NOTES. 1. NO PART OF THIS DRAWING MAY BE COPIED, TRANSFERRED, OR MADE AVAILABLE TO USERS OTHER THAN THE ORIGINAL RECIPIENT, INCLUDING ELECTRONICALLY, WITHOUT PRIOR PERMISSION FROM VECTOS. 2. THIS DRAWING IS TO BE READ IN CONJUNCTION WITH ALL RELEVANT ARCHITECTS & ENGINEERS DRAWINGS & SPECIFICATIONS. 3. ALL DIMENSIONS ARE SHOWN IN MILLIMETRES. 4. NO DIMENSIONS TO BE SCALED FROM THIS DRAWING. 5. CONCRETE GRADES (BS 8500) MASS C16/20 BLINDING C16/20 6. PEDESTRIAN TYPE GULLY GRATINGS TO BE USED WITHIN BLOCK PAVED AREAS AND WHEREVER GULLYS COINCIDE WITH WITH KERBS. 7. ALL GULLY COVERS TO BE CAPTIVE HINGED AND SET TO CLOSE AGAINST ONCOMING VEHICLES. 8. GULLY POTS SHALL BE 450MM INTERNAL Ø BY 900MM DEEP WITH 150MM Ø OUTLET AND MANUFACTURED IN ACCORDANCE WITH BS 5911 PART 230 OR BS EN 295. THE OUTLET SHALL BE FITTED WITH AN APPROPRIATE TRAP AND RODDING EYE UNLESS AGREED OTHERWISE BY THE COUNTY COUNCIL. ALTERNATIVELY PLASTIC GULLY POTS OF APPROVED MANUFACTURE, OR BRICK OR PCC SECTIONAL CATCHPITS MAY BE USED SUBJECT TO THE APPROVAL OF THE COUNTY COUNCIL. GULLY POTS AND SECTIONAL CATCHPITS SHALL BE BEDDED ON ST4 CONCRETE AND SURROUNDED WITH 150MM THICKNESS OF ST2 CONCRETE. AND SHALL BE CONNECTED TO THE MAIN SEWER BY MEANS OF A 150MM Ø CLAY, CONCRETE OR UPVC PIPE, BEDDED AND SURROUNDED BY 150MM THICK ST2 CONCRETE WHEN THE COVER TO THE PIPE IS LESS THAN 1.2M, AND PROVIDED WITH FLEXIBLE JOINTS AT NO MORE THAN 5M CENTRES. 9. ALL PRIVATE AREAS ARE TO DRAIN AWAY FROM THE HIGHWAY. INTERCEPTION DRAINS ARE TO BE PROVIDED WHERE PRIVATE WATER DISCHARGES ONTO THE PUBLIC HIGHWAY. 10. THE FOLLOWING TYPES OF PIPES FROM APPROVED MANUFACTURERS MAY BE USED FOR HIGHWAY SURFACE WATER DRAINS: CONCRETE PIPES MADE WITH SULPHATE RESISTING CEMENT TO BS 5911-1:2002 + A2:2010. "PLASTIC" PIPES (PVCu) TWIN WALL WITH A SMOOTH INTERNAL AND RIBBED EXTERNAL WALLS, WITH CURRENT BBA CERTIFICATION. 11. POSITION MH'S COVERS ¼ CARRIAGEWAY WIDTH OR OUT OF THE MAIN VEHICULAR WHEEL TRACKS AND OPPOSITE ROAD JUNCTIONS TO ENABLE FUTURE MAINTENANCE WITHOUT CLOSING THE ROAD. 12. A CCTV SURVEY AND REPORT WILL BE REQUIRED OF ALL COMPLETED DRAINAGE, INCLUDING GULLY CONNECTIONS, BEING PUT FORWARD FOR ADOPTION. IDEALLY THIS SHOULD BE CARRIED OUT AFTER THE SUBSTANTIAL COMPLETION OF THE CONSTRUCTION WORKS, BUT PRIOR TO THE LAYING OF THE CARRIAGEWAY SURFACE COURSE. ALL PIPES SHOULD BE JETTED CLEAN PRIOR TO THE SURVEY. 13. WHERE THE DEPTH OF COVER TO THE TOP OF PIPE BELOW EITHER THE CARRIAGEWAY OR FOOTWAY IS 1.2M OR LESS, ALL PIPES AND DUCTS, INCLUDING PLASTIC, SHALL HAVE A BED AND SURROUND OF 150MM ST2 CONCRETE. THE LEVEL OF THE UPPER SURFACE OF WHICH SHALL IN NO CASE BE LESS THAN 350MM BELOW FINISHED CARRIAGEWAY LEVEL. THIS IS THE CASE FOR RIDGED AND FLEXIBLE PIPES. 14. BEFORE ENTERING OR BREAKING INTO AN EXISTING SEWER OR DRAIN, NOTICE SHALL BE GIVEN TO THE DRAINAGE UNDERTAKER RESPONSIBLE FOR THE PIPE TO WHICH THE CONNECTION IS TO BE MADE, APPROPRIATE PERMISSION OBTAINED, AND FEES PAID. PROVISIONS SHOULD BE MADE TO ENSURE THEIR CONTINUOUS USE. PLEASE INVESTIGATE THE POINT OF OUTFALL FOR EACH DRAINAGE CONNECTION BEFORE ANY ALTERATION IS MADE. DRAWING NUMBER: REVISION: SCALE: DRAWN: CHECKED: DATE: DRAWING TITLE: PROJECT: CLIENT: REV DETAILS DRAWN CHECKED DATE ISO 9001 CfA Centre for Assessment 17/3345 0120 RED LION CONDUIT LIMITED 9 DWELLING SITE BICKER DRAINAGE STANDARD DETAILS SHEET 4 VD21476-403 # 24.05.2021 JAK PB NTS @ A1 5th Floor, 4 Colston Avenue, Bristol, BS1 4ST - - - - - DESIGNED TO CODE FOR ADOPTION

Upload: others

Post on 15-Oct-2021

1 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: DESIGNED TO CODE FOR ADOPTION

NOTES.

1. NO PART OF THIS DRAWING MAY BE COPIED, TRANSFERRED,

OR MADE AVAILABLE TO USERS OTHER THAN THE ORIGINAL

RECIPIENT, INCLUDING ELECTRONICALLY, WITHOUT PRIOR

PERMISSION FROM VECTOS.

2. THIS DRAWING IS TO BE READ IN CONJUNCTION WITH ALL

RELEVANT ARCHITECTS & ENGINEERS DRAWINGS &

SPECIFICATIONS.

3. ALL DIMENSIONS ARE SHOWN IN MILLIMETRES.

4. NO DIMENSIONS TO BE SCALED FROM THIS DRAWING.

5. CONCRETE GRADES (BS 8500)

MASS C16/20

BLINDING C16/20

6. PEDESTRIAN TYPE GULLY GRATINGS TO BE USED WITHIN

BLOCK PAVED AREAS AND WHEREVER GULLYS COINCIDE

WITH WITH KERBS.

7. ALL GULLY COVERS TO BE CAPTIVE HINGED AND SET TO

CLOSE AGAINST ONCOMING VEHICLES.

8. GULLY POTS SHALL BE 450MM INTERNAL Ø BY 900MM DEEP

WITH 150MM Ø OUTLET AND MANUFACTURED IN

ACCORDANCE WITH BS 5911 PART 230 OR BS EN 295. THE

OUTLET SHALL BE FITTED WITH AN APPROPRIATE TRAP AND

RODDING EYE UNLESS AGREED OTHERWISE BY THE COUNTY

COUNCIL. ALTERNATIVELY PLASTIC GULLY POTS OF

APPROVED MANUFACTURE, OR BRICK OR PCC SECTIONAL

CATCHPITS MAY BE USED SUBJECT TO THE APPROVAL OF

THE COUNTY COUNCIL. GULLY POTS AND SECTIONAL

CATCHPITS SHALL BE BEDDED ON ST4 CONCRETE AND

SURROUNDED WITH 150MM THICKNESS OF ST2 CONCRETE.

AND SHALL BE CONNECTED TO THE MAIN SEWER BY MEANS

OF A 150MM Ø CLAY, CONCRETE OR UPVC PIPE, BEDDED AND

SURROUNDED BY 150MM THICK ST2 CONCRETE WHEN THE

COVER TO THE PIPE IS LESS THAN 1.2M, AND PROVIDED WITH

FLEXIBLE JOINTS AT NO MORE THAN 5M CENTRES.

9. ALL PRIVATE AREAS ARE TO DRAIN AWAY FROM THE

HIGHWAY. INTERCEPTION DRAINS ARE TO BE PROVIDED

WHERE PRIVATE WATER DISCHARGES ONTO THE PUBLIC

HIGHWAY.

10. THE FOLLOWING TYPES OF PIPES FROM APPROVED

MANUFACTURERS MAY BE USED FOR HIGHWAY SURFACE

WATER DRAINS:

CONCRETE PIPES MADE WITH SULPHATE RESISTING CEMENT

TO BS 5911-1:2002 + A2:2010.

"PLASTIC" PIPES (PVCu) TWIN WALL WITH A SMOOTH

INTERNAL AND RIBBED EXTERNAL WALLS, WITH CURRENT

BBA CERTIFICATION.

11. POSITION MH'S COVERS ¼ CARRIAGEWAY WIDTH OR OUT OF THE

MAIN VEHICULAR WHEEL TRACKS AND OPPOSITE ROAD

JUNCTIONS TO ENABLE FUTURE MAINTENANCE WITHOUT CLOSING

THE ROAD.

12. A CCTV SURVEY AND REPORT WILL BE REQUIRED OF ALL

COMPLETED DRAINAGE, INCLUDING GULLY CONNECTIONS,

BEING PUT FORWARD FOR ADOPTION. IDEALLY THIS SHOULD

BE CARRIED OUT AFTER THE SUBSTANTIAL COMPLETION OF

THE CONSTRUCTION WORKS, BUT PRIOR TO THE LAYING OF

THE CARRIAGEWAY SURFACE COURSE. ALL PIPES SHOULD BE

JETTED CLEAN PRIOR TO THE SURVEY.

13. WHERE THE DEPTH OF COVER TO THE TOP OF PIPE BELOW EITHER

THE CARRIAGEWAY OR FOOTWAY IS 1.2M OR LESS, ALL PIPES AND

DUCTS, INCLUDING PLASTIC, SHALL HAVE A BED AND SURROUND

OF 150MM ST2 CONCRETE. THE LEVEL OF THE UPPER SURFACE OF

WHICH SHALL IN NO CASE BE LESS THAN 350MM BELOW FINISHED

CARRIAGEWAY LEVEL. THIS IS THE CASE FOR RIDGED AND FLEXIBLE

PIPES.

14. BEFORE ENTERING OR BREAKING INTO AN EXISTING SEWER OR

DRAIN, NOTICE SHALL BE GIVEN TO THE DRAINAGE UNDERTAKER

RESPONSIBLE FOR THE PIPE TO WHICH THE CONNECTION IS TO BE

MADE, APPROPRIATE PERMISSION OBTAINED, AND FEES PAID.

PROVISIONS SHOULD BE MADE TO ENSURE THEIR CONTINUOUS

USE. PLEASE INVESTIGATE THE POINT OF OUTFALL FOR EACH

DRAINAGE CONNECTION BEFORE ANY ALTERATION IS MADE.

DRAWING NUMBER: REVISION:

SCALE:

DRAWN: CHECKED: DATE:

DRAWING TITLE:

PROJECT:

CLIENT:

REV DETAILS DRAWN CHECKED DATE

ISO 9001

CfA

Centre for Assessment

17/3345

0120

RED LION CONDUIT LIMITED

9 DWELLING SITE

BICKER

DRAINAGE STANDARD DETAILS

SHEET 4

VD21476-403 #

24.05.2021JAKPB

NTS @ A1

5th Floor, 4 Colston Avenue, Bristol, BS1 4ST

---- -

DESIGNED TO CODE FOR ADOPTION