design and simulation of air cooledconditioner
DESCRIPTION
This book is my project research for design air-conditioning system complete with condenser, evaporator, compressor and capillary tube.. if u have any enquiry, can email me at [email protected]. This book is suitable for student or worker that want a guide for design their own system.TRANSCRIPT
CHAPTER 1
INTRODUCTION
1.1 Project Introduction
Nowadays, there are many usage of air conditioning involve either in
commercial, industry and residential. The usage is worldwide and global, not only
certain part of earth. There are varies type and choice of air conditioning can be
found. The selection of air conditioning is depend on the application and type of
building or space.
The system involve in my research is Air Cooled system. Air cooled air
conditioner is a kind of air conditioning equipment that adopts air as the cold or heat
source to regulate the indoor air. So cooling tower, water pump, boiler and relevant
piping system, as well as many auxiliaries are not needed in this air conditioner,
making this ducted air conditioner simpler in structure, easier to install and maintain,
and more energy efficient
1.2 About the System
Air conditioning is a combined process that performs many functions
simultaneously. It conditions the air, provides heating and cooling, controls and
maintains the temperature, and humidity, ensures air movement, air cleanliness,
sound level, and pressure differential in a space within predetermined limits for the
comfort and health of the occupants. A cooling system is a part of a heating,
ventilation and air-conditioning (HVAC) system that provides space cooling. [1]
1
Direct expansion type or DX type is the air is directly cooled from the
refrigerant; therefore the cooling coil is filled with refrigerant. These cooling systems
are widely used in small to medium sized buildings. For larger and more complex
applications, a secondary cooling medium is used to deliver cooling to one or more
locations needing it. This is accomplished by utilizing the chiller to cool the water,
which in turn is pumped to the cooling coil(s). The heat flow path is from the space
to the chilled water to the refrigerant to the atmosphere. [1]
In direct expansion (DX) systems, the air is cooled with direct exchange of
heat with refrigerant passing through the tubes of the finned cooling coil. A basic DX
system comprises of a hermetic sealed or open compressor/s, evaporator (cooling
coil fabricated out of copper tubes and aluminum fins), a supply air blower, filter,
and a condenser. The term "expansion" refers to the method used to introduce the
refrigerant into the cooling coil. The liquid refrigerant passes through an expansion
device (usually a valve) just before entering the cooling coil (the evaporator). This
expansion device reduces the pressure and temperature of the refrigerant to the point
where it is colder than the air passing through the coil. [1]
In the split system, the condensing unit comprising of the condenser,
compressor and condenser fan with motor are located outside, while the indoor unit
consisting of the evaporator, evaporator fan with motor, expansion valve and air
filter is located inside the conditioned room. The indoor and outdoor units are
connected by refrigerant piping. Flexibility is the overriding advantage of a split
system. Because a split system is connected through a custom designed refrigerant
piping system, the engineer has a large variety of possible solutions available to meet
architectural and physical requirements particularly for buildings with indoor and/or
outdoor space constraints. [1]
1.3 Objective
To analyse the effect of evaporating temperature on cooling capacity.
To determine the evaporating temperature for Malaysia conditions.
2
1.4 Project overview
This project is about to design and analyze the effect of evaporating and
condensing temperature on system sizing and design. Its mean by using varies and
different evaporating temperature according to Malaysia conditions that can be found
in Malaysia Standard 1525 (MS1525) handbook. Then determine the effect of varies
temperature on system sizing and design. The process involve is to select and the
compressor, condenser, evaporator and capillary tube. After that, by using the varies
temperature for condensing and evaporating, determine the component sizing and
design for each temperature have tested. Collect the data, then make a graph and
analyze the result.
The software use for this project is :
1. Copeland Selection Software 6.6
2. Microsoft Excel 2007
3. Solvay Fluor
4. Autocad 2010
1.5 Scope of work
Design and select compressor.
Determine the evaporator and condenser capacity.
Design the condenser.
Design the evaporator.
Design and calculate the length of capillary tube.
Doing the analysis then evaluate the result.
Make a conclusion.
3
4
GANTT CHART
The gantt chart is for a period 37 weeks (Semester 6 and Semester 7)
1) Semester 6
JANUARY FEBRUARY MARCH APRILTOPIC / WEEK 1 2 3 4 5 6 7 8 9 10 11 12 13 14Registration of FYP subject FYP briefing Select & register title Discussion about the project Propose the objective Introduction Literature review Methadology Presentation preparing Presentation
2) Semester 7
5
MAY JUNE JULY AUGUST SEPTEMBER OCTOBER NOVEMBER
TOPIC / WEEK 15 16 1718 19 20
21 22 23
24 25 26 27
28 29 30
31 32 33
34 35 36 37
Research & learn how to design system
Design compressor
Design condenser & evaporator
Design capilary tube
Analysis
Conclusion
Preparing the report
Presentation preparing
Presentation
CHAPTER 2
LITERATURE REVIEW
2.1 Basic Concepts
Comfort Air-conditioning – a process of controlling the air temperature,
relative humidity, ventilation, air movement and air cleanliness of a given
space in order to provide the occupants with a comfortable indoor
temperature. [2]
Air-conditioning System – consists of a group of components or equipment
connected in series to control the environmental parameters. [2]
2.2 The Goal of Air Conditioning System Design
The goal of an air conditioning system design is to achieve a highly quality
system that functions effectively and is energy-efficient and cost-effective. The
following are essential for a system to function effectively: [2]
All design criteria are fulfilled, and the requirements of the owner and the
user are satisfied.
A good indoor air quality is provided.
The system is reliable and has adequate fire protection level (e.g. smoke
management).
2.3 Split-System Air Conditioners design standard
Provide complete a DX system for central station air conditioning. The system must consist of matching air-cooled condensing units, compressors, piping, controls, wiring, and other accessories, as well as the appurtenances necessary to provide a fully-automatic system. [3]
6
2.3.1 Materials
i. Condenser coils must be aluminum plate fins, mechanically bonded to
seamless copper tubes, circuited for subcooling.
ii. Provide openings for power and refrigerant connections.
iii. Provide a service access panel.
iv. Provide copper tubes, circuited for sub-cooling. Provide propeller fans
arranged for vertical discharge. Condenser fan motors must have
inherent protection, and must be permanently-lubricated and
resiliently-mounted. Fans must have safety guards. Provide controls
for cycling fans.
v. Compressors must be serviceable, hermetic compressors, with
external spring isolators and an automatically reversible oil pump.
a. Compressors must unload in steps, in response to suction
pressure, for partial load operation. Separate compressors from
condenser fans and coils.
b. Multiple compressor units must have stop-start fans and coils.
Compressor motors must have a part-winding start.
vi. Provide refrigerant piping between air-cooled condensing units and
air conditioning units. Refrigerant piping must be equipped with the
necessary auxiliary equipment, such as strainers, sight glasses, oil
traps, scale traps, and other devices, to make the system complete and
operable under fully-automatic control.
vii. Refrigeration piping must be ACR copper tubing made up with
wrought copper fittings, using silver solder and installed with a
nitrogen charge while soldering. Use the piping size recommended by
the manufacturer of the air conditioning unit and matching air-cooled
unit. Casings must be galvanized steel finished with baked enamel.
7
2.3.2 Quality Control
If this portion of the project includes commissioning, verify that insertions in
the project specifications have been made that refer to the commissioning procedures
in the commissioning specification section. Verify that the systems and equipment
identified in this section of the standards, and listed in the project specifications, do
not conflict with commissioning procedures for testing and training. [3]
2.4 Design Criteria for Scroll compressor
2.4.1 Scroll Compression Process
The diagram shown describes the scroll compression process. The two
components shown are mating involute scrolls. One scroll is fixed in place and the
other scroll orbits within this fixed scroll. One part that is not shown in this diagram
but is essential to the operation of the scroll is the anti-rotation coupling. This device
maintains a fixed angular relation of 180 degrees between the fixed and orbiting
scrolls. This fixed angular relation, coupled with the movement of the orbiting scroll,
is the basis for the formation of gas compression pockets. [4]
As shown here, the compression process involves three orbits of the orbiting
scroll. In the first orbit, the scrolls ingest and trap-off two pockets of suction gas.
During the second orbit, the two pockets of gas are compressed to an intermediate
pressure. In the final orbit, the two pockets reach discharge pressure and are
simultaneously opened to the discharge port. [4]
This simultaneous process of suction, intermediate compression, and
discharge leads to the smooth continuous compression process of the scroll
compressor. [4]
8
Figure 2.1 : The process of the scroll compressor. [4]
2.4.2 Compressor Handling
It is recommended that the plugs in the compressor line connections be left in
place until the compressor is set into the unit. This reduces the chance of
contaminants and moisture getting into the compressor especially if the compressor
is charged with the more hygroscopic POE oil. If the compressor has two lifting tabs,
both must be used for lifting. The discharge connection plug should be removed first
before pulling the suction connection plug to allow the dry air pressure inside the
compressor to escape. Pulling the plugs in this sequence prevents oil mist from
coating the suction tube making brazing difficult. The copper-coated steel suction
tube should be cleaned before brazing. No object (e.g. a swaging tool) should be
inserted deeper than 50 mm into the suction tube or it might damage the suction
screen. [5]
Figure 2.2 : Suction tube brazing. [5]
9
2.4.3 Lubrication and Oil Removal
The compressor is supplied with an initial oil charge. The standard oil charge
for use with refrigerants R407C and R134a is a polyolester (POE) lubricant
Copeland 3MAF (32 cSt). In the field the oil level could be topped up with ICI
Emkarate RL 32 CF or Mobil EAL Arctic 22 CC, if 3MAF is not available. In R22
applications Suniso 3GS is used. Suniso 3GS is compatible with Texaco WF 32 and
Fuchs KM. These oils may be used if an addition is required in the field. [5]
When a compressor is exchanged in the field it is possible that a major
portion of the oil from the replaced compressor may still be in the system. While this
may not affect the reliability of the replacement compressor, the extra oil will add to
rotor drag and increase power usage. To remove this excess oil an access valve has
been added to the lower shell of the compressor. The compressor should be run for
10 minutes, shut down and the access valve opened until oil is somewhere between
1/4 to 1/3 of the sight glass. This operation should be repeated at least twice to make
sure the proper oil level has been achieved. One disadvantage of POE is that it is far
more hygroscopic than mineral oil. Only brief exposure to ambient air is needed for
POE to absorb sufficient moisture to make it unacceptable for use in a refrigeration
system. Since POE holds moisture more readily than mineral oil it is more difficult to
remove it through the use of vacuum. Compressors supplied by Copeland contain oil
with a low moisture content, and this may rise during the system assembling process.
Therefore it is recommended that a properly sized filter-drier is installed in all POE
systems. [5]
Figure 2.3 : Absorption of moisture in ester oil in comparison to mineral oil in [ppm] by weight at 25°C and 50% relative humidity. h = hours. [5]
10
This will maintain the moisture level in the oil to less than 50 ppm. If oil is
charged into a system it is recommended to charge systems with POE containing no
more than 50 ppm moisture content. If the moisture content of the oil in a
refrigeration system reaches unacceptable high levels, corrosion and copper plating
may occur. The system should be evacuated down to 0.3 mbar or lower. If there is
uncertainty, as to the moisture content in the system, an oil sample should be taken
and tested for moisture. Sight glass/moisture indicators currently available can be
used with the HFC refrigerants and lubricants; however, the moisture indicator will
just show the moisture contents of the refrigerant. The actual moisture level of POE
would be higher than the sight glass specifies. This is a result of the high
hygroscopicity of the POE oil. Oil samples would have to be taken from the system
and analyzed to determine the actual moisture content of the lubricant. [5]
2.4.4 Accumulators
Due to the Copeland Scroll’s inherent ability to handle liquid refrigerant in
flooded start and defrost cycle operation, an accumulator is not be required for
durability in most systems, especially those systems designed with thermostatic
expansion valves. However, large volumes of liquid refrigerant which repeatedly
flood back to the compressor during normal off cycles or excessive liquid refrigerant
floodback during defrost or varying loads, no matter what the system charge is, can
dilute the oil. As a result, bearings are inadequately lubricated and wear may occur.
If an accumulator must be used, an oil return orifice size in the range 2 mm² is
recommended. A large-area protective screen no finer than 30 x 30 mesh (0.6 mm²
openings) is required to protect this small orifice from plugging with system debris.
Tests have shown that a small screen with a fine mesh can easily become plugged
causing oil starvation to the compressor bearings. [5]
11
Accumulators are a standard item in air to air heat pumps and are used even
when a thermostatic expansion valve is used to meter refrigerant in the heating mode.
During low ambient conditions the oil returning from the outdoor coil will be very
viscous and difficult to return through the accumulator if the expansion valve is
working properly by maintaining superheat. To prevent slow oil return it may be
possible to remove the accumulator from systems that use expansion valves in
heating. To determine if the accumulator can be removed a defrost test must be done
at an outdoor ambient of around 0 °C in a high humidity environment to ensure that
excessive liquid does not flood back to the compressor during reversing valve
operation, especially when coming out of defrost. Excessive flood back occurs when
the sump temperature drops below the safe operation line shown in Figure 2.4 for
more than 10 seconds. [5]
Figure 2.4 : Bottom shell temperature. [5]
2.4.5 Screens
The use of screens finer than 30 x 30 mesh (0,6 mm² openings) anywhere in
the system is not recommended. Field experience has shown that finer mesh screens
used to protect thermal expansion valves, capillary tubes, or accumulators can
become temporarily or permanently plugged with normal system debris and block
the flow of either oil or refrigerant to the compressor. Such blockage can result in
compressor failure. [5]
12
2.4.6 Crankcase Heaters
The crankcase heater must be mounted below the oil removal valve located
on the bottom shell. The crankcase heater must remain energized during compressor
off cycles. The initial start in the field is a very critical period for any compressor
because all load bearing surfaces are new and require a short break-in period to carry
high loads under adverse conditions. The crankcase heater must be turned on a
minimum of 12 hours prior to starting the compressor. This will prevent oil dilution
and bearing stress on initial start up. If it is not feasible to turn on the crankcase
heater 12 hours in advance of starting the compressor, then use one of the techniques
listed below to prevent possible flooded-start damage to the compressor: [5]
i. Direct a 500 watt heat lamp or other safe heat source (do not use torch) at
the lower shell of the compressor for approximately 30 minutes to boil off
any liquid refrigerant prior to starting; or
ii. Bump start the compressor by manually energizing the compressor
contactor for about one second. Wait five seconds and again manually
energize compressor for one second. Repeat this cycle several times until
the liquid in the shell has been boiled off and the compressor can be
safely started and run continuously.
Due to the Copeland Scroll’s inherent ability to handle liquid refrigerant in
flooded conditions, no crankcase heater is required when the system charge does not
exceed following values:
a) 7,7 kg for ZR 90 K3* ... ZR 19 M3*
b) 11,3 kg for ZR 250 KC*
c) 13,6 kg for ZR 310 KC*…ZR 380 KC*
A crankcase heater is needed to drive out excessive amounts of refrigerant
that have migrated into the shell during standstill periods and no accumulator is
piped to provide free liquid drainage during the off cycle as shown in Figure 2.5. For
correct mounting location of such a heater please see Figure 2.6. [5]
13
Figure 2.5 : Suction accumulator. [5]
Figure 2.6 : Crankcase heater location. [5]
2.4.7 Pumpdown
Recycling pumpdown for control of refrigerant migration may be used
instead of, or in conjunction with, a crankcase heater when the compressor is located
so that cold air blowing over the compressor makes the crankcase heater ineffective.
The Scroll compressor discharge check valve is designed for low leak back and will
allow the use of recycling pump down without the addition of an external check
valve. The low pressure control cut-in and cut-out settings have to be reviewed since
a relatively large volume of gas will re-expand from the high side of the compressor
into the low side on shut down. A one time pump down at the end of a run cycle is
not recommended since refrigerant can still migrate into the compressor after a long
shut down. If a one time pump down is used a crankcase heater must be installed. [5]
14
2.4.8 Minimum Run Time
There is no set answer to how often scroll compressors can be started and
stopped in an hour, since it is highly dependent on system configuration. There is no
minimum off time, because the scrolls start unloaded, even if the system has
unbalanced pressures. The most critical consideration is the minimum run time
required to return oil to the compressor after startup. This is easily determined since
these compressors are equipped with a sight glass. The minimum on time becomes
the time required for oil lost on compressor startup to return to the compressor sump
and restore a normal level in the sight glass. Cycling the compressor for a shorter
time than this, for instance to maintain very tight temperature control can result in
progressive loss of oil and damage to the compressor. [5]
2.4.9 Discharge Temperature Protection
A thermistor with a nominal response temperature of 140 °C is located in the
discharge port of the fixed scroll (Figure 2.7). Excessive discharge temperature will
cause the electronic protector module to trip. The discharge gas sensor is wired in
series with the motor thermistor chain. [5]
Figure 2.7 : Internal discharge temperature protection. [5]
15
2.5 Design Criteria Condensing Temperature
This is a key economic design decision. Lowering the design condensing
temperature lowers the energy consumption by the compressors. However, lowering
the design condensing temperature also increases the size and cost of the condenser,
raising installation costs. Thus, the decision is balance between initial construction
cost and operating costs. [6]
There are 3 design condensing temperatures typically used for ammonia
refrigeration systems. [6]
96.3ºF 185 psig (older standard design)
95ºF 180.7 psig (newer standard design)
90ºF 165.9 psig (enhanced design)
Table 2.1 : Design condensing temperature typically used. [6]
Using the older standard of 96.3ºF as a base, lowering the design condensing
temperature has the following effect on size, or base rating, of the condenser. [6]
96.3
95
90
0 0.2 0.4 0.6 0.8 1 1.2 1.4 1.6 1.8
Condenser size
Condensin
g tem
pera
ture
Chart 2.1 : How condensing temperature affects The size of the condenser. [6]
Thus, a 90ºF condenser is over 50% larger than a 96.3ºF condenser.
Condenser size, or capacity, is mostly achieved through a larger coil bundle – more
surface area of pipes. In general, a 90ºF condenser has 50% more tube area than a
96.3ºF condenser. [6]
2.5.1 Sizing Condenser
16
There are three factors influencing the sizing of a condenser: [6]
1) The total heat rejection required – the capacity of the system compressors.
2) The local climate conditions – the design wet bulb temperature
3) The design condensing temperature
The first two factors are a given and cannot be changed. The third is a design
decision between the owner and designer and the subject of this article. [6]
2.5.2 Total Heat Rejection
Total heat rejection is based on the total compressor capacity of the plant
including a factor for oil cooling and excluding any back-up machines. The equation
is: (BHP x 2545) + (TR x 12000) = Total Heat Rejection, BTU/hr [6]
2.5.3 Wet Bulb
Evaporative condensers work by evaporating water over the condenser’s tube
bundle –cooling the refrigerant gas inside. The temperature at which the water will
evaporate on any given day is called the wet bulb temperature. The wet bulb
temperature is a measure of the humidity in the air. If the humidity is high, the wet
bulb temperature is high. The dry bulb temperature, which is the temperature
measured by a thermometer, has significantly less effect on condenser performance.
Refrigeration system designers size condensers using the ASHRAE 1% wet bulb
temperature for a given location. In other words, 99% of the time the wet bulb
temperature will be below that value. Typical wet bulb values for the Northern
United States are between 72ºF and 80ºF. [6]
2.5.4 How Does a Larger Condenser Affect Energy Consumption
Consider a typical high stage compressor, operating at 20ºF suction and
discharging at various pressures. As the discharge pressure gets lower, the capacity
of the compressor increases, and the BHP/TR (energy input per ton refrigeration)
goes down. Therefore, in effect, it does more for less. The following two graphs
show the relationship between condensing pressure and compressor
performance/energy consumption for various head pressures. [6]
17
Graph 2.1 : RXF-101 Perfomance at various condensing pressures. [6]
Graph 2.2 : Compressor energy consumption vs condensing pressure. [6]
Clearly, the lower the condensing pressure, the lower the energy consumption
of the compressor. The difference between 95ºF (180.7 psig) and 90ºF (165.9 psig)
condensing is approximately 15% lower energy consumption. Thus, at peak
condensing conditions, the larger condenser saves 15% of the compressor energy
costs. However, in Northern climates, and only during daytime hours. Thus the non-
peak performance is also a significant factor. [6]
18
Note that Chart 2.2 shows a relatively linear relationship between condensing
pressure and energy consumption. The larger condenser will achieve consistently
lower head pressures throughout this period, due to its greater surface area. The 90ºF
condenser will typically have 15 psig lower condensing pressures than the 95ºF
condenser, maintaining 12% lower compressor energy cost during this time period as
well. [6]
2.6 Design Criteria Evaporators
In the evaporation process, concentration of a product is accomplished by
boiling out a solvent, generally water. The recovered end product should have an
optimum solids content consistent with desired product quality and operating
economics. It is a unit operation that is used extensively in processing foods,
chemicals, pharmaceuticals, fruit juices, dairy products, paper and pulp, and both
malt and grain beverages. Also it is a unit operation which, with the possible
exception of distillation, is the most energy intensive. [7]
2.6.1 Materials of Construction
The two parameters which control the selection of the material of
construction are corrosion and ease of cleaning. All evaporators for hygienic duties
must be capable of being frequently cleaned in place. In most cases, this means
rinsing the equipment with water, followed by washing with caustic and then acid
cleaning agents, and finally, a further rinsing with water. It is important, particularly
with dairy and meat products, that the evaporator is completely cleaned of all
deposits. The cleaning processes eliminate the use of carbon steel as the material of
construction. Most hygienic evaporators are manufactured in either 304 or 316
stainless steel. [7]
Corrosion is often a major problem with chemical duties and some hygienic
applications. A particular problem with evaporators is the range of concentration of
solids in the process fluid, since the corrosive component will be concentrated as it
passes through the evaporator. In some evaporators, the concentration range can be
as high as 50 to 1.
19
For example, waste water with a chloride content of 40ppm in the feed would
have 2000ppm in the product. While stainless steel would be acceptable for the
initial stages of evaporation, a more corrosion resistant material would be required
for the last one or two stages. [7]
Corrosion is also a major consideration in the selection of gasket materials.
This is particularly important with plate evaporators with elastomeric gaskets sealing
each plate. Many solvents such as chlorinated and aromatic compounds will severely
attack the gaskets. A less obvious form of attack is by nitric acid. This is important
since nitric acid can be present in some cleaning materials. While concentrations of
about 1% up to 140°F (60°C) can be accepted, it is best to eliminate nitric acid from
cleaning materials. Phosphoric and sulfamic acids are less aggressive to gaskets. [7]
Typical materials of construction for a number of evaporator applications are shown
below: [7]
Table 2.2 : Typical materials of construction. [7]
In some cases, the type of evaporator is controlled by the materials of
construction. For example a sulfuric acid evaporator, where the acid concentration
can reach 50%, would utilize graphite tubular heat exchangers and non-metallic
separators and piping. [7]
20
2.7 Effect of Evaporator Temperature
The effect of evaporator temperature on performance of the system is
obtained by keeping the condenser temperature (pressure) and compressor
displacement rate and clearance ratio fixed. To simplify the discussions, it is further
assumed that the refrigeration cycle is an SSS cycle. [8]
a) On Volumetric efficiency and refrigerant mass flow rate:
The volumetric of the compressor with clearance is given by:
For a given condensing temperature (or pressure), the pressure ratio rp
increases as the evaporator temperature (or evaporator pressure) decreases. Hence,
from the expression for clearance volumetric efficiency, it is obvious that the
volumetric efficiency decreases as evaporator temperature decreases. This is also
explained with the help of Graph 2.3, which shows the P-V diagram for different
evaporator pressures. As shown, as the evaporator pressure decreases, the volume of
refrigerant compressed decreases significantly, since the compressor displacement
remains same the clearance volumetric efficiency decreases as evaporator
temperature decreases. In fact, as explained in the earlier lecture, at a limiting
pressure ratio, the volumetric efficiency becomes zero. [8]
Graph 2.3 : P-V diagram for different evaporator pressures and a fixed condenser pressure. [8]
21
The mass flow rate of refrigerant m is given by:
As the evaporator temperature decreases the clearance volumetric efficiency
decreases and the specific volume of refrigerant at compressor inlet ve increases. As
a result of these two effects, the mass flow rate of refrigerant through the compressor
decreases rapidly as the evaporator temperature decreases as shown in Figure 2.8. [8]
Figure 2.8 : Effect of evaporator temperature on clearance volumetric efficiency and refrigerant mass flow rate. [8]
b) On refrigeration effect and refrigeration capacity:
A compressor alone cannot provide refrigeration capacity. By refrigeration
capacity of compressor what we mean is the capacity of a refrigeration system that
uses the compressor under discussion. Figure 12 shows the SSS cycle on P-h
diagram at different evaporator temperatures. It can be seen from the figure that the
refrigeration effect, qe (qe = h1-h4) increases marginally as the evaporator
temperature is increased. This is due to the shape of the saturation vapour curve on
P-h diagram. The effect of Te on refrigerant effect is also shown in Chart 2.2. [8]
22
The refrigeration capacity of the compressor Q is given by:
Chart 2.2 : Effect of evaporator temperature on refrigeration effect on P-h diagram. [8]
Since mass flow rate of refrigerant increases rapidly and refrigerant effect
also increases, though marginally with increase in evaporator temperature, the
refrigeration capacity increases sharply with increase in evaporator temperature as
shown in Chart 2.3. [8]
Chart 2.3 : Effect of evaporator temperature on refrigeration effect and refrigeration capacity. [8]
23
c) On work of compression and power requirement:
At a constant condenser temperature as evaporator temperature increases the
work of compression, Δh (= h-hc21) decreases as shown in Figure 12. This is due to
the divergent nature of isentropes in the superheated region. The work of
compression becomes zero when the evaporator temperature becomes equal to the
condenser temperature (T=Tec) as shown in Figure 14. [8]
The power input to the compressor is given by:
As discussed before, for a given clearance ratio and condenser temperature,
the volumetric efficiency and hence the mass flow rate becomes zero at a lower
limiting value of evaporator temperature (Te = Te,lim). Since the work of
compression becomes zero when the evaporator temperature equals the condenser
temperature, the power input to the compressor, which is a product of mass flow rate
and work of compression is zero at a low evaporator temperature (at which the mass
flow rate is zero). And the power input also becomes zero when evaporator
temperature equals condenser temperature (at which the work of compression
becomes zero). This implies that as evaporator temperature is increased from the
limiting value, the power curve increases from zero, reaches a peak and then
becomes zero as shown in Chart 2.4. [8]
Chart 2.4 : Effect of evaporator temperature on work of compression (Δhc) and power input to compressor (Wc). [8]
24
The variation of compressor power input with evaporator temperature has a
major practical significance. As a mentioned before, there is an evaporator
temperature at which the power reaches a maximum value. If the design evaporator
temperature of the refrigeration system is less than the evaporator temperature at
which the power is maximum, then the design power requirement is lower than the
peak power input. However, during the initial pull-down period, the initial
evaporator temperature may lie to the left of the power peak. [8]
Then as the system runs steadily the evaporator temperature reduces and the
power requirement passes through the peak point. If the motor is designed to suit the
design power input then the motor gets overloaded during every pull-down period as
the peak power is greater than the design power input. Selecting an oversized motor
to meet the power peak is not an energy efficient solution, as the motor will be
underutilized during the normal operation. [8]
One way of overcoming the problem is to throttle the suction gas during the
pull-down so that the refrigerant mass flow rate is reduced and the motor does not
pass through the power peak. In multi-cylinder compressors, some of the cylinders
can be unloaded during the pull-down so as to reduce the power requirement. [8]
d) On COP and volume flow rate per unit capacity:
The COP of the system is defined as:
As discussed before, as the evaporator temperature increases the refrigeration
effect, q increases marginally and the work of compression, Δhec reduces sharply.
As a result the COP of the system increases rapidly as the evaporator temperature
increases as shown in Figure 15. [8]
25
The volume flow rate per unit capacity, V is given by:
As evaporator temperature increases the specific volume of the refrigerant at
compressor inlet reduces rapidly and the refrigerant effect increases marginally. Due
to the combined effect of these two, the volume flow rate of refrigerant per unit
capacity reduces sharply with evaporator temperature as shown in Figure 2.9. This
implies that for a given refrigeration capacity, the required volumetric flow rate and
hence the size of the compressor becomes very large at very low evaporator
temperatures. [8]
Figure 2.9 : Effect of evaporator temperature on COP and volume flow rate per unit capacity (V)
2.8 R407C Characteristics
Compressors designed for operation with HFC refrigerants are factory
supplied with one of the approved oils and are suitably identified. They also can be
used with HCFC R22. Different from single component, azeotropic and near
azeotropic refrigerants, the zeotropic R407* blends are characterized by its relatively
large temperature glide. Therefore, certain influences on system design, service and
maintenance need to be considered. The composition of liquid and vapour of a
zeotropic blend is different when both liquid and vapour are present. Therefore it is
important that charging is carried out in the liquid phase only. [5]
26
If a leak occurs there could be a change in composition of the refrigerant
remaining in the system. Large changes in composition can result in decreasing
superheat at the expansion valve leading to liquid returning to the compressor. [5]
Another characteristic of significant composition change can be the
appearance of sudden “hunting” of the expansion valve. Tests by R 407C
manufacturers have shown that recharging with the original refrigerant can typically
restore satisfactory system operation simply. If it does not result in satisfactory
system operation, it is recommended to analyse the refrigerant composition in the
system prior to replacing the entire system charge. Working with zeotropic blends
requires an understanding of the effect of temperature glide shown in Figure 2.10 [5]
Figure 2.10 : Temperature Glide. [5]
Evaporation at constant pressure takes place with the temperature of the
refrigerant increasing from tex to to2 and condensation takes place with a falling
temperature from tc1 to tc2. Thus the terms “evaporating temperature” and
“condensing temperature” must be redefined. High glide causes considerable
temperature differences within the heat exchangers. Similarly, clear definitions for
“superheating” and “subcooling” are needed. Such new definitions are also necessary
in order to ensure accurate comparisons of performance against other azeotropic or
near azeotropic refrigerants.
27
Evaporating temperature is defined as the mean temperature (tom) between
the dew point temperature (to2) resulting from constant suction pressure (pv1) and
the temperature at which the refrigerant enters the evaporator (tex). Condensing
temperature is defined as the mean temperature (tcm) between the dew-point
temperature (tc1) resulting from constant discharge pressure (pv2) and the boiling-
point temperature (tc2) of the refrigerant. [5]
The superheating of the suction gas is then calculated as the difference in
temperature at the compressor inlet (tv1) and the dew-point temperature (to2) of the
refrigerant at suction pressure (pv1). It is essential that these definitions be followed
when adjusting the superheat setting of expansion valves. Liquid subcooling is
calculated as the difference between actual liquid temperature and the bubble point
temperature (tc2) of the refrigerant at discharge pressure (pv2). [5]
The definitions presented here are based on those specified by the Air-
Conditioning and Refrigeration Institute (ARI) as part of their Alternative
Refrigerants Evaluation Program (AREP). These definitions are used to provide
performance comparison with R 22. System designers normally use data based on the
dew point temperatures as specified in EN 12900. With the Copeland Selection
Software version 4 and above performance data sheets for both mid point and dew
point definitions are available. [5]
It is essential that the glide of R407 refrigerant blends are given careful
consideration when adjusting pressure controls. Furthermore, it is crucial to consider
the effect of pressure losses on glide when sizing heat exchangers. Pressure losses
effectively increase glide significantly in the system. Failure to consider this in heat
energy balance calculations will likely result in undersizing heat exchangers and
other system components. These effects are especially apparent when operating a
system near the limits of its application range. [5]
28
2.9 Malaysia Standard ( MS1525 )
2.9.1 ACMV System Equipment, Electrically Operated, Cooling Mode
These requirements apply to but are not limited to unitary (central) cooling
equipment (air-cooled, water-cooled and evaporatively-cooled) packaged terminal
airconditioners. [9]
ItemAir-cooled
Water-cooled
(water-source)
Dry-bulb Wet-bulb Inlet Outlet
Room air entering
equipment (oC)27 19 - -
Condenser ambient
(air-cooled) (oC)35 24 - -
Refrigerant-water
heat exchanger (oC)- - 29.4 35
NOTES:
1. Data in this table apply to the following types of equipment:
a. Central Air Conditioners Air Evaporatively and Water Cooled, ARI Std 210/240
b. Commercial/Industrial Unitary Air- Conditioning Equipment, ARI Std 340/360
2. Standard Ratings are also based on other standard rating conditions such as but not
limited to electrical conditions; cooling coil air quantity; requirements for separated
(split) assemblies; and minimum external static conditioned-air flow resistance, as
provided in the applicable standards.
Table 2.3 : Standard rating temperatures – cooling. [9]
29
2.9.2 ACMV System Equipment/Component – Heat-Operated (absorption), Cooling Mode
In the heat-operated (absorption) system equipment/components, pumps
included in the package for circulating refrigerant and absorber fluids in the
refrigeration cycle are included in determining the COP of the
equipment/components. [9]
For heat-operated cooling equipment /component, the heat energy input
should be limited to: [9]
a) solar energy;
b) recovered energy from other processes, and
c) natural gas or others (non electric).
Standard rating conditionsHeat source
Direct fired(Gas, oil)
Indirect fired(Steam, hot water)
Airconditioner
Entering conditioned airEntering condenser air
Units Temperatures Temperatures
⁰C
⁰C26.7 DB, 19.4 WB35.0 DB, 23.9 WB
--
Water chillers
Leaving chilled waterFouling factor
Entering chilled waterEntering condenser
Fouling factorLeaving condenser water
Condenser water flow rate
⁰Cm2 K/W
⁰C
⁰Cm2 K/W
⁰Cl/min
7.2-
Per mfg. Spec23.9
-35.0
6.70.00009
12.229.4
0.00018-
Per mfg spec
1. Per ANSI Standard Z21.40.1-1994 and Addenda for Gas-fired absorption summer air-conditioning appliances.2. Per ARI Standard 560-92 for Absorption water-chilling packages.
Table 2.4 : Standard rating conditions – cooling, heat-operated. [9]
30
CHAPTER 3
METHODOLOGY
To design and simulation of air cooled conditioning, there is varies method
can be choose to done this project. This design and simulation is use the software :
a) Coolpack and solkane
b) Copeland Selection Software 6.6
c) Solvay Flour
d) Autocad 2010
3.1 Select and Design The Compressor
To select the compressor, the software use is Copeland Selection Software
6.6. The data use for design and select the compressor is :
Refrigerant : dew point R407C
Requires capacity : 1.00 Kw
Evaporating temperature : 5oC
Condensing temperature : 45 oC
Superheat : 10 oK
Subcool : 0 oK
1) Fill the data in the software
Figure 3.1 : Fill the data in the software
31
2) Select type of compressor
Figure 3.2 : Select type of compressor
3) Export the data to Microsoft Excel document
Figure 3.3 : Export the data to Microsoft Excel
4) Create a graph and find the operation capacity of selected compressor
5) Create a graph and find the power input of selected compressor
6) Find the required data for compressor
The selected compressor is model : ZR22K3E-TFD from brand of Copeland
32
3.2 System Cycle and Air Properties
3.2.1 Air Properties
1) Find the common properties of air.
2) Create the graph for density (kg/m³)
3) From the calculation, calculate the value for density depend on temperature
ambient 32 C.⁰
4) Create the graph for specific heat (kJ/kg.K)
5) From the calculation, calculate the value for specific heat depend on temperature
ambient 32 C.⁰
3.2.2 System Cycle
1) Create a four (4) main component cycle for the system.
2) Create a mollier chart for the system cycle.
3) Then create a table and find the value for :
Tsat (⁰C)
Pressure (bar)
Enthalpy (kj/kg)
Entropy (kj/kg.K)
Specific volume (m³/kg)
3.3 Surface Coefficient (KS) and Capacity of Condenser and Evaporator
1) Create the condenser cycle.
Trefrigerant in = 87.0189 C⁰
Trefrigerant out = 45 C ⁰
Tair in = 32 C ⁰
2) Fill the data for enthalpy for condenser then calculate the Tair out.
3) Calculate the LMTD for Qc superheated and Qc condensation.
4) Calculate the surface coefficient (KS) and the total capacity required for the
condenser.
5) Create the evaporator cycle.
33
Trefrigerant in = 0.86 C⁰
Trefrigerant out = 15 C⁰
Tair in = 25 C ⁰
6) Fill the data for enthalpy for evaporator then calculate the Tair out.
7) Calculate the LMTD for Qe superheated and Qe evaporation.
8) Calculate the surface coefficient (KS) and the total capacity required for the
evaporator.
3.4 Design the Condenser and Evaporator
The step and formula used to design and estimate the sizing of both
component is using the same method except the data is different.
3.4.1 Data
a) Condenser
Oudoor Air = 32 ⁰C to
4
6 ⁰C
Air flow rate = 2000 CFM
Refrigerant in = 87.01889 ⁰C
Refrigerant out = 45 ⁰C
Air face velocity not exceed = 1000 FPM
b) Evaporator
Indoor Air =
11.00
5 ⁰C to 25 ⁰C
Air flow rate = 585 CFM
Refrigerant in =
0.861
5 ⁰C
Refrigerant out = 5 ⁰C
Air face velocity not
exceed=
550 FPM
34
3.4.2 The Calculation
1) Compute the overall heat-transfer coefficient U, refrigerant side.
2) Then compute the overall heat-transfer coefficient U, air side.
3) Then compute the fin efficiency and the surface effevtiveness.
4) Determine the ratio of the refrigerant-side to air-side heat transfer areas.
5) Calculate the overall coefficient, U.
6) Computed the fluid capacity rate.
7) Calculate total volume of the heat exchanger.
8) Calculate the face area.
9) Then determine the depth of coil.
10) Determine the number of rows of tubes.
11) Compute the ratio, air-side.
12) Then find the mean density.
13) Calculate the lost head on the air side of the exchanger.
14) Determine the flow cross-sectional area for the refrigerant.
15) Then determine number of tubes per row.
3.5 Design Capillary Tube
To design the capillary tube, the calculation is used the Solvay Flour.
3.5.1 Data
Saturated Liquid Temp. 45 ºC
Evaporating Temp. 5 ºC
1.2 mm
ID 0.0012 m
Radius 0.0006 m
= 3.1415927
Area
(A)
0.00000113 m²
35
Mass Flow rate 0.0321 kg/s
Table 3.1 : Data for capillary tube
3.5.2 The calculation
1) Create the table for the data range 45 ºC to 5 ºC.
2) Find all the pressure for each temperature.
3) Then calculate the fluid velocity (νf) and vapour velocity (νg).
4) Then calculate the fluid enthalpy (hf) and vapour enthalpy (hg).
5) Then calculate the fluid viscosity (µf) and vapour viscosity (µg).
6) After that calculate the mass flow rate divide by area (W/A).
7) Then find the system velocity.
8) Compute the value for Reynold’s Number and f .
9) By using the formula, then calculate the increment length to find the cumulative
length.
36
CHAPTER 4
SYSTEM DESIGN
4.1 The Compressor Design
4.1.1 Data
Software = Copeland Selection Software Version 6.6 / 39463 (01/08)
Refrigerant = R407C
Power Supply = 380/420V - 3~ - 50Hz
Evaporating Temperature = 5 °C
Condensing Temperature = 45 °C
Suction Superheat = 10 K
Liquid subcooling = 0 K
4.1.2 Determine the Capacity
-20 -15 -10 -5 0 5 7 10 12.5 1530 1.88 2.39 3.02 3.77 4.65 5.66 6.11 6.81 7.43 8.0835 1.74 2.24 2.85 3.58 4.45 5.43 5.86 6.55 7.15 7.7940 1.6 2.08 2.67 3.38 4.21 5.16 5.58 6.25 6.83 7.4545 1.91 2.47 3.15 3.95 4.87 5.27 5.91 6.47 7.07
Capacity kW 50 2.28 2.91 3.67 4.54 4.92 5.53 6.07 6.6555 2.67 3.37 4.19 4.55 5.13 5.64 6.1860 3.06 3.82 4.16 4.7 5.18 5.6965 2.74 3.44 3.75 4.24 4.69 5.1667 3.28 3.58 4.06 4.49 4.94
Table 4.1 : Data of the capacity
Graph 4.1 : Temperature vs capacity
37
30 35 40 45 50 55 60 65 67
ax³
0.000003
0.000003
0.000004
0.000000
0.000003
-0.000005
-0.000007
0.000015
-0.000026
bx² 0.0026 0.0025 0.0025 0.0024 0.0024 0.0024 0.0025 0.0018 0.0027
c x 0.1892 0.1845 0.1783 0.1719 0.1623 0.1521 0.1402 0.1304 0.1195
d 4.6533 4.4455 4.2103 3.9498 3.6668 3.3694 3.0599 2.7401 2.6175
Table 4.2 : Data for temperature vs capacity
Graph 4.2 : Evaporating temperature vs capacity
a b c d x = Tc 45 °C-9E-10 1.69E-08 -1.8E-07 6.12E-06 5.02E-06
1.229E-07 2.19E-06 2.51E-06 0.00124 0.00243 2 35.3713E-06 8.25E-05 0.000233 0.019905 0.171209
7.98702E-05 0.001604 0.203466 5.006261 3.949038Te 5 °C
QѲcomp 4.86647 Kw
4.1.3 Determine the Power Input
-20 -15 -10 -5 0 5 7 10 12.5 1530 0.95 0.94 0.94 0.94 0.93 0.92 0.92 0.91 0.9 0.8835 1.07 1.07 1.07 1.06 1.06 1.05 1.04 1.03 1.01 140 1.21 1.21 1.21 1.21 1.2 1.19 1.18 1.16 1.15 1.1345 1.37 1.37 1.37 1.36 1.35 1.34 1.32 1.3 1.28
Power Input kW 50 1.55 1.55 1.54 1.53 1.52 1.5 1.48 1.4555 1.76 1.75 1.73 1.72 1.7 1.67 1.6560 1.98 1.96 1.95 1.92 1.9 1.8765 2.24 2.22 2.2 2.18 2.15 2.1267 2.33 2.31 2.29 2.26 2.23
Table 4.3 : Data for the power input
38
Graph 4.3 : Temperature vs capacity
30 35 40 45 50 55 60 65 67
a x³ -0.000004-
0.000003 -0.000003-
0.000005 -0.000009-
0.000003 0.000007 0.000001 -0.000043
b x² 0.0001 0.0001 0.0001 0.0002 0.0002 0.0002 0.0005 0.0004 0.0010
c x 0.0012 0.0017 0.0020 0.0020 0.0016 0.0028 0.0016 0.0027 0.0157
d 0.9325 1.0591 1.2015 1.3626 1.5427 1.7507 1.9800 2.2402 2.3886Table 4.4 : Data for evaporating temperature vs power input
Graph 4.4 : Evaporating temperature vs capacity
a b c d x = Tc 45 °C-5.1E-09 4.85E-08 1.5E-06 7.11E-06 -3.394E-077.1E-07 6.2311E-06 0.000204 0.00054 0.00015514 2 3
3.16E-050.00026567
4 0.008975 0.038882 0.001851240.000449 0.00360179 0.126088 0.057806 1.36174004
Te 5 °C
Wabs.comp 1.374832276 Kw
39
4.1.4 Compressor cycle
P
h
5⁰C
45 ⁰C
2is
1
4
45 ⁰C
15⁰C
SubcoolSuperheat
Chart 4.1 : Compressor cycle
5.34 m³/hDisplacement @ 50 hz
h
2is
1
15⁰CSuperheat
ref R407CTe ( ⁰C ) 5ηv 0.981207187LP ( pa ) 547098.2899HP ( pa ) 1967321.153h1 ( kj/kg ) 411.3270897h4 ( kj/kg ) 267.844709V1 ( m³/kg ) 0.04291252Vswept ( m³/h ) 5.34Vsuct ( m³/h ) 5.239646381Vsuct ( m³/s ) 0.001455457m ( kg/s ) 0.033916846Qѳcomp ( kW ) 4.866469806Wabs.comp ( kW ) 1.374832276h2is ( kj/kg ) 442.2709295ηeff 0.763378535T2is ( ⁰C ) 62.12789229S1 ( kj/kg.K ) 1.768467784
Table 4.5 : Data of the compressor cycle
40
4.1.5 Compressor Select
Type : Copeland Scroll – Compressor
Model : ZR22K3E-TFD
1) Perfomance at specified operating point ZR22K3E-TFD Data at 50 Hz
Table 4.6 :Perfomance at specified operating point ZR22K3E-TFD Data at 50 Hz
2) Compressor mechanical and physical data
Table 4.7 : Compressor mechanical and physical data
3) Compressor electrical data (380/420V - 3~ - 50Hz)
Table 4.8 : Compressor electrical data (380/420V - 3~ - 50Hz)
41
4.2 System Cycle and Air Properties
4.2.1 Determine the Density and Specific Heat of Air
Common properties for air are indicated the table below :
Temperature
Density
Specific heat capacity
Thermal conductivity
Kinematic viscosity
Expansion coefficient
Prandtl's number
- t - - ρ - - cp - - l - - ν - - b - - Pr -
(oC) (kg/m3)(kJ/kg.K) (W/m.K) x 10-6 x 10-3
(m2/s) (1/K) -150 2.793 1.026 0.0116 3.08 8.21 0.76-100 1.98 1.009 0.016 5.95 5.82 0.74-50 1.534 1.005 0.0204 9.55 4.51 0.7250 1.293 1.005 0.0243 13.3 3.67 0.71520 1.205 1.005 0.0257 15.11 3.43 0.71340 1.127 1.005 0.0271 16.97 3.2 0.71160 1.067 1.009 0.0285 18.9 3 0.70980 1 1.009 0.0299 20.94 2.83 0.708100 0.946 1.009 0.0314 23.06 2.68 0.703120 0.898 1.013 0.0328 25.23 2.55 0.7140 0.854 1.013 0.0343 27.55 2.43 0.695160 0.815 1.017 0.0358 29.85 2.32 0.69180 0.779 1.022 0.0372 32.29 2.21 0.69200 0.746 1.026 0.0386 34.63 2.11 0.685250 0.675 1.034 0.0421 41.17 1.91 0.68300 0.616 1.047 0.0454 47.85 1.75 0.68350 0.566 1.055 0.0485 55.05 1.61 0.68400 0.524 1.068 0.0515 62.53 1.49 0.68
Table 4.9 : Common properties for air
x = Tambient 32 ( ⁰C )
42
Graph 4.5 : Temperature vs density
Density = 1.140904 kg/m3
Graph 4.6 : Temperature vs specific heat
Specific Heat
= 1.004714 kJ/kg.K
43
4.2.2 System Cycle
The air-conditioning system component :
CONDENSOR
EVAPORATOR
TXV COMPRESSOR
3 2
14
5 6
1
23
4,5 5b
2is
5a
P
h
Condenser
TXV
Evaporator
Compressor
Superheat
Superheat
3a3b
Figure 4.1 : Air conditioning system component
The system cycle :
1
23
4,5 5b
2is
5a
P
h
Condenser
TXV
Evaporator
Compressor
Superheat
Superheat
3a3b
Chart 4.2 : System cycle
44
Tc 45 ⁰C
Te 5 ⁰C
Ref. R407C
Superhea
t 10 K
Subcool 0 K
Table 4.10 : Data for the system cycle
Tsat ( ⁰C) P (bar) T (⁰C) H (kj/kg) S (kj/kg.K) V (m³/kg)
1 5 5.39944031 15 420.7456446 1.801735842 0.045338828
2is 45 19.4159502 71.29131 453.5751144 1.801735842
2 45 19.4159502 87.01889 472.0087329
3 45 19.4159502 45 267.844709
4 5 5.39944031 0.861535 267.844709
5 5 5.39944031 0.861535 267.844709
5a -1.144306 5.39944031 -1.14431 198.301363
5b 5.0000031 5.39944031 5.000003 411.3270926
Table 4.11 : Table for the system cycle
3a = 456.7923 h
3b
= 0.000963 V
ŋis = 0.8-(0.004*(Ţ-5)*2)-0.5/(Ţ-0.3) = 0.640411471
Ţ = pH/pL = 3.595919032
Interpolate
5a 4 5b
198.3014
267.8447
1 411.327093
-1.14431 x 5.00000305
45
x = (271.1996-198.3014)÷(411.3271-198.3014)
= (x+1.14431)÷(5.000003+1.14431)
= 0.32645515
= 2.00584139
x = 0.86153518
4.3 Condenser and Evaporator Capacity
4.3.1 Data
Qѳcomp ( kW ) 4.866469806
Q=m*ΔH
Te 5 ⁰C
Tc 45 ⁰C
Ref. R407C
LP 5.399440315 bar
HP 19.41595019 bar
H1 411.3270897 Kj/kg
H4 267.844709 Kj/kg
m 0.033916846 kg/s
V1 (m3/kg) 0.042913
Vswept ( m³/h ) 5.34
Vsuct ( m³/h ) 5.239646
Vsuct ( m³/s ) 0.001455
Table 4.12 : Data for calculate condenser and evaporator capacity
46
4.3.2 The Condenser
Condenser
Superheat
SuperheatEvaporator
45 ⁰C 45 ⁰C
87.0189 ⁰C
32 ⁰C
0.86⁰C15⁰C
25 ⁰CT3
T4
T1T2
0.86⁰C
P
P
h
h
Chart 4.3 : Condenser system cycle
Tambient 32 oC
Qcondensation = 6.07 Qc superheated= 0.49
tliquid = t4 45 tvapour = t3a 45 tenter cond = t2 87.02
hliquid,45ºC= h4 267.84 hvapour,45ºC= h3a 456.79 henter cond = h2 472.01
t2 = 46 t1 = 39 tair in = 32.0
DT2 = 1.00 DT3 = 6.00 DT4 = 55.02
LMTDcond = 2.79 LMTDsup = 22.12
KScond = 2.174 KSsuperheated= 0.022
Table 4.13 : Table for the condenser capacity
Condenser
Vair = 3000.00 m3/h
Density air = 1.141 kg/m3
ṁair = 0.9508 kg/s
Cp air = 1.0044 kJ/kg K
Qtotal cond = 6.55 kW
KS = 2.196 kW/K
47
4.3.3 The Evaporator
SuperheatEvaporator
0.86⁰C15⁰C
25 ⁰CT3
T4
0.86⁰C
P
h
Chart 4.4 : Evaporator system cycle
Troom 25 oC
Qevaporation = 4.61 Qc superheated = 0.30
tenter evap = t5 0.86 tvapour5ºC = t5b 5.00 texit evap = t1 15.00
henter evap = h5 267.84 hvapour,5ºC=h5b 411.33 hexit evap = h1 420.75
tair in = 25.0 t3 = 18.0 t4 = 11.0
DT1 = 24.14 DT2 = 13.00 DT3 = 4.00
LMTDevap = 18.00 LMTDsup = 7.63
Ksevap = 0.256 KS superheated = 0.040
Table 4.14 : Data for the evaporator capacity
Evaporator
Vair = 3000.00 m3/h
Density air = 1.141 kg/m3
ṁair = 0.9508 kg/s
Cp air = 1.0047 kJ/kg K
Qtotal cond = 4.91 kW
KS = 0.296 kW/K
48
4.4 Sizing the Condenser
4.4.1 Data
Oudoor Air = 32 ⁰C to
4
6 ⁰C
Air flow rate = 2000 CFM
Refrigerant in = 87.01889 ⁰C
Refrigerant out = 45 ⁰C
Air face velocity not exceed = 1000 FPM
4.4.2 Calculation and Design
1. Compute the overall heat-transfer coefficient U, refrigerant side.
V = 0.000091446 m3/s
V = 1.164916855 m/s
m = 0.094931265 kg/s
ρ = 1037.586844 kg/m3
V1 = 0.00096328616 m3/kg
Dinside = 0.01 m
Rinside = 0.005 m
= 0.000117884 kg/m.s
A = 0.0000785398 m2
Cp = 1.705911601 J/kg.k
K = 0.0754295 w/m.k
ReD= ρ V Dμ
=102533
Pr= μC pK
=9.59784
49
hi=0.023KD
(Re D)0.8(Pr )0.3=3488.286Btu
ft2. hr .℃=19807.4
W
m2 . K
2. Compute the overall heat-transfer coefficient U, air side.
L/D = 60
A face velocity = 900 ft/m
Gfr=Pfr V fr=3900.8lbm
hr . ft2=5.29026
kg
m2 . s
σ = 0.555
GC=Gfr
σ=7028.46
lbmhr . ft2 =9.5320001
kgm2 . s
Doutside = 0.01715 m
μ = 0.044 lb/ft.s = 0.06548 kg/m.s
ReD=GC D
μ=8987.87
D = 0.01715 m = 0.05627 ft
Dh = 0.000333248 m
Xb = 0.0275082 m
Xa = 0.03175 m
π = 3.141592654
AA t
=4 Xb Xa
π Dh D=8.99904
JP=(Re D)−0.4 ( AA t
)−0.15
=0.018854
50
Chart 4.5 : Heat-transfer correlation for smooth plate-fin-tube coils. [12]
j-factor = 0.006
ho=( j−factor ) (GC ) (0.24 ) (0.71 )−2/3=12.71698Btu
hr . ft2 . F=72.210303
W
m2 K
3. To compute the fin efficiency and the surface effevtiveness.
Dim1=Xa
2
L=0.0159 m
Dim2=(( Xa
2)
2)+( Xb)2
1 /2
¿ ¿2
M=0.01588 m
φ= Mr
=1.851913
β= LM
=0.999676
ℜr
=(1.27 ) (φ )¿
51
ln (ℜr
)=0.676666643
∅=(ℜr −1)(1+0.35 ln (ℜr ))=1.1964
y = 0.0005 ft
k = 100 Btu.ft/ft2.hr.F
m=¿
r = 0.008575 m = 0.02813 ft
tanh ( m x r x ∅ ) = 0.640565651
Fin efficiency =
η=tanh (m×r ×∅ )
m× r×∅=0.843813
A f
A=0.919
Surface effectiveness =
ηso=1−A f
A(1−η )=0.856464
4. Determine the ratio of the refrigerant-side to air-side heat transfer areas.
⍺ = 100 ft1
Xa = 0.104166667 ft
Xb = 0.09025 ft
Dinside = 0.032808399
A i
Ao
=π D i
Xa Xb α=0.109637
52
5. Calculate the overall coefficient, U.
1U0
= 1ho ηso
+ 1
h i(A i
Ao
)=10.59004
Btu
hr . ft2. F=60.13301
W
m2. K
6. Computed the fluid capacity rate.
p = 0.07223697
Q = 120000 ft3/s
Q=p Q=8668.44lbhr
=1.092223kgs
Cair=0.24 m=2080.425Btu
hr . F
air = air
ref = refrigerant
Tao = 46 ⁰C = 114.8 ⁰F
Tai = 32 ⁰C = 89.6 ⁰F
Tri = 87.0188855 ⁰C = 188.634 ⁰F
Tao = 45 = 113 ⁰F
C ref=Cair(T ao−T ai
Tri−T ro)=693.1632
Btuhr . F
Cmin
Cmax
=0.3332
Tco = 46 ⁰C
Tci = 32 ⁰C
Thi = 87.0188855 ⁰C
ε=T co−T ci
T hi−T ci
=0.254458
53
Chart 4.6 : Effectiveness for counter-flow exchanger. [12]
NTU = 0.35
Ao=NTU (Cmin)
Uo
=22.90899 ft2
7. Calculate total volume of the heat exchanger.
V=Ao
α=0.22909 ft3
8. Calculate the face area.
A fr=QV fr
=2.22222 ft2=0.20645 m2
9. Determine the depth of coil.
L= VA fr
=0.10309 ft=0.062844 m
10. Determine the number of rows of tubes.
N r=LXb
=2.284553
So the number of rows will then be 4 because N must be integer and a
multiple of two for flow arrangement.
54
11. Compute the ratio, air-side.
AAC
= αVσ A fr
=18.5749
12. Find the mean density.
P = 2116.8
Tci = 549.27 Rankine
Tco = 574.47 Rankine
R = 53.35
Pm=P
2 R ( 1Tci
+1
Tco)=0.070653
lb
ft3 =1.131713kg
m3
13. Calculate the lost head on the air side of the exchanger.
D¿
D=
( AA t
)
1+(Xa−D)
s
=5.305619
D* = 0.090991373 m
¿ = 0.102703632
¿ = 1.517693322
(Xa−D
4 (s− y))−0.4
= 0.466203452
(Xa
D¿−1)−0.5
= 1.08381619
FP=( Re D )−0.25( DD¿ )
0.25( Xa−D4 (s− y))
−0.4
( Xa
D¿−1)−0.5
=0.0787591
55
Chart 4.7 : Correlation of friction data for smooth plate-fin-coils. [12]
f = 0.013
Gc = 9.532000148 kg/m2.s = 7028.46 lbm/hr.ft2
gc = 1 kg.m/N.s2 = 32.17 lbm.ft/lbf.s2
ƿ1 = 0.065243716 lb/ft3 = 1.04507 kg/m3
ƿ2 = 0.07606144 lb/ft3 = 1.21835 kg/m3
σ = 0.555
Tho = 572.67 Rankine
Thi = 648.3039939 Rankine
¿¿ = 0.90802
(p1
p2
−1) = 0.1658
(1+σ 2) = 1.30803
( fAAC
p1
pm
) = 0.26149
56
∆ Po=(GC)2
2 gC p12 [ (1+σ 2 )( p1
p2
−1)+( fA
AC
p1
pm
)]
¿0.4344lb
ft2
or
¿20.798 Pa
Also,
∆ Po=0.007 ft w .g
14. The flow cross-sectional area for the refrigerant.
Ch = 2080.424748 Btu/hr.F
V = 1.164916855 m/s = 3.82191 ft/s
ƿ = 1037.586844 kg/m3 = 69.0482 lb/ft3
Cp = 1.705911601 kJ/kg.K = 0.40754 Btu/lb.F
A=Ch
V pCp
=0.00537 ft2=0.00049920 m2
15. Determine number of tubes per row.
Di = 0.01 m
N= 4 A
π Di2=6.35601
Since N must be integer, 8 tubes are required.
To adapt to the flow arrangement, a coil that is 16 tubes high must be used.
H=16 Xa=0.508 m
W =A fr
H=0.4064 m
The shape of the coil, height of 0.508 m and width of 0.4064 m, may be
unacceptable.
57
Lw=2 (no . of rows ) (W )=2.43838058 m=7.99993628 ft
Chart 4.8 : Friction factors for pipe flow. [11]
moody friction = 0.024
D = 0.01 m = 0.03281 ft
V = 1.164916855 m.s = 3.82191 ft/s
g = 9.81 m/s2 = 32.1639 ft/s2
Lf w=moody friction( Lw
D )( V 2
2 g )+(no . of returnbends )( V 2
2 g ) ¿4.50783 ft w . g
Use 2-row coil, and the coil will then have 8 tubes per row.
H=8 Xa=0.381 m
W =A f r
H=0.541862m
Lw=2 (no . of rows ) (W )=4.3348988 m=14.2221 ft
58
Lf w=moody friction( Lw
D )( V 2
2g )+(no .of returnbends )( V 2
2g ) ¿4.633092 ft w . g
4.4.3 Drawing of Condenser
1) Isometric View
Figure 4.2 : Isometric view of condenser
2) Plant View
Figure 4.3 :Plant view of condenser
59
3) Side View
Figure 4.4 :Side view of condenser
4) Front View
Figure 4.5 : Front view of condenser
60
4.5 Sizing the Evaporator
4.5.1 Data
Indoor Air =
11.00
5 ⁰C to 25 ⁰C
Air flow rate = 585 CFM
Refrigerant in =
0.861
5 ⁰C
Refrigerant out = 5 ⁰C
Air face velocity not
exceed=
550 FPM
4.5.2 Calculation and Design
1. Compute the overall heat-transfer coefficient U, refrigerant side.
V = 0.001455457 m3/s
V = 18.53145821 m/s
m = 0.033916845 kg/s
ρ = 23.3032221 kg/m3
V1 = 0.04291252068 m3/kg
Dinside = 0.01 m
Rinside = 0.005 m
= 0.0000113048 kg/m.s
A = 0.0000785398 m2
Cp = 0.966744498 J/kg.k
K = 0.013006608 w/m.k
ReD= ρ V Dμ
=382001
Pr= μC pK
=3.0249
61
hi=0.023KD
(Re D)0.8(Pr )0.3=1218.307Btu
ft2. hr .℃=6917.86
W
m2 . K
2. Compute the overall heat-transfer coefficient U, air side.
L/D = 60
A face velocity = 500 ft/m
Gfr=Pfr V fr=2217.99lbm
hr . ft2=3.008036
kg
m2 . s
σ = 0.555
GC=Gfr
σ=3996.38
lbmhr . ft2 =5.419885
kgm2 . s
Doutside = 0.01715 m
μ = 0.044 lb/ft.s = 0.06548 kg/m.s
ReD=GC D
μ=5110.49
D = 0.01715 m = 0.05627 ft
Dh = 0.000333248 m
Xb = 0.0275082 m
Xa = 0.03175 m
π = 3.141592654
AA t
=4 Xb Xa
π Dh D=8.99904
JP=(Re D)−0.4 ( AA t
)−0.15
=0.02363
62
Chart 4.9 : Heat-transfer correlation for smooth plate-fin-tube coils. [12]
j-factor = 0.0075
ho=( j−factor ) (GC ) (0.24 ) (0.71 )−2/3=9.038575Btu
hr . ft2 . F=51.32338
W
m2 K
3. Compute the fin efficiency and the surface effevtiveness.
Dim1=Xa
2
L=0.0159 m
Dim2=(( Xa
2)
2)+( Xb)2
1 /2
¿ ¿2
M=0.01588 m
φ= Mr
=1.851913
β= LM
=0.999676
63
ℜr
=(1.27 ) (φ )¿
ln (ℜr
)=0.676666643
∅=(ℜr −1)(1+0.35 ln (ℜr ))=1.1964
y = 0.0005 ft
k = 100 Btu.ft/ft2.hr.F
m=¿
r = 0.008575 m = 0.02813 ft
tanh ( m x r x ∅ ) = 0.5648951
Fin efficiency =
η=tanh (m×r ×∅ )
m× r×∅=0.88
A f
A=0.919
Surface effectiveness =
ηso=1−A f
A(1−η )=0.892162
4. Determine the ratio of the refrigerant-side to air-side heat transfer areas.
⍺ = 170 ft1
Xa = 0.104166667 ft
Xb = 0.09025 ft
Dinside = 0.032808399
64
A i
Ao
=π D i
Xa Xb α=0.064493
\
5. Calculate the overall coefficient, U.
1U 0
= 1ho ηso
+ 1
h i(A i
Ao
)=7.313307
Btu
hr . ft 2 . F=41.526857
W
m2 . K
6. Computed the fluid capacity rate.
p = 0.073933
Q = 35100 ft3/s
Q=p Q=2595lbhr
=0.32697593kgs
Cair=0.24 m=622.8112Btu
hr . F
air = air
ref = refrigerant
Tao = 25 ⁰C = 77 ⁰F
Tai = 11.004772 ⁰C = 51.809 ⁰F
Tri = 0.8615352 ⁰C = 33.551 ⁰F
Tao = 5.0000031 = 41 ⁰F
C ref=Cair(T ao−T ai
Tri−T ro)=2106.186
Btuhr . F
Cmin
Cmax
=0.2957
Tco = 5.0000031 ⁰C
Tci = 0.8615352 ⁰C
Thi = 25 ⁰C
65
ε=T co−T ci
T hi−T ci
=0.171447
Chart 4.10 : Effectiveness for counter-flow exchanger. [12]
NTU = 0.2
Ao=NTU (Cmin)
Uo
=17.03227 ft2
7. Calculate total volume of the heat exchanger.
V=Ao
α=1.002 ft3
8. Calculate the face area.
A fr=QV fr
=1.17 ft2=0.1086957 m2
9. Determine the depth of coil.
L= VA fr
=0.085632 ft=0.03915111m
66
10. Determine the number of rows of tubes.
N r=LXb
=1.413151
So the number of rows will then be 2 because N must be integer and a
multiple of two for flow arrangement.
11. Compute the ratio, air-side.
AAC
= αVσ A fr
=18.5749
12. Find the mean density.
P = 2116.8
Tci = 536.67 Rankine
Tco = 511.47859 Rankine
R = 53.35
Pm=P
2 R ( 1Tci
+1
Tco)=0.07058
lb
ft3 =1.21342kg
m3
13. Calculate the lost head on the air side of the exchanger.
D¿
D=
( AA t
)
1+(Xa−D)
s
=5.305619
D* = 0.090991373 m
¿ = 0.1182726
¿ = 1.517693322
(Xa−D
4 (s− y))−0.4
= 0.466203452
(Xa
D¿−1)−0.5
= 1.08381619
FP=( Re D )−0.25( DD¿ )
0.25( Xa−D4 (s− y))
−0.4
( Xa
D¿−1)−0.5
=0.0907
67
Chart 4.11 : Correlation of friction data for smooth plate-fin-coils. [12]
f = 0.013
Gc = 5.4198853 kg/m2.s = 3996.376 lbm/hr.ft2
gc = 1 kg.m/N.s2 = 32.17 lbm.ft/lbf.s2
ƿ1 = 0.0798475 lb/ft3 = 1.278997 kg/m3
ƿ2 = 0.0716598 lb/ft3 = 1.147847 kg/m3
σ = 0.555
Tho = 500.67001 Rankine
Thi = 498.22076 Rankine
¿¿ = 0.23988
(p1
p2
−1) = 0.11426
(1+σ 2) = 1.30803
( fAAC
p1
pm
) = 0.3235
68
∆ Po=(GC)2
2 gC p12 [ (1+σ 2 )( p1
p2
−1)+( fA
AC
p1
pm
)]
¿0.1135lb
ft2
or
¿5.432 Pa
Also,
∆ Po=0.0018 ft w . g
14. Determine the flow cross-sectional area for the refrigerant.
Ch = 2106.186494 Btu/hr.F
V = 18.531458210 m/s = 60.79875 ft/s
ƿ = 23.3032221 kg/m3 = 2.326135 lb/ft3
Cp = 0.96674498 kJ/kg.K = 0.692866Btu/lb.F
A=Ch
V pCp
=0.00597057 ft2=0.0005547 m2
15. Calculate number of tubes per rows.
Di = 0.01 m
N= 4 A
π Di2=7.06245164
Since N must be integer, 8 tubes are required.
To adapt to the flow arrangement, a coil that is 16 tubes high must be used.
H=16 Xa=0.508 m
W =A fr
H=0.2139679 m
69
The shape of the coil, height of 0.508 m and width of 0.2139679 m, may be
unacceptable.
Lw=2 (no . of rows ) (W )=0.428 m=1.404 ft
Chart 4.12 : Friction factors for pipe flow. [11]
moody friction = 0.023
D = 0.01 m = 0.03281 ft
V = 18.53145821 m.s = 5.066562 ft/s
g = 9.81 m/s2 = 32.1639 ft/s2
Lf w=moody friction( Lw
D )( V 2
2 g )+(no . of returnbends )( V 2
2 g ) ¿5.97947 ft w . g
Use 2-row coil, and the coil will then have 8 tubes per row.
H=8 Xa=0.254 m
W =A f r
H=0.4279 m
70
Lw=2 (no . of rows ) (W )=1.7117432 m=5.165955 ft
Lf w=moody friction( Lw
D )( V 2
2g )+(no .of returnbends )( V 2
2g ) ¿5.56157 ft w . g
4.5.3 Drawing of Evaporator
1) Isometric View
Figure 4.6 : Isometric view of evaporator
2) Plant View
71
Figure 4.7 : Plant view of evaporator
3) Side View
Figure 4.8 : Side view of evaporator
4) Front View
Figure 4.9 : Front view of evaporator
72
4.6 Sizing the Capillary Tube
4.6.1 Data
Saturated Liquid Temp. 45 ºC
Evaporating Temp. 5 ºC
1.2 mm
ID 0.0012 m
Radius 0.0006 m
= 3.1415927
Area
(A) 0.00000113 m²
Mass Flow rate 0.0321 kg/s
73
74
75
4.6.2 Calculation
Position
Temp.
Pressure ν1 = νf νg ν2 h1 = hf hg h2 µ1 = µf µg µ2 w/A VRe f
ºC kPa m³/kg m³/kg m³/kg kJ/kg kJ/kg kJ/kg Pa.s Pa.s Pa.s kg/s.m² m/s
1 45 1751.0063670.0009633 0.0132 267.84471
424.91157
0.0001179 28384.2104 27.342117 288936 0.0142
2 44 1706.9516050.0009584 0.0136
0.001083266.18508
424.73394
267.750.0001194 0.00001417
0.000118 28384.2104 27.2026 285277 0.0143
3 43 1663.7538680.0009536 0.014
0.001080264.5367
424.54448
266.090.0001209 0.00001407
0.000120 28384.2104 27.065983 281671 0.0143
4 42 1621.4003250.0009488 0.0144
0.001077262.8991
424.34371
264.440.0001225 0.00001398
0.000121 28384.2104 26.932151 278116 0.0144
5 41 1579.8783970.0009442 0.0148
0.001074261.27187
424.13201
262.800.000124 0.00001388
0.000123 28384.2104 26.800998 274611 0.0144
6 40 1539.175740.0009397
0.015300 0.001072259.65456
423.90978
261.170.0001256 0.00001379
0.000125 28384.2104 26.672422 271157 0.0145
7 39 1499.280230.0009352
0.015700 0.001069258.04679
423.67738
259.550.0001272 0.00001369
0.000126 28384.2104 26.546328 267750 0.0145
8 38 1460.1799570.0009309
0.016200 0.001067256.44816
423.43516
257.940.0001288 0.00001360
0.000128 28384.2104 26.422628 264392 0.0146
9 37 1421.8632060.0009266
0.016700 0.001065254.8583
423.18341
256.340.0001305 0.00001352
0.000129 28384.2104 26.301236 261080 0.0146
10 36 1384.3184560.0009224
0.017200 0.001064253.27685
422.92249
254.750.0001321 0.00001343
0.000131 28384.2104 26.182072 257815 0.0146
11 35 1347.5343610.0009183
0.017700 0.001062251.70345
422.65266
253.170.0001338 0.00001335
0.000133 28384.2104 26.065062 254594 0.0147
12 34 1311.4997510.0009142
0.018200 0.001060250.13779
422.37418
251.590.0001355 0.00001326
0.000134 28384.2104 25.950132 251417 0.0147
13 33 1276.2036180.0009103
0.018800 0.001059248.57955
422.08729
250.020.0001372 0.00001318
0.000136 28384.2104 25.837216 248284 0.0148
14 32 1241.6351080.0009064
0.019300 0.001057247.02841
421.79224
248.460.0001389 0.00001310
0.000138 28384.2104 25.726248 245193 0.0148
15 31 1207.7835210.0009025
0.019900 0.001056245.48408
421.48923
246.910.0001407 0.00001303
0.000140 28384.2104 25.617167 242145 0.0149
16 30 1174.6382970.0008987
0.020500 0.001055243.94629
421.17849
245.360.0001424 0.00001295
0.000141 28384.2104 25.509916 239137 0.0149
17 29 1142.189015 0.0008950.021100 0.001055
242.41478420.86016
243.820.0001442 0.00001287
0.000143 28384.2104 25.404437 236169 0.0150
18 28 1110.4253870.0008914
0.021800 0.001054240.88928
420.53451
242.290.000146 0.00001280
0.000145 28384.2104 25.300678 233241 0.0150
76
19 27 1079.337250.0008878
0.022400 0.001053239.36956
420.20167
240.760.0001479 0.00001273
0.000147 28384.2104 25.198589 230352 0.0151
20 26 1048.9145680.0008842
0.023100 0.001053237.85538 419.8618
239.240.0001497 0.00001265
0.000149 28384.2104 25.098121 227501 0.0151
PositionTemp. Pressure ν1 = νf νg ν2 h1 = hf hg h2 µ1 = µf µg µ2 w/A V
Re fºC kPa m³/kg m³/kg m³/kg kJ/kg kJ/kg kJ/kg Pa.s Pa.s Pa.s kg/s.m² m/s
21 25 1019.1474180.0008807
0.023800 0.000881236.34653 419.51507
236.350.0001516 #VALUE!
#VALUE!28384.2104 24.999229 224687 0.0152
22 24 990.02599690.0008773
0.024600 0.000877234.8428 419.16161
234.840.0001535 0.00001251
0.00015328384.2104 24.901867 221910 0.0152
23 23 961.54060830.0008739
0.025300 0.000874233.34399 418.80158
233.340.0001554 0.00001245
0.00015528384.2104 24.805993 219169 0.0153
24 22 933.68166470.0008706
0.026100 0.000871231.84992 418.43511
231.850.0001574 0.00001238
0.00015728384.2104 24.711568 216463 0.0153
25 21 906.43968250.0008673
0.026900 0.000867230.36041 418.06232
230.360.0001593 0.00001231
0.00015928384.2104 24.618553 213792 0.0153
26 20 879.80527870.0008641
0.027700 0.000864228.8753 417.68331
228.880.0001613 0.00001225
0.00016128384.2104 24.52691 211156 0.0154
27 19 853.76916850.0008609
0.028600 0.000861227.39444 417.29826
227.390.0001633 0.00001218
0.00016328384.2104 24.436603 208553 0.0154
28 18 828.32216260.0008578
0.029500 0.000858225.91767 416.90725
225.920.0001654 0.00001212
0.00016528384.2104 24.347599 205983 0.0155
29 17 803.45516430.0008547
0.030400 0.000855224.44486 416.51039
224.440.0001674 0.00001206
0.00016728384.2104 24.259864 203445 0.0155
30 16 779.15916760.0008516
0.031400 0.000852222.97588 416.10779
222.980.0001695 0.00001199
0.00017028384.2104 24.173366 200940 0.0156
31 15 755.4252550.0008486
0.032400 0.000849221.51062 415.69954
221.510.0001716 0.00001193
0.00017228384.2104 24.088076 198465 0.0156
32 14 732.24459510.0008457
0.033400 0.000846220.04897 415.28575
220.050.0001738 0.00001187
0.00017428384.2104 24.003965 196022 0.0157
33 13 709.60844090.0008428
0.034500 0.000843218.59082 414.86651
218.590.0001759 0.00001181
0.00017628384.2104 23.921003 193608 0.0157
34 12 687.5081280.0008399
0.035600 0.000840217.13608 414.44191
217.140.0001781 0.00001175
0.00017828384.2104 23.839163 191225 0.0158
35 11 665.9350728 0.0008370.036800 0.000837
215.68467 414.01205
215.680.0001803 0.00001170
0.00018028384.2104 23.75842 188871 0.0158
36 10 644.88077110.0008342
0.038000 0.000834214.23651 413.57701
214.240.0001826 0.00001164
0.00018328384.2104 23.678748 186545 0.0159
77
37 9 624.33679660.0008315
0.039200 0.000831212.79153 413.13683
212.790.0001849 0.00001158
0.00018528384.2104 23.600123 184248 0.0159
38 8 604.29479920.0008287
0.040500 0.000829211.34965 412.6917
211.350.0001872 0.00001152
0.00018728384.2104 23.522521 181978 0.0160
39 7 584.746504 0.0008260.041800 0.000826
209.91084 412.24164
209.910.0001895 0.00001147
0.00019028384.2104 23.445919 179736 0.0160
40 6 565.68371030.0008234
0.043200 0.000823208.47502 411.78675
208.480.0001919 0.00001141
0.00019228384.2104 23.370296 177521 0.0161
41 5 547.09828990.0008207
0.044700 0.000821207.04217 411.32709
207.040.0001943 0.00001136
0.00019428384.2104 23.29563 175332 0.0161
Position
Temp.a b c x fm Vm a′ b′ c′
Increment CumulativeºC Length m Length m
1 45
2 4464376.85 168309.76 -1663.43 0.010 0.0143 27.272
48015
0.1409.807
0.01180.0118
3 4368565.85 170030.67 -1652.09 0.010 0.0143 27.134
47076
0.1389.655
0.01160.0234
4 4272885.80 171727.32 -1641.21 0.010 0.0143 26.999
46152
0.1369.504
0.01140.0348
5 4177336.67 173400.58 -1630.76 0.009 0.0144 26.867
45245
0.1359.355
0.01120.0460
6 4083071.32 175127.05 -1620.74 0.009 0.0144 26.737
44352
0.1339.213
0.01110.0570
7 3987816.44 176755.78 -1611.13 0.009 0.0145 26.609
43475
0.1319.065
0.01090.0679
8 3893918.47 178438.60 -1601.91 0.009 0.0145 26.484
42611
0.1308.925
0.01070.0786
78
9 37100224.40 180100.57 -1593.06 0.009 0.0146 26.362
41762
0.1288.785
0.01050.0892
10 36106734.17 181742.45 -1584.58 0.009 0.0146 26.242
40927
0.1268.647
0.01040.0995
11 35113447.74 183364.92 -1576.45 0.009 0.0147 26.124
40105
0.1258.508
0.01020.1098
12 34120365.03 184968.62 -1568.65 0.008 0.0147 26.008
39297
0.1238.371
0.01000.1198
13 33128923.28 186627.52 -1561.17 0.008 0.0148 25.894
38501
0.1228.240
0.00990.1297
14 32136288.47 188195.22 -1554.00 0.008 0.0148 25.782
37718
0.1208.104
0.00970.1394
15 31145383.75 189818.66 -1547.12 0.008 0.0149 25.672
36948
0.1187.975
0.00960.1490
16 30154771.78 191425.05 -1540.53 0.008 0.0149 25.564
36189
0.1177.846
0.00940.1584
17 29164452.50 193014.89 -1534.20 0.008 0.0149 25.457
35443
0.1157.718
0.00930.1677
18 28176106.35 194660.55 -1528.13 0.008 0.0150 25.353
34709
0.1147.595
0.00910.1768
19 27186420.90 196218.56 -1522.30 0.008 0.0150 25.250
33986
0.1127.468
0.00900.1857
20 26198813.76 197832.72 -1516.70 0.008 0.0151 25.148
33274
0.1117.346
0.00880.1946
79
Position
Temp.a b c x fm Vm a′ b′ c′
Increment CumulativeºC Length m Length m
80
21 25211604.38 199431.66 -1511.33 0.008 0.0151 25.049
32574
0.1097.225
0.00870.2032
22 24226699.92 201086.48 -1506.16 0.007 0.0152 24.951
31885
0.1087.109
0.00850.2118
23 23240342.52 202655.95 -1501.19 0.007 0.0152 24.854
31207
0.1066.989
0.00840.2201
24 22256411.29 204281.55 -1496.41 0.007 0.0153 24.759
30539
0.1056.873
0.00820.2284
25 21272998.95 205892.97 -1491.80 0.007 0.0153 24.665
29882
0.1046.758
0.00810.2365
26 20290105.42 207490.53 -1487.36 0.007 0.0154 24.573
29236
0.1026.644
0.00800.2445
27 19309961.44 209144.03 -1483.08 0.007 0.0154 24.482
28599
0.1016.534
0.00780.2523
28 18330473.61 210783.86 -1478.94 0.007 0.0155 24.392
27973
0.0996.424
0.00770.2600
29 17351641.86 212410.35 -1474.94 0.007 0.0155 24.304
27357
0.0986.314
0.00760.2676
30 16375923.26 214092.41 -1471.07 0.007 0.0156 24.217
26751
0.0976.209
0.00750.2750
31 15401014.16 215761.25 -1467.32 0.007 0.0156 24.131
26155
0.0956.103
0.00730.2824
32 14426914.48 217417.13 -1463.68 0.007 0.0157 24.046
25568
0.0945.998
0.00720.2896
33 13456331.77 219128.24 -1460.14 0.007 0.0157 23.962
24991
0.0935.896
0.00710.2966
34 12486727.99 220826.47 -1456.69 0.007 0.0158 23.880
24423
0.0915.795
0.00700.3036
35 11 520996.44 222579.51 -1453.33 0.006 0.0158 23.799 2386 0.090 5.69 0.0068 0.3104
81
5 6
36 10556429.42 224319.71 -1450.05 0.006 0.0159 23.719
23316
0.0895.598
0.00670.3172
37 9593026.85 226047.27 -1446.84 0.006 0.0159 23.639
22776
0.0875.500
0.00660.3238
38 8633980.79 227829.29 -1443.70 0.006 0.0160 23.561
22245
0.0865.405
0.00650.3302
39 7676300.87 229598.74 -1440.62 0.006 0.0160 23.484
21723
0.0855.309
0.00640.3366
40 6723397.11 231422.16 -1437.58 0.006 0.0161 23.408
21209
0.0845.217
0.00630.3429
41 5775608.44 233299.13 -1434.59 0.006 0.0161 23.333
20705
0.0835.126
0.00620.3490
From the table, the final length of capillary tube is 0.3490 meter.
CHAPTER 5
RESULT AND ANALYSIS
5.1 Effect of Evaporating Temperature On Cooling Capacity
5.1.2 Evaporating Temperature Vs Cooling Capacity
The main objective for this project is to to analyse the effect of evaporating
temperature on cooling capacity. That is mean by using varies evaporating
temperature (constant condensing temperature Tc=45⁰C) that is 2⁰C to 13⁰C then to
look out the result of the cooling capacity for each temperature tested.
Temperature (⁰C) 2 3 4 5 6 7 8 9 10 11 12 13
Cooling Capacity (kW) 4.3 4.48 4.67 4.87 5.06 5.27 5.48 5.69 5.91 6.13 6.36 6.59Table 5.1 : Data for evaporating temperature vs cooling capacity
0 2 4 6 8 10 12 140
1
2
3
4
5
6
7 Te vs Cooling Capacity
Evaporating Temperature (⁰C)
Cooling Capacity (kW)
Graph 5.1 : Evaporating temperature Vs cooling capacity
The graph show that when the evaporating temperature is increased, the
cooling capacity will also increased.
82
Then from the data above, there are the factor that need to be calculated to
determine the optimum evaporating temperature for Malaysia conditions. That is :
a) Compression ratio
b) Coefficient of performance (C.O.P)
c) Power consumption
5.1.2 Compression Ratio and Coefficient of Perfomance Vs Cooling
Capacity
Temperature (⁰C) 2 3 4 5 6 7 8 9 10 11 12 13Cooling Capacity (kW) 4.3
4.48
4.67
4.87
5.06
5.27
5.48
5.69
5.91
6.13
6.36
6.59
Compression Ratio3.98
3.85
3.72
3.59
3.48
3.36
3.26
3.15
3.05
2.95
2.86
2.77
C.O.P2.81
2.87
2.92
2.98
3.04 3.1
3.17
3.23
3.29
3.36
3.43 3.5
Table 5.2 : Data for evaporating temperature Vs cooling capacity Vs compression ratio Vs
C.O.P
4.3 4.48 4.67 4.87 5.06 5.27 5.48 5.69 5.91 6.13 6.36 6.590
0.5
1
1.5
2
2.5
3
3.5
4
4.5
Compression Ratio & C.O.P vs Cooling Capacity
Compression RatioC.O.P
Cooling Capacity (kW)
Chart 5.1 : Cooling capacity Vs compression ratio & C.O.P
The chart contain two (2) type of data versus cooling capacity which is the
compression ratio and C.O.P. From the chart, its show that when the cooling
capacity is increased, the compression ratio is decreased and meanwhile, the
C.O.P value will be increased.
83
5.1.3 Power Consumption Vs Cooling Capacity
For the power consumption, the calculation is make for eight (8) hours per
day and calculate for a month (20 days of working period). From the latest electricity
tariff by Tenaga Nasional Berhad (TNB), the rate of charge per kw/h is RM 0.218.
Cooling Capacity (kW)
4.3 4.484.67
4.87 5.06 5.27 5.48 5.69 5.91 6.13 6.36 6.59
Rate (RM)150.02
156.43
163169.74
176.67
183.76
191.03
198.5
206.11
213.92
221.91
230.08
Table 5.3 : Data for cooling capacity vs rate
2 3 4 5 6 7 8140150160170180190200210220230240
Power Consumption vs Cooling Capacity
Cooling Capacity (kW)
Rate (RM)
Graph 5.2 : Cooling capacity Vs rate
The graph show that the power consumption will be increased when the
cooling cacacity increased.
From the calculation and comparison have been done, the optimum evaporating
temperature for Malaysia conditions is about 8 C to 9 C. Its because from the criteria⁰ ⁰
for compression ratio and C.O.P, its about the ideal value compare the other tested
temperature.
After design all the required component for the system, then by using the formula
and calculation that have been used in Microsoft Excel, the next step is :
Research the effect of condensing temperature on condenser sizing.
Research the effect of evaporating temperature on evaporator sizing.
84
Research the effect of condensing temperature and evaporating temperature
on capillary tube length.
5.2 Effect of Condensing Temperature On Condenser Sizing
5.2.1 Temperature Vs Depth
Temperature (⁰C) 35 37 39 41 43 45 47 49
Depth (mm)81.2 72.1
68.5 66.7
62.9 62.8
62.8 62.7
Table 5.4 : Data for condensing temperature vs depth
34 36 38 40 42 44 46 48 5060
65
70
75
80
85 Tc vs Depth
Condensing Temperature (⁰C)
Wid
th (m
m)
Graph 5.3 : Condensing temperature Vs depth
The graph show that the depth design for the coil is become more smaller
when the condensing temperature is increased.
5.2.2 Temperature Vs Height
Temperature (⁰C) 35 37 39 41 43 45 47 49
Height (mm) 286 286286 286 381
381 381 381
Table 5.5 : Data for condensing temperature vs height
34 36 38 40 42 44 46 48 50280
300
320
340
360
380
400 Tc vs Height
Graph 5.4 : Condensing temperature Vs height
85
The graph show that the height design of the coil is same for the range
temperature 35 C to 41 C and 43 C to 49 C.⁰ ⁰ ⁰ ⁰
5.2.3 Temperature Vs Width
Temperature (⁰C) 35 37 39 41 43 45 47 49
Width (mm) 722 722722 722 542
542 542 542
Table 5.5 : Data for condensing temperature vs width
34 36 38 40 42 44 46 48 50530
560
590
620
650
680
710Tc vs Width
Condensing Temperature (⁰C)
Width (mm)
Graph 5.5 : Condensing temperature Vs width
The graph show that the width design of the coil is same for the range
temperature 35 C to 41 C and 43 C to 49 C.⁰ ⁰ ⁰ ⁰
5.2.4 Temperature Vs Rows of Tube
Temperature (⁰C) 35 37 39 41 43 45 47 49Rows of tube 4 4 4 4 4 4 4 4
Table 5.6 : Data for condensing temperature vs rows of tube
34 36 38 40 42 44 46 48 502
4
6 Tc vs Rows of tube
Condensing Temperature (⁰C)
Rows of tube
Graph 5.6 : Condensing temperature Vs rows of tube
86
The graph show that the number rows of tube is same although the
condensing temperature is increased.
5.2.5 Temperature Vs Tube per Rows
Temperature (⁰C) 35 37 39 41 43 45 47 49Tube per row 6 6 6 6 8 8 8 8Table 5.7 : Data for condensing temperature vs tube per rows
34 36 38 40 42 44 46 48 504
5
6
7
8
9
10 Tc vs Tube per row
Condensing Temperature (⁰C)
Tube per row
Graph 5.7 : Condensing temperature Vs tube per rows
The graph show that the width number of tube per row of the coil is same for
the range temperature 35 C to 41 C and 43 C to 49 C.⁰ ⁰ ⁰ ⁰
5.3 Effect of Evaporating Temperature On Evaporator Sizing
5.3.1 Temperature Vs Depth
Temperature (⁰C) 2 3 4 5 6 7 8 9 10 11 12 13
Depth (mm) 35.6 37.4 39.239
40 41 41 45 46 48.1 50 52
Table 5.8 : Data for evaporating temperature vs depth
1 2 3 4 5 6 7 8 9 10 11 12 13 1434
38
42
46
50Te vs Depth
Evaporating Temperature (⁰C)
Wid
th (m
m)
87
Graph 5.8 : Evaporating temperature Vs depth
The graph show that the depth design for the coil is become more bigger
when the evaporating temperature is increased.
5.3.2 Temperature Vs Height
Temperature (⁰C) 2 3 4 5 6 7 8 9 10 11 12 13
Height (mm)318
254
254
254
254
254
254
191
191
191
191
191
Table 5.9 : Data for evaporating temperature vs heigth
1 2 3 4 5 6 7 8 9 10 11 12 13 14180200220240260280300320
Te vs Height
Graph 5.9 : Evaporating temperature Vs heigth
The graph show that the height design of the coil is same for the range
temperature 3 C to 8 C and 9 C to 13 C.⁰ ⁰ ⁰ ⁰
5.3.3 Temperature Vs Width
Temperature (⁰C) 2 3 4 5 6 7 8 9 10 11 12 13
Width (mm)342
428
428
428
428
428
428
571
571
571
571
571
Table 5.10 : Data for evaporating temperature vs width
88
1 2 3 4 5 6 7 8 9 10 11 12 13 14330380430480530580
Te vs Width
Evaporating Temperature (⁰C)
Width (mm)
Graph 5.10 : Evaporating temperature Vs width
The graph show that the width design of the coil is same for the range
temperature 3 C to 8 C and 9 C to 13 C.⁰ ⁰ ⁰ ⁰
5.3.4 Temperature Vs Rows of Tube
Temperature (⁰C) 2 3 4 5 6 7 8 9 10 11 12 13Rows of tube 2 2 2 2 2 2 2 2 2 2 2 2
Table 5.11 : Data for evaporating temperature vs rows of tube
1 2 3 4 5 6 7 8 9 10 11 12 13 140
1
2
3
4Te vs Rows of tube
Evaporating Temperature (⁰C)
Rows of tube
Graph 5.11 : Evaporating temperature Vs rows of tube
The graph show that the number rows of tube is same although the
evaporating temperature is increased.
5.3.5 Temperature Vs Tube per Rows
Temperature (⁰C) 2 3 4 5 6 7 8 9 10 11 12 13Tube per row 10 8 8 8 8 8 8 6 6 6 6 6
89
Table 5.12 : Data for evaporating temperature vs tube per rows
1 2 3 4 5 6 7 8 9 10 11 12 13 14456789
10
Te vs Tube per row
Evaporating Temperature (⁰C)
Tube per row
Graph 5.12 : Evaporating temperature Vs tube per rows
The graph show that the width number of tube per row of the coil is same for
the range temperature 3 C to 8 C and 9 C to 13 C.⁰ ⁰ ⁰ ⁰
From the calculation and comparison have been for that two (2) component, the
design of the coil is related and depend on the setpoint temperature have been set for
the design. When the temperature is different, the depth, number rows of tube and
number of tube per row will be changed. The height and width of the coil design is
change according to the number rows of tube and number of tube per row.
5.4 Effect of Condensing and Evaporating Temperature On Capillary Tube
Length
5.4.1 Condensing Temperature Vs Length
Temperature (⁰C) 35 37 39 41 43 45 47 49
Length (mm) 347 347347 347 348
349 351 353
Table 5.13 : Data for condensing temperature vs length
90
34 36 38 40 42 44 46 48 50340
344
348
352
356
360
Tc vs Length
Condensing Temperature (⁰C)
Length (mm)
Graph 5.13 : Condensing temperature Vs length
The graph show that the length of the capillary tube is same for the
temperature range between 35 C to 41 C and will be increased after that⁰ ⁰
temperature is increased.
5.4.2 Evaporating Temperature Vs Length
Temperature (⁰C)
2 3 4 5 6 7 8 9 10 11 12 13
Depth (mm)419
394
370
349
329
311
294
279
264
251
238
227
Table 5.14 : Data for evaporating temperature vs Length
91
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15200
240
280
320
360
400
440
Te vs Length
Evaporating Temperature (⁰C)
Length (mm)
Graph 5.14 : Evaporating temperature Vs Length
The graph show that the length of the capillary tube is decreased when the
evaporating temperature is increased.
So, the length of capillary tube is change varies to the temperature. Basically, the
function of the capillary tube is to regulate the flow of the refrigerant and then to
drop the temperature and pressure that flow to the evaporator.
92
CHAPTER 6
CONCLUSION AND RECOMMENDATIONS
6.1 Conclusion
The design of air conditioning system is involve a many aspect that need to
focused in term to make that system is running properly and efficient. The most
important thing in designing and building the air conditioning system is the four (4)
main component in the system cycle. That is compressor, condenser, evaporator and
capillary tube. If the design of this component is wrong, the system will become a
problem and also risk to the system damage.
The main objective of this project is to analyse the effect of evaporating
temperature on cooling capacity and then to determine the evaporating temperature
for Malaysia conditions. This mean that after designing and calculating by using
Microsoft Excel and Solvay Flour, and the varies evaporating temperature that have
been selected, than compare for each evaporating temperature with cooling capacity.
For the result show that evaporating temperature is increased, the cooling capacity
will also be increased. Its because to managed the system achieve the design setpoint
of evaporating temperature, the cooling capacity must be achieved the criteria to
running correctly.
Then, from the analyse effect of evaporating temperature on cooling capacity,
there we can make a calculation and make a comparison about the compression ratio,
coefficient of performance (C.O.P) and power consumption. Then from that data, we
can conclude which is the optimum evaporating temperature for Malaysia conditions
by look at the margin between the compression ratio ang coefficient of performance
(C.O.P). From this project, the optimum evaporating temperature is between 8 C and⁰
9 C. Its because the margin for the compression ratio and coefficient of performance⁰
(C.O.P) at this temperature is the closest and lower.
93
The other research involve in this project is to analyse the effect of the
evaporating temperature and condensing temperature on the coil design. From the
research, what can be concluded is the design of the coil for condenser and
evaporator is depend on the evaporating and condensing temperature. The
temperature is effect directly on the sizing depth of the coil, number rows of tube and
number of tube per row. Then from the design of number rows of tube and number of
tube per row, it will determine the result of the design sizing for the height and width
of the coil.
For the capillary tube, there also have been make a research to see the effect
of the evaporating and condensing temperature on the length of capillary tube. So
from the result, it can be conclude that when the condensing temperature increased,
the length of capillary tube is increased. Its become more longer because to achieve
the indoor setpoint, its require more length for capillary tube to drop the temperature
and pressure. For the evaporating temperature, the length is decreased because when
the evaporating temperature is increased, the capillary tube is required less operation
and not need to drop the pressure and temperature to the lower value.
What can be concluded in design and select the compressor is, the main
factor involved in this section is the type of refrigerant use, the evaporating and
condensing temperature and the value of the subcool and superheat. For this design,
the refrigerant use is R407c.
That’s all what can be concluded from this project and the last word that can
be said is that to design the air conditioning system, there are a lot of factor must be
review in designing the component.
6.2 Recommendations
After finished doing this final year project, there is some recommendations
that can be make and must be review for the future benefit. For the first thing I want
to recommend is about the knowledge to finish the project. For your information,
there are a lot of difficulties I have challenged in the period to finish this project. The
lack of knowledge is one of the factor. During the learning process in the class, I’m
recommend to the department of Air Conditioning and Refrigeration to make a
discussion about add the topic into the syllabus for student.
94
The other recommendations is about the development of the software. The
industry and responsible department should build and create a one software about to
design a complete air conditioning system. That involve design and select the
compressor, to design evaporator and condenser and design the capillary tube or
expansion valve.
For this project, what I hope in the future is that my project can help and be
the reference to the other student who want to design the air conditioning system.
Although my project is not perfect, but hopefully this can guide student in designing
their own air conditioning system.
95
REFERENCES
1. Continuing Education and Development, Inc., (2009), “Description of Cooling
Systems,” Selection Tips for Air Conditioning Systems, page 2 – 4.
2. Dr. Sam C M Hui, (2007), “Basic Concepts,” Brief Notes on Air Conditioning
System Design, page 1.
3. Michelle Addington, (2010), “Split-System Air Conditioners,” Yale University
Design Standards, page 25 - 26.
4. Carlyle Compressor Company, (2000), “Application Guide,” Millenium Scroll
Compressor Catalogue, page 1 - 21.
5. Emerson Climate Technologies, (2003), “Scroll Compressor for Air-
Conditioning,” Copeland Scroll, page 1 - 22. .
6. Gartner and Harrison, (2010), “Lowering Condensing Pressure,” Gartner –
Refrigeration & MFG. Inc, page 1 - 4.
7. SPX Brand, (2009), “Evaporators Type Selection,” Evaporator Handbook,
page 4 - 33.
8. IIT Kharagpur, (2008), “Lesson 19 – Perfomance of Reciproating Compressor,”
Refrigeration and Air Conditioning, Ver.6, page 2 - 24.
9. Department of Standards Malaysia, (2007), “ACMV system equipment,
electrically operated, cooling mode & system cooling equipment/component,
heat-operated,” Malaysia Standard (MS1525), page 35 - 38.
10. “Temperature, Density, Specific Heat, Thermal Conductivity, Expansion
Coefficient, Kinematic Viscosity and Prandtl's Number for Temperatures
Ranging 150 - 400 C,” in ⁰ Air Properties, from
http://www.engineeringtoolbox.com.
11. Faye C. McQuiston, Jerald D.Parker and Jeffrey D.Spitler, (2005) “Chapter 10 –
Flows, Pumps, and Piping Design,” Heating, Ventilating and Air Conditioning
Analysis and Design, Vol.6, page 299 – 307.
12. Faye C.McQuiston, Jerald D.Parker and Jeffrey D.Spitler, (2005), “Chapter 14 –
Extended Surface Heat Exchangers,” Heating, Ventilating and Air Conditioning
Analysis and Design, Vol.6, page 482 – 513.
13. W.F.Stoecker and J.W.Jones, (1982), “Chapter 13 – Expansion Devices,”
Refrigeration and Air Conditioning, Vol.2, page 264 – 269.
96