DIIM
DesignInstallationInspectionMaintenance & Management
Bill McHugh, FCIARich Walke, CTI for FCIA
• FCIA Members• Firestop Contractors• Firestop Manufacturers• Firestop Consultants• Firestop Distributors, Reps, Friends
• 3rd Party Contractor Programs – FM 4991, UL Qualified • 3rd Party Inspection Company Accreditation, IAS AC291; FM/UL/IFC
Exams• ASTM E2174/E2393 Inspection Standards• FREE PDF MOP - Specifiers @ AE Firms, AHJ’s• FREE Life Safety Digest – PDF FOR ALL• Tools for Specifiers – 07-84-00
FCIA –Firestop Contractors International Association
2
• FCIA – DIIM – Firestopping• Who is FCIA?• Design – Specs, Codes, Testing, Products• Installation –
•FM 4991, UL/ULC Qualified Firestop Contractor Programs• Inspection –
•ASTM E2174 / E2393 Inspection Standards•IAS AC 291, Inspector Qualifications
• Maintenance – Fire Codes; Barrier Management• Firestopping for Safety –
•Repairs??
Outline
3
• Effective Compartmentation•Fire Barriers, Fire Walls / Floors, Smoke Barriers•Firestopping, Fire Dampers, Swinging and Rolling Fire Doors, Fire Rated Glazing
• Detection & Alarm Systems• Sprinkler Suppression Systems• Education & Egress –
•Building Owners & Managers, Building Occupants and Firefighters
“TOTAL FIRE PROTECTION”
4
QUALITYPROCESS
5
D-DESIGNSpecs, Code, Standards
I-INSTALLATIONFM 4991, UL QFCP, AND Mfr. Education
MAINTENANCEFire CodesBarrier Management
I – INSPECTIONIBC Ch. 17NFPA 80ASTM E2174/2393
• Properly Designed and Specified Firestopping• FCIA – 07-84-00 - Specification
• Tested and Listed Systems – ASTM E814 / UL 1479, ASTM E1966 / UL 2079, FM 4990, ULC-S115, ASTM E2837, E2307, E3037, more
• Professional Installation – FCIA Member, FM 4991 Approved, UL/ULC Qualified Contractors
• Properly Inspected – ASTM E2174 / 2393 Processed by IAS AC 291 Accredited Inspection Agencies, Inspectors w/FM, UL, ULC,IFC Exam Success
• Maintained & Managed – Annually – FCIA Members – NFPA 1, 101, International Fire Code
Firestopping for Safety “DIIM”
6
• International Codes –•New and Existing Buildings – International Building Code –Chapter 7
• International Fire Code – Chapter 7• NFPA 5000 / 101 – Chapter 8• National Building Code of Canada• UAE Fire and Life Safety Code• Many other Country Codes…
• Minimum Requirements – Construction & Maintenance
Building & Fire Code Requirements
7
[BF] FIRE RESISTANCE. That property of materials or their assemblies that prevents or retards the passage of excessive heat, hot gases or flames under conditions of use. [IBC 2018 202]
[BF] FIRE-RESISTANCE RATING. The period of time a building element, component or assembly maintains the ability to confine a fire, continues to perform a given structural function, or both, as determined by the tests, or the methods based on tests, prescribed in Section 703. [IBC 2018, 202]
Building & Fire Code Requirements
8
703.3 Methods for determining fire resistance. The application of any of the methods listed in this section shall be based on the fire exposure and acceptance criteria specified in ASTM E119 or UL 263. The required fire resistance of a building element, component or assembly shall be permitted to be established by any of the following methods or procedures:1. Fire-resistance designs documented in approved sources.2. Prescriptive designs of fire-resistance-rated building elements, components or
assemblies as prescribed in Section 721.3. Calculations in accordance with Section 722.4. Engineering analysis based on a comparison of building element, component or
assemblies designs having fire-resistance ratings as determined by the test procedures set forth in ASTM E119 or UL 263.
5. Alternative protection methods as allowed by Section 104.11.6. Fire-resistance designs certified by an approved agency.
Fire Resistance
9
• Fire-Resistance Rated Barriers – Defined Terms•Exterior Walls•Fire Walls•Fire Barriers•Fire Partitions (Not NFPA)•Smoke Barriers•Smoke Partitions•Archaic Assemblies
Building & Fire Code Requirements
10
• Archaic Assemblies•Clay Tile Block•Gypsum Block•Plaster•Clay Tile/Concrete•Unidentified Assemblies
• Tested … Calculated … Prescriptive
Existing Buildings
11
• Smoke Barriers differ from Smoke Partitions?• Smoke Barrier –
• IBC – Hourly Rated, Quantified Firestop “L” Rating• < 5cfm/sf (IBC 2006)• < 50 cfm, 100 sf of Wall Area (IBC 2009)
• NFPA – … ‘restricting the passage of smoke’…• Hourly Rated, Quantified Firestop L Rating Chapter 8• NO quantified “L” Rating … Healthcare Chapter• Continuous, Barrier to Barrier, … through concealed spaces• Not always fire-resistance-rated
• Smoke Partition –• IBC – Continuous barrier, not fire rated…’retard’• NFPA – Continuous membrane that is designed to form a barrier to limit the transfer of smoke….
Smoke Barriers & Firestopping
12
• Products Become Systems Through….• Test Standard References
• Structural Elements & Assemblies – ASTM E119, UL 263• Fire & Smoke Barriers – ASTM E119, UL 263• Firestopping – ASTM E814 / UL 1479, ULC-S115, UL 2079, ASTM E1966,
E2307, E2837, …test method…”• Fire/Smoke Dampers – UL 555, UL 555S• Swinging/Rolling Fire Doors – UL 10B, 10C• Fire Rated Glazing – UL 9, NFPA 252
• SYSTEM Testing = Suitability statement for use of a product in a specific system/design application
Fire Resistance SYSTEMS
13
• NEW Buildings – 07-84-00 Specs•www. FCIA .org
• Part I – Focus on•Systems•Not Products•Manufacturers
• “Single Manufacturer to the greatest extent possible” – EJ’s
Specs – Starts Barrier Management Process
• NEW Buildings – 07-84-00 Specs•www. FCIA .org
• Part II– Contractor/Installer Qualifications•FCIA Member in Good Standing, AND•FM 4991, Standard for the Approval of Firestop Contractors, OR
•UL Qualified Firestop Contractor Program•AND•Manufacturer Accredited, Approved, Trained
Specs – Key Parts
• NEW Buildings – 07-84-00 Specs•www. FCIA .org
• Part II – Qualifications – Special Inspection•Special Inspection Agency –
•IAS AC 291 Accredited Special Inspection Agencies•Special Inspector Qualifications
•FM Firestop Exam•UL Firestop Exam•AND•IFC Exam
Specs – Key Parts
• NEW Buildings – 07-84-00 Specs• Part III – Execution
•Special Inspection•ASTM E 2174 - Penetrations•ASTM E 2393 - Joints
Specs – Key Parts
• Reference 01-78-00 Closeout Submittals•01 78 29 Final Site Survey•01 78 33 Bonds•01 78 36 Warranties•01 78 39 Project Record Documents•01 78 43 Spare Parts•01 78 46 Extra Stock Materials•01 78 53 Sustainable Design Closeout Documentation
Specs – Don’t Forget Division 1 – ALL DivisionsDocumentation for Building Life Cycle
D-DESIGN
QUALITYPROCESS
I-INSTALLATIONSystems SelectionSystems AnalysisSelf InspectionFCIA, FM & UL MACC
I-INSPECTION
19
Firestopping for ContinuityI – Listed Systems
20
• Firestop Systems Directories –• UL• Intertek• FM Approvals• Others
Systems Selection & Analysis…Not as easy as it looks…
Firestopping for Continuity Products Become Systems
21
• Wall or Floor Construction Type, Rating• Wall or Floor Thickness• Penetrating Item, Coverings• Size, Type, Thickness• Annular Space Sizes• Joint / Gap Sizes• Backing Materials• Fill Material(s)= Rated Firestop System
How do Contractors Select/Analyze Systems& Inspection Agencies Analyze?
STI Graphic
22
Engineering Judgments/EFRRA
• Field or other Variances to Tested and Listed Systems?•No System Exists, period….
• Why???•Lack of Planning•Unique Conditions
Fire Stop Technologies, Inc. Photo
23
• First Action in Process•Find another system – Same Manufacturer•Find another system – Different Manufacturer• If no system exists in either case….
• Second Action –•Engineering Judgment – “EJ”•Equivalent Fire Resistance Rated Assembly – “EFRRA”
• Based on engineering, IFC Protocol• Inspection Agency?
Engineering Judgments/EFRRA
24
• Each Trade• “He/She who pokes hole, fills hole”
• Multiple Contracts•Firestop Contractors, Trades
• Single Source Firestop Contractor•FCIA Member in Good Standing•FM 4991, UL, ULC Qualified
3 Firestop Installation Methods
25
1. Office Facility Quality Management System Audit2. Field – Jobsite Audit3. Employ a person
•UL/FM Firestop Exam @ 80% or better•DRI if employed by Approved/Qualified Firm
•Designated Responsible Individual (DRI)4. Annual Audit
Firestop Contractor Qualifications FM & UL/ULC – 4 Components
26
FM, UL/ULC Company Audit of Management System (MS)• Employee Training & Education• Systems Selection• Communicate systems to Field• Material Controls• Systems installation “protocol”• Labeling• Record keeping - Variance Procedures• Non-Conformances• Documentation• Project closeout
27
Master Audit Certificate of Compliance ProgramA Jobsite Specific Management System Audit – Ouraudit provides verified processes were followed toproperly installed firestop systems.
A Renewable Jobsite Specific Certificate – Aftercompletion of a successful audit, we issue a jobsitespecific certificate that is renewable for the buildingowner.
Improved Firestop Systems Documentation – TheMACC certificate in conjunction with the firestopsystems documentation, builds the fire-resistanceinventory required by the 2018 International Fire Code for fire and smoke protection features.
UL Slide
28
D-DESIGN
QUALITYPROCESS
I-INSPECTIONASTM E2174, E2393IAS AC291 AccreditationInspector QualificationsInspection Process 29
• Each Construction Discipline – MEP, etc.• “He/She who pokes hole, fills hole”
• Multiple Contracts•Firestop Contractors, Trades
• Single Source Firestop Contractor•FCIA Member in Good Standing•UL/ULC Qualified, or FM 4991
Why Inspection?Firestop Installation Methods
30
• NFPA 101 / 5000 – Chapter 8 – Annex• 2012 International Building Code
•CH 17 – Special Inspections (FCIA Proposals)•Buildings 75’ & higher above Fire Department Access•Occupancy Type III, IV, Chapter 16 Table 1604.5•Residential > 250 Occupants – 2021 (FCIA Proposal)
• Abu Dhabi International Building Code
Inspection in CodesASTM E2174 – ASTM E2393
31
• “Standard Practice for On-Site Inspection of Installed Fire Stops – Penetrations - Joints”•Standard Inspection Procedure•Special Inspection Agency Companies• Independent•Hired by & Reports to..
•Building Owner, Architect, Owners Rep, other than GC= Authorizing Authority
Firestop Systems InspectionASTM E2174 – ASTM E2393
32
Measure Sealant Thickness at Bond Lines to Pen./Assy. – Not Middle of Annular Space
Adler Photos
33
• Equipment –•Tapes•Tablets w/Systems•Borescope to explore areas thatare concealed or partially concealed
•NOT MICROMETERS
Firestop InspectionASTM E2174 – ASTM E2393
34Firestop Southwest, Affinity Firestop Photos
• Repairs• Instruction requirements bymanufacturer
•Listed systems•Patching
•Systems….•Adhesion•Movement•T, L, W Ratings•As recommended by MFR
Firestop Repairs
Affinity Firestop Photo35
D-DESIGN
QUALITYPROCESS
M-MAINTENANCEFire CodesBarrier Management
I-INSPECTION
36
• NFPA 101• NFPA 1• International Fire Code
•Minimum Requirements Stated•Frequency•What really happens?
Fire Codes Require Maintenance
37
• SECTION 4.6.12 Maintenance, Inspection, and Testing.• 4.6.12.1 Whenever or wherever any device, equipment, system, condition, arrangement, level of protection, fire-resistive construction, or any other feature is required for compliance with the provisions of this Code, such device, equipment, system, condition, arrangement, level of protection, fire-resistive construction, or other feature shall thereafter be continuously maintained … in accordance with applicable NFPA requirements or requirements developed as part of a performance-based design, or as directed by the AHJ.
National Fire Protection AssociationNFPA 101 – 2018
38
• 4.6.12.2 No existing life safety feature shall be removed or reduced where such feature is a requirement for new construction.
• 4.6.12.3* Existing life safety features obvious to the public, if not required by the Code, shall be either maintained or removed.
• 4.6.12.4 Any device, equipment, system, condition, arrangement, level of protection, fire-resistive construction, or any other feature requiring periodic testing, inspection, or operation to ensure its maintenance shall be tested, inspected, or operated as specified elsewhere in this Code or as directed by the AHJ.
• 4.6.12.5 Maintenance, inspection, and testing shall be performed under the supervision of a responsible person who shall ensure that testing, inspection, and maintenance are made at specified intervals in accordance with applicable NFPA standards or as directed by the AHJ.
National Fire Protection AssociationNFPA 101 – 2018
39
• 12.2* Construction.•12.2.2 Fire safety construction features for new and existing occupancies shall comply with this Code and the referenced edition of NFPA 101.
• 12.3 Fire-Resistive Materials and Construction.•12.3.1 The design and construction of fire walls and fire barrier walls that are required to separate buildingsor subdivide a building to prevent the spread of fireshall comply with Section 12.3 and NFPA 221.
National Fire Protection AssociationNFPA 1 – 2018
40FCIA Added Emphasis
•12.3.2* Quality Assurance for Penetrations and Joints. In new buildings three stories or greater in height, a quality assurance program for the installation of devices and systems installed to protect penetration and joints shall be prepared and monitored by the RDP responsible for design. Inspections of firestop systems and fire-resistive joint systems shall be in accordance with 12.3.2.1 and 12.3.2.2.
National Fire Protection AssociationNFPA 1 – 2018
41FCIA Added Emphasis
•12.3.2.1 … Penetrations … shall be inspected in accordance with ASTM E2174 …
•12.3.2.2 … Joint systems … shall be inspected in accordance with ASTM E2393 …
•FCIA INTIATIVE WITH KOFFEL ASSOC.…
National Fire Protection AssociationNFPA 1 – 2018
42
FCIA Added Emphasis
•12.3.3* Maintenance of Fire-Resistive Construction, Draft-Stop Partitions, and Roof Coverings.•12.3.3.1 Required fire-resistive construction, including fire barriers, fire walls, exterior walls due to location on property, fire-resistive requirements based on type of construction, draftstop partitions, and roof coverings, shall be maintained and shall be properly repaired, restored, or replaced where damaged, altered, breached, penetrated, removed, or improperly installed.
National Fire Protection AssociationNFPA 1 – 2018
43
FCIA Added Emphasis
•12.3.3.2 Where required, fire-rated gypsum wallboard walls or ceilings that are damaged to the extent that through openings exist, the damaged gypsum wallboard shall be replaced or returned to the required level of fire-resistance using a listed repair system or using materials and methods equivalent to the original construction.
National Fire Protection AssociationNFPA 1 – 2018
44
FCIA Added Emphasis
•12.3.3.3 Where readily accessible, required fire-resistance-rated assemblies in high-rise buildings shall be visually inspected for integrity at least once every 3 years.
•12.3.3.3.1 The person responsible for conducting the visual inspection shall demonstrate appropriate technical knowledge and experience in fire-resistance-rated design and constructionacceptable to the AHJ.
•12.3.3.3.2 A written report prepared by the person responsible for conducting the visual inspection shall be submitted to the AHJ documenting the results of the visual inspection.
National Fire Protection AssociationNFPA 1 – 2018
45
FCIA Added Emphasis
SECTION 703FIRE-RESISTANCE-RATED CONSTRUCTION• 703.1 Maintenance. The required fire-resistance rating of fire-resistance-rated
construction (including walls, firestops, shaft enclosures, partitions, smoke barriers, floors, fire-resistive coatings and sprayed fire-resistant materials applied to structural members and fire-resistant joint systems) shall be maintained. Such elements shall be visually inspected by the owner annually and properly repaired, restored or replaced when damaged, altered, breached or penetrated. …
Openings made therein for the passage of pipes, electrical conduit, wires, ducts, air transfer openings, and holes made for any reason shall be protected with approved methods capable of resisting the passage of smoke and fire. …
2009 International Fire Code Maintenance
46FCIA Added Emphasis
SECTION 703FIRE-RESISTANCE-RATED CONSTRUCTION• 703.1 Maintenance. The required fire-resistance rating of fire-resistance-
rated construction, including, but not limited to walls, firestops, shaft enclosures, partitions, smoke barriers, floors, fire-resistive coatings and sprayed fire- resistant materials applied to structural members and fire-resistant joint systems, shall be maintained. Such elements shall be visually inspected by the owner annually and properly repaired, restored or replaced when damaged, altered, breached or penetrated. Records of inspections and repairs shall be maintained. …
2015 International Fire Code Maintenance
47
FCIA Added Emphasis
SECTION 703FIRE-RESISTANCE-RATED CONSTRUCTION• 703.1 Maintenance. (Continued) Where concealed, such elements shall
not be required to be visually inspected by the owner unless the concealed space is accessible by the removal or movement of a panel, access door, ceiling tile or similar movable entry to the space. Openings made therein for the passage of pipes, electrical conduit, wires, ducts, air transfer openings and holes made for any reason shall be protected with approved methods capable of resisting the passage of smoke and fire. Openings through fire-resistance-rated assemblies shall be protected by self- or automatic-closing doors of approved construction meeting the fire protection requirements for the assembly.
2015 International Fire Code Maintenance
48
SECTION 703FIRE-RESISTANCE-RATED CONSTRUCTION
• 703.1.1 Fireblocking and draftstopping. Required fireblocking and draftstopping in combustible concealed spaces shall be maintained to provide continuity and integrity of the construction.
• 703.1.2 Smoke barriers and smoke partitions. Required smoke barriers and smoke partitions shall be maintained to prevent the passage of smoke. Openings protected with approved smoke barrier doors or smoke dampers shall be maintained in accordance with NFPA 105.
2015 International Fire Code Maintenance
49
SECTION 703FIRE-RESISTANCE-RATED CONSTRUCTION
• 703.1.3 Fire walls, fire barriers and fire partitions. Required fire walls, fire barriers and fire partitions shall be maintained to prevent the passage of fire. Openings protected with approved doors or fire dampers shall be maintained in accordance with NFPA 80.
2015 International Fire Code Maintenance
50
SECTION 701GENERAL• 701.1 Scope. The provisions of this chapter shall govern the inspection
and maintenance of the materials, systems and assemblies used for structural fire-resistance, fire-resistance-rated construction separation of adjacent spaces and construction installed to resist the passage of smoke to safeguard against the spread of fire and smoke within a building and the spread of fire to or from buildings. New buildings shall comply with the IBC.
2018 International Fire CodeMaintenance
51
FCIA Added Emphasis
SECTION 701GENERAL• 701.2 Fire-resistance-rated construction. The fire-resistance rating of
the following fire-resistance-rated construction shall be maintained:1. Structural members2. Exterior walls3. Fire walls, fire barriers, fire partitions4. Horizontal assemblies5. Shaft enclosures
2018 International Fire Code Maintenance
52
SECTION 701GENERAL• 701.3 Smoke barriers. The fire-resistance rating and smoke-resistant
characteristics of smoke barriers shall be maintained.• 701.4 Smoke partitions. The smoke-resistant characteristics of smoke
partitions shall be maintained.
2018 International Fire Code Maintenance
53
SECTION 701GENERAL• 701.5 Maintaining protection. Materials, systems and devices used to
repair or protect breaches and openings in fire-resistance-rated construction and construction installed to resist the passage of smoke shall be maintained in accordance with Sections 703 through 707.
2018 International Fire Code Maintenance
54
FCIA Added Emphasis
SECTION 701GENERAL• 701.6 Owner’s responsibility. The owner shall maintain an inventory of
all required fire-resistance-rated construction, construction installed to resist the passage of smoke and the construction included in Sections 703 through 707. Such construction shall be visually inspected by the owner annually and properly repaired, restored or replaced where damaged, altered, breached or penetrated.
• FCIA Initiative with Koffel Assoc. – ‘Inventory’…
2018 International Fire Code Maintenance
55
FCIA Added Emphasis
SECTION 701GENERAL• 701.6 Owner’s responsibility Cont. Records of inspections and
repairs shall be maintained. Where concealed, such elements shall not be required to be visually inspected by the owner unless the concealed space is accessible by the removal or movement of a panel, access door, ceiling tile or similar movable entry to the space.
2018 International Fire Code Maintenance
56
FCIA Added Emphasis
SECTION 701GENERAL• 701.7 Unsafe Conditions. Where any components in this chapter are not
maintained and do not function as intended or do not have the fire-resistance or the resistance to the passage of smoke required by the code under which building was constructed, remodeled or altered, such component(s) or portions thereof shall be deemed an unsafe condition in accordance with Section 111.1.1.
2018 International Fire Code Maintenance
57
FCIA Added Emphasis
SECTION 701GENERAL• 701.7 Unsafe Conditions Cont. Components or portions thereof
determined to be unsafe shall be repaired or replaced to conform to the code under which building was constructed, remodeled or altered, as deemed appropriate by the fire code official. Where the condition of components is such that any building, structure or portion thereof presents an imminent danger to the occupants of the building, structure or portion thereof, the fire code official shall act in accordance with Section 111.2.
2018 International Fire Code Maintenance
58
FCIA Added Emphasis
SECTION 703PENETRATIONS• 703.1 Maintaining protection. Materials and firestop systems used to
protect membrane and through penetrations in fire-resistance-rated construction and construction installed to resist the passage of smoke shall be maintained.
2018 International Fire Code Maintenance
59
FCIA Added Emphasis
SECTION 703PENETRATIONS• 703.1 Maintaining protection cont. The materials and firestop systems
shall be securely attached to or bonded to the construction being penetrated with no openings visible through or into the cavity of the construction. Where the system design number is known, the system shall be inspected to the listing criteria and manufacturer’s installation instructions.
• FCIA Initiative…”Where the system design number is known”…
2018 International Fire Code Maintenance
60
FCIA Added Emphasis
SECTION 704JOINTS AND VOIDS• 704.1 Maintaining protection. Where required when the building was
originally constructed, materials and systems used to protect joints and voids in the following locations shall be maintained. The materials and systems shall be securely attached to or bonded to the adjacent construction, without openings visible through the construction.
2018 International Fire Code Maintenance
61
FCIA Added Emphasis
SECTION 704JOINTS AND VOIDS• 704.1 Maintaining protection cont.
• Subparagraphs 1 through 7 detail the types of joints and voids required to be maintained. This list corresponds to joints and voids which are required to be protected by the 2018 IBC.
• Unprotected joints and voids do not need to be protected where such joints and voids were not required to be protected when the building was originally constructed.
2018 International Fire Code Maintenance
62
FCIA Added Emphasis
SECTION 705DOOR AND WINDOW OPENINGS• 705.1 Maintaining protection. Where required when the building was
originally constructed, opening protectives installed in fire-resistance-rated assemblies, smoke barriers and smoke partitions shall be inspected and maintained in accordance with this section.
2018 International Fire Code Maintenance
63
FCIA Added Emphasis
SECTION 705DOOR AND WINDOW OPENINGS• 705.2 Inspection and maintenance. Opening protectives in fire-
resistance-rated assemblies shall be inspected and maintained in accordance with NFPA 80. Opening protectives in smoke barriers shall be inspected and maintained in accordance with NFPA 80 and NFPA 105. Openings in smoke partitions shall be inspected and maintained in accordance with NFPA 105.
2018 International Fire Code Maintenance
64
FCIA Added Emphasis
SECTION 705DOOR AND WINDOW OPENINGS• 705.2 Inspection and maintenance cont. Fire doors and smoke and draft
control doors shall not be blocked, obstructed, or otherwise made inoperable. Fusible links shall be replaced promptly whenever fused or damaged. Opening protectives and smoke and draft control doors shall not be modified.
2018 International Fire Code Maintenance
65
FCIA Added Emphasis
SECTION 705DOOR AND WINDOW OPENINGS• 705.2.1 Labeling requirements. Where approved by the fire code official,
the application of field-applied labels associated with the maintenance of opening protectives shall follow the requirements of the approved third-party certification organization accredited for listing the opening protective.
2018 International Fire Code Maintenance
66
SECTION 705DOOR AND WINDOW OPENINGS• 705.2.2 Signs. Where required by the fire code official, a sign shall be
permanently displayed on or near each fire door in letters not less than 1 inch (25 mm) high to read as follows:
1. For doors designed to be kept normally open: FIRE DOOR—DO NOT BLOCK.
2. For doors designed to be kept normally closed: FIRE DOOR—KEEP CLOSED.
2018 International Fire Code Maintenance
67
SECTION 705DOOR AND WINDOW OPENINGS• 705.2.3 Hold-open devices and closers. Hold-open devices and
automatic door closers, where provided, shall be maintained. During the period that such device is out of service for repairs, the door it operates shall remain in the closed position.
2018 International Fire Code Maintenance
68
FCIA Added Emphasis
SECTION 705DOOR AND WINDOW OPENINGS• 705.2.4 Door operation. Swinging fire doors shall close from the full-open
position and latch automatically.• 705.2.5 Smoke- and heat-activated doors. Smoke-activated doors shall
be maintained to self-close or automatically close upon detection of smoke. Existing fusible-link type automatic door-closing devices are permitted if the fusible link rating does not exceed 135˚F (57˚C).
2018 International Fire Code Maintenance
69
FCIA Added Emphasis
SECTION 705DOOR AND WINDOW OPENINGS• 705.2.6 Testing. Horizontal and vertical sliding and rolling fire doors shall
be inspected and tested annually to confirm proper operation and full closure. Records of inspections and testing shall be maintained.
2018 International Fire Code Maintenance
70
FCIA Added Emphasis
SECTION 706DUCT AND AIR TRANSFER OPENINGS• 706.1 Maintaining protection. Dampers protecting ducts and air transfer
openings shall be inspected and maintained in accordance with NFPA 80 and NFPA 105. Other products or materials used to protect the openings for ducts and air transfer openings shall be securely attached to or bonded to the construction containing the duct or air transfer opening, without visible openings through or into the cavity of the construction. Any damaged products or materials protecting duct and air transfer openings shall be repaired, restored or replaced.
2018 International Fire Code Maintenance
71
FCIA Added Emphasis
SECTION 706DUCT AND AIR TRANSFER OPENINGS• 706.2 Unprotected openings. Unprotected duct and air transfer openings
in fire-resistance-rated construction and construction installed to resist the passage of smoke shall be protected so as to comply with requirements that were in effect when the building was constructed.
2018 International Fire Code Maintenance
72
FCIA Added Emphasis
SECTION 707CONCEALED SPACES• 707.1 Fireblocking and draftstopping. Required fireblocking and
draftstopping in combustible concealed spaces shall be maintained to provide continuity and integrity of the construction.
2018 International Fire Code Maintenance
73
FCIA Added Emphasis
• 701.6 Owner's responsibility. The owner shall maintain an inventory of all required fire-resistance-rated and smoke resistant construction, and the construction included in Sections 703 through 707 and such construction shall be visually inspected by the owner annually and properly repaired, restored or replaced where damaged, altered, breached or penetrated.
• FCIA Initiative with Koffel Associates
2018 International Fire Code Owner’s Responsibility
74FCIA Added Emphasis
• Life Safety Drawings• Designs, Systems and Assemblies – Listings• Manufacturers Installation and Maintenance Instructions
• How?•Paper & Files•Spreadsheets•Software
2018 International Fire Code Fire-Resistance Inventory Explained
75
2018 IPMC SECTION 703• 703.1 Fire-resistance-rated assemblies. The required fire-resistance
rating of fire-resistance-rated walls, firestops, shaft enclosures, partitions and floors shall be maintained.
• 703.2 Opening protectives. Required opening protectives shall be maintained in an operative condition. Fire and smokestop doors shall be maintained in operable condition. Fire doors and smoke barrier doors shall not be blocked or obstructed or otherwise made inoperable.
International Property Maintenance Code
76
National Fire Code of Canada• Division B – Part 2, Building and Occupant Fire Safety
2.2.1.2 – Damage to Fire Separations – Where fire separations are damaged so as to affect their integrity, they shall be repaired so that the integrity of the fire separation is maintained…
• FCIA Manual of Practice – Appendix, MaintenanceFCIA recommends Barrier Management for Effective Compartmentation and Structural Protection
National Fire Code of Canada
77
• Visual Building Survey/Inspection….•Does it look like the assembly?
•Annular Space•Visible Breaches, unless listing allows•Joint Width•Penetrating Item Types, Coverings•# Penetrating Items, Types•Penetrations in Joints & Not in System/Listing…•Much more…
•Competent Personnel
M–Barrier Management Systems
78
• Wall or Floor Construction Type, Rating• Wall or Floor Thickness• Penetrating Item, Coverings• Size, Type, Thickness• Annular Space Sizes• Joint / Gap Sizes• Backing Materials• Fill Material(s)= Rated Firestop System
How do Contractors Select/Analyze Systems& Inspection Agencies Analyze?
STI Graphic
79
Affinity Firestop Photo
C-AJ-8XXXX???See Tag/LabelIdentification System
Affinity Firestop Photo
C-AJ-???
Affinity Firestop Photo
C-AJ-5209?
Affinity Firestop Photo
C-AJ-8XXX??
Affinity Firestop Photo
W-L-2XXX???NOPE!!
Affinity Firestop Photo
W-L-2XXXWallboardPatch??
NO!!
Affinity Firestop Photo
Good Luck!
• Create a Budget to Meet Code Requirements• Inventory – What Info?
• Life Safety Drawings• Manufacturers Instructions• Tested and Listed Systems (Listings)
• Implement Fire Resistance Management• In House Policy• Outside Contractor Policy
• Monitor Process • Annual Visual Inspection & Keep Records• Show Fire Marshal….Insurance Company
M–Barrier Management Systems Building Owner’s Policy Topics
87
ContactFirestop Contractors International Association
Hillside, IL – +1-708-202-1108 - [email protected]
• Electronic Best Practice Elements•Action Oriented
•Projects - Specifications•Ongoing Surveys – FCIA RPPS 2010-1
•Action Reminders• In Process Status•Record Retrieval
M–Barrier Management Systems
89
• Visual Building Survey/Inspection….•Tested and Listed Systems (Listings)•Manufacturers installation instructions
M–Barrier Management Systems
90
© FCIA 2020
Questions??