Page 1: Design and Detailing of steel in Combined Footingslibvolume3.xyz/civil/btech/semester6/designdrawingofrcstructures/...Design of combined footing – Slab and Beam type- Problem 2 2

Design and Detailing of steel in Combined Footings

Dr. M.C. NATARAJA

Page 2: Design and Detailing of steel in Combined Footingslibvolume3.xyz/civil/btech/semester6/designdrawingofrcstructures/...Design of combined footing – Slab and Beam type- Problem 2 2

Design of combined footing – Slab and Beam type- Problem 2

2 Design a rectangular combined footing with a central

beam for supporting two columns 400x400 mm in size to carry a load of 1000kN each. Center to center distance between the columns is 3.5m. The projection of the footing on either side of the column with respect to center is 1m. Safe bearing capacity of the soil can be taken as 190kN/m2. Use M20 concrete and Fe-415 steel.

Page 3: Design and Detailing of steel in Combined Footingslibvolume3.xyz/civil/btech/semester6/designdrawingofrcstructures/...Design of combined footing – Slab and Beam type- Problem 2 2

Draw to a suitable scale the following

1. The longitudinal sectional elevation

2. Transverse section at the left face of the heavier column

3. Plan of the footing

Marks 60

Page 4: Design and Detailing of steel in Combined Footingslibvolume3.xyz/civil/btech/semester6/designdrawingofrcstructures/...Design of combined footing – Slab and Beam type- Problem 2 2

Solution: Data fck = 20Nlmm2, fy= 415mm2, f b (SBC)= l90 kN/m2, Column A = 400 mm x 400 mm, Column B = 400 mm x 400 mm, c/c spacing of columns = 3.5, PA = 1000 kN and PB = 1000 kN Required: To design combined footing with central beam joining the two columns.

Page 5: Design and Detailing of steel in Combined Footingslibvolume3.xyz/civil/btech/semester6/designdrawingofrcstructures/...Design of combined footing – Slab and Beam type- Problem 2 2

Ultimate loads PuA= 1.5 x 1000 = 1500 kN, PuB = 1.5 x 1000 = 1500 kN

Proportioning of base size

Working load carried by column A = PA = 1000 kN Working load carried by column B = PB = 1000 kN Self weight of footing 10 % x (PA + PB) = 200 kN Total working load = 2200 kN Required area of footing = Af = Total load /SBC=2200/190 = 11.57 m2

Length of the footing Lf = 3.5 +1 +1 =5.5m Required width of footing = b= Af /Lf = 11.57/5.5 = 2.1m Provide footing of size 5.5 x 2.1 m

Page 6: Design and Detailing of steel in Combined Footingslibvolume3.xyz/civil/btech/semester6/designdrawingofrcstructures/...Design of combined footing – Slab and Beam type- Problem 2 2

For uniform pressure distribution the C.G. of the footing should coincide with the C.G. of column loads. As the footing and columns loads are symmetrical, this condition is satisfied.

1000 kN 1000 kN

3.5 m 1 m 1 m

x R p=173.16 kN/m2

(safe) w=363.64 kN/m

Page 7: Design and Detailing of steel in Combined Footingslibvolume3.xyz/civil/btech/semester6/designdrawingofrcstructures/...Design of combined footing – Slab and Beam type- Problem 2 2

Total load from columns = P = (1000 + 1000) = 2000 kN. Upward intensity of soil pressure=Column loads/A provided = P/Af= 2000/5.5 x2.1 =173.16 kN/m2< SBC

Design of slab: Intensity of Upward pressure = p =173.16 kN/m2

Consider one meter width of the slab (b=1m) Load per m run of slab at service = 173.16 x 1 = 173.16 kN/m Cantilever projection of the slab =1050 - 400/2 = 850mm Maximum ultimate moment = 173.16 x 0.8502/2 = 62.55 kN-m. (Working condition)

Page 8: Design and Detailing of steel in Combined Footingslibvolume3.xyz/civil/btech/semester6/designdrawingofrcstructures/...Design of combined footing – Slab and Beam type- Problem 2 2

For M20 and Fe 415, Q u max = 2.76 N/mm2 Required effective depth = √ (62.15 x1.5 x 106/(2.76 x 1000)) = 184.28 mm Using 20 mm bars, effective cover =20/2 +50 say 75 mm Required total depth = 184.28 + 75 = 259.4 mm. However provide 300 mm from shear consideration as well. Provided effective depth = d = 300-75 = 225 mm

p=173.16 kN/m2

1m

850mm

2.1m

Page 9: Design and Detailing of steel in Combined Footingslibvolume3.xyz/civil/btech/semester6/designdrawingofrcstructures/...Design of combined footing – Slab and Beam type- Problem 2 2

To find steel

Mu/bd2 =1.5 x 62.15 x106/1000 x 2252=1.84< 2.76, URS Pt=0.584 % Ast = 1314 mm2

Use #20 mm diameter bar at spacing = 1000 x 314 / 1314 =238.96 mm say 230 mm c/c #20@230 Area provided =1000 x 314 / 230 = 1365 mm2. Hence safe. This steel is required for the entire length of the footing.

Page 10: Design and Detailing of steel in Combined Footingslibvolume3.xyz/civil/btech/semester6/designdrawingofrcstructures/...Design of combined footing – Slab and Beam type- Problem 2 2

Check the depth from one-way shear

considerations

Design shear force=Vu=1.5x173.16x(0.850-0.225)= 162.33 kN Nominal shear stress = τv

= Vu/bd =162330/(1000x225) =0.72 MPa Permissible shear stress pt = 100 x 1365 /(1000 x 225 ) = 0.607 %, τuc = 0.51 N/mm2 Value of k for 300 mm thick slab =1 Permissible shear stress = 1 x 0.51= 0.51 N/mm2

τuc < τv and hence unsafe.

Page 11: Design and Detailing of steel in Combined Footingslibvolume3.xyz/civil/btech/semester6/designdrawingofrcstructures/...Design of combined footing – Slab and Beam type- Problem 2 2

p=173.16 kN/m2

1m

850mm

2.1m

Critical s/n for shear d

Page 12: Design and Detailing of steel in Combined Footingslibvolume3.xyz/civil/btech/semester6/designdrawingofrcstructures/...Design of combined footing – Slab and Beam type- Problem 2 2

The depth may be increased to 400 mm so that d = 325mm Mu/bd2=1.5 x 62.15 x106/1000x3252 = 0.883< 2.76, URS pt=0.26 %, Ast = 845 mm2

Use #16 mm diameter bar at spacing = 1000 x 201 / 845 =237.8 mm, say 230 mm c/c Area provided =1000 x 201 / 230 = 874 mm2.

#16@230

Page 13: Design and Detailing of steel in Combined Footingslibvolume3.xyz/civil/btech/semester6/designdrawingofrcstructures/...Design of combined footing – Slab and Beam type- Problem 2 2

Check the depth from one - way shear

considerations

Design shear force=Vu=1.5x173.16 x (0.850-0.325) = 136.36 kN Nominal shear stress = τv = Vu/bd =136360/(1000x325) = 0.42 MPa Permissible shear stress pt = 100 x 874/(1000 x 325 ) = 0.269 %, τuc = 0.38 N/mm2 Value of k for 400 mm thick slab =1 Permissible shear stress = 1 x 0.38= 0.38 N/mm2

Again τuc < τv and hence slightly unsafe. However provide steel at closure spacing, #16 @150 Ast=201 x 1000/150 =1340 mm2 and pt =0.41% and hence τuc=0.45 MPa and safe.

Page 14: Design and Detailing of steel in Combined Footingslibvolume3.xyz/civil/btech/semester6/designdrawingofrcstructures/...Design of combined footing – Slab and Beam type- Problem 2 2

Check for development length

Ldt= 47 times diameter = 47x16=768 mm Available length of bar = 850 - 25 =825mm > 768 mm and hence safe.

Transverse reinforcement

Required A st = 0.12 bD / 100 = 0.12 x 1000 x 400/100 = 480mm2

Using 10 mm bars, s= 1000 x 79 / 480 = 164.58 mm Provide distribution steel of #10 mm at 160 mm c/c

p=173.16 kN/m2

1m

850mm

2.1m

Page 15: Design and Detailing of steel in Combined Footingslibvolume3.xyz/civil/btech/semester6/designdrawingofrcstructures/...Design of combined footing – Slab and Beam type- Problem 2 2

Design of Longitudinal Beam

The net upward soil pressure per meter length of the beam under service. = w = 173.16 x 2.1 = 363.64 kN/m Shear Force and Bending Moment at service condition

VAC=363.64 x 1= 363.14 kN, VA =1000-363.14 = 636.36 kN VBD = 363.14 kN, VBA= 636.36 kN Point of zero shear is at the center of footing at L/2, Maximum B.M. occurs at E ME = 363.64 x 2.752 / 2 - 1000 (2.75 - 1) = -375 kN.m

Page 16: Design and Detailing of steel in Combined Footingslibvolume3.xyz/civil/btech/semester6/designdrawingofrcstructures/...Design of combined footing – Slab and Beam type- Problem 2 2

MC=375 kN-m

MA=181.82 kN-m MB=181.82 kN-m

V2=636.36 kN

V3=636.36 kN

BMD at

working

+

-

V1=363.63 kN

V4=363.63 kN

SFD

+ _ +

-

1000 kN 1000 kN

363.64 kN/m

1m 1m 3.5 m

1.3 m

Page 17: Design and Detailing of steel in Combined Footingslibvolume3.xyz/civil/btech/semester6/designdrawingofrcstructures/...Design of combined footing – Slab and Beam type- Problem 2 2

Bending moment under column A = MA = 363.64 x 12 / 2 = 181.82 kN.m Similarly bending moment under column B = MB = 181.82 kN-m Let the point of contra flexure be at a distance x from C Then, Mx= 363.63x2/2 – 1000(x-1) = 0 Therefore x = 1.30 m and 4.2m from C

Page 18: Design and Detailing of steel in Combined Footingslibvolume3.xyz/civil/btech/semester6/designdrawingofrcstructures/...Design of combined footing – Slab and Beam type- Problem 2 2

Depth of beam from B.M. Considerations:

The width of beam=400 mm. Assume the beam as rectangular at the center of span where the moment is maximum, we have, d =√ (375 x 1.5 x 106/ (2.76 x 400)) = 713.8 mm Provide total depth of 800 mm. Assuming two rows of bars at an effective cover of 75 mm, the effective depth provided = d= 800-75 = 725 mm.

Page 19: Design and Detailing of steel in Combined Footingslibvolume3.xyz/civil/btech/semester6/designdrawingofrcstructures/...Design of combined footing – Slab and Beam type- Problem 2 2

MC=375 kN-m

MA=181.82 kN-m MB=181.82 kN-m

V2=636.36 kN

V3=636.36 kN

BMD at working

+

-

V1=363.63 kN

V4=363.63 kN

SFD

+

_ +

-

1000 kN 1000 kN

363.64 kN/m

1.3m

4.2m

Page 20: Design and Detailing of steel in Combined Footingslibvolume3.xyz/civil/btech/semester6/designdrawingofrcstructures/...Design of combined footing – Slab and Beam type- Problem 2 2

Check for two way shear The column B can punch through the footing only if it shears against the depth of the beam along its two opposite edges, and along the depth of the slab on the remaining two edges. The critical section for two-way shear is taken at distance d/2 (i.e. 725/2 mm) from the face of the column. Therefore, the critical section will be taken at a distance half the effective depth of the slab (ds/2) on the other side as shown in Fig

Page 21: Design and Detailing of steel in Combined Footingslibvolume3.xyz/civil/btech/semester6/designdrawingofrcstructures/...Design of combined footing – Slab and Beam type- Problem 2 2

4000 x 400 400 x 400 400

5500 mm

2100

mm

+

0.85m

1.75m 1.75m 0.8m

A B

a=1 m b=1

m

3.5m

400

2100 B

D

D+db

D+ds

db/2

400

Page 22: Design and Detailing of steel in Combined Footingslibvolume3.xyz/civil/btech/semester6/designdrawingofrcstructures/...Design of combined footing – Slab and Beam type- Problem 2 2

In this case b=D= 400 mm, d b =725 mm, ds= 325 mm Area resisting two - way shear = 2(b x db + ds x ds) + 2 (D + db)ds = 2 (400 x 725+ 325 x 325) + 2(400+725) 325 = 1522500 mm2

Design shear=Pud= column load – Wu x area at critical section = 1500 – 173.16 x1.5 x(b + ds) x (D + db) =1500-173.16 x 1.5 x (0.400+0.325) x (0.400+ 0.725) =1288.14 kN

Page 23: Design and Detailing of steel in Combined Footingslibvolume3.xyz/civil/btech/semester6/designdrawingofrcstructures/...Design of combined footing – Slab and Beam type- Problem 2 2

τv=Pud/bod= 1288.14x1000/1522500=0.845 MPa Shear stress resisted by concrete = τuc=τucx Ks

where, τuc = 0.25 √ f ck= 0.25√ 20 = 1.11 N/mm2

Ks = 0.5 + d / D = 0.5 + 400/400 = 1.5 ≠ 1 Hence Ks = 1 τuc = 1 x 1.11 = 1.11 N/mm2

Therefore safe

Page 24: Design and Detailing of steel in Combined Footingslibvolume3.xyz/civil/btech/semester6/designdrawingofrcstructures/...Design of combined footing – Slab and Beam type- Problem 2 2

Area of Reinforcement

Cantilever portion BD and AC Length of cantilever from the face of column = 0.8 m. Ultimate moment at the face of column = 363.64x1.5 x 0.82 / 2 = 177.53 kN-m Mumax =2.76 x400 x7252x10 -6= 580.29 kN.m >177.53 kN-m Therefore Section is singly reinforced. Mu/bd2 =177.53x106/(400x7252) =0.844 <2.76, URS pt=0.248%, A st =719.2 mm2

Provide 4 - 16 mm at bottom face, Area provided = 804 mm2,

pt=0.278%

Ld = 47x16 =752 mm

Page 25: Design and Detailing of steel in Combined Footingslibvolume3.xyz/civil/btech/semester6/designdrawingofrcstructures/...Design of combined footing – Slab and Beam type- Problem 2 2

Curtailment: All bottom bars will be continued up to the end of cantilever for both columns. If required two bottom bars of 2-16mm will be curtailed at a distance d (= 725 mm) from the point of contra flexure in the portion BE as shown in figure.

Page 26: Design and Detailing of steel in Combined Footingslibvolume3.xyz/civil/btech/semester6/designdrawingofrcstructures/...Design of combined footing – Slab and Beam type- Problem 2 2

Region AB between points of contra flexures

The beam acts as an isolated T- beam. bf = [ L o /( L o /b + 4 )] + b w, where, L o = 4.2-1.3=2.9 m = 2900 mm b= actual width of flange = 2100 mm, b w = 400 mm bf= [2900/(2900/2100) + 4] + 400 =938.9mm < 2100mm Df = 400 mm, Mu= 1.5 x 375=562.5 kN-m

Page 27: Design and Detailing of steel in Combined Footingslibvolume3.xyz/civil/btech/semester6/designdrawingofrcstructures/...Design of combined footing – Slab and Beam type- Problem 2 2

Moment of resistance Muf of a beam for x u=D f is : (Muf)= [0.36 x 20 x 938.9 x 400 (725 - 0.42x400)] x10-6 = 1506 kN.m > Mu ( = 562.5 kN-m) Therefore Xu<Df

Mu=0.87fyAst(d - fyAst/fckbf), Ast= 2334 mm2

Provide 4 bars of 25 mm and 2 bars of 16 mm, Area provided = 2354 mm2 >2334 mm2

pt = 100 x 2334/(400x725) = 0.805 %

Page 28: Design and Detailing of steel in Combined Footingslibvolume3.xyz/civil/btech/semester6/designdrawingofrcstructures/...Design of combined footing – Slab and Beam type- Problem 2 2

Curtailment: Curtailment can be done as explained in the previous problem. However extend all bars up to a distance ‘d’ from the point of contra flexure i.e up to 225 mm from the outer faces of the columns. Extend 2-16mm only up to the end of the footing.

Page 29: Design and Detailing of steel in Combined Footingslibvolume3.xyz/civil/btech/semester6/designdrawingofrcstructures/...Design of combined footing – Slab and Beam type- Problem 2 2

MC=375 kN-m

MA=181.82 kN-m MB=181.82 kN-m BMD at working

+

-

1000 kN 1000 kN

363.64 kN/m

1.3m

4.2m

Page 30: Design and Detailing of steel in Combined Footingslibvolume3.xyz/civil/btech/semester6/designdrawingofrcstructures/...Design of combined footing – Slab and Beam type- Problem 2 2

Design of shear reinforcement

Portion between column i.e. AB

Max. shear force at A or B=Vumax=1.5 x 636.36 =954.54 kN SF at the point of contra flexure = 954.54-1.5x 363.64x0.3 = 790.9 kN τv=790900/(400x725) =2.73 MPa < τc,max.(2.8 MPa) Area of steel available = 2354 mm2, 0.805 % τc=0.59MPa, τv > τc

Design shear reinforcement is required. Using 12 mm diameter 4 - legged stirrups, Spacing = 0.87 x 415 x (4 x 113) /(2.73-0.59)x400 =190.6 mm say 190 mm c/c Zone of shear reinforcements is between τv to τc

Page 31: Design and Detailing of steel in Combined Footingslibvolume3.xyz/civil/btech/semester6/designdrawingofrcstructures/...Design of combined footing – Slab and Beam type- Problem 2 2

Cantilever portion BD and AC

Vumax = 363.64 x 1.5 = 545.45 kN, Shear from face at distance d = VuD = 545.45-363.64 x1.5(0.400 / 2 + 0.725) = 40.90 kN τv=40900/(400x 725) =0.14 MPa < τc,max. This is very small Steel at this section is 4 – 16 mm, 804 mm2, pt=0.278% τc =0.38N/mm2 (IS:456-2000). No shear steel is needed. Provide minimum steel. Using 12 mm diameter 2- legged stirrups, Spacing = 0.87 x 415 x (2 x 113) /(0.4x400) =509.9 mm say 300 mm c/c

Page 32: Design and Detailing of steel in Combined Footingslibvolume3.xyz/civil/btech/semester6/designdrawingofrcstructures/...Design of combined footing – Slab and Beam type- Problem 2 2

400x400 400x400

#12@300, 2L Stp

#12@190, 4L Stp

#12@300, 2L Stp

#12@190, 4L Stp

#12@300, 2L Stp

4-#25 + 2-#16 2-#16

4-#16

1 m 3.5 m 1 m

2-#16 Side face

2-#12

2-#16

Page 33: Design and Detailing of steel in Combined Footingslibvolume3.xyz/civil/btech/semester6/designdrawingofrcstructures/...Design of combined footing – Slab and Beam type- Problem 2 2

4-25 2-16

C/S at Centre C/S at the junction (Right of B)

400 400

800 800

400

2100

2-16

4-16

2-φ16

Page 34: Design and Detailing of steel in Combined Footingslibvolume3.xyz/civil/btech/semester6/designdrawingofrcstructures/...Design of combined footing – Slab and Beam type- Problem 2 2

5500 mm

2.1

m

Plan of footing slab

Φ20@130

Φ8@160