiver window the IR beam hits the IR eyeand not via infra-red The IR eye is not properly Check the wiring

connected

The transmitter and receiver Check the transmitter andaddresses do not match receiver addresses

LED function display on the IR Replace the battery in the transmitter does not light when transmittera button is pressed. The battery in the IR transmitter is flat.

A scene cannot be No scenes have been stored Program a scenecalled up

The control button has been pres- Don’t press the control button sed for too long (max. 400 ms) as long

The receiver for a scene is The receiver is not being Call up the scene again innot reacting to the call-up reached by the call-up signal the direction of the receivercommand

The receiver was not reached Re-program the sceneby the programming signal

Note: Significance of the group switchChannel mode: A maximum of 28 channels can be controlled with the DIMBEAMIT manual scene transmitter (this can be set with the group switch atthe back of the manual transmitter). Up to 28 channels can therefore be usedin large offices with several manual transmitters.

Scene mode: Since the scenes are stored in the IR module under scenenumbers, it should theoretically be possible to incorporate 28 channels intothe four scenes. However it is not very practical to keep resetting the groupswitches each day (in channel mode). The setting on the group switch has noeffect on how the scenes are called up. If more than one manual scenetransmitter is used in the same room a maximum of four scenes can beprogrammed and called up from the transmitters.

We therefore recommend that you use the BEAMIT system primarilyas a four-channel system.

1246 Quicktr Dimmbar Engl 26.09.2000 9:27 Uhr Seite 37

Page 38: Dimming 1-10 Osram

The two-part DIM MULTI 2 multisensor system is designed for daylight-dependent lighting control for individual luminaires (primarily floor-standingluminaires) or for room lighting. The lighting system is switched on by amotion sensor only if at least one person is present in the room. The setpointvalue is set on a central switch (standard pushbutton switch), or, if you needto, you can switch to manual control mode.

The kit supplied comprises the following two components:

• Multisensor controller (for installation in luminaires)

• Light and motion sensor (integrated in a single casing)

Floor-standing luminaires, suspended strip lighting

1. Normal operation

• When someone enters the room the presence sensor switches the light on(provided the setpoint value is not exceeded). The light sensor detects thelevel of mixed light (comprising artificial light and natural daylight) andadjusts the room lighting according to the available daylight.

• If there is sufficient daylight it switches the artificial lighting off after a presetdelay (10 minutes). As daylight fades the lighting system is switched backon, provided there is at least one person still present.

• If a presence is no longer detected the unit slowly turns down the lightingafter an adjustable delay (1 to 30 minutes) and then switches it off after thepreset switch-off delay (10 minutes). If someone enters the room the lightingis switched on again, provided artificial light is required, and returns to itsconstant value.

• If the lighting system is turned up or dimmed down and a new light value isnot stored the system goes into control mode. Daylight has no effect on thelight value set. After the system has been switched off and on again(manually or by the presence sensor) the unit returns to the stored controlvalue.

2. Semi-automatic operation

It is possible to change to semi-automatic operation (also called holiday modeor green mode) with an external switch (possibly concealed) or with suitablewiring at the multisensor controller.

• In semi-automatic mode the lighting system is not automatically switchedon by movement within the room. You have to use the switch. Thisarrangement ensures that luminaires that are not being used (in holidayperiods, for example) are not switched on unnecessarily.

• If the lighting system is switched off because there is ample natural daylight,it is switched on again as daylight fades and the motion sensor detectssomeone in the room.

• Turn the lighting up and dim it down by holding down the button until themaximum and minimum values are reached; pressing the switch againreverses the direction.

• Store the lighting value as a constant value by pressing the control buttontwice. If the value has been successfully stored the lamp will flash.

• Switch on or off by pushing the button briefly.

• If the lighting system is switched off while there is someone still in thedetection area it will remain switched off and can only be switched on againmanually or if someone enters the room after a certain adjustable delay.

38

4.3 Floor-standing luminaireswith DIM MULTI 2

Operation

Setting and using the setpoint value

Application

1246 Quicktr Dimmbar Engl 26.09.2000 9:27 Uhr Seite 38

Page 39: Dimming 1-10 Osram

39

Operation without a motion sensor

The multisensor controller can also be operated without a motion sensor andonly with a light sensor. In normal operation, the unit now switches the lightingsystem on and off according to the lighting conditions and maintains thelighting level at the stored constant value.

Mains voltage interruption (via a switch or break contact) or failure

When power returns after an interruption in the mains voltage the lightingsystem switches on again (after an adjustable delay) and returns to the storedconstant value.

Function Action

Switch on luminaire Press button briefly. The luminaire only switches on if there is someone in the room.The luminaire adjusts to the last light value stored.

Switch off luminaire Press button briefly. The luminaire switches off after a short delay, irrespective of the operating condition.

More light required Hold down button until the required higher light value is reached.

Less light required Hold down button until the required lower light value is reached.

Go from more light to less Release the switch briefly and hold light or vice versa down again.

Store setpoint value Double-clicking stores the last light value.The last value stored is retained indefinitely, even if the luminaire is not connected to the power supply. The lamp will flash to indicate that the value has been successfully stored.

Switch on one or more Briefly interrupting the power supply luminaires together (switched socket, etc.) switches on all the (emergency ON) luminaires connected to this circuit. They

each adjust to the last light values stored for them.

Overview of the functions of the central switch

1246 Quicktr Dimmbar Engl 26.09.2000 9:27 Uhr Seite 39

Page 40: Dimming 1-10 Osram

The light sensor has an axial detection angle of 130° and the motion sensor adetection angle of approx. 100°, which means that an area with a diameter ofaround 7 m can be covered in a room with a ceiling height of 3 m.

To increase the detection area or provide denser coverage, a number ofsensors can be connected to the multisensor controller. A mixed value(average value) from the connected sensors is then used to measure the lightvalue.

1. Multisensor controller

The casing of the multisensor controller can be installed directly in theluminaires to be controlled. It is fixed in place with two screws. The connected control gear or transformers are supplied directly from theswitching output of the multisensor controller. Its neutral conductor can berouted to the load. When installing the unit, make sure to set the desired delayfor presence detection. The unit must be installed in an enclosed casing or ina luminaire.

2. Light and motion sensor

The sensor can be installed directly in the luminaires to be controlled. It is fixed in place with two screws. If possible, the light and motion sensorsshould be installed so that they point at the people to be detected. The roombrightness should always be measured indirectly; direct light from the roomlighting or workplace lighting should be avoided. Avoid placing the sensor indrafts (near a ventilator for example) as this may cause the sensor to triggerunnecessarily.

Installation and connection

40

Increasing the detection area

3 m

3.5 mDetection field for the motion detector:7 m max.

2.5 m

1246 Quicktr Dimmbar Engl 26.09.2000 9:27 Uhr Seite 40

Page 41: Dimming 1-10 Osram

41

Wiring diagrams

2 3 4 5

N

1L

12 13 14 15

8 9 10 11 6 7

Out, max. 20mA1…10V 0V

Delay time

1-30min.

SwitchesAutomatic/semi-automatic

Light and motion sensor

Switches:On/offBrighter/darkerStore

Multisensor controller

green yellow brown white

Light and motion sensor

green yellow brown white

Light and motion sensor

1. Multisensor controller with a light and motion sensor in normal operation.

2. Multisensor controller with several light and motion sensors and achangeover switch for semi- automatic operation.

green yellow brown white

2 3 4 5

N

1L

12 13 14 15

Light and motion sensor8 9 10 11 6 7

Out, max. 20mA1…10V 0V

Switches:On/offBrighter/darkerStore

Delay time

1-30min.

Multisensor controller

Light and motion sensor

1246 Quicktr Dimmbar Engl 26.09.2000 9:27 Uhr Seite 41

Page 42: Dimming 1-10 Osram

42

Technical data for DIM MULTI 2 1. Multisensor controllerOperating voltage: 230 – 240V, ~ 50/60 Hz, DC not permitted (destroys unit)Fuse protection: External 16 APower input: Approx. 1 W Operating temperature: 0 °C to + 50 °C Adjustable light value: Approx. 20 - 1000 lux (directly at the sensor)Supply and load connections: L, N, PE, switched L (`↑ )Control connections: +, - (1…10 V), sensor and pushbutton or

switch inputs < 10 VDC, nosafety extra-low voltage (SELV)

Load capacity of control output: 100 mA (approx. 100 QUICKTRONIC® DIMMABLEunits), 3 mA active for power dimmer

Terminal assignment: See wiring diagram or printed label If incorrectly connected there isa risk of failure or destruction

Load capacity at switching output: 5 A ohmic load ⇒ 30 * HF 1x18/230-240 DIM, 20 * HF 2x18/230-240 DIM,30 * HF 1x36/230-240 DIM, 20 * HF 2x36/230-240 DIM,20 * HF 1x58/230-240 DIM, 10 * HF 2x58/230-240 DIM

Control time for maintaining 30 s (for full control range)constant value:Delay for absence: Adjustable between 1 and 30 min

(set-screw on the casing)Control delay: 30 s from 100 % to minimum luminous fluxSwitch-off delay: 10 min (after lighting system is dimmed

by light or absence)Parallel connection of sensors: A maximum of 3 light and motion sensorsProtection class, type of protection: I (protective earth), IP 20Maximum cable length: 100 m (control lines 0.5 mm2, load and supply

cables 1.5 mm2)Control terminals: Plug-in terminals for single-wire conductors

0.1 – 0.75 mm2, fine-wire conductors 0.1 – 0.5 mm2

Supply and load terminals: Plug-in terminals for single-wire conductors 0.1 – 1.5 mm2, fine-wire conductors 0.1– 1.0mm2

Dimensions, weight: W x H x D= 189 x 30 x 29 mm, hole spacing 180 mm, approx. 150 g

Note: If the luminaire does not switch on immediately the switch is actuated,cover the sensor with your hand and try again.

‰ 189‰‰ 180

28

304.

5

1246 Quicktr Dimmbar Engl 26.09.2000 9:27 Uhr Seite 42

Page 43: Dimming 1-10 Osram

43

2. Light and motion sensorOperating voltage: 5 VDC (from multisensor controller)Power input: Approx. 5 mW Operating temperature: 0 °C to +50 °C Operating range: Approx. 20 – 1000 lux

(together with multisensor controller)Connections: green (+ 5 V), yellow (light signal),

brown (0 V), white (motion signal) No safety extra-low voltageIf incorrectly connected there is a risk of failure or destruction

Detection area 130° light sensor, 100° motion detector

Parallel connection of sensors: A maximum 3 light and motion sensorsProtection class, type of protection: II (total insulation), IP 20Maximum cable length: 50 m (2 m available at the sensor)Dimensions: See dimensional drawingWeight: Approx. 60 g

Cable lengthapprox. 2 m

1246 Quicktr Dimmbar Engl 26.09.2000 9:27 Uhr Seite 43

Page 44: Dimming 1-10 Osram

44

4.4 Choice of manual control orconstant lighting control

Maximum of 50 ECGs on the control line

Manual control unitHF DIM MCU

DIM ECG

DIM ECG

DIM ECG

brown

white

Mini constant unitDIM MICO

Note: The maximum length of the control line is 50 m

Often you will only want to dim the lighting manually when it is too bright inthe room. In such cases it is sufficient simply to connect DIM MICO and DIMMCU in parallel (without a changeover switch). The light sensor must setwhen DIM MCU is at its 100% setting.

Maximum of 50 ECGs on the control line

Manual control unitHF DIM MCU

DIM ECG

DIM ECG

DIM ECG

brown

whiteChangeoverswitch

Mini constant unitDIM MICO

Either of the two controllers can be selected by switching at the positive pole of the control line.

Note: The maximum length of the control line is 50 m

1246 Quicktr Dimmbar Engl 26.09.2000 9:27 Uhr Seite 44

Page 45: Dimming 1-10 Osram

45

Frequent on/off switching is not ideal for fluorescent lamps or compactfluorescent lamps. Up to now, incandescent lamps have therefore beenpreferred for applications that involve extremely frequent on/off switching,despite the high power consumption. In its standby mode, QUICKTRONIC®

DIMMABLE dims the light whenever it is not needed, eliminating unnecessaryswitching and saving energy.

What’s more, since the light is not completely switched off there is alwaysenough residual light to find your way around. Full light is available instantly,with no pre-heating delay.

Typical applications for this standby circuit include all applications withfrequent on/off switching, such as stairwells, corridors and undergroundgarages, particularly if the light is controlled with motion detectors or timeswitches.

Stairwells, underground garages, corridors

The power ON/OFF information from the motion detector is converted bysignal converter DIM SC into a 1…10 V control voltage which is then used toadjust the dimmer setting between 100% and 1%. The motion detector musthave a proper switching contact; units with Triac switches (for two-wire con-nection, for example) would still need a base load. Several motion detectorsmay be connected in parallel, according to manufacturers’ instructions.

4.5 Standby modes

Application

Standby switching with motion detector

Further luminairesMotion detector

Signal converter

DIM ECG

1246 Quicktr Dimmbar Engl 26.09.2000 9:27 Uhr Seite 45

Page 46: Dimming 1-10 Osram

A special time switch for stairwell lighting (Siemens model 5TT 1302) is usedfor standby switching of the dimmable ECG.

At the push of a button the stairwell lighting time switch switches thedimmable ECG on (100% light). After a maximum of 10 minutes (the time canbe adjusted) the light is dimmed to a preselected level. After a total of 30minutes it is switched off entirely. This 30-minute cycle is restarted each timethe switch is operated.

Standby mode brings its greatest benefit in the evening when the stairwell ismost heavily used. The light changes only between the two settings andactual use of the light switch is rare. At night-time when the stairwell is notused for lengthy periods the remaining 13% power consumption at the lowestdimmer setting is also saved.

For technical data for automatic stairwell switches see the Siemens catalogue.

Since the switch acts on the mains voltage (L) it can be replaced by a motiondetector. Parallel connection with the switch is also possible.

Since the switch-on time is set on the stairwell lighting time switch the switch-on time on the motion detector can and should be set to minimum.

46

Standby switching with timeswitch for stairwell lighting

Standby switching with stairwelllighting time switch and motiondetector

Further luminaires

Stairwell time switch

TSwitch

DIM ECG

Further luminaires

Stairwell time switch

T

DIM ECG

Motion detector

1246 Quicktr Dimmbar Engl 26.09.2000 9:27 Uhr Seite 46

Page 47: Dimming 1-10 Osram

47

Lighting systems with daylight-dependent light control can be operated moreeffectively if the artificial light is switched off as soon as there is sufficientnatural daylight. Such a system consists of a DIM KAD-S lighting controlsystem, a light sensor and a setpoint generator.

The advantage over the other light sensors for constant lighting control is thatan external setpoint generator can be provided in an easily accessible place.

This is useful if the room has such a high ceiling that the sensors are difficultto access.

An alternative to the DIM KAD-S is the AQAD-S unit supplied by Altenburger(order directly from Altenburger or your local retailer). This unit has a setpoint generator built-in.

Offices, factories

A lighting system controlled by a DIM KAD-S unit has two possible modes ofoperation:

1. Semi-automatic with the restart inhibitor off

The setpoint generator is used to select the brightness value to be maintained(e.g. 500 lx). The artificial light moves only between “0” and the fixedmaximum value.

The constant lighting control system continuously compares the actual valuewith the setpoint value and sends the control voltage needed to adjust thebrightness of the artificial light to the ECGs after a fixed delay of around 3seconds.

The time taken to go from 100% luminous flux to the lowest dimmer settingor vice versa is 50 seconds.

If the daylight component at the reference location (light sensor) exceeds thesetpoint value the constant lighting control system switches off the artificiallight after a delay of 4 minutes either directly or (if the wattage is relativelyhigh) with a floating relay contact via contactors (or relays) that can be setseparately.

If, during these 4 minutes, the brightness level dips below the setpoint valueagain (as clouds pass over the sun, for example) this time will not start againuntil the brightness level rises back above the setpoint value.

This delay has been selected so that rapid changes in conditions at thelowest dimmer setting do not cause the system to repeatedly switch on andoff again.

The DIM KAD-S module automatically switches the lighting system on againwhen the brightness level falls below the setpoint value.

4.6 Systems with lighting controlsystem DIM KAD-S

Applications

Operation

1246 Quicktr Dimmbar Engl 26.09.2000 9:27 Uhr Seite 47

Page 48: Dimming 1-10 Osram

48

Semi-automatic control with aconstant lighting control systemand light sensor

2. Semi-automatic with the restart inhibitor on

Instead of automatic activation, you can select manual restart with the“Restart inhibitor” switch on the constant lighting control system. In this case,the lighting system is switched on with the ON/OFF switch. In all otherrespects this operating mode is the same as described in 1. above.

The advantages of constant lighting control with automatic shutdown lie notonly in the savings in residual energy at the lowest dimmer setting but also inlonger lamp life. Because the lamps are switched off, the number of hoursthat they operate each day is reduced and therefore the relamping interval isincreased.

The delays indicated on page 47 depend on the control variables in theconstant lighting control circuit, so in actual practice they may vary slightlyfrom these values according to the prevailing lighting conditions. As far asrestarting the lamps is concerned, you should be aware that this takes placeslightly below the setpoint value (built-in hysteresis). This is necessary toprevent the lighting system being permanently switched on and off around theilluminance setpoint.

The setpoint generator should be wired as shown below, using a standardpotentiometer (potentiometer circuit). This wiring diagram is better than the diagram on page 29 (particularly if theilluminance exceeds 500 lx at the light sensor).

NL

NL

NL

NL

+

+

+ 4

3

2

1

4321

4321

DIM ECG

N – +L

ON/OFF Out+–

NL

Light sensorLF/d/D Maximum of 50 ECGs on the control line

Lamp

Lamp

Lamp

DIM ECG

DIM ECG

KAD-SIn+

Lightsensor

+12V

–VC

On/offswitch

+–

3 blue

2 red

1 green

ElectronicpotentiomerSetpointgenerator22 kΩ

NL

NL

NL

NL

+

+

+ 4

3

2

1

4321

4321

N – +L

Out+–

NL

KAD-SIn+

+12V

–VC

+–

DIM ECG

Light sensorLF/d/D Maximum of 50 ECGs on the control line

Lamp

Lamp

Lamp

DIM ECG

DIM ECG

On/offswitch

3 blue

2 red

1 green

Setpointgenerator22 kΩ

ON/OFF

Lightsensor

1246 Quicktr Dimmbar Engl 26.09.2000 9:27 Uhr Seite 48

Page 49: Dimming 1-10 Osram

Setpoint generator: 22kOhm potentiometer (in potentiometer circuit) orelectronic potentiometer (normal + and –cabling)

ON/OFF switch: The switch input must not be bridged

Restart inhibitor ON: The ON/OFF switch must be connected, otherwisethe lamp cannot be switched

Restart inhibitor OFF: The ON/OFF switch is not needed; switching of thephase before the DIM KAD-S is possible

Effect of voltage interruption: The DIM KAD-S has a memory function; inother words, after a voltage interruption the module resumes operation at itslast setting

Light sensor: The DIM PICO and DIM MICO light sensors are not suitable

Maximum sensitivity at the light sensor: 1000 lx

Temperature: Temperatures up to 55°C are not critical

49

Notes

2,2

19,2

20,5

2819

1346

max. 8

237 230

30

29

4,5

Light sensor LF/d/D (included in scope of supply)

1246 Quicktr Dimmbar Engl 26.09.2000 9:27 Uhr Seite 49

Page 50: Dimming 1-10 Osram

50

4.7 Signal amplifier DIM SA

Technical data for constant lighting control system DIM KAD-SReference DIM KAD-SDimensions See dimensional diagramDistance between mounting holes See dimensional diagramType of fixing Screws Ø = 4 mmWeight 200 gOperating temperature 0 ºC to + 45 ºCTerminals Plug-in terminals

Mains terminals max. 1.5 mm2

Control terminals max. 0.5 mm2

Light sensor connections green:12Vred: Vcblue: -

Rated voltage 220 V (-10%) to 240V (+6%) Frequency AC 50 & 60 Hz; DC not permitted: destroys unitPower input 1.5 mWProtection class I (with PE because of metal casing)Control output 50 mA (approx. 50 ECGs or 15 signal amplifiers)Relay contact AC 5 A (approx. 15 ECGs)Light sensors LF/d/D (included in scope of supply)*Setpoint generator External with trimmer and rotary potentiometers(22kW)Motion detectors Any number can be connected in parallelInput current 1 mA (to controller)Delay

from 100% to 1% luminous flux: 50 suntil KAD-S switches off: 4 minfor the control circuit: 3s

* Note: The other light sensors (DIM PICO, DIM MICO, DIM MULTI and DIM MULTI 2) are notsuitable for DIM KAD-S.

DIM SA signal amplifiers are required for controlling the brightness of largegroups of dimmable ECGs if the load capacity of the relevant controllers orsensors is exceeded (see table below).

Maximum load capacity of the 1…10 V control output

Controller Number of dimmable ECGsDIM MCU 50DIM ICM 10 100DIM IRM 50DIM MICO 100DIM MULTI 50DIM MULTI 2 30DIM KAD-S 50DIM SC 10DIM SA 100

1246 Quicktr Dimmbar Engl 26.09.2000 9:27 Uhr Seite 50

Page 51: Dimming 1-10 Osram

Up to 100 dimmable ECGs or 33 further signal amplifiers can be connectedat the output of the DIM SA (one DIM SA places the same load on a controlleras three dimmable ECGs) or a combination of both. In the case of systems with more than 100 ECGs, several signal amplifierstherefore have to be cascaded.

51

NL3

Manual control unitHF DIM MCU

NL

NL

NL

+

+

+ 4

3

2

1

4321

4321

NL

L2

L1

Relay

N – +L3L2L1

Maximum of 100 ECGs on the control line

Signal amplifierDIM SA

In Out+ +––

NL

Lamp

Lamp

Lamp

DIM ECG

DIM ECG

DIM ECG

– +

Maximum number of ECGs for switchingdepends on:the load capacity of the automatic cutoutsthe load capacity of the contactors

Block diagram for the 1…10 V control line

DIM SAControllerin out

DIM ECG

Maximum of 100 ECGs

DIM ECG

1246 Quicktr Dimmbar Engl 26.09.2000 9:27 Uhr Seite 51

Page 52: Dimming 1-10 Osram

52

4.8 Control via analogue output

Requirements

Technical data for signal amplifier DIM SAReference: DIM SADimensions: See dimensional diagram, casing for

installation in luminairesDistance between mounting holes: See dimensional diagramType of fixing: Screws Ø d 4 mmWeight: 150 gPermissible ambient temperature: – 20 °C& + 50 °CTerminals: Detachable plug terminals for single-wire cablesPermissible wire cross-section

Mains terminals: N, L, PE: 2 x 0.75 mm2 eachControl terminals: 0.5 mm2

Light sensor terminals: +12 V, –, Vc: 0.5 mm2

Rated voltage: 220 V (– 10 %) to 240 V (+ 6%)Battery voltage: DC … Not permissible. Destroys unitFrequency: AC 50 to 60 HzPower input: 2.2 WProtection class: I (with PE, because of metal casing)Effects of incorrect wiring

230 V at control terminal: DestructionReversing of in and out: No defect

Control signal range (In/Out) 1 to 10 V DCLoad capacity of the signal amplifier

Dimmable ECGs: max. 100Other signal amplifier: max. 33

Approval marks v

External control with a 0 -10V analogue output (e.g. PC card) is possible. Thiscontrol module must be able to take the current supplied by the ECG to thecontrol line and reduce the control voltage to at least 1V. Refer to Section 1.1“Properties of the 1…10 V interface”.

The analogue output must meet two requirements. It must be floating. Ittherefore must not be electrically connected to exposed parts or to circuitsthat are subject to SELV requirements (test voltage 2500V; the test voltage forearthed components is 1500V).The analogue output must be able to function as a current sink since it has totake the control current of the QUICKTRONIC® DIMMABLE control gear. Inmost cases it will not be known whether and how much current an analogueoutput can take but an adapter circuit can always be used if need be.

189 180

28

30

4.5

1246 Quicktr Dimmbar Engl 26.09.2000 9:27 Uhr Seite 52

Page 53: Dimming 1-10 Osram

The proposed procedure is as follows:

If there are 1, 2 or 3 QUICKTRONIC® DIMMABLE units, connect the controlterminals directly to the analogue output; if there are four or moreQUICKTRONIC® DIMMABLE units you should connect a signal amplifier in thecircuit. Start the system, set the control voltage to 0 V and use a multimeterto check the reading directly at the analogue output. If the measured value isless than 1 V the system is ok and can be used.

If the control voltage is greater than 1 V, the analogue output cannot takeenough current and an additional current sink is needed in the form of aparallel resistance R. To determine the value, connect a potentiometer(approx. 5 W lin) to the analogue output at a control voltage of 0 V and use itto set a control voltage of 1 V. Disconnect the potentiometer and measure theresistance value (must be greater than 680 W), then obtain and connect theappropriate fixed resistance (design 0207, load capacity 0.25W, or possiblythe next lower resistance value).

Dimmable ECGs with a 1…10 V interface can be easily integrated ininstallations that use the instabus EIB system. The link between EIB and the dimmable lighting system is aswitching/dimming actuator. One switching/dimming actuator is needed perlighting group.

The digital bus signal is converted by the switching/dimming actuator into theanalogue 1…10 V control voltage for QUICKTRONIC® DIMMABLE. The ECGis switched on and off by a built-in relay contact. Parameters can be set forvarious functions, such as on, off, brighter and darker, and a defined controlvoltage can be specified.

Sensors for daylight control and so on are normally connected at the instabuslevel.

Detailed information is available from manufacturers of the instabus EIB system.

53

Adapter circuit

Analogue outpute.g. PC

+

+

DIM ECG

+

+

InSignal

amplifierDIM SA

Out

If required

R

4.9 Control using instabus EIB

1246 Quicktr Dimmbar Engl 26.09.2000 9:27 Uhr Seite 53

Page 54: Dimming 1-10 Osram

Simple control for four preset lighting levels with 100% and 1% luminous fluxand two intermediate values can be provided with two fixed resistors. Thevalues for the resistors for this four-level system are given in the diagramentitled “Guideline values for selecting suitable control resistors” for dimmableECGs.

54

5.1 Circuits with fixed resistors

5. Special circuit diagrams, hints and tips

Control using fixed resistors(four preset values)

Guideline values for selectingsuitable control resistors

NL – +

NL

NL

NL

NL

+

+

+ 4

3

2

1

4321

4321

DIM ECGLamp

Lamp

Lamp

DIM ECG

DIM ECG

R2R1

1 2 3 4R1/2 = RD n

RD: Recommended resistance value from the luminous flux/resistance diagram

On/offswitch

Selectorswitch

Luminous flux as a %age

00

100

Res

ista

nce

in k

Ohm

10

20

30

40

50

60

70

80

90

105 10 20 30 40 50 60 70 80 90 95

1246 Quicktr Dimmbar Engl 26.09.2000 9:27 Uhr Seite 54

Page 55: Dimming 1-10 Osram

For use in existing lighting systems with leading-edge phase dimmers, signalconverter DIM SC is required for operating the dimmable ECG. DIM SCshould only be used if it is impossible to lay new cables. The betteroption is to control the system with manual control unit DIM MCU.

Signal converter DIM SC uses the phase signal of a dimmer to generate the1…10 V DC control signal needed for the dimmable ECG.

A 4-wire building wiring system (~ ,L,N,PE), as is required for example ifSiKRYPT is used for dimming, can continue to be used if a signal converter isinstalled. The ECGs must be earthed (i.e. only protection class I applications).

Upgrades

The output of the signal converter is isolated from the mains.A maximum of ten dimmable ECGs or a maximum of three DIM SA signalamplifiers can be connected at the output of the signal converter.

The signal converter forms only the signal for controlling the brightness of thedimmable ECG. For this reason, the leading-edge phase dimmer is used onlyfor controlling the brightness (light/dark) of the lighting system and not forswitching (ON/OFF). If the phase signal is disconnected the luminous flux fallsto its minimum value but the lighting system remains on.

55

5.2 Upgrades: leading-edgephase dimmers and signalconverter DIM SC

Application

Control output

Brightness control with DIM SC

Control with leading-edge phasedimmers and signal converters

Maximum number of ECGs forswitching depends on:the load capacity of the automaticcutoutsthe load capacity of the contactors

NL3

Switch

NL

NL

NL

+

+

+ 4

3

2

1

4321

4321

N

L

L2

L1

Relay

N – +L3L2L1

Max. 10 ECGs on the control line

Signal converterDIM SCMax. 10 ECGs

In

Out +–

N

Lamp

Lamp

Lamp

DIM ECG

L N

Leading-edgephase dimmer

With leading-edge phase dimmers forfluorescent lamps, the additional switchis often integrated in the dimmer. Anadditional switch in a flush-type box is notalways necessary.

Base load

(dimmer-dependen)

DIM ECG

DIM ECG

1246 Quicktr Dimmbar Engl 26.09.2000 9:27 Uhr Seite 55

Page 56: Dimming 1-10 Osram

An additional mains switch is needed for switching.

Leading-edge phase dimmers may produce harmonics in the mains voltagethat lead to noise in the ECG. If possible, dimmers and ECGs should thereforebe supplied from different mains phases.

Leading-edge phase dimmers for fluorescent lamps often have an additionalmains switch integrated in the dimmer so there is no need for another switchin a second switch box.

A leading-edge phase always needs an ohmic base load in the form of anincandescent lamp or a resistor (approx. 15 to 60 W according to the dimmermanufacturer) in order to operate properly. This means additional losses.

The base load must be installed as close to the dimmer as possible.

Depending on the quality of the leading-edge phase dimmers, the range ofthe phase angle may be limited with the result that it may not be possible tomake full use of the dimming range of the dimmable ECG.

If a common dimmer is used for brightness control for dimmable ECGs andconventional systems there is no guarantee that the lamps will operate insynchronism (uniform change in luminous flux during dimming) and theminimum and maximum luminous fluxes of the two systems may differ fromone another.

If luminaires with conventional dimmers such as SiKRYPT and luminaires withdimmable ECGs are operated on the same mains phase there is likely to benoise from the ECGs. The dimmable ECGs should therefore be connected toa different mains phase than the luminaires with conventional dimmers.

56

Switching

Notes on leading-edge phase dimmers

Combining dimmable ECGs and conventional brightnesscontrol (e.g. SiKRYPT)

189 180

28

30

4.5

1246 Quicktr Dimmbar Engl 26.09.2000 9:27 Uhr Seite 56

Page 57: Dimming 1-10 Osram

Because fluorescent lamps and compact fluorescent lamps are soeconomical they are of interest, in conjunction with dimmable ECGs, tocinema operators.

After sitting through a film in relative darkness, cinema goers often find that fluorescent lamps being switched on at 1% are too bright for their eyes(this is of course subjective).

Recommendation:

Plan a combined lighting system with fluorescent lamps (providing the mainlighting) and incandescent lamps or low-voltage halogen lamps (for the lowestlighting levels).

After the film the fluorescent lamps are not switched on (contribution offluorescent lamps at the lowest dimmer setting 20 lx for example) until theincandescent lamps have brought the illuminance in the cinema up to 100 lx.The jump in illuminance is then not as obvious (see diagram).

At the start of a film, the curve goes in the opposite direction.

57

5.3 Cinema control

Technical data for signal converter DIM SCReference DIM SCDimensions: See dimensional diagramDistance between mounting holes See dimensional diagramType of fixing: Screws Ø < 4 mmWeight: 100 gPerm. ambient temperature: – 20°C to + 50°CTerminals: Detachable plug terminals for single-wire cablesPermissible wire cross-section

Mains terminals: , N, PE: je 2 x 0.75 mm2

Control terminal: 0.5 mm2

Rated voltage: 220 V (– 10 %) to 240 V (+ 6 %)Frequency: AC 50 - 60 HzMains current: < 5 mAPower input: 1.2 WHarmonic content: Very high with leading-edge phase controlProtection class: I (with PE, because of metal casing)Mains connection: , N, PEEffects of incorrect wiring

230 V at control terminal: Fuse respondsFuse: Fine fuse F 0, 1/250 VControl signal range: 1 … 10 V DCLoad capacity of the signal converter

Dimmable ECG: max. 10or signal amplifier max. 3

Approval marks vAlso suitable for trailing-edge phase dimmers

300 lx

Illum

inan

ce

Time after end of film

100 lx

200 lx

Incandescent lamp+ fl. Lamp

Fluorescent lampsswitched on

Incandescent lamps

1246 Quicktr Dimmbar Engl 26.09.2000 9:27 Uhr Seite 57

Page 58: Dimming 1-10 Osram

The familiar temperature problems of dimmed fluorescent lamps can beeliminated by limiting the lower dimmer setting as a function of temperature.

L58W as an example:

Below 0ºC the control voltage for the L58W must be increased to at least 4 V.This corresponds to a dimmer setting of around 25%.

The stability threshold depends to a great extent on the lamp tolerances. Fortypes of control in which the lamp starts at 100% (in standby circuits forexample) the temperature limit may be lower. In the case of automatic control,therefore, it should be possible to set both the response temperature and thecontrol voltage. The following circuit is proposed:

The temperature controller may be a room thermostat for controlling theheating system. The switching temperature (0 ºC for example) must beaccurately adjustable. The switch must be a make switch. In other words, itmust be closed at high temperatures. Such components are available withbimetal contacts (e.g. 2NR9 090-1, power supply not needed) or withtemperature sensors (e.g. 2NR9 078, power supply required). Any heatingresistors for thermal feedback or night-time reduction are not connected(contrary to the wiring diagram). The only mains connection is to the powersupply, if required. Different types of protection are needed, depending on theapplication. For further information contact specialists in heating and air-conditioning.

58

5.4 Temperature-dependentcontrol

Con

trol

vol

tage

[V]

Lamp temperature [°C]

–20 –15 –10 –5 0 5 10 15 20 25

5

4

3

2

1

Unstable

Main controller

Auxiliary controllerapprox. 4V, e.g. DIM MCU

Temperature controller

++

+

––

1

2

1246 Quicktr Dimmbar Engl 26.09.2000 9:27 Uhr Seite 58

Page 59: Dimming 1-10 Osram

For customised lighting control the functions of various 1…10V controllers(sensors) can be easily and cost-effectively combined. This is achieved eitherby connecting the controllers in parallel or by switching between the variouscontrollers.

a) Connecting controllers in parallel

When connected in parallel the controller with the smallest value dictates thedimmer setting.

Typical application:

Problem: Constant lighting control throughout the day, uniform façadelighting at night.

Solution: A time switch is connected in parallel with a light sensor.

b) Switching between controllers

If different control options are combined with the aim of using the one mostappropriate to the situation, it is best to install a changeover switch betweenthe controllers.

Wiring

Changeover takes place at the positive pole of the control line. The negativepoles of all the units are normally connected. This does not affect the wiring ofthe mains supply cables.

59

5.5 Combining severalcontrollers

DIM ECG

DIM ECG

+–

+–

+–

+–

DIM ECG+–

2

Controller

1

Controller

1246 Quicktr Dimmbar Engl 26.09.2000 9:27 Uhr Seite 59

Page 60: Dimming 1-10 Osram

Typical application 1:Multi-functional room with a choice between constant lighting control (e g.DIM MICO) and manual control (e.g. DIM MCU).Variant: Two separately controlled lighting strips (via two DIM MICOs) are tobe operated together with a manual control unit (see detailed wiring).

Typical application 2:Lighting control in a sports hall with two different illuminances (e.g. 300 lux for training and 500 lux for competitions).Solution: Install two DIM MICOs with a changeover switch

For certain applications it is sometimes necessary to place upper or lowerlimits on the control voltage for dimmable ECGs. The reasons for this includespecial combinations of lamps and ECGs and flickering at low temperatures.

a) Upper limits

The simplest way to achieve this is to connect a Zener diode with anappropriate value in parallel. To limit the control voltage to 7 V, for example, aZener diode with a rated value of 7 V or a value close to this should be used.(Zener diodes are available from series E24. Type Bzx 55C xVx isrecommended. For xVx, for example, 7V5 = 7.5 V should be used. At least 20ECGs can be controlled with this type.)

If a number of controllers are connected in parallel, the controller with thelowest value will dictate the control voltage for the dimmable ECG.

This applies to all passive controllers (i.e. units that act as current sinks).

60

5.6 Placing upper and lowerlimits on the control voltage

DIM ECG

DIM ECG

+–

+–

+–

+– Changeover switch

2

Controller

1

Controller

DIM MICO #1 +

DIM MCU

DIM MICO #2

+

++

+ 1st lighting strip

2nd lighting strip

a

b

c

d

2-pole changeover switch

Detailed wiring (positive pole only)

1246 Quicktr Dimmbar Engl 26.09.2000 9:27 Uhr Seite 60

Page 61: Dimming 1-10 Osram

b) Lower limits

A lower limit can be effectively imposed by connecting two controllers inseries. The sum of the two units is then used. One unit cannot undershoot thecontrol voltage imposed by the other unit.

Important: If two controllers are connected in series (e.g. DIM MCU) thesmallest achievable control voltage is approx. 2 V (~= 4% luminous flux).

The connections should be made as shown in the diagram below.

All 1…10 V dimming components can also be used in conjunction withHALOTRONIC® electronic transformers if an HT 1…10 DIM module isconnected between the dimming components and HALOTRONIC®.

This module converts the 1…10V signal into a phase signal.

This application is mainly of interest for remote control or scene control (DIM BEAMIT; see 4.2).

Remote control of tungsten-halogen lamps

61

5.7 Incorporating HALOTRONIC

DIM ECG

DIM ECG

Controller

Further ECGs+–

+

+

+

Zener diode

DIM ECG

DIM ECG

+–

+–

+–

Controller

1

Further ECGs+–

2 +–

Controller

DIM FB

DIM IE HT 1–10 DIM HALOTRONIC®DIM ICM 10

1246 Quicktr Dimmbar Engl 26.09.2000 9:27 Uhr Seite 61

Page 62: Dimming 1-10 Osram

62

For general wiring and operating instructions see the QUICKTRONIC® Guideand the chapter on electronic control gear in the Lighting Programme.

General

• We recommend that you allow new lamps to burn in for at least 50 hoursat 100% luminous flux.

• All the control lines of an ECG installation must be connected with thecorrect polarity (+/–).

• The control line is isolated from the power line but not at safety extra-lowvoltage (SELV). Cables and terminals that are approved for 230 V musttherefore be used.

• The ECG can be tested for correct operation as follows:1. Switch on the ECG with an open control line. The lamp must ignite andoperate at rated output.2. Short-circuit the control line (jumper). The lamp must operate atminimum brightness.

• The controller must be able to accept the current supplied by the ECG inthe control line (current sink) and reduce the control voltage. Thisrequirement is met by suitably dimensioned potentiometers and all OSRAMcontrol components. Normal power supply units, converter cards and soon do not necessarily have this ability. To check, connect the controller, setto lowest brightness and measure the voltage on the control line. The valueshould be 1 V or less.

Safety instructions

• The units should be installed and tested only by a qualified electrician.• Power to the units must be switched off before any work is undertaken. • The relevant safety and accident prevention regulations must be observed.• UV resistant cables must be used if the units are to be operated inside

luminaires.

Please note the following when wiring luminaires with QUICKTRONIC®

DIMMABLE:

• Mains and control cables may be routed together.• Mains and control cables should not be laid together with or parallel to the

lamp cables.• Avoid crossing mains cables and lamp cable; if this is not possible, they

should cross at right angles.• It is best to use coloured cables for the sake of clarity.• Do not use shielded lamp cables.• Dimmable ECGs must be earthed.• In the case of two-lamp dimmable ECGs, the cables for connections 4, 5,

6 and 7 should be the same length (no more than 5 cm difference) toavoid different brightnesses in the two lamps.

• The dimmable ECG must always be installed near the lamp(s) so that thelamp cables can be kept short in the interests of good radio interferenceprotection. The maximum permissible cable length is 2 m. Certain lampcables carry a somewhat higher voltage against earth. To avoid radiointerference, these “hot wires” should be as short as possible. These areconnections 3 and 4 on single-lamp QUICKTRONIC® DIMMABLE units,and connections 1, 2 and 3 on two-lamp units.

6.1 Installation in luminaires

Wiring

6. Installation in luminaires, wiring andoperating instructions

1246 Quicktr Dimmbar Engl 26.09.2000 9:27 Uhr Seite 62

Page 63: Dimming 1-10 Osram

63

Both single-core cables and multi-core cables may be used with the terminalsof QUICKTRONIC® DIMMABLE ECGs. For wiring T5 luminaires, please alsorefer to the notes on page 65.

a) Single-core cables

• These should have a cross-section of 0.5 mm2 at least and 1.5 mm2 atmost. The minimum cross-section for the lamp cables is 0.5 mm2.

• You can insert solid conductors with a cross-section of 0.75 mm2 to 1.5 mm2 in the terminals without operating the release tab.

• In the case of single-core cables with a cross-section of 0.5 mm2 to 0.75 mm2, you have to press down the tab before inserting the conductorin the cable.

b) Multi-core cables

• These should have a cross-section of 0.5 mm2 at least and 1 mm2 at most.

• Multi-core cables may be inserted directly into the terminals.

• Multi-core cables must not be soldered, particularly in the case of screwterminals. Solder “wanders” in the course of time and the reliability of thecontact diminishes significantly.

• Ferrules may be used but they are not essential.

• Multi-core cables can only be inserted into the terminals while the releasetab is held down.

An adapter terminal may be required in the luminaire to accommodate thedifferent conductor cross-sections.

For QUICKTRONIC® terminal block, about 8 to 10 mm of insulation should bestripped from the ends of both single-core and multi-core cables.

• Because the lamp electrodes are permanently heated and because thisleads to higher currents compared with normal QUICKTRONIC® ECGs,check that all the wires make good contact in holders and in the ECGs.The lamps must also be properly seated and make good contact in theholders. Special holders are not required.

A master/slave circuit with two-lamp dimmer units is not possible because of the capacitive leakage currents that can lead to imbalances, differentluminances and unstable operation in the dimmed state.

• If a number of dimmable ECGs are installed in a luminaire the individuallamp/ECG systems must be physically separate from one another (at least12 cm apart) to achieve optimum decoupling of the lamp circuits. Mutualinterference can lead to flickering and different brightness levels at lowdimmer settings. Luminaires with more than one dimmable ECG shouldtherefore only be wired by the luminaire manufacturer. “On-site” upgradesare not recommended.

Wiring recommendations for 3 and 4-lamp dimmable luminaires

The following diagrams show examples of correct wiring for 3 and 4-lampluminaires with tubular fluorescent lamps. Note the following:

• Mains and control cables should be laid tight to the wall of the luminaire.

• HF cables should be laid close together and in parallel near the lamp.

• The lamp axes should be at least 12 cm apart (lamps with different ECGs).

Cable types and cable cross-sections

Insulation

Holders

Master/slave circuit

Multi-lamp luminaires

1246 Quicktr Dimmbar Engl 26.09.2000 9:27 Uhr Seite 63

Page 64: Dimming 1-10 Osram

Note on the diagrams:

For the sake of clarity the mains cable and the control cable are each shownas a single line.

64

1 2

4 3

1 3

7 6

1 2

5 4

+/– mains Luminaire terminals

+ /– mains

DIM ECG2-lamp

17 2356

Lam

p

Lam

p

Lam

p

4321

DIM ECG1-lamp

mains – /+

Through-wiring

HF wiring Keep these cables as short as possible

4

1

3

Luminaire terminals

2

4

1 2

5 4

+ /– mains

17 23456

Lam

p

Lam

p

HF wiring Keep these cables as short as possible

+/– mains

4321

mains – /+

3

6

1

7

Lam

p

Through-wiring

DIM ECG1-lamp

DIM ECG2-lamp

3-lamp dimmable luminaireVariant 1: The two ECGs are switched together

3-lamp dimmable luminaireVariant 2: The two ECGs can be switched separately

1246 Quicktr Dimmbar Engl 26.09.2000 9:27 Uhr Seite 64

Page 65: Dimming 1-10 Osram

The reflector should never rest on the lamp otherwise there may be problemswith vibrations and noise.In the case of luminaires with OSRAM DULUX L lamps there should be aminimum gap of 15 mm between the lamp and the reflector. Is the gap is lessthan this the capacitive coupling between the reflector and the lamp maycause the two arms of the OSRAM DULUX L to burn at differentbrightnesses. The preheating time may also be shortened, thereby reducingthe life of the lamp.

In luminaires with T5 lamps there should be a minimum gap of 6 mm betweenthe lamp and the reflector. If the gap is smaller than this, capacitive leakagecurrents may lead to uneven brightness along the lamp.

Luminaires with two-lamp dimmable ECGs for T5 lamps

Al low dimmer settings, T5 lamps have a much higher resistance than T8lamps, which is why parasitic capacitances in the luminaire affect the dimmingof T5 lamps more so than that of T8 lamps. To avoid synchronism problemsand malfunctions at low ambient temperatures, please note the following inaddition to the notes for T8 lamps if you are using two-lamp dimmable T5ECGs:

• The lamp cables should not be longer than the lamp.

• Do not lay lamp cables in narrow metal tubes or the like. The maximumcapacitance of a lamp cable to earth is 100 pF. Do not, in anycircumstances, use shielded lamp cables.

• Lay cables 1, 2 and 3 away from cables 4, 5, 6 and 7. The maximumcapacitance of the two groups is 20 pF.

65

Dimming T5 fluorescent lamps

Minimum reflector gaps

1

7

+/– mains Luminaire terminals

Through-wiring

2 1

54

+ /– mains

DIM ECG2-lamp

1 72 3 4 5 6

Lam

p

Lam

p

3

6

1 2

5 4

+ /– mains

DIM ECG2-lamp

17 23456

Lam

p

Lam

p

6 7

3 1

HF wiring Keep these cables as short as possible

4-lamp dimmable luminaire

1246 Quicktr Dimmbar Engl 26.09.2000 9:27 Uhr Seite 65

Page 66: Dimming 1-10 Osram

Type of cable

Since the lamp voltage of FH and FQ lamps can rise above 250 V when theyare dimmed specially insulated cables must be used (class H07 cables).Dimmable ECGs for T5 lamps therefore carry labels indicating the maximumoperating voltages (400 V between cables or 430 V to earth).

VDE-approved H07 cables (cross-section 0.5 or 0.75 mm2 ) can be obtainedfrom the following companies:

Coroplast, Fritz Müller KG, Mittener Str. 271, D-42279 Wuppertal.

Conductor cross-section 0.5 to 0.75 mm2. Rated thickness 0.7 mm.

• The wiring must be such that all signal and control cables stop carryingcurrent as soon as the mains voltage is disconnected.

• All the component of the main and control circuits must be designed for aworking voltage of 250 V with respect to earth.

• “Bell wire” must not be used for the control line as the control voltage of 1to 10 V is not safety extra-low voltage (SELV).

• Detailed information on cable selection and wiring is given in the latesteditions of the relevant guidelines for setting up electrical systems (seewiring instructions for the controllers).

According to DIN VDE 0100 Part 520, Section 528.11, main circuits andassociated auxiliary circuits may be laid together even if the auxiliary circuitscarry a lower voltage than the main circuits.

Note the following:

• The cables used must be insulated against the highest operating voltagesor each conductor of a multi-core cable must be insulated against the nextvoltage occurring in the cable (in accordance with DIN VDE 0100/11.85, T520, Section 528.11).

• If wires are laid in cabling tubes or channels only the conductors of a maincircuit and those of the associated auxiliary circuits may be laid together (inaccordance with DIN VDE 0100/11.85, T 520, Section 528.11).

• Several main circuits and their associated auxiliary circuits may becombined in a cable (in accordance with DIN VDE 0100/11.85, T 520,Section 528.11).

The length of the control cable is limited only by the drop in voltage. As ageneral rule, we can say that cable lengths of 100 m are not at all critical.

The following formula can be used to arrive at a more accurate estimate:

For example for 1.5 mm2, strip lighting, fed from one end: Lmax = 35 km/number of ECGs

= 350 m for 100 ECGs = 700 m for 50 ECGs

If DIM SA signal amplifiers are used the system can be any size at all.

66

Length of the control cable

6.2. Wiring instructions

working voltage 430 VRMS

use class H07 lamp wires

1246 Quicktr Dimmbar Engl 26.09.2000 9:27 Uhr Seite 66

Page 67: Dimming 1-10 Osram

QUICKTRONIC® DIMMABLE is suitable for emergency lighting systems toVDE 0108. The voltage range and the ignition times for the lamps in apermanent circuit (lamp already on, power supply is switched from AC to DC)and on standby (emergency luminaires are switched on from cold) are shownin the table in Section 7.1.

If QUICKTRONIC® DIMMABLE is used in emergency lighting systems suitablemeasures should be taken to interrupt the control line at the positive poleduring emergency operation. Appropriate changeover converters that areeasy to wire in are available from retailers. These converters forward apredefinable control voltage to the dimmable ECG and therefore enable thelamps to operate at less than 100% luminous flux to save the batteries.

Note that some accessory components (such as DIM SA signal amplifiers andDIM ICM 10) are not approved for battery operation. You must thereforeensure that these components are not connected to the dc source. Thesignal amplifier, for example, would constitute a fixed resistance connected tothe control line and the dimmer setting for an ECG is then 20%, sometimeshigher.

The sensor is installed above a reference surface in the room (such as a desk)so that it detects the reflected light, comprising daylight and artificial light.Direct light and reflected light from windowsills and so on should be avoidedas they may lead to control deviations. The sensor should also be placedsufficiently far away from the windows so that the window is outside thesensor’s beam angle. The mounting bracket for the DIM MICO unit must notbe placed near the lamp electrodes (risk of overheating) nor where a wirecoming loose from a terminal could come into contact with it.

Setting the illuminance

• The light sensor should be set with the aid of a lux meter with little daylight(evenings, darkened room) in a room furnished for use.

• Bring the lighting system up to 100% luminous flux by turning the casing ofthe DIM PICO or turning the potentiometer on DIM MICO or DIM MULTI.

• The luminaire should be operated for approx. 30 minutes to ensure that theluminous flux has stabilised.

• Turn the casing or potentiometer until the unit starts to dim the lamp(s).Compare the illuminance reading on the lux meter with the desiredilluminance (if you are not using a lux meter, turn back the setting slightly toensure that the luminaire does not start to dim too early).

• When making adjustments to the light sensor you should remember thatyour own body will affect the luminous flux that reaches the light sensor.You should therefore stand well away from the sensor to check the finalsetting.

67

Emergency lighting

Installing and operating light sensors

DIM ECG–

+

DCAC

1–10V normal1–10V emergencylighting

– +– +

230/240V

Switching from AC to DC (incl. positive pole)

1246 Quicktr Dimmbar Engl 26.09.2000 9:27 Uhr Seite 67

Page 68: Dimming 1-10 Osram

68

The permissible ambient temperatures are shown in the table below.

Lamp type Ambient temperature

T8 lamp 0°C

T5 lamp 10°C

DULUX L 10°C with QT-FQ DIM15°C with HF…DIM

DULUX D/E,T/E 5°C

If the lamps start flickering below the allowed temperature range of the ECGsand at low dimmer settings you should raise the minimum dimmer setting (forexample by turning up the controller or placing a lower limit on the controlvoltage).

Between the undimmed and fully dimmed operating statuses of a lamp(reduction in luminous flux to 1%) the correlated colour temperature of DULUX L 36 rises by about 150 K.

The colour difference appears greater than it really is because of theenormous difference in luminance. The subjective perception of the humaneye does not reflect the objective change in colour temperature.

As soon as the lamp is switched to the lowest dimmer setting (by short-circuiting the control input with a wire jumper) there is a temporary colour shiftof up to 400K, which reduces after 30 or 40 minutes to the colour differencementioned above (stabilisation phase).

Note: Measuring the correlated colour temperature when the lamps aregreatly dimmed places high demands on the electronics and on the receiverin the colorimeter. Standard colorimeters may well give incorrect readings.

Both normal and amalgam lamps (IN lamps) can be dimmed. Amalgam lampsare somewhat slower to react however:

• It is noticeable that, unlike normal models, IN lamps go through a transient condition which lasts for about three minutes. The type oftransient condition depends on the burning position.

• Luminous flux stabilises itself in IN lamps after about 25 minutes; in normalmodels this takes about 10 minutes.

• Changes in colour temperature do not occur and serious reductions incolour temperature cannot be detected immediately after the dimmingprocess.

Colour temperature

6.3 Operating instructions

Temperature

Dimming amalgam lamps

1246 Quicktr Dimmbar Engl 26.09.2000 9:27 Uhr Seite 68

Page 69: Dimming 1-10 Osram

69

Question: What is the maximum permissible length of the 1…10 V controlline?

Answer: The maximum permissible length of the control line is 100 m.(Note: Owing to the low control current a fall in voltage on thecontrol line is only apparent after about 300 to 400 m)

Question: What cable cross-section should the 1…10 V control line have?Answer: The recommended cross-section is 1.5 mm2. The insulation

around the cable must be designed for mains voltage.

Question: Can control and power cables be laid together?Answer: Yes; see VDE 0100 520 Section 528.11. Note the following:

• The cables must be designed for the maximum operatingvoltage (VDE 0100/11.85, T520 Section 528.11)

• If wires are laid in cabling tubes or channels only theconductors of a main circuit and those of the associatedauxiliary circuits may be laid together.

• Several main circuits and their associated auxiliary circuitsmay be combined in a cable (VDE 0100/11.85, T520 Section528.11)

Question: Is there a simple low-cost method of controlling fixed lightinglevels?

Answer: Yes, fixed resistances (see 5.1) can be used as a simple way ofcontrolling preset lighting levels with 100% and 1% luminousflux and a number of intermediate values.

Question: Only three-core cabling is available. Can I use it to operatedimmable ECGs?

Answer: If only three wires (L, N, PE) are laid to the luminaire and nocontrol line, you can dim via the IR remote control. Connect theICM 10 module to the +/– terminal of the control input on theECG (installed in the luminaire or on the ceiling). To do this,connect the IR sensor, which is controlled via remote control FB.In small systems this arrangement can be used to makeluminaires dimmable without an existing control line.

Question: Can dimmable ECGs from OSRAM be used in emergency lightingsystems?

Answer: Yes, but installing dimmable ECGs in emergency lightingsystems involves additional costs. Components such as signalamplifiers, ICM 10 and the constant light module would bedestroyed if supplied with dc voltage so these components haveto be isolated from the power supply when changeover to dcvoltage takes place.

Question: Can two-pin compact fluorescent lamps be dimmed?Answer: No. Two-pin lamps must not be operated by electronic control

gear. Because there is a glow starter integrated in the basethere may be problems such as unreliable starting, shorter lamplife and destruction of the ECG. In dimmed mode, additionalheating of the lamp electrodes is not possible, which would lead to a drastic reduction in the life of the lamp. Basically, onlyfour-pin lamps with the label /E (such as DULUX S/E, D/E andT/E) can be operated with electronic control gear and thereforedimmed.

Question: Does operating fluorescent lamps permanently at low dimmersettings have any effect on lamp life?

Answer: Long-term operation of fluorescent lamps and ECGs fromOSRAM at any dimmer setting has no adverse effect on the lifeof the lamps.

6.4 FAQs (frequently asked questions)

1246 Quicktr Dimmbar Engl 26.09.2000 9:27 Uhr Seite 69

Page 70: Dimming 1-10 Osram

70

6.5 Troubleshooting tips

Problem Possible cause Remedy1) The lamp always burns at 100% Control line is not or not correctly Check the wiring

luminous flux connected to the controller The controller is not an adequate Check whether the control voltage

current sink and cannot therefore is reduced during dimming; if necessary,reduce the control voltage insert a parallel resistor in the

control line (see Section 4.9)2) The lamp always burns with minimum The + and – terminals of the control line are Connect lines with the correct polarity

brightness the wrong way round Short-circuit on the control line Check wiring

3) 100% luminous flux is not reached, some The + and – terminals on one or more Check wiring lamps always burn at minimum brightness dimmable ECGs are not connected correctly

4) The lamp does not produce the desired The potentiometer or resistors are incorrectly Check resistor values as per Section 4.2;luminous flux when controlled with a dimensioned or the specified values from use electronic potentiometer DIM MCUpotentiometer or fixed resistors Section 1.2 have not been divided by the

number of dimmable ECGs connected5) The lamp flickers at low dimmer settings The temperature is too low (see 5.3) Set the ECG to a dimmer setting with more

luminous flux or take appropriate measures (e.g. trim potentiometer on DIM MCU) to ensure that the critical lower dimmer setting cannot be accessed

The lamp has not burned in Burn in the lamp (approx. 50 h) DULUX L and T5: inadequate mercury Burn in the lamp for longer; if necessary,

distribution limit the lower dimmer setting (approx. 1.9 V) Lamp too near the reflector Lamp faulty Lamp not suitable (wrong filaments)

6) Daylight-dependent lighting system The sensitivity of the light sensor has not been Repeat the setting procedure as per with DIM LS correctly set Section 4.5a) No control or incomplete control The light sensor is being over or under Small corrections can be made by turning

controlled because it is incorrectly positioned or pulling out the tube on the light sensor; in the room (it may be pointing at a bright repeat the setting procedure. The light window, dark carpet etc.) sensor may have to be repositioned; see 4.5

b) Dims too much The light sensor is pointing at bright windows Increase the distance to the windowc) Dims up and down seemingly at random The light sensor is pointing at a surface with Reposition the light sensor

fluctuating reflectance (e.g. highly frequented walkway or dark desk sometimes covered in white paper)

7) Uneven brightness along DULUX L and The distance between the reflector and the Increase the distance between the reflector T5 lamps lamp is too small; there are capacitive and the lamp

leakage currents8) The lamps are flickering in synchronism The fault lies outside the dimmer system Check the N conductor connection; check

(e.g. N conductor break, control voltage not ok) the controller9) Two-lamp dimmable ECG: flickering, uneven Incorrect wiring in the luminaire (common pole Check wiring

brightness, lamps go out, uneven blackening 1 may be connected to 3), inadequate filament heating

10) No reaction from the multi-channel system BUS or not connected Connect BUS and with DIM BK 10

Question: Is it possible to dim fluorescent or compact fluorescent lampsand halogen lamps together?

Answer: Fluorescent lamps or compact fluorescent lamps can bedimmed in parallel with low-voltage halogen lamps. In this case,HALOTRONIC® electronic transformers are controlled viadimmer module 1…10 DIM and the 1…10 V control line. Thesame components, such as manual control units DIM MCU,signal amplifiers, light sensors and so on, can be used.

Question: Is it possible to dim a lighting system with a master/slave circuit?Answer: No, you cannot operate a two-lamp dimmable ECG with a

master/slave circuit. The different cable lengths to the lamps canlead to synchronism problems, which in turn can lead to adifference in brightness between the lamps at low dimmersettings.

Problems may occur when wiring or installing QUICKTRONIC® DIMMABLE.The following table should help you locate the possible causes and takesuitable measures.

1246 Quicktr Dimmbar Engl 26.09.2000 9:27 Uhr Seite 70

Page 71: Dimming 1-10 Osram

Comfort

• 100% – 1% luminous flux with T8, FQ and FC fluorescent lamps andDULUX L and F lamps, 100% – 3% with FH fluorescent lamps, DULUX D/Eand T/E

• Flicker-free start

• Lamp starts without a sudden flash at any dimmer setting

• Flicker-free light

• Silent operation with no humming from chokes or phase dimmers

• No flashing from defective lamps

• Automatic restart after replacement

Economy

• 50% longer life compared with conventional dimming, greatly reducedthermal load. The costs of replacement, maintenance and disposal arereduced by a third.

• Up to 70% savings in electricity costs with automatic daylight-dependentcontrol

• Suitable for use in emergency lighting systems to VDE 0108

• Warm start

• No compensation needed

Safety

• Safe shutdown of the power supply to defective lamps

• Compliance with European standards for safety (EN 60928), performance(EN 60929) and EMC (radio interference suppression to EN 55015, VDE0875; harmonic content to EN 61000-3-2; immunity to EN 61547)

• Protection against short duration voltage surges (to VDE 0160) andtransient overvoltages

• Improved fire safety because control gear temperatures are lower withQUICKTRONIC® DIMMABLE and luminaires can therefore be constructedto meet the ((Symbol)), ((Symbol)) and ((Symbol)) standards (EN 60598/DINVDE 0710 and DIN VDE 0711).

• Approval marks: ENEC, VDE, VDE-EMC

Range

The current range of OSRAM dimmable ECGs is specified in the latest versionof the Lighting Programme publication.

71

7.1 QUICKTRONIC® DIMMABLE

7. Range, lamp combinations

1246 Quicktr Dimmbar Engl 26.09.2000 9:27 Uhr Seite 71

Page 72: Dimming 1-10 Osram

72

Recommended voltage ranges

QUICKTRONIC® DIMMABLE control gear can be operated on AC or DCvoltage. The table below shows the recommended voltage ranges and thebehaviour of the ECGs at overvoltage and undervoltage.

Behaviour of two-lamp dimmable ECGs in the event of a lamp fault

Two-lamp dimmable ECGs cannot operate in single-lamp mode. If one lamp develops a fault the other is switched off.

Load capacity of relays and cutouts

QT-FQ 1 x 24 DIM = HF 1 x 36 DIM

QT-FQ 2 x 24 DIM == HF 2 x 36 DIM

QT-FQ 1 x 39 DIM == HF 1 x 36 DIM

QT-FQ 2 x 39 DIM = HF 2 x 58 DIM

QT-FQ 1 x 54 DIM = HF 1 x 58 DIM

QT-FQ 2 x 54 DIM = HF 2 x 58 DIM

QT-FQ 1 x 80 DIM = HF 2 x 58 DIM

QT-FH 1 x … DIM = HF 1 x 58 DIM

HF…DIM QT-FH...DIM QT-T/E...DIMQT-FQ...DIMQT-FC...DIM

Recommended continuous voltage range1. AC voltage 198 – 254 V 198 – 254 V 198 – 254 V2. DC voltage 154 – 276 V 176 – 254 V 176 – 254 V

Overvoltage protection: Up to 280 V Up to 280 V Up to 280 VContinuous overvoltage (24 h)

Behaviour on exceeding 1. Up to 350 V~ under 1 hour Over 280 VOvervoltage limits No damage to ECG ECG failure possible

2. Over 350 V~ ECG failure possible

Behaviour at undervoltage:1. Voltage drop Not thermally critical, drop in luminous flux

during operation 2. Starting at undervoltage Under 176 V, start unreliable

Dimming range 1%–100% 3%–100% 3%–100%Starting time

1. Cold lamp < 0.5 s < 2 s < 2 s2. Warm lamp < 0.5 s < 2 s < 2 s

1246 Quicktr Dimmbar Engl 26.09.2000 9:27 Uhr Seite 72

Page 73: Dimming 1-10 Osram

73

7.2 Lamps recommended foruse with QUICKTRONIC®

DIMMABLE

The recommended combinations are also given in the latest edition of theOSRAM Lighting Programme.

Lamp ECG model System Commentswattage

DULUX D/E, T/E 18 1-lamp QT-T/E 1x18/230-240 DIM 20 W2-lamp QT-T/E 2x18/230-240 DIM 39 W

DULUX D/E, T/E 26 1-lamp QT-T/E 1x26/230-240 DIM 28 W2-lamp QT-T/E 2x26/230-240 DIM 56 W

DULUX T/E 32 1-lamp QT-T/E 1x32/230-240 DIM 35 W2-lamp QT-T/E 2x32/230-240 DIM 72 W

DULUX T/E 42 1-lamp QT-T/E 1x42/230-240 DIM 46 W

DULUX L, F 18 1-lamp HF 1x18/230-240 DIM 19 W Φ min.: 2%; Ta > 15°C2-lamp HF 2x18/230-240 DIM 37 W Φ min.: 2%; Ta > 15°C

DULUX L, F 24 1-lamp QT-FQ 1x24/230-240 DIM 30 W2-lamp QT-FQ 2x24/230-240 DIM 52 W

DULUX L, F 36 1-lamp HF 1x36/230-240 DIM 36 W Φ min.: 1,7%2-lamp HF 2x36/230-240 DIM 71 W Φ min.: 1,7%

DULUX L 40 1-lamp QT-FQ 1x39/230-240 DIM2-lamp QT-FQ 2x39/230-240 DIM

DULUX L 55 1-lamp HF 1x58/230-240 DIM 56 W Φ min.: 1,7%2-lamp HF 2x58/230-240 DIM 114 W Φ min.: 1,7%1-lamp QT-FQ 1x54/230-240 DIM 60 W2-lamp QT-FQ 2x54/230-240 DIM 116 W

FC 22 1-lamp QT-FQ 1x24/230-240 DIM 27 W2-lamp QT-FQ 2x24/230-240 DIM 55 W

FC 40 1-lamp QT-FQ 1x39/230-240 DIM 45 W2-lamp QT-FQ 2x39/230-240 DIM 85 W1-lamp QT-T/E 1x42/230-240 DIM 45 W

FC 55 1-lamp QT-FC 1x55/230-240 DIM 63 W2-lamp QT-FQ 2x54/230-240 DIM 118 W

FH 14 1-lamp QT-FH 1x14/230-240 DIM 18 WFH 21 1-lamp QT-FH 1x21/230-240 DIM 25 WFH 28 1-lamp QT-FH 1x28/230-240 DIM 33 WFH 35 1-lamp QT-FH 1x35/230-240 DIM 40 W

FQ 24 1-lamp QT-FQ 1x24/230-240 DIM 27 W2-lamp QT-FQ 2x24/230-240 DIM 55 W

FQ 39 1-lamp QT-FQ 1x39/230-240 DIM 45 W2-lamp QT-FQ 2x39/230-240 DIM 85 W

FQ 54 1-lamp QT-FQ 1x54/230-240 DIM 61 W2-lamp QT-FQ 2x54/230-240 DIM 122 W

FQ 80 1-lamp QT-FQ 1x80/230-240 DIM 88 W

L 18 1-lamp HF 1x18/230-240 DIM 19 W2-lamp HF 2x18/230-240 DIM 36 W

L 20 (T12) 1-lamp HF 1x18/230-240 DIM 19 W Φ min.: 2,1%; Ta >15°C;L 22 C 1-lamp HF 1x36/230-240 DIM 20 W Φ min.: 4,0%; Ta >15°C;L 30 1-lamp HF 1x36/230-240 DIM 31 W Φ min.: 2,5%; Ta >15°C;

Uc max.: 8,2 V2-lamp HF 2x36/230-240 DIM 63 W Φ min.: 2,5%; Ta >15°C;

Uc max.: 8,2 VL 32 C 1-lamp HF 1x36/230-240 DIM 33 WL 36 1-lamp HF 1x36/230-240 DIM 36 W

2-lamp HF 2x36/230-240 DIM 71 WL 36 /-1 1-lamp HF 1x36/230-240 DIM 32 W Φ min.: 2,5%; Ta >15°C;

2-lamp HF 2x36/230-240 DIM 65 W Φ min.: 2,5%; Ta >15°C;L 38 1-lamp HF 1x36/230-240 DIM 37 W Φ min.: 1,5%; Ta >15°C;

2-lamp HF 2x36/230-240 DIM 60 W Φ min.: 1,5%; Ta >15°C;L 40 (T12) 1-lamp HF 1x36/230-240 DIM 37 W Φ min.: 1,3%; Ta >15°C;L 40 C 1-lamp HF 1x36/230-240 DIM 37 W Φ min.: 2%; Ta >15°C;

Uc min.: 2VL 58 1-lamp HF 1x58/230-240 DIM 56 W

2-lamp HF 2x58/230-240 DIM 114 WL 65 (T12) 1-lamp HF 1x58/230-240 DIM 56 W Φ min.: 1%; Ta >15°C;

1246 Quicktr Dimmbar Engl 26.09.2000 9:27 Uhr Seite 73

Page 74: Dimming 1-10 Osram

74

Manual controls

Constant lighting control

Miscellaneous

* The basic circuits are indicated in bold

7.3 1…10 V dimmingcomponents from OSRAM

Reference Description Wiring diagrams* Technical data for

DIM MCU Manual control unit 11, 44, 51, 60 12

DIM ICM 10 IR control module 14, 15, 29 16

DIM FB 10-channel remote control 14, 15 17for DIM ICM 10

DIM IE IR receiver for 14, 15 17DIM ICM 10

DIM BK 10 Bus controller for 29 30DIM ICM 10

DIM IRM IR module for scene 35 34, 36control for DIM IRM

DIM IRE IR eye for DIM IRM 35 36

DIM BEAMIT 4-channel manual 35 35scene transmitter

DIM PICO Single-luminaire sensor 20 20

DIM MICO Mini constant unit 22, 44, 60 22

DIM MULTI Multisensor 25, 26 27

DIM MULTI 2 2-part multisensor for 41 42, 43installation in luminaires

DIM KAD-S Lighting control system 48 50for installation in luminaires

DIM SA Signal amplifier 51 52

DIM SC Signal converter for 45, 55 57leading-edge phase dimmers

1246 Quicktr Dimmbar Engl 26.09.2000 9:27 Uhr Seite 74

Page 75: Dimming 1-10 Osram

Device specifications

DIM MCU or DIM MCU P* Electronic potentiometer for 1…10 V* For 1 control point* Integrated switch* With rotary button and cover (on DIM MCU P)* Control of a maximum of 50 QUICKTRONIC® DIMMABLE units

DIM ICM 10* Touch dimming/IR control module for a maximum of 10 IR channels* Control via conventional switch* Any number of switches can be connected in parallel * 1-switch or 3-switch operation possible* Memory function for the last dimmer value* Control via 10-channel IR remote control possible* Casing for installation in luminaire* Control of a maximum of 100 QUICKTRONIC® DIMMABLE units

DIM BK 10* Bus controller for multi-channel systems for DIM ICM 10* Switch can be connected* A maximum of 10 channels can be controlled

DIM FB* 10-channel remote control for DIM ICM 10* Single and group control of the channels possible* 3 switches for on/off, brighter and darker* IR frequency: 455 kHz so immune to ECG-operated fluorescent lamps

DIM IE* Small infra-red receiver for DIM ICM 10* Easy to install in drill holes (21 mm)* IR frequency: 455 kHz, so immune to ECG-operated fluorescent lamps

DIM IRM* 1…10 V control module for scene controller DIM BEAMIT* Control via conventional switch possible* Any number of switches can be connected in parallel* Control of a maximum of 50 QUICKTRONIC® DIMMABLE units

DIM IRE* Infra-red receiver for DIM IRM* Easy to install in drill holes (13 mm)* IR frequency: 447.5 kHz, so immune to ECG-operated fluorescent lamps

DIM BEAMIT* Scene control for dimmable ECGs with 1…10 V interfaces* Individually adjustable scenes or moods can be called up* A maximum of 4 scenes can be stored* Maximum of 4 lighting groups* Elegant 4-channel IR remote control

75

1246 Quicktr Dimmbar Engl 26.09.2000 9:27 Uhr Seite 75

Page 76: Dimming 1-10 Osram

76

DIM PICO* 1…10 V mini light sensor for single luminaires in single and open-plan offices* Up to 50% energy savings* Simple clip-on fitting for T8 and T5 lamps* Direct connection to the 1…10 V-interface * Compensates for 50% of the incoming daylight* Easy to adjust by turning the casing* Controls a maximum of 5 QUICKTRONIC® DIMMABLE units

DIM MICO* 1…10 V mini light sensor for strip lighting in single and open-plan offices * Up to 60 % energy savings* Direct connection to the 1…10 V-interface* No additional signal amplifier required* Compensates for 100% of the incoming daylight * Easy to adjust the lighting level with a screwdriver* Controls a maximum of 100 QUICKTRONIC® DIMMABLE units* Mounting bracket for simple installation

DIM MULTI* 1…10 V sensor for daylight-dependent control with automatic shutdown (3 minutes delay) * With integrated activatable motion detector (between 5 and 30 minutes delay)* Energy savings of 70% and more* Compensates for 100% of the incoming daylight* Easy to adjust with three setscrews on the sensor* For ceiling mounting in single and open-plan offices * Controls a maximum of 50 QUICKTRONIC® DIMMABLE units

DIM MULTI 2* 1…10 V control system for daylight-dependent control with automatic shutdown

(3 minutes delay) * With integrated activatable motion detector (between 1 and 30 minutes delay)* Manual control mode possible* Energy savings of 70% and more* Compensates for 100% of the incoming daylight* Pushbutton adjustment of the setpoint value* For installation in floor-standing luminaires and strip lighting * Controls a maximum of 100 QUICKTRONIC® DIMMABLE units

DIM KAD-S* 1…10 V control system for daylight-dependent control with automatic shutdown

(4 minutes delay) * Energy savings of up to 70% * Compensates for 100% of the incoming daylight* Setpoint value adjustment via external potentiometer * For installation in luminaires * Controls a maximum of 50 QUICKTRONIC® DIMMABLE units

DIM SC * Signal converter for converting from leading-edge phase signal to 1…10 V signal* Controls a maximum of 10 QUICKTRONIC® DIMMABLE units

DIM SA * Signal amplifier for 1…10 V signal* Only in conjunction with other controllers (such as sensors)* Controls a maximum of 100 QUICKTRONIC® DIMMABLE units

Device specifications

1246 Quicktr Dimmbar Engl 26.09.2000 9:28 Uhr Seite 76

Page 77: Dimming 1-10 Osram

Application Lighting requirementsOffices and factories Energy savings with daylight-dependent lighting controlSchools Energy savings with daylight-dependent lighting controlConference rooms, meeting rooms Situation-dependent lighting has priority, for example for and presentation rooms overhead presentations and slide projectionSound, music, TV, film and video High flexibility. The lighting level in these rooms is constantlystudios being adjusted as scenery is changed. This is a normal part

of the production processRestaurants, hotel foyers The right atmosphere comes from lighting that blends in

with the surroundingsCAD rooms, PC rooms, control Users can adjust the lighting level to suit their work and/or rooms and film studios luminance conditions at the workplaceHospitals and doctors’ surgeries Individually adjustable lighting is a significant factor for the

efficiency of medical staff and for the comfort of patientsTunnel systems For reasons of safety, illuminance levels particular at the

entrances to tunnels should be adjusted to prevailing daylight conditions

Multi-purpose rooms High flexibility to cope with different usesStations, airports, shopping centres Energy savings with daylight-dependent lighting controlConcert halls, cinemas, theatres Flexible lighting to cope with all situations from audience

arrival to actual performanceMuseums, exhibition rooms Flexible lighting, dimmed for sensitive exhibits

One control point Section 2.2

Switch control (more than one control point) Section 2.3

Remote control (1 channel) Section 2.3

77

8.1 Overview of applications

8. Appendix

ECG Lamp

ECG Lamp

Switch

DIM ICM-10

ECG Lamp

ECG Lamp

Switch

DIM ICM-10

DIM IE

DIM FB

ECG Lamp

ECG Lamp

DIM MCU

1246 Quicktr Dimmbar Engl 26.09.2000 9:28 Uhr Seite 77

Page 78: Dimming 1-10 Osram

Remote control (more than one channel) Section 4.1

Scene control Section 4.2

Constant lighting control Section 3.1, 3.2

Constant lighting control with automatic shutdown Section 3.3

78

ECG Lamp

ECGDIM MULTI

Lamp

ECG Lamp

ECG Lamp

DIM PICODIM MICO

DIM IRM ECG

DIM BEAMIT

DIM IRE

ECG Lamp

Lamp

1 2

3 4OFF

Per channel

DIM BK10 DIM ICM-10

DIM ICM-10 ECG

ECG

DIM ICM-10

DIM FB

DIM IE

1246 Quicktr Dimmbar Engl 26.09.2000 9:28 Uhr Seite 78

Page 79: Dimming 1-10 Osram

Constant lighting control with automatic shutdownPresence detection and manual switch control Section 4.3

Choice of manual control or constant lighting control Section 4.4

Constant lighting control with 2 lux values (e.g. sports hall) Section 5.5

79

DIM MCU Lamp

Changeoverswitch

ECG Lamp

DIM MICO

ECG

Lamp

Changeoverswitch

ECG Lamp

DIM MICO

DIM MICO ECG

ECG Lamp

ECG Lamp

Switch

DIM MULTI 2

1246 Quicktr Dimmbar Engl 26.09.2000 9:28 Uhr Seite 79

Page 80: Dimming 1-10 Osram

80

DIM

MC

U

DIM

ICM

-10

DIM

FB

DIM

IE

DIM

BK

10

DIM

BE

AM

IT

DIM

IRM

DIM

IRE

1…10 V controlcomponent

required

Application

DIM PICO 50 no – – 50% – Single luminaire, single office

DIM MICO 100 no – – 60% – Strip lighting, single and open-plan offices

DIM KAD-S 100 yes yes – 70% – Strip lighting, open-plan offices, factories

DIM MULTI 100 yes – yes >70% – Strip lighting, single and open-plan offices

DIM MULTI 2 100 yes yes yes >70% yes Floor-standing luminaires

Co

mp

ensa

tio

n o

f…

% o

f d

aylig

ht

Aut

om

atic

shu

tdo

wn

at lo

wes

t d

imm

erse

ttin

g

Ext

erna

l set

po

int

gen

erat

or

Inte

gra

ted

pre

senc

ese

nso

r

Max

imum

ene

rgy

savi

ngs

Man

ual c

ont

rol m

od

e

Guidelines for constant lighting control

Guidelines for manual control

DIM FB

DIM IE HT 1–10 DIM HALOTRONIC®DIM ICM 10

Signal amplifier Section 4.7

Remote control of tungsten-halogen lamps Section 5.7

DIM SA EVG

EVG Lamp

LampControlleror sensor

One control point X(e.g. single office)

More than one control point (e.g. open-plan office Xwith more than one door)

IR remote control X X X(one channel)

IR remote control X X X X(more than one channel)

IR + switch combined X X X X

Scene control X X X

1246 Quicktr Dimmbar Engl 26.09.2000 9:28 Uhr Seite 80

Page 81: Dimming 1-10 Osram

81

8.2 1…10 V dimmingcomponents from othermanufacturers

8.3 ECOS ’99

Friwo COMPIT ITD-10 Touch dimming module, switch dimmingvon-Liebig-Str. 11 Switch module, switching with switches or remote controlD-48346 OstbevernTel.: +49 2532/81-0Fax: +49 2532/81-112

Altenburger NS4-S, NS4 WV-S, IR-ST/S Hall dimmers/simple control for large roomsSchloßweg 5 AQP-S Daylight-proportional control/versatile transitional lightingD-77960 Seelbach AQS-S, AQ NS-S Constant lighting control/energy savings from use Tel.: +49 7823/509-0 of available daylightFax: +49 7823/2761 AQ NP-S Inverse daylight-proportional control/

etc. constant lighting control with outdoor light sensor

Siemens AG Erlangen instabus EIB componentsA&D ET Multifunctional and modular lighting control for switching and dimmingPostfach 3240 Calibration and definition of functions via instabus softwareD-91050 Erlangen Manual control via switches, also via IR remote controlTel.: +49 9131/720893 Light sensor, IR motion detector, timer switch, 4-fold scene memoryFax: +49 9131/724936

Feller AG Beam-it Remote control system with different modulesBergstraße 70 Manual IR transmitter 4-channel remote controlPostfachCH-8810 Horgen 1Tel.: +41-1-72872-0Fax.: +41-1-72872-99

Busch-Jaeger 6599-0-2035 El. potentiometer

Insta Insta 51165 Manual control unit

Berker Art. Nr. 2891 Manual control unit

Jung 240-10 Manual control unit

Gira 30960 Manual control unit309613096230963

ECOS 99 is the latest version of the successful cost/benefit analysis programdeveloped by OSRAM LIGHT CONSULTING GmbH for assessing lightingsystems.

New features in ECOS 99 include the ability to compare ECG systems withone another, calculate electricity costs on the basis of standard or specialtariffs and incorporate any air-conditioning costs in the analysis.

We have retained the self-explanatory user interface, the simple process ofselecting lamps and control gear from the database running in the back-ground and the clear presentation of the results.

With ECOS ’99 you can easily check the cost of lighting systems in thecontext of specific projects.

Program features:

• Systems can be compared with one another

• Dimmable systems can be included

• Even easier to use and to enter information

• Costs can be converted to euros

• ECG systems can be compared with CCG systems (as before)

• Graphics and project data can be printed out

• Basic formulas can be viewed.

ECOS ’99 is indispensable for lighting designers, OEMs, wholesalers andinstallers. Arguments in favour of using ECGs can be backed up with propercostings.

ECOS ’99 can be launched from the Lighting Programme 1999/2000 CD-ROM or from the hard disk.

1246 Quicktr Dimmbar Engl 26.09.2000 9:28 Uhr Seite 81

Page 82: Dimming 1-10 Osram

82

9. Index

Analogue output 52Cable cross-section 63Characteristics 7Cinema control 57Colour temperature 68Constant lighting control 18Cost/benefit program 81Device specifications 74 fDIM BEAMIT 31DIM IRE 31DIM IRM 31Dimming amalgam lamps 68DIM MULTI 2 38Emergency lighting 67Floor-standing luminaires 38Green mode 38HALOTRONIC® 61Holiday mode 38instabus EIB 53Lampholders 63Length of control line 64Light and motion sensor 38 ffLoad from T5 dimmers 72Manual control unit 10Memory function 12Mini constant unit 21Minimum reflector clearances 64Multicore cables 63Multi-lamp luminaires 63Multi-channel systems 28Multisensor controller 38 ffMaster/slave circuit 63Overview of applications 77 ffPC card 52Pictograms 8Potentiometer 10Properties of the 1…10 V interface 6Scene control 31Short-circuiting the control line 7Signal amplifier 50Single-luminaire sensor 19Single-switch operation 12Solid cables 63Stripping length 63Temperature 68Three-switch operation 12Types of cable 63Wiring 62

1246 Quicktr Dimmbar Engl 26.09.2000 9:28 Uhr Seite 82

Page 83: Dimming 1-10 Osram

83

1246 Quicktr Dimmbar Engl 26.09.2000 9:28 Uhr Seite 83

Page 84: Dimming 1-10 Osram

THERE IS LIGHT. AND THERE IS OSRAM.

HEAD OFFICEGERMANY

OSRAM GmbHHellabrunner Strasse 181543 MünchenTel.: +49-89-62 13-0Fax: +49-89-62 13-20 20

INTERNATIONAL ADRESSES

Albania(supported by OSRAM Greece)

ArgentinaOSRAM Argentina S.A.C.I.Ramos Mejia 24561643 BeccarPcia. de Buenos AiresTel.: +54-11-47 19-80 00Fax: +54-11-47 19-80 01

AustraliaOSRAM Australia Pty LtdLevel 11, 423 Pennant Hills RoadP.O. Box 673Pennant Hills NSW 2120Tel.: +61-2-94 81-83 99Fax: +61-2-94 81-94 68

AustriaOSRAM Österreichische Glühlampenfabrik GmbHLemböckgasse 49/C/51230 WienPostfach 1 62 1231 WienTel.: +43-1-6 80 68Fax: +43-1-6 80 68-7

Baltic provinces:Estonia, Latvia, Lithuania(supported by OSRAM Finland)

BelgiumN.V. OSRAM S.A.Mercuriusstraat 281930 Zaventem Zuid 7Tel.: +32-2-7 19 29 11Fax: +32-2-7 20 99 75

Bosnia-Herzegovina(supported by OSRAM Croatia)

BrazilOSRAM do Brasil Lâmpadas Elétricas Ltda.Av. dos Autonomistas, 422906090-901 Osasco-SPTel.: +55-11-70 84 74 08Fax: +55-11-70 85 94 95

BulgariaOSRAM EOODNikola Obreschkov 1, Wh. A., App. 11113 Sofia / BulgariaTel.: +359-2-73 02 42Fax: +359-2-73 02 42

CanadaOSRAM SYLVANIA INC.2001 Drew RoadMississaugaOntario L5S 1S4Tel.: +1-905-6 73 61 71Fax: +1-905-6 73 62 90

ChileOSRAM Chile Ltda.Santa Elena de Huechuraba 1135 BHuechuraba, Santiago de ChileTel.: +56-2-7 40 09 39Fax: +56-2-7 40 04 66

ChinaOSRAM Foshan Lighting Co. Ltd.East-West Highway, XiebianDali Town, Nanhai CityGuangdong, 528231 P.R.C.Tel.: +86-757-64 82-111Fax: +86-757-64 82-222

OSRAM Shanghai Rep. OfficeHarbour Ring Plaza No. 18 Xi Zang Middle RoadRoom 2802, 2803 AShanghai, 200001 P.R.C.Tel.: +86-21-53 85 28 48Fax: +86-21-64 82 12 19

ColombiaOSRAM de ColombiaDiagonal 109 # 21-05 Oficina 614Santafé de BogotáTel.: +57-1-612 28 67Fax: +57-1-612 28 67

CroatiaOSRAM d.o.o.Ozalijska 9310000 ZagrebTel.: +385-1-363-70 00Fax: +385-1-363-76 45

Czech RepublicOSRAM spol. s.r.o., PrahaTylovo námesti 3/1512000 Praha 2Tel.: +420-2-219 87-100Fax: +420-2-219 87-120

DenmarkOSRAM A/SDybendalsvaenget 3Postboks 2592630 TåstrupTel.: +45-44-77 50-00Fax: +45-44-77 50-55

EcuadorOSRAM del Ecuador S.A.Casilla 09-01-8410GuayaquilTel.: +593-4-89 36 09Fax: +593-4-89 35 58

FinlandOY OSRAM ABValuraudankuja 300700 HelsinkiTel.: +358-9-3 74 21 00Fax: +358-9-3 74 22 48

FranceOSRAM SAS5 Rue d'AltorfBP 1 0967124 Molsheim CedexTel.: +33-388-49 75 99Fax: +33-388-49 75 97

Great BritainOSRAM Ltd.East Lane, P.O. Box 17Wembley, Middlesex HA9 7PGTel.: +44-208-9 04 43 21Fax: +44-208-9 01 12 22

GreeceOSRAM A.E.Athinon Av. 5610441 AthenTel.: +30-1-5 20 18 00Fax: +30-1-5 22 72 00

Hong KongOSRAM Prosperity Co. Ltd.Attn. Mr. Ludwig MolderingsRm 1409 Harbour Centre25 Harbour Road, WanchaiHong KongTel.: +852-25 11 22 68Fax: +852-25 11 20 38

HungaryOSRAM KFT.Kis-Buda CenterFrankel Leó út 30-341023 BudapestPf.: 700/611535 BudapestTel.: +36-1-3 26-48 68Fax: +36-1-3 26-41 45

IcelandJóhann Olafsson & Co. h/f43 Sundaborg 13104 ReykjavikTel.: +354-1-533 19 00Fax: +354-1-533 19 30

IndiaOSRAM India Pvt. Ltd.Indomag House, GF 81/1 AdchiniSri Aurobindo Marg110017 New DelhiTel.: +91-11-6 52 61-85Fax: +91-11-6 52 61-84

IndonesiaPT OSRAM IndonesiaJalan Pasar Kemis km-1Desa KeroncongKecamatan Jatiwung15000 TangerangTel.: +62-21-5 90 01 27Fax: +62-21-5 90 05 59

IrelandOSRAM Limited Linfield Industrial EstateLinfield RoadBelfast, BT12 5GLTel.: +44-2890-23 81 25Fax: +44-2890-33 23 99

OSRAM Ltd.8 Raglan RoadDublin 4Tel.: +353-1- 21 62-550Fax: +353-1- 21 62-555

ItalyOSRAM Società RiuniteOSRAM Edison-Clerici S.p.A.Via Savona 105Casella Postale 1 41 0620144 MilanoTel.: +39-02-42 49-1Fax: +39-02-42 49-380

JapanMitsubishi Electric OSRAM Ltd.OSRAM-MELCO Ltd.Tobu Yokohama Bldg.No. 3 (4F) 8-29Kita-Saiwai 2-chome, Nishi-ku220-0004 YokohamaTel.: +81-45-3 23 51-20Fax: +81-45-3 23 51-55

OSRAM Ltd.Tobu Yokohama Bldg.No. 3 (5F) 8-29Kita-Saiwai 2-chome, Nishi-ku220-0004 YokohamaTel.: +81-45-3 23 51-01Fax: +81-45-3 23 51-10

KoreaOSRAM Korea Co., Ltd., Seoul3rd. Fl. Ye-Sung Bldg. 150-30Samsung-Dong, Kangnam-KuSeoul 135-090 Tel.: +82-2-5 54 41 12Fax: +82-2-5 56 16 44

Macedonia(supported by OSRAM Greece)

MalaysiaOSRAM (Malaysia) Sdn Bhd7.05-7.06 Amoda Building22 Jalan Imbi55100 Kuala LumpurTel.: +60-3-2 45 95-33Fax: +60-3-2 45 95-35

MexicoOSRAM de México, S.A. de C.V.Camino a Tepalcapa No. 8Col. San Martin54900 Tultitlán/Edo. de MéxicoTel.: +52-5-8 99-18 00Fax: +52-5-8 99-19 00

NetherlandsOSRAM Nederland B.V.Vennootsweg 152404 CG Alphen a/d RijnPostbus 3 322400 Alphen a/d RijnTel.: +31-172-48 38 38Fax: +31-172-44 30 25

NorwayOSRAM Fabrikken A/SDrammensveien 350271 OsloPostboks 2824/Solli0204 OsloTel.: +47 23 27 67 - 00Fax: +47 23 27 67 - 40

PhilippinesOSRAM Philippines724 Moriones Street Corner Juan LunaTondo, ManilaTel.: +63-2-24-397-14/-17Fax: +63-2-24-397-19

PolandOSRAM sp. z o.o.ul. Wiertnicza 11702-952 WarszawaTel.: +48-22-6 51 78 69Fax: +48-22-6 42 14 18

PortugalOSRAM Empresa de Aparelhagem Eléctrica Lda.Rua das Quintinhas, Lote 122799-522 CarnaxideTel.: +351-21-4 16 58 60Fax: +351-21-4 17 12 59

RomaniaOSRAM Romania S.R.L.Sos. Pipera Nr. 41 Sector 2BucarestiTel.: +40-1-2 33 02-12Fax: +40-1-2 33 02-14

RussiaRep. Office OSRAM GmbHUl. Malaja Kaluschskaja 27117071 MoscowTel.: +7-095-9 58 12-72Fax: +7-095-9 58 12-83

SingaporeOSRAM Singapore Pte. Ltd.159 Sin Ming Road#05-04 Amtech Building575625 SingaporeTel.: +65-5 52 01 10Fax: +65-5 52 71 17

Slovak RepublicOSRAM Slovakia a.s., Nové ZámkyKomárnanská cesta 794093 Nové ZámkyTel.: +421-817-64 64-111Fax: +421-817-64 64-880

Slovenia(supported by OSRAM Austria)

South AfricaOSRAM (Pty.) Ltd., Midrand260, 15th Road1685 RandjesparkPrivate BAG X 2061683 MidrandTel.: +27-11-8 05 17-77Fax: +27-11-8 05 17-11

SpainOSRAM, S.A.Calle de la Solana, 4728850 Torrejón de Ardoz (Madrid)Tel.: +34-91-6 55 52 00Fax: +34-91-6 77 92 40

SwedenOSRAM ABRudanvägen 1Box 5 0413625 HaningeTel.: +46-8-7 07 44-00Fax: +46-8-7 07 44-40

SwitzerlandOSRAM AGIn der Au 6Postfach 6 388401 Winterthur/TössTel.: +41-52-2 09 91 91Fax: +41-52-2 09 99 99

TaiwanOSRAM Taiwan Co. Ltd.Sung Chiang Road, 7th FloorP.O. Box 46304TaipeiTel.: +886-2-25 08 35 02Fax: +886-2-25 09 67 82

ThailandOSRAM Thailand Co., Ltd.100/45, 24th FloorSathorn Nakorn TowerNorth Sathorn Road Khwaeng Silom Khet Bangrak, Bangkok 10500 Tel.: +66-2-6 36 74-75Fax: +66-2-6 36 74-77

TurkeyOSRAM AMPUL TIC. A.S.Barbaros BulvariMürbasan SokakAEG Binasi80700 Istanbul/BesiktasTel.: +90-212-2 16 32 98Fax: +90-212-2 66 52 32

UkraineOSRAM KievRep. Office OSRAM GmbHul. Moskovskaya 37/2252015 KievTel.: +380-44-2 90 11 38Fax: +380-44-2 90 11 38

United Arab EmiratesOSRAM Middle East FZENew High Rise Building4th Floor, LOB 14P.O. Box 17476Jebel Ali, DubaiTel.: +971-4-88 13-767Fax: +971-4-88 13-769

USAOSRAM SYLVANIA INC.100 Endicott StreetDanvers, MA 01923Tel.: +1-978-777-19 00Fax: +1-978-777-12 47

VietnamOSRAM Singapore Pte. Ltd.Rep. Office VietnamPDD Office Building, 8th Floor 162 Pasteur StreetHo Chi Minh CityTel.: +84-8-22 85-41Fax: +84-8-22 85-42

YugoslaviaOSRAM BelgradRep. Office OSRAM GmbHc/o SIEMENS d.o.o.Knez Mihailova 30/II11000 BeogradTel.: +381-11-30 30-860Fax: +381-11-30 30-853

Internethttp://www.osram.dehttp://www.osram.comhttp://www.osram.de/lightatwork/http://www.osram.com/lightatwork/

130

T03

E 9

/00

St

OS

RA

M W

I S

ubje

ct t

o c

hang

e w

itho

ut n

otic

e. E

rro

rs a

nd o

mis

sio

ns e

xcep

ted

. z

Prin

ted

on

pap

er t

reat

ed w

ith c

hlo

rine-

free

ble

ach.

2046 QT dimm E 26.09.2000 9:34 Uhr Seite 2