design of hospital building

Upload: api-133394718

Post on 06-Apr-2018

233 views

Category:

Documents


1 download

TRANSCRIPT

  • 8/2/2019 DESIGN OF HOSPITAL BUILDING

    1/43

    1

    DESIGN OF SLAB

    INTERIOR PANEL SLAB:

    Step 1:

    Room size 4.23mx5.23m

    Ly/Lx= 5.23/4.23

    =1.24

  • 8/2/2019 DESIGN OF HOSPITAL BUILDING

    2/43

    2

    Mx= x.w.lx^2

    = 0.045x13.875x4.23^2

    =11.17kN.m

    My= y.w.lx^2

    =0.032x13.875x4.23^2

    =7.94 kN.m

    M max = 0.138.f ck.b.d^2

    d^2 = M max/ 0.138.f ck.b

    = 11.17x10^6/(0.138x25x1000)

    d = 56.9< 170 mm

    hence safe.

    Step 4:

    Check for shear,

    Ly/Lx = 1.24

    Co-efficient for shear = x in ly direction= 0.33

    =x in lx direction = 0.393

    Max .design shear = x.w.lx

    = 0.398x13.875x4.23

    =23.4kN.

    V/bd = 23.4x10^3/(1000x170)

    = 0.138

    Safe minimum: shear for M25 concrete is equal to 0.29 and hence slab is safe and shear.

  • 8/2/2019 DESIGN OF HOSPITAL BUILDING

    3/43

    3

    Step5:

    Area of steel,

    d = 170mm.

    steel for short direction.

    M/bd^2 = (11.17x10^6)/(1000x170^2).

    = 0.39

    {From SP 16, table3:}

    Pt = 0.11%

    As=(0.11x1000x170)/100

    = 187.34mm^2.

    spacing = (/4 x 10^2)/187.34

    = 419mm.

    Spacing = 400mm.

    Provide 10mm dia @ 400mm c/c.

    Steel for longer direction,

    d = 170-10=160mm.

    M/(bd^2) = 7.94x10^6/(1000x160^2)

    = 0.087.

    Ast = (0.087x1000x160)/100

    = 139.2 mm^2.

    Spacing = ((/4 x10^2)x1000)/139

    = 565 mm.

    Spacing = 550mm.

    Provide 10 mm dia @ 300 mm c/c.

  • 8/2/2019 DESIGN OF HOSPITAL BUILDING

    4/43

    4

    Step 6:

    Check deflection ,

    Span depth ratio = 20.

    Pt = 0.11%.

    F1 = 2.

    Allowable l/d ratio = 20x2 = 40.

    Actual span/depth ratio = 4.23/0.170

    = 24.9.

    There fore assumed span depth ratio is enough to control deflection.

  • 8/2/2019 DESIGN OF HOSPITAL BUILDING

    5/43

    5

    INTERIOR PANEL SLAB

    Step 1:

    Thickness of slab and durability consideration

    Lx = 4230mm.

    Ly = 5230mm.

    Cover for mild exposure= 15mm

    As the span is large and loading heavy , assume a span depth ratio of 25 instead of usual 35.

    d= 4230/25

    = 169.2mm

    = 170mm.

    h = 170+6+15=191mm.

    step 2:

    Design of loads.

    Dead load= 0.19x25x1= 4.75 kN /m^2

    Floor finish = 1kN/m^2

    Live load = 4 kN/m^2

    Total load = 9.775kN/m^2

    Factored load = 1.5x9.775 = 14.66kN/m^2.

    Step 3:

    Checking for depth:

    Ly/Lx = 5.23/4.23 = 1.24.

    From the table ,

    x = 0.045.

    y = 0.032.

    Mx= x.w.lx^2

  • 8/2/2019 DESIGN OF HOSPITAL BUILDING

    6/43

    6

    = 0.045x14.66x4.23^2

    =11.8kN.m

    My= y.w.lx^2

    =0.032x14.66x4.23^2

    =8.394 kN.m

    Check for depth from maximum. bending moment

    M max = 0.138.f ck.b.d^2

    d2 = M max/ 0.138.f ck.b

    = 11.8x10^6/(0.138x25x1000)

    d = 58.5< 170 mm

    hence safe.

    Step 4:

    Check for shear,

    Ly/Lx = 1.24

    Co-efficient for shear

    x in ly direction= 0.33

    x in lx direction = 0.393

    Max .design shear = x.w.lx

    = 0.398x14.66x4.23

    =24.687kN.

    V/bd = 24.68x10^3/(1000x170)

    = 0.145

    Safe min: shear for M25 concrete is equal to 0.29 and hence slab is safe and shear.

  • 8/2/2019 DESIGN OF HOSPITAL BUILDING

    7/43

    7

    Step5:

    Area of steel,

    steel for short direction.

    d = 170mm.

    m/bd2 = (11.8x10^6)/(1000x170^2).

    = 0.408.

    {From sp 16, table3:}

    Pt = 0.11%

    As=(0.11x1000x170)/100

    = 187.34mm^2.

    spacing =1000x( (/4 x 10^2)/187.34)

    = 419mm.

    Spacing = 400mm.

    Provide 10mm dia @ 400mm c/c.

    Steel for longer direction,

    d = 170-10=160mm.

    M/(bd^2) = 8.394x10^6/(1000x160^2)

    = 0.328.

    Pt = 0.092.

    Ast = (0.092x1000x160)/100

    = 147.2mm^2.

    Spacing = ((/4 x8^2)x1000)/147

    = 340 mm.

    Spacing = 340mm.

    Provide 8 mm dia @ 340 mm c/c.

  • 8/2/2019 DESIGN OF HOSPITAL BUILDING

    8/43

    8

    Step 6:

    Check deflection :

    Span depth ratio = 20.

    Pt = 0.11%.

    F1 = 2.0

    Allowable l/d ratio = 20x2 = 40.

    Actual span/depth ratio = 4.23/0.170

    =24.88.

    There fore assumed span to depth ratio is enough to control deflection.

  • 8/2/2019 DESIGN OF HOSPITAL BUILDING

    9/43

    9

    ONE LONG EDGE DISCONTINUOUS SLAB

    Step 1:

    Thickness of slab and durability consideration

    Lx = 4230mm.

    Ly = 5230mm.

    {From IS 456-2000} Cover for mild exposure= 15mm

    As the span is large and loading heavy , assume a span to depth ratio of 25 instead of usual 35.

    d= 4230/25

    = 169.2mm

    = 170mm.

    h = 170+6+15=191mm.

    step 2:

    Design of loads :

    Dead load = 0.19x25x1= 4.75 kN /m^2

    Floor finish = 1kN/m^2

    Live load = 4 kN/m^2

    Total load = 9.775kN/m^2

    Factored load = 1.5x9.775 = 14.66kN/m^2.

    Step 3:

    Checking for depth:

    Ly/Lx = 5.23/4.23 = 1.24.

    From the table 26 {IS 456-2000}

    x = 0.054.

    y = 0.037.

    Mx= x.w.lx^2

  • 8/2/2019 DESIGN OF HOSPITAL BUILDING

    10/43

    10

    = 0.054x14.66x4.23^2

    =14.16N.m

    My= y.w.l-+^2

    =0.037x14.66x4.23^2

    =9.7 kN.m

    Check for depth from max. bending moment

    M max = 0.138.f ck.b.d^2

    d^2 = M max/ 0.138.f ck.b

    = 14.16x10^6/(0.138x25x1000)

    d= 64.1< 170 mm

    hence safe.

    Step 4:

    Check for shear,

    Ly/Lx = 1.24

    Co-efficient for shear {from IS 456-2000}

    x in ly direction= 0.33

    x in lx direction = 0.393

    Max .design shear = x.w.lx

    = 0.398x14.66x4.23

    = 24.687kN.

    V/bd = 24.68x10^3/(1000x170)

    = 0.145

    Safe min: shear for M25 concrete is equal to 0.29 and hence slab is safe and shear.

  • 8/2/2019 DESIGN OF HOSPITAL BUILDING

    11/43

    11

    Step5:

    Area of steel,

    steel for short direction.

    d = 170mm.

    M/bd2 = (14.16x10^6)/(1000x170^2).

    = 0.49.

    {From sp 16, table3:}

    Pt = 0.138%

    As=(0.138x1000x170)/100

    = 234.6 mm^2.

    spacing =1000x( (/4 x 10^2)/234.6)

    Spacing = 300mm.

    Provide 10mm dia @ 300mm c/c.

    Steel for longer direction,

    d = 170-10=160mm.

    M/(bd2) = 9.7x10^6/(1000x160^2)

    = 0.34.

    {from IS 456-2000} Pt = 0.096.

    Ast = (0.096x1000x160)/100

    = 163.2mm^2.

    Spacing = ((/4 x8^2)x1000)/163

    = 308 mm.

    Spacing = 300mm.

    Provide 8 mm dia @ 300 mm c/c.

  • 8/2/2019 DESIGN OF HOSPITAL BUILDING

    12/43

    12

    Step 6:

    Check deflection :

    Span depth ratio = 20.

    {from IS 456-2000} Pt = 0.138%.

    F1 = 2.0

    Allowable l/d ratio = 20x2 = 40.

    Actual span/depth ratio = 4.23/0.170

    =24.88.

    There fore assumed span depth ratio is enough to control deflection.

  • 8/2/2019 DESIGN OF HOSPITAL BUILDING

    13/43

    13

    DESIGN OF BEAMS

    DESIGN OF T- BEAM:

    Step 1:

    Datas

    L = 5.23m.

    Spacing =4.23m.

    Df= 190mm.

    Fck= 20 N/mm^2

    Fy = 415 N/mm^2

    Step 2:

    Cross sectional dimensions,

    Basic span/depth ratio for simply supported beam is 20

    For tee beams, assuming the width of rib = 230mm and flange width = 4.23m.

    the ratio of web width to flange width is equal to

    230/4230 = 0.054.

    Reduction factor = 0.8. [from fig 6 IS 456]

    Hence, basic span/depth = 20x0.8

    = 16.

    d = span/16

    5230/16 = 326.88mm.

    Adopt overall depth = 400mm

    Cover = 50mm.

    Hence tee beam parameters are,

    d = 350mm

    D = 400mm

  • 8/2/2019 DESIGN OF HOSPITAL BUILDING

    14/43

    14

    bw = 230mm

    Df= 190mm

    Step 3:

    Loads

    Self weight of slab = 0.19x25x4.23

    = 20.09kN/m

    Floor finish = 1x4.23

    = 4.23 kN/m

    Self weight of rib = 0.23x0.21x25

    = 1.21kN/m

    Plaster finish = 0.45 kN/m

    Water proofing = 2x4.23=8.46 kN/m

    Weight of parapet wall = 0.6x0.23x19

    = 2.62 kN/m

    Total dead load = 37.06 kN/m

    Live load = 1.5 kN/m

    Design ultimate load = 1.5x(37.06+1.5)

    =57.84 kN/m

    Step 4:

    Ultimate moment and shear force

    Mu = (wl^2)/8

    = (57.84x5.23^2)/8

    = 197.76kN.m

    Vu = wl/2 = (57.84x5.23)/2

    = 151.25kN

  • 8/2/2019 DESIGN OF HOSPITAL BUILDING

    15/43

    15

    Step 5 :

    Effective width of flange

    1) bf= [Lo/6+bw+6Df]

    = [5.23/6+0.23+(6x0.19)]

    = 2.24m

    2) c/c of rib = (4.23-0.23) = 4m

    Hence the least value of 1 & 2is

    bf= 2.42m.

    step 6:

    moment capacity of flange

    Muf= 0.36*fck.bf.df.(d-0.42df)

    = 0.36x20x2242x190x(350-0.42x190)

    = 828.72kN.

    Since Mu < Muf, Xu < Df

    Hence the section is consider as rectangular width b =bf

    Step 7:

    Reinforcements

    Mu = 0.87.fy.Ast.d(1-[fy.Ast/bdfck])

    197.76x10^6= 0.87x415xAstx350x(1-415xAst/2242x350x20)

    Ast = 1635.67mm^2.

    Provide 4 numbers of 25mm dia (Ast= 1963mm^2) and 2 hanger bars of 12mm dia on compresion force

    Step 8:

    Shear reinforcement

    v = Vu/bw.d

    = 151.25x10^3/(230x350)

  • 8/2/2019 DESIGN OF HOSPITAL BUILDING

    16/43

    16

    = 1.88 N/mm^2.

    Pt = 100 Ast/bw.d

    = (100x1963)/230x350

    =2.44

    c = 0.818

    balance shear = Vu c.bw.d

    = 151.25x10^3-0.818x230x350

    = 85.40kN.

    Using 8mm dia two legged strirup the spacing is

    Sv = (0.87x415x2x50x350)/85.4x10^3

    = 147.97mm

    Sv >or= 0.75d

    0.75x350 = 262.5mm.

    Sv = 300mm.

    Whichever is less

    Provide 8mm dia two legged strirup at 145mm c/c length of beam.

  • 8/2/2019 DESIGN OF HOSPITAL BUILDING

    17/43

    17

    DESIGN OF L BEAM

    Step 1:

    Datas

    L = 5m.

    Spacing=4.23m.

    Df= 190mm.

    fck= 20 N/mm^2

    fy = 415 N/mm^2

    Step 2:

    Cross sectional dimensions,

    since L beam is subjected to bending torsion and shear force assume a trial section

    having span / depth ratio = 12.

    d = span/12

    5000/12 = 416.67mm.

    d = 450mm.

    Adopt overall depth D = 500mm

    bw = 230mm.

    step 3 :

    Effective span

    Effective span is the least of

    1) c/c of supports = 5.23m

    2) Clear span + eff.depth = 5+0.45

    = 5.45m.

  • 8/2/2019 DESIGN OF HOSPITAL BUILDING

    18/43

    18

    Step 4:

    Loads

    Self weight of slab = 0.19x25x0.5x4.23

    = 10.05kN/m

    Floor finish = 1x0.5x4.23

    = 2.13 kN/m

    Self weight of rib = 0.23x0.31x25

    = 1.78kN/m

    Water proofing = 2x0.5x4.23=4.23 kN/m

    Weight of parapet wall = 0.6x0.23x19

    = 2.62 kN/m

    Total dead load = 23.97 kN/m

    Live load = 1.5 x0.5x4.23= 3.17kN/m

    Step 5:

    Effective flange width

    1) bf= [Lo/12+bw+3Df]

    =[ 5230/12+230+(3x190)]

    = 1235.8mm.

    2) bf= bw +0.5 time spacing b/n ribs

    = 230+(0.5x4000)

    = 2230mm

    bf = 1235mm.

    step 6 :

    ultimate bending moment and shear force at support s/c.

    Mu = 1.5(23.97x5.23^2)/12

    = 81.93kN.m

  • 8/2/2019 DESIGN OF HOSPITAL BUILDING

    19/43

    19

    Vu = 1.5(0.5x23.97x5.23) = 94 kN.

    At centre span s/c

    Mu = 1.5(23.97x5.23^2)/24

    = 40.98 kN.m

    Step 7 :

    Torsional moments at support s/c.

    (Working load /mrip s.w)= (23.97-1.78)

    = 22.19 Kn/m.

    Total ultimate load on slab = 1.5(22.19x5.3)

    = 176.4 kN.

    Total ultimate shear force = 0.5x176.4

    = 88.21 kN.

    Distance of centroid of shear force from c/c = (0.5x1235-190)

    = 427.5mm.

    Ultimate torsional moment Tu = (88.21x0.427)

    = 37.67 kN.m

    Step 8:

    Equivalent bending moment and shear force :

    {Is 456:2000 clause 41.42}

    Mel = (Mu+Mt)

    Mt = Tu[1+(D/b)/1.7]

    = 37.67[1+(500/230)/1.7]

    = 70.3 kN.m

    Mel = (81.93+70.3)

    = 152.3 kN.m

  • 8/2/2019 DESIGN OF HOSPITAL BUILDING

    20/43

    20

    Ve = Vu +1.6(Tu/B)

    = 94+1.6(37.67/0.23)

    = 356.1 kN.

    Step 9:

    Main longitudinal reinforcement

    Mel = 152.3 kN.m

    Mu,lim = 0.138.f ck.b.d^2

    = 0.138x20x230x450^2

    = 128.5 kN.m

    Mel < Mu,lim

    Mel = 0.87.fy.Ast.d[1-Ast.fy/bd.fck]

    152.3x10^6 = 0.87x415xAstx450[1-415xAst/230x450x20]

    Ast = 1251mm^2.

    Provide 3nos of 25mm dia (Ast = 1472mm^2)

    Ast min = (0.85.bw.d/fy)

    = (0.85x230x450/415)

    = 212mm^2.

    = 212/(/4x12^2)

    = 1.85 = 2nos.

    Provide 2 nos of 12mm dia (Ast = 226mm^2)

    Step 10:

    Shear reinforcement :

    ve = (ve/bw.d)

    =(356.1x10^3/(230x450))

    = 3.4N/mm^2.

    Pt = (100Ast/bw.d)

  • 8/2/2019 DESIGN OF HOSPITAL BUILDING

    21/43

    21

    = (100x1472/230x450)

    =1.4

    c= 0.7N/mm^2 < ve .

    hence shear reinforcement are required.

    Using 10mm dia and 25mm side covers and bottom cover 50mm.b1 =

    180mm, d1 = 400mm,Asv = 157mm^2.

    1).Sv = 92mm.

    2).Sv = 91.3mm.

  • 8/2/2019 DESIGN OF HOSPITAL BUILDING

    22/43

    22

    DESIGN OF COLUMN

    Step 1:

    Slenderness ratio consideration :

    Le/D = (0.65x3600)/230

    = 10.17

  • 8/2/2019 DESIGN OF HOSPITAL BUILDING

    23/43

    23

    Step 4:

    Pu = 440.1 kN.

    b = 230mm.

    D = 230mm.

    Fck= 20N/mm^2.

    Fy = 415N/mm^2.

    Step 5:

    Assume Pt = 3%.

    Pt = 100xAst/b.d

    Ast = (3x230x190)/100

    = 1311mm^2.

    Provide 5 nos of 20mm dia bars (Ast=1570mm^2)

    Ag = 230x230

    = 52,900mm^2.

    Ac = Ag- Ast

    = 52,900-1570

    = 51,330mm^2.

    Pu = 0.4 fck. Ac + 0.67.fy.Ast

    = 0.4x20x51,330 + (0.67x415x1570)

    = 859.7 kN > 440.1Kn.

    Step 6:

    Detail of longitudinal steel.

    Use cover = 40mm

    Steel spacing = 230-40-40-20

    = 130mm.

    = 130/2 = 65mm.

  • 8/2/2019 DESIGN OF HOSPITAL BUILDING

    24/43

    24

    Clear spacing between bars = 65-20

    = 45 < 230.

    Step 7:

    Transerverse steel :

    Dia of link not less than ,20/4 or 6mm.

    Use 10mm, spacing not less than

    1) Dimension of column = 230mm.

    2)16 times dia of long steel = 16x20

    =320mm.

    3) 300mm.

    Adopt 300mm spacing between each link.

  • 8/2/2019 DESIGN OF HOSPITAL BUILDING

    25/43

    25

    DESIGN OF COLUMN

    Step 1:

    Slenderness ratio consideration :

    Le/D = (0.65x3600)/230

    = 10.17

  • 8/2/2019 DESIGN OF HOSPITAL BUILDING

    26/43

    26

    Step 4:

    Pu = 288.83 kN.

    b = 230mm.

    D = 230mm.

    Fck = 20N/mm^2.

    Fy = 415N/mm^2.

    Step 5:

    From IS 456-2000 Assume Pt = 3%.

    Pt = 100xAst/b.d

    Ast = (3x230x190)/100

    = 1311mm^2.

    Provide 5 nos of 20mm dia bars (Ast=1570mm^2)

    Ag = 230x230

    = 52,900mm^2.

    Ac = Ag- Ast

    = 52,900-1570

    = 51,330mm^2.

    Pu = 0.4 fck. Ac + 0.67.fy.Ast

    = 0.4x20x51330 + (0.67x415x1570)

    =785.08 kN > 288.3Kn.

    Step 6:

    Detail of longitudinal steel.

    Use cover = 40mm

    Steel spacing = 230-40-40-20

    = 130mm.

  • 8/2/2019 DESIGN OF HOSPITAL BUILDING

    27/43

    27

    = 130/2 = 65mm.

    Clear spacing between bars = 65-20

    = 45 < 230.

    Step 7:

    Transerverse steel

    Dia of link not less than ,20/4 or 6mm.

    Use 10mm, spacing not less than

    1) Dimension of column = 230mm.

    2)16 times dia of long steel = 16x20

    =320mm.

    3) 300mm.

    Adopt 300mm spacing between each link.

  • 8/2/2019 DESIGN OF HOSPITAL BUILDING

    28/43

    28

    Design of column on ground floor

    Step 1:

    Slenderness ratio consideration :

    Le/D = (0.65x3600)/230

    = 10.17

  • 8/2/2019 DESIGN OF HOSPITAL BUILDING

    29/43

    29

    Total load = (2x151.23)+137.6+440.1

    = 880.2 kN.

    Step 4:

    Pu = 880.2 kN.

    b = 230mm.

    D = 230mm.

    Fck= 20N/mm^2.

    Fy = 415N/mm^2.

    Step 5:

    Assume Pt = 4%.

    Pt = 100xAst/b.d

    Ast = (4x230x190)/100

    = 1748 mm^2.

    Provide 6 nos of 20mm dia bars (Ast=1885mm^2)

    Ag = 230x230

    = 52,900mm^2.

    Ac = Ag- Ast

    = 52,900-1885

    = 51,015mm^2.

    Pu = 0.4 fck. Ac + 0.67.fy.Ast

    = 0.4x20x51,015 + (0.67x415x1885)

    = 932.24kN > 880.2. kN

  • 8/2/2019 DESIGN OF HOSPITAL BUILDING

    30/43

    30

    Step 6:

    Detail of longitudinal steel.

    Use cover = 40mm

    Steel spacing = 230-40-40-20

    = 130mm.

    = 130/2 = 65mm.

    Clear spacing between bars = 65-20

    = 45 < 230.

    Step 7:

    Transerverse steel

    Dia of link not less than ,20/4 or 6mm.

    Use 10mm, spacing not less than

    1). Dimension of column = 230mm.

    2).16 times dia of long steel = 16x20

    =320mm.

    3). 300mm.

    Adopt 300mm spacing between each link.

  • 8/2/2019 DESIGN OF HOSPITAL BUILDING

    31/43

    31

    DESIGN OF FOOTING

    Step 1:

    Pu = 932 kN.

    b = 230mm.

    D = 230mm.

    P = 200kN/m^2.

    Fck= 20N/mm^2.

    Fy = 415N/mm^2.

    Step 2:

    Load on column = 932 kN.

    Assume s.w of footing (10%) = 93.2 kN.

    Total factored load Wu = 1025.2 kN.

    Footing area = [1025.25/(1.5x200)]

    Area = 3.42 m^2.

    L x B = 3.42 m^2.

    (1.5BxB) = 3.42 m^2.

    1.5B^2 = 3.42 m^2.

    B = 1.5m.

    L = 1.5 x B

    = 1.5x1.5

    L = 2.25m.

    Factored soil pressure at base is computed as

    Pu = [932.2/(1.5x2.25)]

    = 276.2 kN/m^2.

  • 8/2/2019 DESIGN OF HOSPITAL BUILDING

    32/43

    32

    1.5x200 = 300 > 276.2 kN/m^2.

    Hence the footing area is adequate since the soil pressure developed at base is less

    than the factored bearing of soil.

    Step 3:

    Factored B.M :

    Cantilever projection from the

    short side face on column} = 0.5(2.25-0.23)

    = 1.01m.

    Cantilever projection from the

    long side face on column} = 0.5(1.5-0.23)

    = 0.635m.

    B.m at short side face of column is (0.5.Pu.L^2) = 0.5x276.2x1.01^2

    = 140.8 kN.m

    B.m at short side face of column is = (0.5x276.2x0.635^2)

    = 55.69 kN.m

    Step 4:

    Depth of footing :

    a) From moment consideration we haveMu = 0.138.fck.b.d^2.

    d = 225.9mm.

    b) From shear stress consideration use have the critical s/c for one way shear is

    located at a distance d from the face of column.

    Vu =276.2[1000.23-d].

    Assuming the shear strength of c = 0.36 N/mm^2

    For M25 grade concrete with Pt = 0.25.

  • 8/2/2019 DESIGN OF HOSPITAL BUILDING

    33/43

    33

    C = (Vul/b.d)

    0.36 = 276.2[1000.23-d] / (1000xd)

    0.36x1000xd = 276.2[1000.23-d].

    = 434mm.

    d = 450mm.

    D = 500mm.Step 5 :

    Reinfocement in footing :

    1). Longer direction

    Mu = 0.87.fy.Ast.d[1-Ast.fy/b.d.fck]

    140.8x10^6 = 0.87x415xAstx450

    . [1-415xAst/ 1000x450x20]

    Ast = 896mm^2.

    Adopt 16mm dia bars of 5 nos [Ast = 1005mm^2]Spacing = 200mm c/c.

    2).shorter direction:

    55.69x10^6 = 162472.5 Ast- 5.99 Ast^2.

    Ast = 347 mm^2.

    Ratio of long to short side

    Bc = [2.25/1.5]

    = 1.5.

    Reinfocement in cement bond width 2m is

    [2/B+1] Ast = [2/1.5+1]2x347

    = 555.2mm^2.

    Min . reinforcement = 0.12/100 x 1000x500

    = 600mm^2.

    Provide 12mm dia bar 6 nos (Ast = 1206.4mm^2)

    Spacing = 150mm.

    Step 6 :

    Check for shear stress :The critical s/c for one way shear is located at distance d from the face of column . ultimate shear force

    per width in the longer direction .

    Vu = (276.2x0.635)

    = 175.4kN.

    100xAst/b.d = 100x1005.5/ (1000x230)

    = 0.44.

    {Table 19 from IS 456:2000}

  • 8/2/2019 DESIGN OF HOSPITAL BUILDING

    34/43

    34

    = ks. c = 2x0.34

    = 0.68.

    c = Vu/bd

    = 175.4x10^3/(1000x450)

    = 0.39.

    v < Ks. c.Hence safe.

  • 8/2/2019 DESIGN OF HOSPITAL BUILDING

    35/43

    35

    DESIGN OF FOOTING

    Step 1:

    Pu = 859.7 kN.

    b = 230mm.

    D = 230mm.

    P = 200kN/m^2.

    fck= 25N/mm^2.

    fy = 415N/mm^2.

    Step 2:

    Load on column = 859.7 kN.

    Assume s.w of footing (10%) = 85.97 kN.

    Total factored load Wu = 945.67kN.

    Footing area = [945.67/(1.5x200)]

    Area = 3.15 m^2.

    L x B = 3.15 m^2.

    (1.5BxB) = 3.15 m^2.

    1.5B^2 = 3.15m^2.

    B = 1.45m.

    L = 1.5 x B

    = 1.5x1.45

    L = 2.175m.

    Provide L = 2.5m, B = 2m.

    Factored soil pressure at base is computed as

    Pu = [945.6/(2.5x2)]

    = 189.12 kN/m^2.

    1.5x200 = 300 > 189.12 kN/m^2.

  • 8/2/2019 DESIGN OF HOSPITAL BUILDING

    36/43

    36

    Hence the footing area is adequate since the soil pressure developed at base is less than

    the factored bearing of soil.

    Step 3:

    Factored B.M :

    Cantilever projection from the

    short side face on column} = 0.5(2.5-0.45)

    = 1.025m.

    Cantilever projection from the

    long side face on column} = 0.5(2-0.30)

    = 0.85m.

    B.m at short side face of column is (0.5.Pu.L^2) = 0.5x189.12x1.025^2

    = 99.35 kN.m

    B.m at short side face of column is = (0.5x189.12x0.85^2)

    = 80.4 kN.m

    Step 4:

    Depth of footing :

    a) From moment consideration we haveMu = 0.138.fck.b.d^2.

    d = 170 mm.

    b) From shear stress consideration use have the critical s/c for one way shear is

    located at a distance d from the face of column.

    Vu =189.12[689.7 -d].

    Assuming the shear strength of c = 0.36 N/mm^2

    For M25 grade concrete with Pt = 0.25.

    c = (Vul/b.d)

    0.36 = 189.12[689.7-d] / (1000xd)

  • 8/2/2019 DESIGN OF HOSPITAL BUILDING

    37/43

    37

    0.36x1000xd = 189.12[1000.23-d].

    = 237.5mm.

    d = 300 mm.

    D = 350 mm.

    Step 5 :

    Reinfocement in footing.

    1). Longer direction

    Mu = 0.87.fy.Ast.d[1-Ast.fy/b.d.fck]

    99.35x10^6 = 0.87x415xAstx300

    . [1-415xAst/ 1000x300x20]

    Ast = 970 mm^2.

    Adopt 16mm dia bars of 5 nos [Ast = 1008mm^2]Spacing = 200mm c/c.

    2).shorter direction:

    80.4x10^6 = 108315 Ast - 5.99 Ast ^2.

    Ast = 775 mm^2.

    Ratio of long to short side

    Bc = [2.5/2]

    = 1.25.

    Reinfocement in cement bond width 2m is

    [2/B+1] Ast = [2/1.5+1]2x775

    = 1240 mm^2.

    Min . reinforcement = 0.12/100 x 1000x230

    = 276 mm^2.

    Provide 10mm dia bar 4 nos (Ast = 314.16mm^2)

    Spacing = 285mm.

    Provide 10mm dia @ 250mm c/c.

    Step 6 :

    Check for shear stress :

    The critical s/c for one way shear is located at distance d from the face of column . ultimate shear force

    per width in the longer direction .

    Vu = (189.12x0.885)

    = 167.4kN.

    100xAst/b.d = 100x1008/ (1000x300)

  • 8/2/2019 DESIGN OF HOSPITAL BUILDING

    38/43

    38

    = 0.336.

    {Table 19 from IS 456:2000}

    = ks . c = 2x0.41

    = 0.82.

    c = Vu/bd

    = 167.4x10^3/(1000x300)= 0.56

    v < Ks. c.

    Hence safe.

  • 8/2/2019 DESIGN OF HOSPITAL BUILDING

    39/43

    39

    DESIGN OF STAIR CASE

    Data:

    Types of stair case Dog-legged

    Tread T =250mm

    Rise R = 150mm

    Fck=20N/mm2

    Fy=415 N/mm2

    Width of each flight = 1.6m

    Height of each flight=5/2=2.5m

    Number of rises required =2.5/0.15=17

    Number of tread flight =17-1=16

    Space occupied by tread =16250=4000mm=4.0m

    Keep the landing with=2m

    Passage=1.5m

    Effective span:

    The loading on each flight

    The loading slab is assumed to span in the some direction as the stairs and is considered to

    act together to form a single slab

    Bearing of the slab =300mm

    The effective span =4+1.5+0.300/2=5.65m

    Loads:

    Assume the waist slab thickness =200mm

    Weight of slab w on slope =0.2125000

    =5000N/m2

    Dead weight of horizontal span

    W=Ws /T =

  • 8/2/2019 DESIGN OF HOSPITAL BUILDING

    40/43

    40

    =5000 /0.250

    =3830.95N/m

    Dead weight of step is given by

    W= (R /21000)125000

    =(150/2000)125000

    W =1875N/m2

    Weight of finishing =1000N/m

    Live load =5000N/m

    Total load= 5830.95+1875+1000+5000

    =13706N/m

    Factored load =1.513706

    =10559N/m

    Bending moment:

    M =Wul2/8=205595.652/8

    =82036.55N-m

    Check depth of waist slap:

    D=/0.138Fckb

    = 3/0.138201000

    Main reinforcement :

    Mu=0.87Fy Astd [1-Ast Fy/bd Fck]

    93.505106 = 0.87415Ast180[1- Ast415/100023020]

    =1042.75mm2

    Numbers of bars needed in 1.6m width

  • 8/2/2019 DESIGN OF HOSPITAL BUILDING

    41/43

    41

    =1.61042.75//4122

    = 15 No's

    Adopt 15 No's of 12mm rod

    Spacing =1600/15=107mm100mm

    Provide 15 No's of 12mm bars at 100mm c/c in main reinforcement

    Distribution reinforcement:

    =0.12 % cross area

    =0.12/1001000200=240mm2

    Adopt 10mm bars

    Spacing =1000ast/Ast=1000/4102/240=327mm

    Provide 10mm bars @300mm c/c

  • 8/2/2019 DESIGN OF HOSPITAL BUILDING

    42/43

    42

    CONCLUSION

    This project deals with the design considering thevertical loads alone. The extent of the project can be

    done by considering the earthquake load. More forces will be considered based on the strength criteria

    in our codal provisions.

    The HOSPITAL BUILDING is framed structure and designed by LIMIT STATE METHOD and the

    structure provided to be safe. The drawings were prepared using AUTO-CAD.

    Thus the object of the project has been successfully achieved and evaluated in all aspects.

    The project has enlightened us in the field of analysis and design.

  • 8/2/2019 DESIGN OF HOSPITAL BUILDING

    43/43

    BIBLIOGRAPHY

    IS 456-2000 Indian Standard Plain and Reinforcement Concrete of Practice. SP-16 Design Aids for Reinforcement Concrete to IS 456-2000.

    References:

    Varghes.P.C, (2002) Limit State Design of Reinforced Concrete. Krishna Raju.N, (2003) Design of Reinforced Concrete Structures.