differntial protection (1)

81
Power System Protection Rizwan Khan University of Engineering and Technology, Lahore 1

Upload: salman-zafar

Post on 27-Sep-2015

14 views

Category:

Documents


0 download

DESCRIPTION

Protection

TRANSCRIPT

  • Power System Protection

    Rizwan KhanUniversity of Engineering and Technology, Lahore

    1

  • Transformer Protection

    2Rizwan Khan (Lecturer - UET LHE)

  • Introduction

    Overcurrent Protection

    Percentage Differential Protection

    Causes of False Differential Currents

    Supervised Differential Relays

    Three Phase Transformer Protection

    Contents of Transformer Protection

    3Rizwan Khan (Lecturer - UET LHE)

  • Volts per Hertz Protection

    Non Electrical Protection

    Protection Systems for Transformers

    Summary

    4

    Contents of Transformer Protection

    Rizwan Khan (Lecturer - UET LHE)

  • 5Rizwan Khan (Lecturer - UET LHE)

  • Transformer Faults Statistics

    6Rizwan Khan (Lecturer - UET LHE)

  • The inherent characteristics of power transformers introduce a

    number of unique problems that are not present in the protection

    of transmission lines, generators, motors or other power system

    apparatus.

    In general, a transformer may be protected by fuses, overcurrent

    relays, differential relays and pressure relays, and can be

    monitored for incipient trouble with the help of winding

    temperature measurements, and chemical analysis of the gas

    above the insulating oil.

    Introduction

    7Rizwan Khan (Lecturer - UET LHE)

  • Transformer Size

    Location and Function

    Voltage

    Connection and Design

    Factors of Transformer Protection

    8Rizwan Khan (Lecturer - UET LHE)

  • Transformer Size

    9

    Transformer Size Protection

    2500kVAFuses

    Thermal Overload Relays

    2500-5000kVAFuses

    Overcurrent Relays

    5000-10000kVA

    Fuses

    Overcurrent Relays

    Ordinary Differential Relays

    Above 10MVA

    Fuses

    Overcurrent Relays

    Percentage Differential Relays

    Temperature & Pressure Relays

  • If the transformer is an integral part of the bulk power system,

    it will probably require more sophisticated relays in terms of

    design and redundancy.

    If it is a distribution station step down transformer, a single

    differential relay and overcurrent backup will usually sufficient.

    If the transformer is near a generation source, the high X/R ratio

    of the fault path will require harmonic restraint relays to

    accommodate the higher magnetic inrush currents.

    Location and Function

    10Rizwan Khan (Lecturer - UET LHE)

  • Generally, higher voltages demand more sophisticated and costly

    protective devices, due to the effect of a delayed fault clearing on

    the system performance, and the high cost of transformer repair.

    The protection schemes will vary considerably between auto

    transformers, and two or three winding transformers. The

    winding connection of a three phase transformer, whether delta or

    wye, will make a difference in the protection scheme chosen.

    Also important are the presence of tertiary windings, type of

    grounding used, tap changers or phase-shifting windings.

    Voltage, Connection and Design

    11

  • 12Rizwan Khan (Lecturer - UET LHE)

  • Fuses

    Time Delay Overcurrent Relays

    Instantaneous Relays

    Overcurrent Protection

    13Rizwan Khan (Lecturer - UET LHE)

  • Clearly, the fuse interrupting capability must exceed the maximum

    short-circuit current that the fuse will be called upon to interrupt.

    The continuous rating of the fuse must exceed the maximum

    transformer load.

    Typically, the fuse rating should be greater than 150% of the

    maximum load.

    It is also clear that the transformer magnetizing current should not

    cause damage to the fuse.

    Fuse

    14Rizwan Khan (Lecturer - UET LHE)

  • The minimum melt characteristic of the fuse must coordinate with

    (i.e. should be well separated from) the protective devices on the

    low side of the power transformer. In considering the

    coordination, the ambient temperature, prior loading and reclosing

    adjustment factors should be taken into account.

    The speed ratio of the fuse is dened as the ratio between the

    minimum melt current values at two widely separated times: for

    example, 0.1 and 100 s. It is desirable to have a fuse with as high a

    speed ratio as possible.

    Fuse

    15Rizwan Khan (Lecturer - UET LHE)

  • Fuse

    16

  • Protection against excessive overload, or persisting external fault,

    is provided by time-delay overcurrent relays.

    The pickup setting is usually 115% of the maximum overload

    acceptable.

    The time-delay overcurrent relays must coordinate with the low-

    side protective devices. These may include low-voltage bus relays

    for phase-to-phase faults, phase-directional relays on parallel

    transformers and the breaker failure relay timers on the low-

    voltage breakers.

    Time Delayed/Instantaneous O/C Relays

    17Rizwan Khan (Lecturer - UET LHE)

  • 18Rizwan Khan (Lecturer - UET LHE)

  • Differential Protection

    19Rizwan Khan (Lecturer - UET LHE)

  • For a normal power transformer

    If we use current transformers having turns ratios of 1 : n1 and 1 :

    n2 on the primary and the secondary side respectively, under

    normal conditions the currents in the secondary windings of the

    current transformers are related by

    20

    Differential Protection

    Rizwan Khan (Lecturer - UET LHE)

  • If we select the CTs appropriately, we may make N1n1 = N2n2, and

    then, for a normal transformer, i1s = i2s. However, if an internal

    fault develops, this condition is no longer satisfied, and the

    difference of ils and i2s becomes much larger; in fact, it is

    proportional to the fault current. The differential current provides a

    highly sensitive measure of the fault current.

    21

    Differential Protection

    Rizwan Khan (Lecturer - UET LHE)

  • Mismatching in CT Ratings

    Mismatching in Errors of Transformations

    Tap Changer of Transformer

    22

    Practical Issues in Differential Protection

    Rizwan Khan (Lecturer - UET LHE)

  • First, it may not be possible to obtain the CT ratios on the primary

    and the secondary side which will satisfy the condition N1n1 =

    N2n2, as we must select CTs with standard ratios.

    A somewhat less desirable procedure is to use auxiliary CTs to

    achieve the same goal.

    In any case, even with these adjustments, there remains some

    residual ratio mismatch, which leads to a small differential current

    id during normal conditions.

    23

    Practical Issues in Differential Protection

    Rizwan Khan (Lecturer - UET LHE)

  • Second, the errors of transformation of the two CTs may differ

    from each other, thus leading to significant differential current

    when there is normal load flow, or an external fault.

    Finally, if the power transformer is equipped with a tap changer, it

    will introduce a main transformer ratio change when the taps are

    changed.

    24

    Practical Issues in Differential Protection

    Rizwan Khan (Lecturer - UET LHE)

  • In a percentage differential relay, the differential current must exceed a

    fixed percentage of the through current in the transformer. The through

    current is defined as the average of the primary and the secondary

    currents:

    The current ir is known as the restraint current a name that comes from

    the electromechanical relay design, where this current produced a

    restraint torque on the moving disc25

    Percentage Differential Protection

  • 26

    Percentage Differential Relay Characteristics

    Rizwan Khan (Lecturer - UET LHE)

  • 27Rizwan Khan (Lecturer - UET LHE)

  • Magnetizing Inrush Current during Energization

    Harmonic Content of the Inrush Current

    Magnetizing Inrush during Fault Removal

    Sympathetic Inrush

    Transformer Over-excitation

    CT Saturation 28

    Causes of False Differential Currents

    Rizwan Khan (Lecturer - UET LHE)

  • Consider the energization of an unloaded power transformer. As

    the switch is closed, the source voltage is applied to the

    transformer, and a magnetizing current is drawn from the source.

    Let the source voltages and flux linkages are,

    29

    Magnetizing Inrush Current during Energization

    Rizwan Khan (Lecturer - UET LHE)

  • 30

    Magnetizing Inrush Current during Energization

    Rizwan Khan (Lecturer - UET LHE)

  • In reality, the magnetizing inductance of the transformer is

    nonlinear.

    As the flux linkages go above the saturation knee point, a much

    larger current is drawn from the source. The magnitude of this

    current is determined by the slope of the magnetizing

    characteristic in the saturated region, and by the leakage

    inductance of the transformer.

    It is obvious that magnetizing inrush currents of the order of fault

    currents are possible.31

    Magnetizing Inrush Current during Energization

    Rizwan Khan (Lecturer - UET LHE)

  • It should be clear that in most modern transformers very large

    inrush currents are possible, depending upon the instant of

    energization, and the remnant flux in the transformer core. Since

    the inrush current flows only in the primary and not in the

    secondary winding of the transformer, it is clear that it produces a

    differential current which is 200% of the restraining current, and

    would cause a false operation.

    32

    Magnetizing Inrush Current during Energization

    Rizwan Khan (Lecturer - UET LHE)

  • The false operation of a percentage differential relay for a

    transformer is prevented by taking advantage of the fact that the

    inrush current is rich in harmonic components.

    While the fault current is a pure fundamental frequency

    component (except for a possible decaying DC component).

    33

    Harmonics Content of the Inrush Current

    Rizwan Khan (Lecturer - UET LHE)

  • When a fault external to, but near, the transformer is removed by

    the appropriate circuit breaker, the conditions inside the

    transformer core are quite similar to those during magnetization of

    the transformer.

    As the voltage applied to the transformer windings jumps from a

    low pre-fault value to the normal (or larger) post-fault value, the

    flux linkages in the transformer core are once again forced to

    change from a low pre-fault value to a value close to normal.

    34

    Magnetizing Inrush Current during Fault Removal

    Rizwan Khan (Lecturer - UET LHE)

  • Depending upon the instant at which the fault is removed, the

    transition may force a DC offset on the flux linkages, and primary

    current waveforms similar to those encountered during

    energization would result.

    It should be noted that as there is no remnant flux in the core

    during this process; the inrush is in general smaller than that

    during the transformer energization.

    35

    Magnetizing Inrush Current during Fault Removal

    Rizwan Khan (Lecturer - UET LHE)

  • 36

    Sympathetic Inrush

    Rizwan Khan (Lecturer - UET LHE)

  • The phenomenon which causes inrush to flow in a previously

    energized transformer, when a parallel bank is energized, is known

    as the sympathetic inrush.

    The current waveforms of a typical sympathetic inrush

    phenomenon are illustrated in next slide.

    37

    Sympathetic Inrush

    Rizwan Khan (Lecturer - UET LHE)

  • 38

    Sympathetic Inrush

  • During load rejection and certain other operating conditions, a

    transformer may be subjected to a steady-state overvoltage at its

    nominal frequency.

    During over-excitation, the transformer flux remains symmetric,

    but goes into saturation for equal periods in the positive and the

    negative half-periods of the waveform, due to the rich contents of

    the harmonics.

    39

    Transformer Over-excitation

    Rizwan Khan (Lecturer - UET LHE)

  • For certain external faults, where the fault currents are large, it is

    likely that one of the CTs may saturate, this may directly effect the

    operation of both ordinary and percentage differential relay.

    40

    CT Saturation

    Rizwan Khan (Lecturer - UET LHE)

  • 41Rizwan Khan (Lecturer - UET LHE)

  • To desensitize the differential relay when the transformer is

    energized.

    Introduction of the Concept of Voltage Supervision

    Harmonics Characterization as Supervised Differential Relay

    42

    How to Avoid False Differential Currents

    Rizwan Khan (Lecturer - UET LHE)

  • One of the earliest ideas was to desensitize the differential relay when

    the transformer is energized. Thus, the less sensitive relay would not see

    the inrush current, thus avoiding a false trip.

    However, this is a poor practice, as it is precisely during the initial

    energization of the transformer, when the transformer is first energized,

    or some repair work on the transformer may have been completed, that

    the transformer is in need of protection. This is to ensure that the repair

    work has been successfully completed, and no maintenance tools

    inadvertently left inside or around the transformer.

    43

    Desensitize the Differential Relay

    Rizwan Khan (Lecturer - UET LHE)

  • It may be expected that during the inrush conditions, the

    transformer voltage would be close to normal, while during faults,

    the voltage would be much less. Thus, an under-voltage relay may

    be used to supervise the differential relay.

    In general, this type of voltage supervision is not preferred, as the

    under-voltage relay tends to be slow, and consequently the entire

    protection becomes slower.

    44

    Voltage Supervision

    Rizwan Khan (Lecturer - UET LHE)

  • The method currently in use on large transformers is based upon using

    the harmonic characterization of the inrush and over-excitation currents.

    The differential current is almost purely sinusoidal when the transformer

    has an internal fault, whereas it is full of harmonics when the

    magnetizing inrush current is present, or when the transformer is

    overexcited.

    Thus, the differential current is filtered with filters tuned to an

    appropriate set of harmonics, and the output of the filters is used to

    restrain the differential relay.45

    Harmonics Characterization

  • 46

    Supervised Differential Relays

  • 47Rizwan Khan (Lecturer - UET LHE)

  • The major difference between three-phase transformer protection and

    that of three single-phase transformers is the necessity to deal with the

    effect of a wyedelta transformation.

    Under normal load conditions, the currents in the primary and secondary

    windings are in phase, but the line currents on the wye and delta sides of

    the three-phase transformer are out of phase by 30.

    The difficulty is resolved by connecting the current transformers in such

    a manner that they undo the effect of the wyedelta phase shift produced

    by the main transformer.48

    Three Phase Transformer Protection

    Rizwan Khan (Lecturer - UET LHE)

  • The current transformers on the wye side of the power transformer

    are connected in delta, and the current transformers on the delta

    side of the power transformer are connected in wye.

    In addition to the phasing consideration discussed above, it is also

    necessary to adjust the turns ratios of the CTs so that the delta

    connection on the wye side of the power transformer produces

    relay currents that are numerically matched with the relay currents

    produced by the wye-connected CTs.

    49

    Three Phase Transformer Protection

    Rizwan Khan (Lecturer - UET LHE)

  • 50

    Three Phase Transformer Protection

  • Consider the three-winding transformer shown in Figure 8.13. One

    winding is assumed to be delta connected, while the other two are

    assumed to be wye connected. The CTs must of course be

    connected in wye on the delta side and in delta on the wye side of

    the power transformer.

    This will ensure that the phase shifts created in the currents of the

    power transformer are compensated by the CTs, so that the

    secondary currents are once again in phase.

    51

    Multi Winding Transformer Protection

    Rizwan Khan (Lecturer - UET LHE)

  • 52

    Multi-winding Transformer Protection

    Rizwan Khan (Lecturer - UET LHE)

  • It is interesting to note that under certain conditions a two-winding

    differential relay can be used to protect a three-winding

    transformer. If the transformer is connected to a source only on

    one side, the other two winding CTs could be paralleled to

    produce a net secondary current, which can then be used in a two-

    winding protection scheme.

    53

    Multi Winding Transformer Protection

    Rizwan Khan (Lecturer - UET LHE)

  • The regulating transformers may regulate the turns ratio or the

    phase shift between the primary and the secondary windings.

    The regulating transformers usually consist of two transformers:

    one to provide the magnetizing current for the transformers and

    the other to provide the variable turns ratio or the variable phase

    shift.

    In either case, the percentage differential relay is not suitable for

    the protection of these transformers. Often, a sudden pressure

    relay (SPR) provides the most sensitive protection.54

    Regulating Transformers Protection

  • 55Rizwan Khan (Lecturer - UET LHE)

  • Transformer cores are normally subjected to flux levels

    approaching the knee point in their magnetizing characteristic.

    If the core flux should exceed the saturation level, the flux patterns

    in the core and the surrounding structure would change, and

    significant flux levels may be reached in the transformer tank and

    other structural members. As these are not laminated, very high

    eddy currents are likely to result, producing severe damage to the

    transformer.

    56

    Voltage/Hertz Protection

    Rizwan Khan (Lecturer - UET LHE)

  • As the flux is proportional to the voltage, and inversely

    proportional to the operating frequency, the significant relaying

    quantity is the ratio of the per unit voltage to the per unit

    frequency. This is known as volts/hertz protection.

    This protection is specially needed in the case of unit-connected

    generator transformers. If the turbinegenerator is shut down with

    the voltage regulator in service, the volts/hertz limit of the

    transformers (and indeed of generators as well) could be easily

    exceeded.57

    Voltage/Hertz Protection

    Rizwan Khan (Lecturer - UET LHE)

  • Similar conditions could also be reached by load rejection with

    voltage regulators disconnected, or in manual position, or with

    faulty instrumentation in the regulator circuits.

    The volts/hertz capability of transformers is specified by

    manufacturers.

    Many volts/hertz relays have two settings, a lower setting for

    alarm and a higher setting which may be used for tripping.

    58

    Voltage/Hertz Protection

    Rizwan Khan (Lecturer - UET LHE)

  • 59

    Voltage/Hertz Protection

    Rizwan Khan (Lecturer - UET LHE)

  • 60Rizwan Khan (Lecturer - UET LHE)

  • When a fault occurs inside an oil-filled transformer tank, the fault

    arc produces gases, which create pressure waves inside the oil. In

    the conservator type of tank construction, which is more

    common in Europe, the pressure wave created in the oil is detected

    by a pressure vane in the pipe which connects the transformer tank

    with the conservator.

    The movement of the vane is detected by a micro-switch, which

    can be used to sound an alarm, or trip the transformer. This type of

    a relay is known as a Buchholz relay.61

    Pressure Devices

  • In the USA, the more common transformer construction is of the

    tank type with a gas cushion at the top of the tank. In such a

    transformer, the pressure wave is detected by a SPR mounted on

    the side of the transformer. The mechanical sensor consists of a

    bellows and a pressure equalizer, which together is insensitive to

    slow changes of pressure, for example those caused by thermal or

    loading changes in the transformer.

    However, a pressure wave created by a fault is detected by the

    relay, and can be used to trip or alarm.62

    Pressure Devices

  • Faults on the bushings, and connecting leads, do not create an arc

    in the insulating oil or gas, and must be protected by differential

    relays.

    63

    Pressure Devices

    Rizwan Khan (Lecturer - UET LHE)

  • Some devices simply measure the oil temperature, usually the top

    oil.

    Other devices use a combination of current, by placing a small

    search coil around a lead, and oil temperature to measure the total

    effect of load and ambient temperature.

    The critical temperature is referred to as the hot-spot

    temperature, and is the highest temperature that will occur

    somewhere in the winding.

    64

    Temperature Devices

    Rizwan Khan (Lecturer - UET LHE)

  • The temperature devices actuate alarms to a central dispatching

    office, to alert the operators, who can either remotely unload the

    transformer by opening the circuit breaker, or can dispatch an

    operator to the station.

    The hot-spot sensors are also commonly used to start and stop

    cooling fans and pumps.

    65

    Temperature Devices

    Rizwan Khan (Lecturer - UET LHE)

  • 66Rizwan Khan (Lecturer - UET LHE)

  • Parallel Transformer Banks

    Tapped Transformer Banks

    Substation Design

    Station Service

    Generator Station Design

    67

    Protection Systems for Transformers

    Rizwan Khan (Lecturer - UET LHE)

  • It is not uncommon when two transformers are connected in

    parallel with no circuit breakers used to separate them that a single

    differential relay is used for the protection of both banks.

    However, the problem of sympathetic inrush presents difficulties

    to the common differential relay, when one of the transformers is

    energized with its switch while the other transformer is in service.

    The sympathetic inrush is now likely to trip the two transformers.

    The problem can be dealt with satisfactorily by the use of separate

    differential relays.68

    Parallel Transformer Banks

    Rizwan Khan (Lecturer - UET LHE)

  • Connecting a transformer directly to the high-voltage transmission

    line is a practical and relatively inexpensive way of providing

    service to an isolated industrial or residential load.

    In the next slides, complete protection schemes are introduced for

    the protection of lines and for the protection of tapped transformer,

    in different scenarios.

    69

    Tapped Transformer Banks

    Rizwan Khan (Lecturer - UET LHE)

  • 70

    Tapped Transformer Banks

    Full complement of circuit breakers for transformer protection

  • 71

    Tapped Transformer Banks

    Direct connection of transformer and transmission lines - shows a variation in which

    the line circuit breakers are not used. In this configuration a line fault will remove the

    transformer by opening the remote terminals.

  • 72

    Tapped Transformer Banks

    Use of motor-operated air break switches at a transformer tap

  • Since a power transformer interconnects two or more voltage

    levels, its location requires special consideration in the design of a

    substation and the protection of all of the elements within it.

    Usually the various voltage levels are contained within separate

    areas, each with its own bus configuration and associated

    equipment and separated by considerable distances.

    Proceeding Figures show 345 kV/138 kV station with different

    protection schemes.

    73

    Substation Design

    Rizwan Khan (Lecturer - UET LHE)

  • 74

    Substation Design

    Substation transformer with a full complement of circuit breakers

  • 75

    Substation Design

    MOAB connection of a transformer to a 345 kV bus

  • Most power transformers are built with a delta tertiary winding to

    provide a path for third harmonics and to help stabilize the neutral.

    Although the capacity of the tertiary need not be very large, it is a

    good source for the station auxiliary equipment such as circuit

    breaker air compressors, oil pumps, battery chargers, etc.

    If the load taken off the tertiary is large enough to upset the

    transformer differential, it must be connected into the differential

    CTs, as shown in Figure on next slide.

    76

    Station Service

    Rizwan Khan (Lecturer - UET LHE)

  • 77

    Station Service

    Protection of generating station service transformer

  • The most common configuration used presently for large

    generating plants is a unit-connected system. In this system, the

    generator, generator step up transformer (GSU), the unit auxiliary

    transformer (UAT) and the reserve or start up auxiliary

    transformer (RAT) are all connected as a unit and their protection

    and controls are interrelated.

    Figure on next slide, shows a typical design with the associated

    zones of protection.

    78

    Generator Station Design

    Rizwan Khan (Lecturer - UET LHE)

  • 79Generating station transformers and their protection systems

  • References

    Stanley H. Horowiz, Arun G. Phadke, Power System

    Relaying, 3rd Edition, Chapter No. 8

  • THANKS FOR YOUR TIME81