digital controller fb900 fb400 - cascade.netcascade.net/wp-content/uploads/2020/01/c...(rex-f900)...
TRANSCRIPT
FB900FB400
R
Digital Controller
RKC's conventional temperature controller(REX-F900)
60mm
100mm
FB900
Digital controller
FB900FBFB400400
Plug-in lock released bar
A/M R/LR/S
Digital input
Universal inputUniversal input
Power feedforwardPower feedforward
Remote setting input
PFF input
DC voltage • DC current
Communication
WIN UCI (setting/monitoring tool)
ANSI, MODBUS communication
Digital outputUp to 4 pointsUp to 4 pointsp pp p
Up to 3 pointsUp to 3 pointsAnalog retransmission
poutput
Heat/Cool controlPosition proportioningcontroll
High-performance specifications of samplingtime of 0.1 sec and accuracy of 0.1%.Evolved PID control and auto-tuning functionAdditionally, design of an extremely narrowdepth of 60 mmAt last, the temperature controller satisfyingboth controllability and operability has comeon stage.
A depth of 60 mm contributing to narrowing control panel depth and lessening mounting spaceThis temperature controller is nearly half the size of our conventionaltemperature controllers.
(As of December, 2004 for the plug-in type temperature controller)p gA depth of 60 mm: the shortest length in the world!
11So constructed that the plug-in lock is easily released.
y p y p gEasy maintenance due to the employment of plug-inconstruction22
Waterproof/Dustproof : NEMA4X3
Numerous inputs and outputs4
Packing superior expandability into a slender bodykicking suPacking supPacking supe
Up to 2 pointsp p s
Inter-controller communication
Up to 7 pointsp p
( )WIN UCI (Loader communication)
<AT (Auto-tuning)>
<PID Control>
Incorporating evolved PID: Incorporap
"Brilliant II PID" into this controllerB illi"Brillia"Brillian
SV
Only execution at power ON Only execution at SV change Execution at power ON and SV change
Power ON
SV2
SV1
SV2
SV1
New heat/cool PID control enforced with undershoot suppression of the cool side
SV
SV
USS gain : Small
USS gain : Large
* USS setting range : 0.000 to 1.000
FAST
MEDIUM
SLOW
Control response parameter USS (Under Shoot Suppression) gain
PV NEW
Two types of PID control are selectable: "response emphasized type" and "follow-up emphasized type".
SV
SVPV
PV
Overshoot
Hunting
SV change
Tuning
ON
AT function when limiter is effective.AT function when limiter is not effective.
SV
AT output limiterHighAT output limiterLow
PV
Output 100%
Output 0%
Output 100%
Output 0%
AT ON AT ON
1 sec 1 sec
200 SV PV
100
250ms sampling controller( C) ( C)
200 SV PV
100
A/M R/LR/S
FB400
PV
SV MV
Heat control
Heat/Cool control
1In addition to "measured-value derivative type PID control which is most adaptive to conventional fixed value control, this controller has been incorporated, as standard, with "deviation derivative type PID control which displays its power in cascade control as well as in ramp control by using a rate of setting change limiter, etc. The most adaptive control type can be freely selected depending on the temperature control mode used.
Three types of sampling time are selectable: 0.05 sec (high-speed sampling type), 0.1 sec (standard type) and 0.25 sec (high-resolution type).An integral/derivative setting unit of 0.1 sec which enables a fast responding control system to be tuned up to its limits is also selectable. Further, this controller incorporated with a rate of setting change limiter/a rate of output change limiter (both of them can be set independently for temperature rise and fall) takes account of its use even in applications with special heaters.
In addition to the conventional control response parameter setting corresponding to controllability against both temperature rise and disturbance in heat control, this controller has newly been incorporated with the USS (Under Shoot Suppression) function and dedicated cool control algorithm.Further, as it can set PID constants independently on the heat and cool sides, it enables control which extremely suppresses undershooting even in a control system where a cooling gain is very large.
The conventional enhanced AT function and brilliant PID control algorithm have been improved. PID constants at which fast responsiveness can be expected on both the heating and cooling sides are automatically calculated.
As PID constants are automatically calculated from the temperature characteristics during the temperature rise, no time to execute the AT function becomes needed. Therefore, this function is effective if used in equipment whose AT execution time becomes extremely long.Its execution is selectable when "only at power on/only at setting change/at both power on and setting change". "Only at the beginning/at all times" can also be selected.
The amount of control output at ON/OFF when the AT function is executed is freely settable.Effective to prevent equipment damages by ON/OFF output when the AT function is executedCan be set independently on the ON/OFF sides.
Any type of control can be freely selected through front key manipulation.
• Prior to factory shipment, set to measured-value derivative type PID control.
2
3
4
1
2
3
Being able to select the specification of a sampling time of 0.05 sec and also responding to any high-speed temperature rise processes.
• Prior to factory shipment, the sampling period is set to 0.1 sec (standard specification).
• Can be selected from among dedicated control algorithms for air cool/water cool control. (Selectable)
Being able to select each control of "heating/cooling/heating and cooling/position proportioning"
Further, the new AT function calculating the most adaptive PID constants
Incorporating the "startup tuning" function which can shorten AT execution time
• Startup tuning is not available with Heat/Cool PID control type.• Validity/invalidity of the startup tuning function can be set. • Heater power needs to be turned on simultaneously with or before turning on power to the temperature controller.• If no adaptive PID constants can be obtained after executing the startup tuning function, execute the AT function.
Lessening an effect upon equipment by ON/OFF output when the AT function is executed.
Measured-value derivative type PID controlResponse emphasized type Follow-up emphasized type
Deviation derivative type PID control
Most adaptive to conventional fixed value control
Most adaptive to conventional fixed value control
Follow-up
Follow-up
50ms sampling controller
Cool control
Position proportional controlt l
Tuning
ON
Tuning
ON
Tuning
ON
Power ON
SV change
SV
PV
A/M R/LR/S
FB400
PV
SV MV
SV MV
A/M R/LR/S
FB400
PV
SV MV
• Resolution can be set.
• Measured value/set value and also CT1/CT2 input value can also be displayed.• Prior to factory shipment, manipulated output display is selected.• The FB900 is for 20-dot display and the FB400 is for 10-dot display.
• Can be set to any of the following selection modes.
(Also possible to invalidate the direct mode selection key function.)
Pressing the MODE select key for 2 sec enables the same mode selection as in the conventional REX-F900/F400.
(Direct mode select key)
(Multi-Memory Area function)
For selecting frequently used modes, a dedicated key is provided. Easy and quick operation is performed for various modes of process control.
As this is a 7-segment display unit with a character height of 20 mm, it has realized high visibility even from a distance.Additionally, this 5-digit display unit enables the wide display range of -19999 to 19999. (The display range varies depending on the input type.)
Set value
Event 1 to 4 Set value
LBA time
LBA dead band
Control response
Overlap/Deadband
Proportional band(Heat and Cool)Proportional band(Heat and Cool)Integral time(Heat and Cool)
Area soak timeLink area number
RUN/STOP
Direct Mode Selection
Delivering a user-friendly interface
Eight different types of set values (SV) and event set values can be registered.Only the area selection enables the simultaneous and easy setting most adaptive for each process/recipe.
Selection of up to 8 processes/recipes
Area 1
Area No.
0% -10˚C 0˚C +10˚C100%
A/M MONI AREA
FB900A/M MONI AREA
FB900
• Memory area operation lapsed time (Soak time) display is available.
Linked area No.
Soak time
SV changing rate limiter(Up)
Area1(Step1)
Area2(Step2)
Area3(Step3)
Area4(Step4)
Area5(Step5)
Area6(Step6)
Area7(Step7)
Area8(Step8)
PID/AT
A/M R/LR/S
FB900
PV
SV MV
A/M R/LR/S
FB400
PV
SV MV
1
Large, Clear 5-digit Display Unit2
The manipulated output/deviation are clearly visible.3
4
Up to 16-segment (8-step) ramp/soak control can easily be accomplished by using area soak time, link area number and SV changing rate limiter in multi-memory
Ramp/Soak control5
Auto Manual
Memory area select
Monitoring display select
Memory area select
Monitoring display select
Auto/Manual
Remote/LocalAuto/Manual
Auto/Manual
RUN/STOP
Remote/Local
Manipulated output Deviation
Derivative band(Heat and Cool)
Setting change rate (Up and Down)
Set value
Event 1 to 4 Set value
LBA time
LBA dead band
Control response
Overlap/Deadband
Proportional band(Heat and Cool)Proportional band(Heat and Cool)Integral time(Heat and Cool)
Area soak timeLink area number
Area 8
Derivative band(Heat and Cool)
Setting change rate (Up and Down)
Design considering safety and ecologyDDeDesDesi
Possible to perform stable temperature control without partial burning and/or partial thermal expansion by rising the temperature evenly throughout all of the zones in multi-point temperature control.If control is started with the startup tuning learning function activated during the first startup of each controller, from the next time each controller within a group starts rising the temperature evenly by referring to a channel whose temperature rise is slow. As a result, all of the channels will finally and simultaneously arrive at the set value.• Up to 16 groups can be configured (up to 32 sets in total).• Functioning via "inter-controller communication" using communication.
When automatic temperature rise is not setCH A
CH A CH B CH C CH D
B
DC
All CH Temperature rise completion
Start
All CH Temperature rise completion
Start
When automatic temperature rise is set
Control supporting an improvement in quality
(Automatic temperature rise with learning function)
(Power feedforward function)
Dedicated transformer
Thyristor unit
Power feedforward function
A/M R/LR/SPFF Input
V
Control output
PID output
PFF correction +
CH A
CH BCH C
CH D
CH A
CH BCH C
CH D
CH C
CH D
CH BCH A
CH C
CH D
CH BCH A
RS-485
Up to32 units
A/M R/LR/S A/M R/LR/S A/M R/LR/S A/M R/LR/S A/M R/LR/S A/M R/LR/S A/M R/LR/S
Group 1 Group 16
Enabling temperature rise without time dispersion1
Possible to optionally incorporate the PFF (power feedforward) function effective for temperature control placing much emphasis on stability.
Our instrument power supply circuits are designed so as to be reinforcement insulated. Thus, it is not necessary to add basic insulation on the equipment side, resulting in a reduction in equipment cost.
The safety standards on electrical equipment (JISC 1010-1 and IEC 61010-1) request that the secondary side of the equipment which may be touched by the operator should be double insulated or reinforcement insulated* from high voltage causing electric shock.
<Requirements for electrical equipment according to safety standards>
Compensating the control output by monitoring even power supply voltage variations2
1
Time
Time
Having achieved safety and low cost by the employment of reinforced insulation
Having achieved environment-friendly "lead-free" printed circuit boards according to the EU directive (waste electrons/electrical equipment directive (WEEE directive)/directive of restricting the use of harmful materials for electrical products (ROHS directive))Reducing a power consumption of 30%.
2
• Insulation safeguarding personnel from electric shock which is equal to double insulation or higher is called "reinforced insulation".
Employing environment-friendly "lead-free"
Power and drive circuits have newly been designed. For the FB900, a power consumption of 5 VA/set (at 240 VAC) is saved when compared with our REX-F900. As a result, heat generation lessens also contributing to cooling within control panels.
3 Reducing a power consumption of 30% • Power consumption ratio of our products (the comparison of the REX-F900 and the FB900 with the same specifications)
CH A waitCH B waitCH C wait
Measured value (Max. 8000 data), trend graph and event history logs is managed by using a personal computer. Data can be stored in the file in the CSV format.
Providing the user with the setting/monitoring tool "Win-UCI"
Loader communication connector
USB port
Upload
Data logging and trend graph screen
Temperature monitor/ setting screen• Any picture image (bitmap format) can be embedded in the background.
Download
Win UCI can be downlaod from RKC's website at www.rkcinst.com.
RS-485
Up to31 units
RS-232C
Instrument data can be easily copied.
Communication converter : COM-K
USB
CSV File
Loader communication
A/M R/LR/S
A/M R/LR/S A/M R/LR/S A/M R/LR/S
User mapping area
0000 PV monitor0001
SV monitor
PV monitorSV monitorEvent monitorProportional bandIntegral timeDerivative time
0002CT1 monitor
0003CT2 monitor
0XX0
0XX1
0XX2
0XX3
0XX4
0XX5
0XX6
(Up to 16 item)
RUN/STOP status
Cable length : 1m
70
(Unit : mm)
26
RS-422A/485
USB
Connector (Phoenix contact)(Attached accessories)
A/M R/LR/S
FB900
PV
SV MV
39
Data communication as desired
Data on this controller can be easily managed by using the USB or serial port of a personal computer (incorporated with Windows 2000/XP).
1
As up to 16 data items which need to be always used can be freely mapped to consecutive addresses, the amount of data to be transferred widely lessens, thereby achieving high-speed, smooth communication.
2
Temperature data is easily managed by using a personal computer.
Setting & Monitor
Converter
Converter
All data within the instrument can be collectively converted to one file and then be read into a personal computer. This is very convenient for data transfer during instrument maintenance or replacement.• The instrument hardware specifications need to be matched.
As the temperature controller is driven by USB bus power, it can be used without instrument power wiring.
• Attached as standard when without the communication function.
Loader communication (data storage/transfer) screen
Cable length : 1mLoader communication
Having achieved high-speed data collection.
• Mapping is set by Win-UCI.
PV monitorSV monitorEvent monitorProportional bandIntegral timeDerivative timeRUN/STOP status
"Seven items from 0XX0"
Communicationconverter
User mapping function (Modbus protocol)
A/M R/LR/S
SV
A/M R/LR/S
SV
A/M R/LR/S
Enabling linked operation via communication
FB400/900 can be connected CC-Link, Ethernet, PROFIBUS andDeviceNet via communication converter "COM-J" MAPMAN function (RKC's unique program-free connection systemto PLCs) is available via communication converter "COM-J"
(RS-485)
Inter controller communication
Up to32 units
Group 1
CH A CH CCH B CH D
Master Slave Master Slave
CH1 CH3CH2 CH4CH1 CH3CH2 CH4
A/M R/LR/SA/M R/LR/SA/M R/LR/SA/M R/LR/SA/M R/LR/SA/M R/LR/SA/M R/LR/SA/M R/LR/S
A/M R/LR/S
A/M R/LR/S A/M R/LR/S
A/M R/LR/S A/M R/LR/S A/M R/LR/S A/M R/LR/S
A/M R/LR/S A/M R/LR/S A/M R/LR/S
CH A • B • C • D
SV MV
RUN RUN RUN RUNA/M R/LR/S
STOPA/M R/LR/S
STOPA/M R/LR/S
STOPA/M R/LR/S
STOP
SV
A/M R/LR/S
SV
A/M R/LR/S
SV
A/M R/LR/S
SV
CC-Link Ethernet • Released soon
Communicationprotocol converter PLC
MitsubishiMELSEC series
OmronSYSMAC series
Program free
RS-485
MAPMAN
PROFIBUSDeviceNet
COM-JG COM-JLCOM-JHCOM-JC
COM-JE
3Linked operation such as of cascade, ratio, etc. is possible only by using a dedicated communication line (inter-controller communication) without using analog signals such as remote input, analog output, etc.
Can be connecting to open network 4
• The dedicated communication line (inter-controller communication) uses communication port 2 of the controller.• When inter-controller communication is used, remote signal is not used.
Possible to perform stable temperature control without partial burning and/or partial thermal expansion by rising the temperature evenly throughout all of the zones in multi-point temperature control.
Effective when the thermal delay between the final work and heat source is large. Temperature control is performed with slave controllers receiving a correction signal (output signal) from the master as a set value so that the master controller temperature will become constant.
If the master controller temperature setting is changed, the set value of controllers on the slave side is changed together with the ratio always being set.
If any controller is set to STOP within each group, controllers within the group are automatically selected together.When controller which press the STOP key is set to RUN, within the group are automatically selected together.
• Up to 16 groups can be configured (up to 32 sets in total).
• Up to 16 groups can be configured (up to 32 sets in total).
• Up to 16 groups can be configured (up to 32 sets in total).
Automatic temperature rise with learning function
Ratio control
Group STOP/RUN function
Cascade control
Group 1 Group 2 Group 16
Temperature rise completionStart
Ratio Ratio Ratio Ratio Ratio Ratio
Group 1Group 1
CC-LinkCommunicationConverter
DeviceNetCommunicationConverter
PROFIBUSCommunicationConverter
EthernetCommunicationConverter
a)Thermocouple Type : K, J, T, E, PLII, U, L Less than -100°C (-148°F) : ±1.0°C (±1.8°F) -100 to +500°C (-148 to 932°F) : ±0.5°C (±0.9°F) More than 500°C (932°F) : ±(0.1% of reading + 1 digit) Type : N, S, R, W5Re/W26Re Less than 0°C (32°F) : ±2.0°C (±3.6°F) 0 to 1000°C (32 to 1832°F) : ±1.0°C (±1.8°F) More than 1000°C (1832°F) : ±(0.1% of reading + 1 digit) Type B Less than 400°C (752°F) : ±70.0°C (±126°F) 400 to 1000°C (752 to 1832°F) : ±1.0°C (±1.8°F) More than 1000°C (1832°F) : ±(0.1% of reading + 1 digit) • Cold junction temperature error ±1.0°C (1.8°F) (at 5 to 40°C) (41 to 104°F) ±1.5°C (2.7°F) (at -10 to 5°C and 40 to 50°C) (at 16 to 41°F and 104 to 122°F) b) RTD Less than 200°C (392°F) : ±0.2°C (±0.4°F) More than 200°C (392°F) : ±(0.1% of reading + 1 digit)c) DC voltage and DC current ±(0.1% of span)±1.5°C (2.7°F)
More than 20MΩ (500V DC) between measured terminals and groundMore than 20MΩ (500V DC) between power terminals and groundMore than 20MΩ (500V DC) between measured and power terminals1000V AC for one minute between measured terminals and ground1500V AC for one minute between power terminals and ground2300V AC for one minute between measured and power terminals
Performance
Insulationresistance
Dielectricvoltage
a) Brilliant ΙΙ PID control • Direct action/Reverse action is selectableb) Brilliant ΙΙ PID control (Heat/Cool type)c) Position proportioning control without feedback resistance • a), b), c) is selectablea) For PID control (Direct action/Reverse action)b) For Heat/Cool PID control (For extruder, air cooling)c) For heat/Cool PID control (For extruder, water cooling)d) For heat/Cool PID controlPID constants are automatically calculated from the temperaturecharacteristics during the temperature rise.(Not available for Heat/Cool PID control type) a) Only execution at power ON b) Only execution at SV change c) Execution at power ON and SV change d) Only execution at the beginning e) Only execution at all time f) No startup tuning • a) to f) is selectablea) Proportional band : Temperature input, 0 to input span (°C,°F) Voltage • Current input, 0.0 to 1000.0% of input span (ON/OFF action when P = 0) • Differential gap at ON/OFF action (High/Low individual setting) : Temperature input : 0 to input span (°C,°F) Voltage • Current input : 0.0 to 10.0% of input spanb) Integral time : 0 to 3600 sec or 0.0 to 1999.9 sec (selectable) (Integral action is OFF when I = 0)c) Derivative time : 0 to 3600 sec or 0.0 to 1999.9 sec (selectable) (Derivative action is OFF when D = 0)d) Cool side proportional band : Temperature input : 1(0.1, 0.01) to input span (°C,°F) Voltage • Current input : 0.0 to 1000.0% of input spane) Cool side integral time : 0 to 3600 sec or 0.0 to 1999.9 sec (selectable) (Integral action is OFF when I = 0)f) Cool side derivative time : 0 to 3600 sec or 0.0 to 1999.9 sec (selectable) (Integral action is OFF when I = 0)g) Overlap/Deadband Temperature input : -span to +span (°C,°F) Voltage • Current input : -100.0 to +100.0% of input spanh) Control response : Slow, Medium, Fasti) Setting change rate limiter 0 to span/1 to 3600 sec (High/Low individual setting)j) Output limiter : -5.0 to +105.0% (High/Low individual setting) k) Output change rate limiter : 0.0 to 100.0%/sec (Up/Down individual setting)l) Proportional cycle : 0.1 to 100.0 secm) Cool side proportional cycle : 0.1 to 100.0 secn) Manual reset : -100.0 to +100.0%o) Output at stop : -5.0 to +105.0% (Heat/Cool individual setting)
Control method
Autotuning
Startup tuning
Setting range
5 to 1000 secOFF, 0.1 to 200.0% of motor time0.1 to 10.0%0.1 to 5.0%a) Close: OFF, Open: OFFb) Close: ON, Open: OFFc) Close: OFF, Open: ON • a), b), c) is selectable
Motor time
Action at stop
Neutral zoneDifferential gap
Integral output limiter
Number of outputs
Number of area
Output function
Output signal
OutputUp to 2 points (OUT1, OUT2)Control output, analog retransmission output,event output • See output allocation table (page 11)a) Relay contact output, Form a contact 250V AC 3A (Resistive load) • Electric life : 300,000 cycle or moreb) Voltage pulse output, 0/12V DC (Load resistance : More than 600Ω)c) Current output, 4 to 20mA DC, 0 to 20mA DC (Load resistance : Less than 600Ω)d) Continuous voltage output, 0 to 5V DC, 1 to 5V DC, 0 to 10V DC (Load resistance : More than 1kΩ)e) SSR (Triac) output, Rated current : 0.5Af) Open collector output (Sink type) Load voltage : Less than 30V DC Load current : Less than 100mA ON voltage : Less than 2V (at max load current)
• Universal input a) Temperature, Current, Low voltage input group Thermocouple : K, J, E, T, R, S, B, N (JIS/IEC) PLII (NBS), W5Re/W26Re (ASTM) U, L (DIN) RTD : Pt100 (JIS/IEC), JPt100 (JIS) • 3-wire system Low voltage (Input impedance : More than 1MΩ) 0 to 1V DC, 0 to 100mV, 0 to 10mV DC -100 to +100mV DC, -10 to +10mV DC Current (Input impedance : 1MΩ) 4 to 20mA, 0 to 20mA b) High voltage input group High voltage (Input impedance : 1MΩ) -1 to +1V DC, 0 to 5V DC, 1 to 5V DC, 0 to 10V DC (Use dip switch to change input group.)0.1sec • 0.05sec/0.25sec is selectable.0.2µV/Ω (Thermocouple input)
0.01% of reading/Ω (RTD input) • Maximum 10Ω per wireThermocouple input : Up-scale/Down-scale (Selectable)RTD input : Up-scaleLow voltage input : Up-scale/Down-scale (Selectable)Current input : Value around 0mAHigh voltage input : Value around 0VDown-scale (RTD input)0.1 to 100.0 sec. (OFF when 0 is set.) -span to +span0.500 to 1.500PV = (Input value x PV ratio + PV bias)Low level cut off : 0.00 to 25.00% of span
Up to 8 pointsa) Set value (SV)b) Event setting 1 to 4c) LBA timed) LBA dead bande) Proportional bandf) Integral timeg) Derivative timeh) Cool side proportional bandi) Cool side integral timej) Cool side derivative timek) Overlap/Deadbandl) Control response parameterm) Setting change rate limiter(Up/Down)n) Soak time 0 min 00 sec to 199 min 59 sec or 0 hr 0 min to 99 hr 59 min (selectable)o) Linking area number : OFF, 1 to 8
Setting item
Memory area function
Specifications
InputInput
Sampling time
Influence of externalresistanceInfluence of leadresistance
Input short actionInput digital filterPV biasPV ratioSquare root extraction
Input break action
Control
Position Proportional Control
Measuring accuracy
Close horizontalmounting error
NEMA4X, IP66 • Waterproof/Dustproof protection only effective from the front panel mounted installation.
a) 90 to 264V AC (50/60Hz, Selectable) Rating : 100 to 240V ACb) 24V AC ±10% (50/60Hz, Selectable) Rating : 24V ACc) 24V DC ±10% Rating : 24V DCa) 100 to 240V AC type FB900 : 13.0VA (240V), 8.7VA(100V) FB400 : 11.9VA (240V), 7.8VA(100V)b) 24V AC type FB900 : 9.3VA FB400 : 8.2VAb) 24V DC type FB900 : 300mA FB400 : 250mAA power failure of 20m sec or less will notaffect the control action. If power failure of morethan 20m sec occurs, controller will restart. HOTstart (1,2) or COLD start (selectable)Backed up by non-volatile memory• Data retaining period : Approx. 10 years• Number of writing : Approx. 1,000,000 times.(Depending on storage and operating conditions.)-10 to +50°C (14 to 122°F)5 to 95% RH (Non condensing)• Absolute humidity : MAX.W.C 29g/cm3 dry air at 101.3kPaFB900 : Approx. 290gFB400 : Approx. 230gFree from corrosive and flammable gas and dust.Free from external noise, vibration, shock and exposureto direct sunlight.CE Mark, UL, C-UL, C-Tick markCompliance with
Standards
Communications
General Specification
Waterproof/Dustproof
Communication methodProtocol
Communication methodProtocol
Bit configuration
Communication speed
COM1
2400bps, 4800bps, 9600bps, 19200bps, 38400bps• Selectablea) RKC standard protocol Start bit : 1 Data bit : 7 or 8 Parity bit : 1 (odd or even) or none Stop bit : 1 or 2b) MODBUS protocol Start bit : 1 Data bit : 8 (binary or byte data) Parity bit : 1 (odd or even) or none Stop bit : 1 or 2 (Fixed to 1 bit for parity 1)• SelectableRS-485 : 32 units (Including host)RS-422A : 16 units (Including host)RS-232C : 1 unit
Maximumconnection
Supply voltage
Power consumption
Power failure
Memory backup
Ambient temperatureAmbient humidity
Weight
Operatingenvironment
COM2 • COM2 can use Inter-controller communication.
Up to 4 pointsProcess high, Process low, Deviation highDeviation low, Deviation high/low, Band,Set value high, Set value low, MV value high,MV value low, Cool side MV value high, Coolside MV value low, LBA (Control loop break alarm) • LBA is assignable to event 4.a) Deviation alarm Event setting : -input span to +input span Event action differential gap : 0 to input spanb) Process alarm/Set value alarm Event setting : Same as input range Event action differential gap : 0 to input spanc) MV alarm -5.0 to +105.0%d) LBA LBA time : 0 to 7200 sec (LBA is OFF when 0 is set.) Dead band : 0 to input spanAssignable to digital output (DO 1 to 4) • See output allocation table (page 11)a) Hold/Re-hold action (Valid for deviation/band/process alarm only) • Hold action is valid when the instrument is power-ON or transferred from STOP to RUN. Re-Hold action is valid when the instrument is power-ON, transferred from STOP to RUN or changed the set-value.b) Selection of event action for input abnormality.c) Energized/de-energized action is selectable.d) Delay timer : 0.0 to 600.0 sece) Interlock function is available.
Event (Alarm)
Output method
Other function
Up to 2 points (1 point per CT 1 point inapt)CTL-6-P-N, CTL-12-S56-10L-N (Selectable)CTL-6-P-N : 0 to 30ACTL-12-S56-10L-N : 0 to 100A0.0 to 100.0A±5% of input value or 2A (whichever is larger)Assignable to output 2 or digital output (DO 2 to 4) • See output allocation table (page 11)
Heater break alarm (HBA)Number of alarm
Number of input
CT TypeInput range
Input methodFunction
Input rangeDisplay accuracyOutput method
a) Low voltage, current group 0 to 1V DC, 0 to 100mV DC, 0 to 10mV DC 4 to 20mA DC, 0 to 20mA DCb) High voltage group 0 to 5V DC, 1 to 5V DC, 0 to 10V DC• Universal input0.1 sec (at measuring sampling 0.05 sec)0.2 sec (at measuring sampling 0.1 sec)0.5 sec (at measuring sampling 0.25 sec)±0.1% of span
Remote setting input
Accuracy
Output type
Output signal
Power feed forward (PFF) input
• Not available with slave controller of inter-controller communication (Ratio control, Cascade control)
• Use communication port 2
• Exclusive power feed transformer is required.
Up to 7 points (DI 1 to 4, DI 5 to 7)Non-voltage contact inputDI 1 to 4 : Memory area selection + Area setDI 5 to 7 : RUN/STOP, Remote/Local, Auto/Manual Interlock reset, Power supply frequency selecting • Selectable
Digital input (DI)
Up to 4 points (DO 1 to 4)Event output, Heater break alarm (HBA), FAILRelay contact output, Form a contact 250V AC 1A (Resistive load)
(Optional)
(Optional)
(Optional)
(Optional)
(Optional)
(Optional)
Number of output
Number of eventEvent type
Setting range
Output functionOutput signal
Function : Automatic temperature rise, Cascade control, Ratio control, Group STOP/RUN
Up to 3 points• Assignable to AO (For analog output), output 1 or output 2Measured value (PV), Set value (SV)Manipulated value (MV), Deviation (PV/SV)• Selectable4 to 20mA DC, 0 to 20mA DC (Load resistance : Less than 600Ω)0 to 1V DC, 0 to 5V DC, 1 to 5V DC, 0 to 10V DC (Load resistance : More than 1kΩ)
Analog retransmission output (AO)
Resistance valueSampling time
Standard : 135Ω0.1 sec (at measuring sampling 0.05 sec)0.2 sec (at measuring sampling 0.1 sec)0.5 sec (at measuring sampling 0.25 sec)
• Not available with CT or PFF input.
• Not available with PFF or CT 2 points input.
Specifications
Digital output (DO)
Input
Sampling time
Number of output
Feed back resistance (FBR) input (Optional)
(Optional)
Number ofcommunication
COM1/COM2
Up to 2 points
Based RS-485/RS-422/RS-232Ca) ANSI X3.28 sub-category 2.5A4 (RKC standard)b) MODBUS-RTU • Selectable
Based RS-485a) ANSI X3.28 sub-category 2.5A4 (RKC standard)b) MODBUS-RTU • Selectable
(Optional)
(Optional)
Inter-controller Communication
S
(96 x 96mm 1/4 DIN size)(48 x 96mm 1/8 DIN size)
FB900FB400
Specifications
Measuring input
Digital input (DI 1 to 4)
Remote setting input
<Relay contact output>
Digital output
Output 1
Output 2
Power Supply
N1
N1
N1
NPT1234F
N145WXY
NABC
34
0 to 5V DC, 0 to 10V DC, 1 to 5V DC
0 to 10mV DC, 0 to 100mV DC, 0 to 1V DC, 0 to 20mA DC, 4 to 20mA
Relay contact output
Relay contact output
DO1
DO2
DO3
DO4
Digital outputControl outputAnalog output
Voltage pulse output (0/12V DC)
Triac outputOpen collector outputNot supplied
Not supplied
Not supplied
Not supplied
Not supplied
Not supplied
Not supplied
Not supplied
DC mA, mV, V
Voltage pulse output (0/12V DC)
Triac outputOpen collector output
DC mA, mV, V
24V AC/DC100 to 240V AC
DO 1DO 1 + DO 2DO 1 + DO 3DO 1 + DO 2 + DO 3DO 1 + DO 2 + DO 3 + DO 4
PFF input (With transformer 100 to 120V AC type)
DI 4 points (DI 1 to 4)
CT input 1 pointCT input 2 points
PFF input (With transformer 200 to 240V AC type)CT input 1 point + PFF input (With transformer 100 to 120V AC type)CT input 1 point + PFF input (With transformer 200 to 240V AC type)Feed back resistance input
DI 3 points (DI 5 to 7)
COM1 : RS-232C
None : Default setting
Version symbolInstrument versionSpecify Initial setting code (See page 11)
COM1 : RS-422ACOM1 : RS-485COM1 : RS-232CCOM1 : RS-485COM1 : Not supplied
COM2 : Not suppliedCOM2 : Not suppliedCOM2 : Not suppliedCOM2 : RS-485COM2 : RS-485COM2 : RS-485
White case • Waterproof/Dusproof protectionBlack case • Waterproof/Dusproof protection
White caseBlack case
K
J
-100.00 to +100.00°C, -199.99 to +199.99°F-328.0 to +1184.0°F-200.0 to +640.0°C,
-100.00 to +100.00°C, -199.99 to +199.99°F-328.0 to +1562.0°F-200.0 to +850.0°C,
0.0 to +1652.0°F
-200.0 to +800.0°C,
-200.0 to +800.0°C,
-200 to +1200°C
-200 to +1372°C-328.0 to +1200.0°F
-328 to +2192°F
-250.0 to +800.0°F-328 to +2502°F
0 to 1390°C0 to 1300°C,
-50 to +1768°C, -58 to +3214°F-50 to +1768°C, -58 to +3214°F
0 to +2372°F0 to +2534°F
-200.0 to +400.0°C, -328.0 to +752.0°F-200.0 to +700.0°C,
-200 to +1000°C,-328.0 to +1292.0°F
-328 to +1832°F
T
SR
PLII
B
Pt100
JPt100
N
E
W5Re/W26Re
0 to 10mV DC, 0 to 100mV DC
-1 to +1V DC, 0 to 5V DC 0 to 10V DC, 1 to 5V DC
4 to 20mA DC, 0 to 20mA DC
-10 to +10mV DC -100 to +100mV DC
0 to 1V DC
Input Type345
CodeOutput Type
0 to 5V DC0 to 1V DC
0 to 10V DC
0 to 20mA DC1 to 5V DC
4 to 20mA DC
678
N
• Event function output
CT input (For HBA)Power feed forward (PFF) inputFeed back resistance
Communication
Analog retransmissionoutput (AO)
Case color •Waterproof/Dustproof
Initial setting
(Memory area selection)
Digital input (DI 5 to 7)(Mode selection)
(DO1 to 4)
(OUT 1)
(OUT 2)
MV
TD
NABCDE
NMV
TD
N
S
H
0.0 to 600.0°C, 32.0 to 1112.0°FU0 to 1800°C, 0 to 3272°F
L 0.0 to 900.0°C,
0 to 2300°C, 0 to 4200°F
Model and Suffix Code
-19999 to +19999(Scale range and decimal point areprogrammable)
Input Range Table Output Code Table
Model Code :
Terminal cover
See Input Range Table
See Output Code Table
Range
: necessary : Either of selectable
KFB400-58
(FB900 uses 2 unit)
FB400 FB900
Model and Suffix Code
Universal Input (Field configurable)
See Output Code Table
DC mA, mV, V See Output Code Table
Y
PIDcontrol
Heat/CoolPIDcontrol
Positionproportioningcontrol
Analogretransmissionoutput
Alarm LBA HBA
(Relaycontactoutput)
(Relaycontactoutput)
AO
CT
* : Use dip switch to change the input group between Low Voltage (thermocouple, RTD, mV/mA) and High Voltage (V). The factory setting for Input is Low Voltage Input. Specify "H" if high voltage input is desired as factory setting.
*
Lowvoltagegroup
Highvoltagegroup
Thermocouple
Max
.63
Max.70
Max.68
2-M4
5959
±0.5
50
Mounting dimension
* Supplied when power feed forward function is specified.
* When ordering transformer for replacement, please specify one of the following model codes. 100 to 120V AC type : PFT-01 200 to 240V AC type : PFT-02
(For Power feed forward input)
±1
±0.2
Model code
Current transformer for heater break alarm (HBA)
CTL-6-P-N (0 to 30A)CTL-12-S56-10L-N (0 to 100A)
(Sold separately)
(Sold separately)
** : When inter-controller communication is used, please specify code "W, X or Y (COM2 : RS-485). Slave controller of ratio or cascade control type is not available with remote setting input.*
**
* 0 to 1V DC output type can be specified only analog retransmission output.
• The initial value setting code is for factory shipment by setting each initial value to the detailed specification desired by the customer. If desired, separately specify the initial value setting code by specifying "Initial setting provided" in the Model and codes. (Unnecessary to be specified when "Initial setting is none.")
Initial set code
Control method
Power frequency
Measuring input
Remote settingsignal
Output allocation
Event 1 type
Event 2 type
Event 3 type
Event 4 type
CT1 type
N12345678
Position proportional PID control without FBR50Hz60Hz
0 to 1V DC
0 to 10V DC1 to 5V DC0 to 20mA DC4 to 20mA DCNo event 1
No event 2
Heat/Cool PID control with ATHeat/Cool PID control with AT for extruder (Air cooling type)Heat/Cool PID control with AT for extruder (Water cooling type)
PID control with AT (Reverse action)PID control with AT (Direct action)
Control loop break alarm (LBA)
CTL-6-P-NCTL-12-S56-10L-N
CTL-6-P-NCTL-12-S56-10L-NNo communication 1 (COM1)ANSI/RKC standard protocolMODBUS protocolNo communication 2 (COM2)ANSI/RKC standard protocolMODBUS protocol
Communication 1
Communication 2
0 to 5V DC
CT2 type
FDGAWZ
56
N
N
N
N
NPS
NPS
N12
N12
Specifications
1
Code
2
3
4
5
6
7
Output 1(OUT 1)
Output 2(OUT 2)
Digital Output 1(DO 1)
Digital Output 2(DO 2)
Digital Output 3(DO 3)
Digital Output 4(DO 4)
Control output 1 Control output 1 HBA
HBA
HBA
HBA
HBA
FAIL
See output allocation table
See event type code table
See event type code tableNo event 3See event type code table
See input range code table
Initial set code table
CodeEvent typeDeviation HighDeviation LowDeviation High/LowBandDeviation High with Alarm HoldDeviation Low with Alarm Hold
Process High with Alarm HoldProcess Low with Alarm Hold
ABCDEF
Deviation High/Low with Alarm Hold
Deviation High with Alarm Re-HoldDeviation Low with Alarm Re-HoldDeviation High/Low with Alarm Re-Hold
Process HighProcess Low
GHJK
Output allocation table
Input range code table
LQRT
Set value HighSet value LowMV value HighMV value LowCool side MV value HighCool side MV value Low
VW1234
No remote setting signal0 to 10mV DC0 to 100mV DC
No CT1
No CT2
No event 4See event type code table
Event type code table
Control output 1 Control output 1
Control output 2 Control output 2 Control output 2 Control output 2
Control output 1 Control output 1 Control output 1 (De-energized)
Event 1
Event 1
Event 1
Event 1
Event 1
Event 1
Event 1
Event 2
Event 2
Event 2
Event 2
Event 2
Event 2
Event 3
Event 3
Event 3
Event 3
Event 3
Event 3
Event 4
Event 4
Event 4
Event 4
FAIL(De-energized)
FAIL(De-energized)
tototototototototototototototototototototo
-200.0 +400.0°C-200.0 +800.0°C
0.0 400.0°C0.0 800.0°C
-200 +1372°C0 400°C0 800°C
-250.0 +800.0°F-328.0 +400.0°F
0.0 800.0°F0.0 1600.0°F
-328 +2502°F0 800°F0 1600°F
-200.0 +400.0°C-200.0 +800.0°C
0.0 400.0°C0.0 800.0°C
-200 +1200°C0 400°C0 800°C
RangeCodeInputK 35K 40K 09K 10K 41
02KK 04K C6K C4K A4K B2K C5K A1K A2J 27J 32J 08J 09J 15J 02J 04
K
J
tototototototototototototototototototototo
-200.0 +700.0°F-328.0 +1200.0°F
0.0 800.0°F0.0 1600.0°F
-328 +2192°F0 800°F0 1600°F
-200.0 +400.0°C-328.0 +752.0°F
-50 +1768°C-58 +3214°F-50 +1768°C-58 +3214°F
-200.0 +700.0°C-200 +1000°C
-328.0 +1292.0°F-328 +1832°F
0 1800°C0 3272°F0 1300°C0 2372°F
RangeCodeInputJ C7J C6J B6J B2J B9
A1JJ A2T 19T C2S 06S A7R 07R A7E 21E 06E A9E B1B 03B B2N 02N A7
J
T
S
R
E
B
N
Thermocouple
totototototototo
0 1390°C0 2534°F0 2300°C0 4200°F
0.0 600.0°C0.0 1112.0°F0.0 900.0°C0.0 1652.0°F
RangeCodeInputA 02A A2W 03W A2U 04
B2UL 04L A3
totototototototototo
-100.00 +100.00°C-200.0 +850.0°C-200.0 +200.0°C
-199.99 +199.99°F-328.0 +1562.0°F
-100.00 +100.00°C-200.0 +640.0°C
-199.99 +199.99°F-328.0 +1184.0°F-200.0 +200.0°F
RangeCodeInputD 34D 35D 21D C8D C9
29PP 30P C8P C9P D1
Pt100
JPt100
W5Re/W26Re(NBS)PLII
(DIN)U
(DIN)L
(ASTM)
RTD
RangeCodeInput1 012 013 014 015 01
016
DC Current • Voltage
0 to 10mV0 to 100mV0 to 1V0 to 5V0 to 10V1 to 5V
RangeCodeInput7 018 019 019 029 03
0 to 20mA4 to 20mA
-100 to +100mV-1 to +1V
-10 to 10mV
0.0 to 100.0%0.0 to 100.0%
• The selection of energized/de-energized" is possible except for the FAIL output. (Prior to factory shipment, set to "energized".) • Invalid for the non-existing output/event function.
(Caution) • When used as heating/cooling control/position proportioning control, select any code of 1 to 4. • When HBA (heater break alarm) is used, necessary to select "CT input provided" in the Model and codes.
5
Printed in Japan : NOV.2004 OBB8H(P) All Rights Reserved.C9400FB01
Unit : mm
CT1
CT2
COM
COM
(1)
(2)
(4)
(SET)
SG
T(A)
T(B)
R(A)
R(B)
SG
T/R(A)
T/R(B)
(3)
(2)
SG
SD
RD(1)
25
26
27
28
29
30
31
32
33
35
34
36
13
14
15
16
17
18
19
20
21
23
22
24(AO)
CT1
PFF
COM
(1) (2) (3)
A
B
B
(*)
(*)
(*)
(*)
(*)
(*)
(*)
(*)
(*) Optional
FB400
2592+0.8
0
92+
0.8
0
Panel cutout
302545
+0.80
92+
0.8
030
FB900
FB900
FB400
Non voltage contact input
COM
DI 5
DI 6
DI 7
DI 1
DI 2
DI 3
DI 4
(O)
(W)
(C)
(A) (B) (C)
1
2
3
4
5
6
7
8
9
11
10
12
AC
100-240V24V
DC
24VL
N
NO
NO
NO
(1) (2) (3)
NO
(1) (2) (3)
48
96
96
96
L
92+
0.8
0
L
92+
0.8
0
NO
NODO4
COM
COM
DO3
DO2
DO1
(DO 3, 4)Relay contact output
T/R(A)
T/R(B)(4)
AO
DescriptionNo DescriptionNo
91.8
107.
7
10.1 1.0 *160
91.8
107.
7
10.1 1.0*160
91.8
44.8
7
8
9
10
11
12
1
2
3
4
5
6
19
20
21
22
23
24
13
14
15
16
17
18
31
32
33
34
35
36
25
26
27
28
29
30
7
8
9
10
11
12
1
2
3
4
5
6
19
20
21
22
23
24
13
14
15
16
17
18
31
32
33
34
35
36
25
26
27
28
29
30
A/M R/LR/S
FB900
PV
SV MV
A/M R/LR/S
FB400
PV
SV MV
External Dimensions
(Panel thickness must be between 1 to 10mm)
Panel cutout
(Panel thickness must be between 1 to 10mm)
*1 IP65 waterproof/dustproof protection is molded into case and can not be added in the field.
*1 IP65 waterproof/dustproof protection is molded into case and can not be added in the field.
<Close horizontal mounting>* Up to 6 units
L=(96Xn-4)
n : Number of controllers (2=<n=<6)
+0.8 0
n : Number of controllers (2=<n=<6)
L=(48Xn-3)+0.6 0
• Use the solder less terminal appropriate to the screw size. Screw size : M3X6
Rear terminals
Power supply
Digital output 3, 4
(DO 1, 2)Relay contact output
Digital output 1, 2
Communication
(2) Voltage pulse / Current/Voltage(1) Relay contact output
(3) SSR (Triac) / Open collector
(A) Thermocouple(B) RTD(C) Voltage/Current
CT1,CT2 inputFeedback resistance inputCT1 input +Power feed forward input
(1)(2)
(3)
(1) RS-232C(2) RS-485(3) RS-422A
(4) RS-485
Digital input(Memory area selection)
Analogretransmissionoutput
Remote setting input
Measured input
Main output (OUT2)
(2) Voltage pulse / Current/Voltage(1) Relay contact output
(3) SSR (Triac) / Open collector
Main output (OUT1)
Communication 1
Communication 2
DI1 to DI4
Non voltage contact input
Digital input(Mode selection)
DI5 to DI7
DescriptionNo
OPEN
CLOSE
•Before operating this product, read the instruction manual carefully to avoid incorrect operation. •This product is intended for use with industrial machines, test and measuring equipment. It is not designed for use with medical equipment.
•If it is possible that an accident may occur as a result of the failure of the product or some other abnormality, an appropriate independent protection device must be installed. Safety
Warning
(RIKA KOGYO CO.,LTD)HEAD OFFICE : 16-6, KUGAHARA 5 CHOME OHTA-KU TOKYO 146-8515 JAPAN PHONE : 03-3751-9799 ( +81 3 3751 9799 ) Email : [email protected] FAX : 03-3751-8585 ( +81 3 3751 8585 ) http://www.rkcinst.com/
R
CT : Current transformer for heater break alarmPFF : Power feedback transformer
Caution for imitated products
As products imitating our product now appear on the market, be careful that you don'tpurchase these imitated products. We will not warrant such products nor bear theresponsibility for any damage and/or accident caused by their use.