    Device No. Relay Title

    1 Master Element

    2 Time delay starting and closing relay

    3 Checking or interlocking relay

    4 Master contactor

    5 Stopping Device

    6 Starting Circuit Breaker

    7 Anode Circuit Breaker

    8 Control Power Disconnecing Device

    9 Reversing Device10 Unit Sequence switch

    11 Reserved for future application

    12 Over - speed Device

    13 Centrifugal Speed Switch

    14 Under Speed Device

    15 Speed or Frequency Matching Device

    16 For Future applications

    17 Shunting or Discharge Switch

    18 Accelerating or Decelerating device

    19 Starting to running transition Contractor

    20 Electrical operated valve

    20BD20 BL

    20BP

    20 CH

    20 D

    20 EP

    20IS

    20 MA

    20 R

  • 8/7/2019 Device No.

    2/44

    20 RF

    20S

    20TT

    20 VT

    20 ac

    20 ao

    20 bc20 bo

    20 to

    20tc

    21 Distance Relay

    22 Equalizer Circuit Breaker

    23 Temperature Control Device

    24 For Future applications

    25 Synchronizing or synchronism check Device

    26 Apparaus Thermal Device

    26F

    26O

    26 W

    27 Under Voltage Relay

    27/50

    27/59

    28 For Future applications

    29 Isolating Contactor

    30 Annuniciator Relay

    31 Separate excitation relay

    32 Directional power relay (reverse power relay)

    33 Position Switch

  • 8/7/2019 Device No.

    3/44

    34 Motor operated sequence switch

    35 Brush operating or slip ring short circuiting device

    36 Polarity device

    37 Under current or under power relay

    38 Bearing protective Device

    38M1

    38M2

    38P1

    38P2

    38C1

    38C2

    38L1

    38L2

    38H1

    38H2

    39 Mechanical condition monitor

    39VB

    39SF

    40 Field Failure Relay

    41 Field Circuit Breaker

    42 Running Circuit Breaker

    43 Manual transfer or Selector Device

    44 Unit Sequence strating relay

    45 Atmospheric condition monitor

    45HA

    45SM

    45FR

  • 8/7/2019 Device No.

    4/44

    46 Reverse phase or phase balance current relay

    47

    48 Incomplete sequence relay

    48L

    49 Machine or transformer thermal relay

    50

    50BF

    50G

    50N

    50/51VR

    51 AC time over current relay

    51G

    51LR

    51N

    52 AC circuit breaker

    52a52b

    52aa

    52bb

    52LC

    52LS

    53 Exciter or DC generator relay

    54 Reserved for future application

    55 Power factor relay

    56 Field application relay

    Phase sequence voltage relay (Phase reversal voltagerelay)

    Instantaneous over current or rate of rise relay (High setphase over current relay)

  • 8/7/2019 Device No.

    5/44

    57 Short-circuited or grounding device

    58 Power rectifier misfire relay

    59 Over voltage relay

    59N59 G / 27TN

    60 Voltage or current balance relay

    60FL

    61 For Future applications

    62 Time delay stopping and opening relay

    63 Liquid or gas pressure swich

    63MT

    63TC

    64 Ground protective relay

    64G

    64N

    64R

    65 Governor

    66 Notching or Jogging device

    67 AC directional over current relay

    67P

    67N

    68 Blocking relay

    69 Permissive control device

    70 Electrical operated rheostat

  • 8/7/2019 Device No.

    6/44

    71 Level switch

    71SB

    71SO

    71ST

    71L

    71H

    72 DC circit Breaker

    73 Load resistor contactor

    74 Alarm relay or trip circuit supervision relay

    75 Position changing mechanism

    76 DC over current relay

    77 Pulse transmitter

    78 Phase angle measuring, or out of step protection relay

    79 Auto reclosing relay

    80 Flow switch

    80AR

    80AM

    80LO

    80SO

    80W

    81 Frequency relay

    82 DC reclosing relay

    83 Automatic selective control or transfer relay

    84 Operating mechanism

  • 8/7/2019 Device No.

    7/44

    85 Carrier or pilot wire receiver relay

    85PLCC

    85TP

    86 Locking out relay

    86E

    87 Differentional protection relay

    87B

    87BFP

    87CD

    87G

    87G(SP)

    87M

    87N

    87T

    87TEED

    87TG

    88 Auxiliary motor or motor generator

    8888C

    88CA

    88F

    88FR

    88FE

    88FSC

    88FSH

    88FM

    88FMC

    88L88P

    88LO

    88PSO

    88PSU

    88PW

    89 Line switch

  • 8/7/2019 Device No.

    8/44

    90 Regulating device

    91 Voltage directional relay

    92 Voltage and power directional relay

    93 Field changing contractor

    94 Tripping or trip free relay

    95 Generator back up protection impedance relay.

    96 Auto loading relay

    97 Trip circuit supervision relay

    Note:- Device Number 95 to 99 used for specific applications on individual in

  • 8/7/2019 Device No.

    9/44

    Definition and Function

    An indicating device such as a control switch, float switch etc.

    A device generally controled by device No. 1

    A device used to place and hold a equioment out of function.

    A device whose principle function is to connect a machine to its source of starting voltage

    Circuit breaker used in the anode circuits of power rectifier

    A device used for the purpose of reversing functions

    A speed switch which functions on over speed

    A device serves to open or to close a shunting circuit.

    Blow Down ValveBlock Valve

    By Pass Valve

    Check Valve

    Discharge Valve

    Electro pneumatic instrumentation

    Isolation Valve

    Manifold Valve

    Pressurizing Valve

    A device whose function is to give a desired amount of time delay before or after any pointof operation in switching sequence.

    A device, which operates in response to the position of a number of other devices or to anumber of predetermined conditions in a equipment

    A disconnecting device such as a pull out fuse, MCCB/ MCB used for the purpose ofconnecting and disconnecting a control circuit

    A device used to change the sequence in which unit may be placed in and out of service inmultiple unit equipments

    A slip-frequency relay or any device operates at appoximately synchronous speed ofmachine

    A speed switch which functions when the speed of the machine falls below a predeterminedvalue.

    A device functions to match and hold the speed or the frequency of a machine or of a

    system equal to that of another machine or system.

    A device used to close or to cause the closing of circuits, which are used to increase ordecrease the speed of a machine.

    A device which operates to initiate or cause the automatic transfer of a machine from thestarting to the running power connection

    A solenoid or motor operated valve, which is used in vacuum, air gas, oil, water or similarlines. Following suffix letters are used to designate applications:

  • 8/7/2019 Device No.

    10/44

    Relief Valve

    Suction Valve

    Throttling Control Valve

    Vent Valve

    Open only when valve is fully closed

    Open except when valve is fully opened

    Closed only when valve is fully closedClosed except when is fully opened

    Opened by torque responsive mechanism, to stop valve opening

    Closed by torque reponsive Mechanism to stop valve closing

    A circuit breaker, which serves to control or make and break the equalizer

    A device functions when the temperature exceeds/ decreases a predetrmined value.

    Field winding (Rotor) over temperature

    Transformer oil over temperature

    Transformer winding over temperature

    A device, which functions on a given value of under-voltge.

    It is used for designating under/ over voltage protection.

    A relay, which functions on a desired value of power flow in a given direction.

    A relay, which functions when the circuit addmittance, impedance, or reactance increasesor decreases beyound pre-determined value.

    A device functons to raise or to lower the temperature of a machine or other apparatuswhen its temperature varies beyound a predetermined value.

    (This device number is widely used for designating Volt/Hertz protection of generator).

    A device operates when two AC circuits are within the desired limits of frequncy, phaseangle, or voltage to permit the paralleling of these two AC circuit

    It is used for designating inadvertent energization protection of altenator

    An isolator used expressly for disconnecing one circuit from another for the prupose ofemergency operation.

    A non-automatically reset relay which gives a number of separate visual indications uponthe functioning of protective device.

    A device connects a circuit such as the shunt field of a synchroous converter to a source ofseparate excitation during starting sequence.

    A device used for makes and break contacts when the main device or apparatus, which hasno device function number, reaches a given position.

  • 8/7/2019 Device No.

    11/44

    Motor bearing, inboard

    Motor bearing, outboard

    Pump bearing, inboard

    Pump bearing, outboard

    Compressor bearing, inboard

    Compressor bearing, outboard

    Gear bearing, low speed,inboard

    Gear bearing, low speed, outboard

    Gear bearing, high speed,inboard

    Gear bearing, high speed, outboard

    Viberation Monitor

    Seal Failure Monitor

    A device, which functions to apply or remove the field excitation of a machine.

    Explosive atmosphere monitor

    Smoke monitor

    A multi-contact switch, which fixes the operating sequences of major devices during startingand stopping or during other sequential switching operations.

    A device used for raising, lowering or shifting the brushes of a machine, or for short-circuiting of slip rings.

    A device operates or permits the operation of another device on a predetermined polarity

    only.A device, which functions when the current or power flow decreases below a predeterminedvalue.

    A device, which functions on excessive bearing temperature or on other abnormalmechanical conditions such as undue wear, which may eventually result in excessivebearing temperature.

    A device, which functions upon the occurrence of an abnormal mechanical condition suchas vibration and seal failure.

    A relay, which functions on failure of machine field current or on excessive value of thereactive component of armature current in AC machine.

    A device whose principal function is to connect a machine to its source of running voltageafter having been brought up to the desired speed on the starting connection.

    A device transfer the control circuits so as to modify the plan of operation of the switchingequipment or of some of the devices.

    a device, which functions to start the next available unit in amultiple,unt equipment on thefailure or on the non-availablity of the preceding unit.

    A device, which function upon the occurrence of a predetermined atmospheric conditionsuch as hazardous, explosive atmosphere, smoke or fire.

  • 8/7/2019 Device No.

    12/44

    Locked rotor current

    Instantaneous over current breaker failure protection

    Instantaneous over current ground fault relayconnected to neutral

    Instantaneous over current earth fault relay

    Voltage restraint, instantaneous and time over current relay

    Time delayed ground fault over current relay(Standby earth fault relay) connected to neutral

    Excessive starting time

    Time delayed earth fault over current relay.

    Auxiliary switch closed when the circuit breaker is closedAuxiliary switch closed when the circuit breaker is opened

    Circuit breaker spring charging limit switch

    A relay, which functons when the poly- phase current are of reverse phase sequence orcontains negative phase sequence due to unbalanced load.

    A device, which functions upon a predetermined value of poly-phase voltage in the desiredphase sequence.

    A device, which returns the equipment to the normal or off position and locks it out if the

    normal starting or stopping sequence is not properly completed within a predeterminedtime.

    A device, which functions when the temperature of AC machine armature or other loadcarrying winding exceeds a predetermined value.

    A relay, which functions instantaneously on an excessive value of current or an excessiverate of current rise.

    A relay with either a definite or inverse time characterstics, which functions, when current inan AC circuit exceeds a preset value.

    A circuit breaker, which is used to close and interrupt an AC power circuit under normalconditions or to interrupt this circuit under fault or emergency condition.

    Auxiliary switch closed when the operating mechanism of the circuit breaker is in operatedposition

    Auxiliary switch closed when the operating mechanism of the circuit breaker is in non-operated position

    Latch checking switch, closed when the circuit breaker mechanism linkage is latched afteran opening operation

    A device, which forces the DC machine field excitation to build up during starting or whichfunctions when the machine voltage has build up to given value.

    A relay, which operates when the power factor in an AC circuit becomes above or below aset value. Also used for automatic switching control of capacitor bank.

    A relay, which automatically controls the application of the field excitation to a synchronousmotor at some predetermined point in the slip cycle.

  • 8/7/2019 Device No.

    13/44

    A device, which functions if one or more of the power rectifier anodes fails to fire.

    A relay, which operates on agiven value of over voltage.

    Neutral displacement relay (over voltage)100% stator ground fault protection

    Voltage transformer fuse failure relay

    Transformer main tank Buchholz relay

    Transformer tap changer protection relay

    Restricted earth fault relay

    Differential earth fault protection

    Rotor earth fault protection

    A equipment which controls the gate or valve opening of prime mover.

    Directional phase fault relay

    Ground directional relay

    A power or stored energy operated device, which functions to short circuit or to ground acircuit in response to automatic or manual means.

    A voltage balance relay, which operate on a given difference in voltage between twocircuits. Current balance relay operates on given difference in current input or out in acircuit.

    A time delay device, which serves in conjunction with the device, which initiates theshutdown stopping or opening operation in an automatic sequence.

    A device, which operates on given values of liquid or gas pressure or on a given rate ofchange of these values.

    A device, which functions on the failure of the insulation of a machine, transformer or otherapparatus to ground.

    A device, which functions to allow only a specified number of operations of given device orequipment. It also function to energize a circuit or to permit intermittent acceleration orjogging of a machine at lower speeds for mechanical positioning.

    A device, which functions on desired value of AC over current flowing in a predetermineddirection.

    A device which initiates a pilot singnal for blocking or tripping on external faults in atransmission line or operate with other devices to block reclosing on an out-of-step condition

    or on power swings. This device number is also used for desingnating out-of-stepprotection.

    A two position manaually operated switch, which in one position permits the closing of acircuit breaker or placing of equipment in operation and in the other position prevents thecircuit breaker or the equipment from being operated.

    A rheostat, which is used to vary the resistance of a circuit in response to some means ofelectrical control.

  • 8/7/2019 Device No.

    14/44

    A switch, which operates on given value or on a given rate of change of level.

    Switch reponse level in scrubber

    Switch reponse to level in seal oil tank

    Switch reponse to level in storage tank

    Low oil level

    High oil level

    A relay, which functions when the current in a DC circuit exceeds a given value.

    A relay, which controls the automatic reclosing and locking out of an AC circuit breaker.

    A switch operates on a given values or on given rate of change of flow.Switch responsive to flow of room ventilation air

    Switch responsive to flow of air to force ventilated motor

    Switch responsive to flow of lubricating oil

    Switch responsive to flow of seal oil

    Switch responsive to flow of water

    A circuit breaker used to close close and interrupt a DC power circuit under normalconditions or to interrupt this circuit under fault or emergency conditions.

    A contactor used to shunt or insert a step of load limiting, shifting or indicating resistance inpower circuit.

    A relay other than annunicator, which is covered under device No. 30, which used tooperate or to operate in connection with visual or audible alarm.

    A mechanism, which is used for moving a removable circuit breaker unit to and from theconnected, disconnected and test position.

    This unit is used to generate and transmit pluses over a telemetering or pilot wire circuit tothe remote indicating or receiving device.

    A relay, which functions at a predetermined phase angle between two voltages or twocurrents or between voltage and current.

    A relay, which functions on a predetermined value of frequency either under or over onnormal system frequency or rate of change of frequency

    A device, which control the automatic closing and reclosing of a DC circuit breaker generallyin response to load circuit conditions.

    A device, which operate to select automatically between certain sources of conditions in anequipment or performs a transfer operation automatically.

    Complete electrical mechanism or servomechanism, including the operating motor,solenoids, position switches etc, for a tap chager, induction regulatoror any piece ofapparatus, which has no device function numbers.

  • 8/7/2019 Device No.

    15/44

    Carrier or pilot wire relay phase comparision via power line carrier communication

    Tele protection equipment via OPGW fiber optic cable

    Electrically reset locking out relay

    Bus differential protection

    Bus failure differential protection

    Phase segregated curent differential protection for transmission feeder

    Generator differential protection

    Differential protection for split phase winding generators (turn to turn short circuit)

    Motor differential protection

    100% Restricted earth fault differential protection

    Transformer differential protection

    Teed feeder differential protection

    Combined generator and transformer differential protection

    Spring charge motor of circuit breakerCompressor

    Compressor, instrument air

    fan

    Ventilation fan (delivering air to room)

    Exhaust Fan

    Fan as space cooling unit

    Fan on space heating unit

    Fan serving forced ventilated air

    Fan serving forced air cooler

    LubricatorPump

    Pump, lube oil

    Pump, seal oil

    Sump pump

    Water pump

    A device used as a disconnecting or isolating switch in AC or DC circuit.

    A device, which is operated or restrained by a singal used in connection with carrier-currentor DC pilot wire fault directional relaying.

    An electrically operated, hand or electrically reset relay, which functions to shutdown andhold an equipment out of service on the occurance of abnormal condition.

    A protective relay, which functions on a precentage of phase angle or other quantitativedifference of two currents or some other electrical quantities.

    One equipment used for operating auxiliary equipments such as pumps, blowers, exciter,rotating magnetic amplifiers etc.

  • 8/7/2019 Device No.

    16/44

    stallations.

    A device whose function is to regulate a quantity or quantities such as voltage, current,power, speed, frequency, temperature and load at a certain value.

    A relay, which operates when the voltage across an open circuit breaker or contractorexceeds a given value in given direction.

    A relay, which permits or causes the connection of two circuits when the voltage differencesbetween them exceeds a given value in a predetermined direction and causes these twocircuits to be disconnected from each other when power flowing, between them exceeds agiven value in opposite direction.

    A device functions to increase or decrease in one-step the values of field excitation in amachine.

    A device, which function to trip a circuit breaker, contactor or equipment or to permitimmediate tripping by other device or to prevent immediate reclosure of a circuit interrupterin case it should open automatically even through its closing circuit is maintained in closedcondiion.

  • 8/7/2019 Device No.

    17/44

    Remarks

  • 8/7/2019 Device No.

    18/44

    Distance relay is being used for phase and ground fault ofthe trasmmision lines.

  • 8/7/2019 Device No.

    19/44

    Typically DC circuit breaker

    Used to designate Loss of field relay / Exciter failure relay

    / reactive power relay

  • 8/7/2019 Device No.

    20/44

    Negative phase sequence relaly.

    Genrator or motor stator winding temprature protection

    Frame leakage relay.

  • 8/7/2019 Device No.

    21/44

  • 8/7/2019 Device No.

    22/44

  • 8/7/2019 Device No.

    23/44

  • 8/7/2019 Device No.

    24/44

  • 8/7/2019 Device No.

    25/44

    Device No. Relay Title

    87G Differential Protection Relay

    87TD Transverse differential relay

    50/51 V Voltage restrained over current relay

    26F Rotor winding temperature protection

    50/51 G

    59N

    Neutral displacement relay (over voltage)

    46

    32 Directional power relay (reverse power relay)

    40 Field Failure Relay

    64F Field ground relay / Rotor earth fault relay

    81 Frequency relay

    27/59 Under / over voltage relay

    49 Winding temperature protection

    95 Back up impedance relay

    78 Out of step protection relay

    38 Bearing protective Device

    12 Over - speed Device

    Negative phase sequence relay or phase balancecurrent relay

  • 8/7/2019 Device No.

    26/44

    25 Synchronizing or synchronism check Device

    87TG Baised differential relay

    24 Volts / hertz relay (Over fluxing relay)

    14 Under Speed Device

    25 Synchronism check relay

    49 Generator stator winding temperature

    32 Reverse power relay

    50 / 51 V Voltage restraint over current relay

    51 N Standby earth fault relay

    59 Over voltage relay

    64G Restricted earth fault relay

    67 Directional over current relay

    81 High / low frequency relay

    87 G High speed percentage differential relay

    12 Over speed switch

    14 Low oil pressure switch

    15 High engine temperature switch

  • 8/7/2019 Device No.

    27/44

    Definition and Function

    Differential protection for split phase winding generators (turn to turn short circuit)

    Field winding (Rotor) over temperature

    Neutral ground fault relay

    Neutral displacement relay (over voltage)

    A relay, which functions on a desired value of power flow in a given direction.

    It is used for designating under/ over voltage protection.

    Generator back up protection impedance relay.

    A speed switch which functions on over speed

    A relay, which functons when the poly- phase current are of reverse phase sequence orcontains negative phase sequence due to unbalanced load.

    A relay, which functions on failure of machine field current or on excessive value of thereactive component of armature current in AC machine.

    A relay, which functions on a predetermined value of frequency either under or over onnormal system frequency or rate of change of frequency

    A device, which functions when the temperature of AC machine armature or other loadcarrying winding exceeds a predetermined value.

    A relay, which functions at a predetermined phase angle between two voltages or two

    currents or between voltage and current.

    A device, which functions on excessive bearing temperature or on other abnormalmechanical conditions such as undue wear, which may eventually result in excessivebearing temperature.

  • 8/7/2019 Device No.

    28/44

    Combined generator and transformer differential protection

    PROTECTION RELAYS FOR DIESEL ENGINE DRIVEN GENERATORS

    A device operates when two AC circuits are within the desired limits of frequncy, phaseangle, or voltage to permit the paralleling of these two AC circuit

    A speed switch which functions when the speed of the machine falls below a predeterminedvalue.

  • 8/7/2019 Device No.

    29/44

    Relay Application

    For generator internal protection

    Inter turn fault protection i.e. turn to turn fault

    Over current and short circuit protection

    Protection against rotor winding overheating

    Earth fault protection. Relay connected to the neutral CT.

    Relay connected to the secondary of earthing transformer

    Protection against unbalanced load

    Protection against motoring (prime mover / drive failure)

    Protection against loss of Excitation

    Protection against rotor earth fault

    Protection against low or high frequncy.

    Protection against low or high voltage

    For back up protection of GT unit

    Pole slip protection

    Protection against bearing over heating

    Protection against over speed

    Genrator or motor stator winding over temprature /heating protection

  • 8/7/2019 Device No.

    30/44

    For auto synchronizing generators

    To detect voltage regulator malfunction

    To dtetect governor failure

    Protection against overheating stator winding

    Protection against motoring

    Overload and short circuit protection

    Earth fault protection

    Over voltage protection

    Earth fault protection of stator winding

    Directional protection of paralleled generator

    High / low fequency protection

    Protection against internal phase faults and earth faults.

    For over all protection of combined generator transformerunit

    Check difference in bus and generator voltage / phaseangle / frequencies

    Shunts down the engine if the engine speed exceeds the

    set value or 110%shunts down the engine if the lube oil pressure reducesbelow the set value

    Shuts down the engine if the engine temperature exceedsthe set value

  • 8/7/2019 Device No.

    31/44

    Technical Requirement

    Protection against generator winding fault

    Only for generators with spli-phase winding.

    Applicable only for separately excited generator

    Inverse time delay relay for NGR earthing

    Mho or reactance relay

    DC shunt excitation or thyristor excitation system

    Measuring single phase voltage

    Measuring three phase voltage

    Additional protection for GT combined unit.

    Measuring Phase angle

    For deisel generator sets and hydro generator

    Relay operates even if the sustained fault current islower than full load current

    Generator neutral earthed via grounding transformer.Used for combined GT unit.

    Time lag over current relay with negative sequencefilter

    Inverse time relay for DG set. Definite time relay forturbine generator

    RTD embeded in the stator winding detectstemperature

    For turbo/ hydro generators. Not for dieselgenerators

  • 8/7/2019 Device No.

    32/44

    Additional protection for GT combined unit.

    Protection against under speed.

    Compare bus voltage, frequency and phase anglewith enerator

    Protection against over excitation, over fluxing of GTunit.

  • 8/7/2019 Device No.

    33/44

    Device No. Relay Title

    87CD Phase segregated current differential protection

    87TEED High speed biased differential relay

    87BFP

    51/51 N Non directional over current and earth fault relay

    85 P Pilot wire relay

    67 AC directional over current relay

    67N AC directional ground fault relay

    21 Distance Relay

    85PLCC

    85TP Teleprotection equipment for power network

    54 FL Frame leakage relay

    79 Auto reclosing relay

    87B

    87 B Precentage restraint bus differential relay

    21 Switched 3 or 4 zone distance relay

    F/D Fault Locator / Disturbance recorder

    Power line carrier relaying scheme. (carriercurrent protection)

    High impedance circulating current bus differentialrelay

  • 8/7/2019 Device No.

    34/44

    Definition and Function

    Phase segregated curent differential protection for transmission feeder

    Teed feeder differential protection

    Bus failure differential protection

    Ground directional relay

    Carrier or pilot wire relay phase comparision via power line carrier communication

    Tele protection equipment via OPGW fiber optic cable

    A relay, which controls the automatic reclosing and locking out of an AC circuit breaker.

    Bus differential protection

    A relay with either a definite or inverse time characterstics, which functions, when current inan AC circuit exceeds a preset value.

    A device, which is operated or restrained by a singal used in connection with carrier-currentor DC pilot wire fault directional relaying.

    A device, which functions on desired value of AC over current flowing in a predetermineddirection.

    A relay, which functions when the circuit addmittance, impedance, or reactance increasesor decreases beyound pre-determined value.

  • 8/7/2019 Device No.

    35/44

    Relay Application

    Phase fault and earth fault protection

    Breaker failure protection

    Back up over current and earth fault protection

    Phase fault protection for Teed feeder lines

    Phase fault protection

    Earth fault protection

    Inter tripping circuit breaker on the other end of the line

    Inter tripping circuit breaker on the other end of the line

    Earth fault protection

    Auto reclosing crcuit breaker after a fault trip

    Phase fault and earth fault protection in the bus zone

    Instantaneous over current relay

    Phase fault and earth fault protection

    Measuring location of transient / persistent faults

    Phase fault and earth fault protection of Teed feeder Busbar

    Distance relay is being used for phase and ground fault ofthe trasmmision lines.

  • 8/7/2019 Device No.

    36/44

    Technical Requirement

    IDMT characteristic, plain over current relay

    For double circuit feeders

    For double circuit feeders

    3 Zone transmission lines

    Via OPGW fiber optic cable

    For Gas Insulated stations

    High impedance circulating impedance relay

    Low impedance voltage relay

    Applicable only for under grond cable transmission

    Record graphically the fault voltage and current

    Phase segregated relay for 1 pole and 3 poleoperation

    Protection for one-and-half circuit breaker bus bararrangement

    Tripping the circuit breakera associated with faultyzone

    Suitable for 3 ended short distance lines or cablefeeders

    Phase comparision via power line carriercommunication

    With provision for dead end closing/ synchronismcheck

  • 8/7/2019 Device No.

    37/44

    Device No. Relay Title

    50

    50G Instantaneous Earth fault relay

    50N Instantaneous phase over current relay fault relay

    51

    51G Standby earth fault relay

    51N IDMT phase over current earth fault relay.

    50BF Breaker failure protection relay.

    59 Over voltage relay

    64G Restricted earth fault relay

    67N / 87 N

    87T High speed based transformer differential relay

    64N High Impedance relay.

    74 Alarm relay or trip circuit supervision relay

    26 W Winding Over temperature

    26O Oil Over temperature

    63MT Main tank Buchholz relay

    63TC Tap changer protection relay (Buchholz type)

    Instantaneous over current or rate of rise relay(High set phase over current relay)

    AC time over current relay / IDMT phase overcurrent relay

    Directional / Differential connection for earth faultprotection

  • 8/7/2019 Device No.

    38/44

    20

    25 Synchronism check relay

    27 Under Voltage relay

    49 Over current protection

    50 Instantaneous over current relay

    51 Time delay over current relay

    51 N IDMT Earth fault relay

    63 B Buchholz relay

    26 WT Winding temperature high

    Electrical operated valve (Tank over pressurerelief valve)

  • 8/7/2019 Device No.

    39/44

    Definition and Function

    Instantaneous over current ground fault relay connected to neutral

    Instantaneous over current earth fault relay

    Time delayed ground fault over current relay(Standby earth fault relay) connected to neutral

    Time delayed earth fault over current relay.

    Instantaneous over current breaker failure protection

    A relay, which operates on agiven value of over voltage.

    Restricted earth fault relay

    Ground directional relay

    Transformer differential protection ( High speed based transformer differential relay)

    Differential earth fault protection

    Transformer winding over temperature

    Transformer oil over temperature

    Transformer main tank Buchholz relay

    Transformer tap changer protection relay

    A relay, which functions instantaneously on an excessive value of current or an excessiverate of current rise.

    A relay with either a definite or inverse time characterstics, which functions, when current inan AC circuit exceeds a preset value.

    A relay other than annunicator, which is covered under device No. 30, which used tooperate or to operate in connection with visual or audible alarm.

  • 8/7/2019 Device No.

    40/44

    DISTRIBUSTION SUBSTATATION AND TRANSFORMER PROTECTION

    A solenoid or motor operated valve, which is used in vacuum, air gas, oil, water or similarlines. Following suffix letters are used to designate applications:

  • 8/7/2019 Device No.

    41/44

    Relay Application

    Short Circuit Protection

    Zero sequence current protection

    Earth fault protection

    Over load protection

    For back up protection of neutral grounding resistor.

    Earth fault protection

    Breaker failure protection

    Over voltage /over fluxing protection

    Internal - earth fault protection

    Differential ground fault protection

    Protection circuit Supervpsion

    Winding over heating protection

    Cooling system control

    Short Circuit / Winding damages.

    Flash over /Fault in tap changer

    Directional / Differential connection for earth faultprotection

    Internal protection (short circuit, earth fault, fault in tapchanger).

  • 8/7/2019 Device No.

    42/44

    Incipient faults.

  • 8/7/2019 Device No.

    43/44

    Technical Requirement

    Relay operates due to short circuit fault.

    Inverse Definite Minimum Time (IDMT) characteristic

    Earth fault protection.

    Dial type winding thermometer

    dial type oil thermometer

    Operates due to oil surge or gas.

    Oil surge in the tap changer tank.

    Relay is connected to the CT provided in the neutralbushing / neutral earthing

    Relay operates due to Earth fault in primary,secondary and tap changer.

    For two winding transformer relay is required in theprimary only, but for three winding transformer relayis required in all the three windings.

    Relay is connected to the CT installed before neutral

    grounging resistor.

    If the primary protection fails to trip the CB relay willinitiate a trip of all of the CB associated with thesame bus section.

    Relay operate due to over voltage or due tosuturation of magnetic circuit.

    For deita connected or un earthed star winding, relayis connected to residual circuit of the CT.

    Star connected winding, CT"s are connected in deltaand delta connected winding CT's are connected instar.

    For transformers grounded through groundingresistor.

    Relay operates if CT circuit wiring becomes opencircited.

  • 8/7/2019 Device No.

    44/44

    Excessive oil pressure in the main tank.