Page 1: Derrick Haas Regional Technical Manager - IEEE Region 5...Simple Protective Relay Auxiliary input (ac or dc) Settings Output (dry contact) Contact used to energiz e circuit breaker

Copyright © SEL 2016

Protective Relay Fundamentals

Derrick Haas

Regional Technical Manager

Page 2: Derrick Haas Regional Technical Manager - IEEE Region 5...Simple Protective Relay Auxiliary input (ac or dc) Settings Output (dry contact) Contact used to energiz e circuit breaker

• Fault types

• Electrical equipment damage

• Time versus current plot

• Protection requirements

• Protection system elements

Protection Review

Page 3: Derrick Haas Regional Technical Manager - IEEE Region 5...Simple Protective Relay Auxiliary input (ac or dc) Settings Output (dry contact) Contact used to energiz e circuit breaker

• Short circuits

• Contacts with ground

▪ Isolated neutral systems

▪ High-impedance grounded systems

• Open phases

Power System Faults

Page 4: Derrick Haas Regional Technical Manager - IEEE Region 5...Simple Protective Relay Auxiliary input (ac or dc) Settings Output (dry contact) Contact used to energiz e circuit breaker

Typical Short-Circuit-Type Distribution

Single-phase-to-ground 70 – 80%

Phase-to-phase-to-ground 10 – 17%

Phase-to-phase 8 – 10%

Three-phase 2 – 3%

Page 5: Derrick Haas Regional Technical Manager - IEEE Region 5...Simple Protective Relay Auxiliary input (ac or dc) Settings Output (dry contact) Contact used to energiz e circuit breaker

abc

Distribution

Substation

Faults in Electrical SystemsProduce Current Increments

I

I

Wire

Page 6: Derrick Haas Regional Technical Manager - IEEE Region 5...Simple Protective Relay Auxiliary input (ac or dc) Settings Output (dry contact) Contact used to energiz e circuit breaker

–t

e eiT(t) (T – T )e T= +2dWI R

dt=

Temperature Rise From Current

t

T

Equilibrium

Ti

Te

I

T

Constant

Current

Page 7: Derrick Haas Regional Technical Manager - IEEE Region 5...Simple Protective Relay Auxiliary input (ac or dc) Settings Output (dry contact) Contact used to energiz e circuit breaker

Factors Influence Wire Heating

d

Current

Magnitude Wire Material

Properties

Ambient

Temperature

and Other

Environmental

Factors

I

Wire Size

Page 8: Derrick Haas Regional Technical Manager - IEEE Region 5...Simple Protective Relay Auxiliary input (ac or dc) Settings Output (dry contact) Contact used to energiz e circuit breaker

t

T

td

Insulation Damage

Ti

Td

Te

Insulated Conductor (Cable) Thermal Damage

I

Insulation

Page 9: Derrick Haas Regional Technical Manager - IEEE Region 5...Simple Protective Relay Auxiliary input (ac or dc) Settings Output (dry contact) Contact used to energiz e circuit breaker

Damage

Curve

I1Imd I

t

I2 I3

t1t2t3

t2t3 t

T

t1

Td

Ti

I = Imd

I = I1

I = I2 > I1

I = I3 > I2

Insulated Conductor Thermal Damage

I

T

Page 10: Derrick Haas Regional Technical Manager - IEEE Region 5...Simple Protective Relay Auxiliary input (ac or dc) Settings Output (dry contact) Contact used to energiz e circuit breaker

Damage

Curve

Rating

In Imd I

t

Electrical Equipment ComponentThermal Damage Curve

Page 11: Derrick Haas Regional Technical Manager - IEEE Region 5...Simple Protective Relay Auxiliary input (ac or dc) Settings Output (dry contact) Contact used to energiz e circuit breaker

Mechanical forces (f1 and f2) produced by short-circuit

currents cause instantaneous damage to busbars,

insulators, supports, transformers, and machines

Mechanical Damage

i1i2

f1 f2

f1 (t) =k i1 (t) i2 (t)

Page 12: Derrick Haas Regional Technical Manager - IEEE Region 5...Simple Protective Relay Auxiliary input (ac or dc) Settings Output (dry contact) Contact used to energiz e circuit breaker

Real-World Mechanical Damage

Page 13: Derrick Haas Regional Technical Manager - IEEE Region 5...Simple Protective Relay Auxiliary input (ac or dc) Settings Output (dry contact) Contact used to energiz e circuit breaker

• Reliability

▪ Dependability

▪ Security

• Selectivity

Power System Protection Requirements

Page 14: Derrick Haas Regional Technical Manager - IEEE Region 5...Simple Protective Relay Auxiliary input (ac or dc) Settings Output (dry contact) Contact used to energiz e circuit breaker

• Speed

▪ System stability

▪ Equipment damage

▪ Power quality

• Sensitivity

▪ High-impedance faults

▪ Dispersed generation

Power System Protection Requirements

Page 15: Derrick Haas Regional Technical Manager - IEEE Region 5...Simple Protective Relay Auxiliary input (ac or dc) Settings Output (dry contact) Contact used to energiz e circuit breaker

• Fault detection

• Faulted element disconnection

• Fault indication

Protection Functions

Page 16: Derrick Haas Regional Technical Manager - IEEE Region 5...Simple Protective Relay Auxiliary input (ac or dc) Settings Output (dry contact) Contact used to energiz e circuit breaker

• Fuses

• Automatic reclosers

• Sectionalizers

• Circuit breakers

• Protective relays

Protective Devices

Page 17: Derrick Haas Regional Technical Manager - IEEE Region 5...Simple Protective Relay Auxiliary input (ac or dc) Settings Output (dry contact) Contact used to energiz e circuit breaker

• Protective

• Regulating

• Reclosing and synchronism check

• Monitoring

• Auxiliary

Relay Classification

Page 18: Derrick Haas Regional Technical Manager - IEEE Region 5...Simple Protective Relay Auxiliary input (ac or dc) Settings Output (dry contact) Contact used to energiz e circuit breaker

IEEE C37.2 Device Numbers

51 Time-overcurrent relay

50 Instantaneous-overcurrent relay

67 Directional-overcurrent relay

21 Distance relay

87 Differential relay

52 Circuit breaker

Page 19: Derrick Haas Regional Technical Manager - IEEE Region 5...Simple Protective Relay Auxiliary input (ac or dc) Settings Output (dry contact) Contact used to energiz e circuit breaker

Protective Relaying System

52

Relay

DC

Supply

Communications

Channel

DC

Supply

Circuit Breaker

Current

Transformers

(CTs)

Voltage

Transformers

(VTs)

Page 20: Derrick Haas Regional Technical Manager - IEEE Region 5...Simple Protective Relay Auxiliary input (ac or dc) Settings Output (dry contact) Contact used to energiz e circuit breaker

• Protective relays

• Circuit breakers

• CTs and VTs (instrument transformers)

• Communications channels

• DC supply system

• Control cables

Protection System Elements

Page 21: Derrick Haas Regional Technical Manager - IEEE Region 5...Simple Protective Relay Auxiliary input (ac or dc) Settings Output (dry contact) Contact used to energiz e circuit breaker

• Protective relays

▪ Monitor

▪ Detect

▪ Report

▪ Trigger

• Circuit breakers

▪ Interrupt

▪ Isolate from

abnormal condition

Protection System Elements

Page 22: Derrick Haas Regional Technical Manager - IEEE Region 5...Simple Protective Relay Auxiliary input (ac or dc) Settings Output (dry contact) Contact used to energiz e circuit breaker

• CTs

▪ Current scaling

▪ Isolation

• VTs

▪ Voltage scaling

▪ Isolation

Instrument Transformers

Page 23: Derrick Haas Regional Technical Manager - IEEE Region 5...Simple Protective Relay Auxiliary input (ac or dc) Settings Output (dry contact) Contact used to energiz e circuit breaker

Overcurrent Relay Connections

52

50, 51 50, 51 50, 51 50N, 51N

3I0

Ia

IbIc

a

b

c

Residual

Current

Page 24: Derrick Haas Regional Technical Manager - IEEE Region 5...Simple Protective Relay Auxiliary input (ac or dc) Settings Output (dry contact) Contact used to energiz e circuit breaker

DC Station

Battery SI Relay

Contact

Relay

Circuit

Breaker

52a

(+)

(–)

SI

52

TC

DC Tripping Circuit

Page 25: Derrick Haas Regional Technical Manager - IEEE Region 5...Simple Protective Relay Auxiliary input (ac or dc) Settings Output (dry contact) Contact used to energiz e circuit breaker

• 51 elements

▪ Pickup setting

▪ Time-dial setting

• 50 elements

▪ Pickup setting

▪ Time delay

Overcurrent Relay Setting

Page 26: Derrick Haas Regional Technical Manager - IEEE Region 5...Simple Protective Relay Auxiliary input (ac or dc) Settings Output (dry contact) Contact used to energiz e circuit breaker

• What is the function of power system protection?

• Name two protective devices

• For what purpose is IEEE device 52 used?

• Why are seal-in and 52a contacts used in the dc

control scheme?

• In a typical feeder OC protection scheme, what does

the residual relay measure?

Review

Page 27: Derrick Haas Regional Technical Manager - IEEE Region 5...Simple Protective Relay Auxiliary input (ac or dc) Settings Output (dry contact) Contact used to energiz e circuit breaker

Copyright © SEL 2016

Digital Relay Basics

Page 28: Derrick Haas Regional Technical Manager - IEEE Region 5...Simple Protective Relay Auxiliary input (ac or dc) Settings Output (dry contact) Contact used to energiz e circuit breaker

Simple Protective Relay

Auxiliary input

(ac or dc)

Settings

Output (dry contact)

Contact used to

energize circuit

breaker trip coil

Set relay thresholds

and operation time

Current,

voltage (I and V),

or other quantities

Input

Page 29: Derrick Haas Regional Technical Manager - IEEE Region 5...Simple Protective Relay Auxiliary input (ac or dc) Settings Output (dry contact) Contact used to energiz e circuit breaker

Electromechanical Instantaneous Overcurrent Elements

Page 30: Derrick Haas Regional Technical Manager - IEEE Region 5...Simple Protective Relay Auxiliary input (ac or dc) Settings Output (dry contact) Contact used to energiz e circuit breaker

Magnetic Attraction UnitInstantaneous Element

Force of contact: F = k • I2

Contacts

ArmatureHinge

Coil

Contacts

Coil

Iron core

Adjustable

stop

Contacts

Hinge

Restraining

magnet

Operating

magnet

Page 31: Derrick Haas Regional Technical Manager - IEEE Region 5...Simple Protective Relay Auxiliary input (ac or dc) Settings Output (dry contact) Contact used to energiz e circuit breaker

• Tap in relay current coil

• Adjust air gap

• Adjust spring

Alternatives for Setting Pickup Current

Page 32: Derrick Haas Regional Technical Manager - IEEE Region 5...Simple Protective Relay Auxiliary input (ac or dc) Settings Output (dry contact) Contact used to energiz e circuit breaker

Electromechanical Inverse-Time Overcurrent Elements

Page 33: Derrick Haas Regional Technical Manager - IEEE Region 5...Simple Protective Relay Auxiliary input (ac or dc) Settings Output (dry contact) Contact used to energiz e circuit breaker

Induction Disk Overcurrent Relay -5 -6 -7 -8 -9 1.0

Main coil

NT turns

Spring

Permanent

magnetMain core

Disk

Moving

contact

Time dial

Page 34: Derrick Haas Regional Technical Manager - IEEE Region 5...Simple Protective Relay Auxiliary input (ac or dc) Settings Output (dry contact) Contact used to energiz e circuit breaker

Simplified ViewShaded Pole Element

Main

coil

NT

turns

Permanent

magnet

Taps

Spring

Disk

AxisΦ2Φ1

Page 35: Derrick Haas Regional Technical Manager - IEEE Region 5...Simple Protective Relay Auxiliary input (ac or dc) Settings Output (dry contact) Contact used to energiz e circuit breaker

Electromagnetic Induction Principle

Φ2Φ1

F2F1iΦ1

iΦ1

iΦ2

iΦ2

Torque

Page 36: Derrick Haas Regional Technical Manager - IEEE Region 5...Simple Protective Relay Auxiliary input (ac or dc) Settings Output (dry contact) Contact used to energiz e circuit breaker

• Pickup current setting – taps in relay current coil

• Time-current curve setting – controls initial disk

position (time-dial setting)

Summary of Induction 51 Element Settings

Page 37: Derrick Haas Regional Technical Manager - IEEE Region 5...Simple Protective Relay Auxiliary input (ac or dc) Settings Output (dry contact) Contact used to energiz e circuit breaker

Microprocessor-Based Protection

Page 38: Derrick Haas Regional Technical Manager - IEEE Region 5...Simple Protective Relay Auxiliary input (ac or dc) Settings Output (dry contact) Contact used to energiz e circuit breaker

Digital Relay I/O Scheme

Computer-based

relay (digital)

Computer

communications

Analog inputs

Discrete inputs

Auxiliary inputs

(ac or dc)

Dry contact outputs

(trip and alarm)

“Live” outputs

Page 39: Derrick Haas Regional Technical Manager - IEEE Region 5...Simple Protective Relay Auxiliary input (ac or dc) Settings Output (dry contact) Contact used to energiz e circuit breaker

Digital Relay Architecture

Microprocessor

RAM ROM / PROM EEPROM

Discrete

output

subsystem

Operation

signaling

Analog

input

subsystem

Discrete

input

subsystem

Analog-to-

digital

(A/D)

conversion

Tripping

Outputs

Communications

ports

Page 40: Derrick Haas Regional Technical Manager - IEEE Region 5...Simple Protective Relay Auxiliary input (ac or dc) Settings Output (dry contact) Contact used to energiz e circuit breaker

Digital Relay Algorithm

Read present sample k

Digital filtering

Phasor calculation

Protection methods

Relay logic

Modify if

required

Trip order

No trip

Page 41: Derrick Haas Regional Technical Manager - IEEE Region 5...Simple Protective Relay Auxiliary input (ac or dc) Settings Output (dry contact) Contact used to energiz e circuit breaker

Relay OperationAnalog Inputs

Page 42: Derrick Haas Regional Technical Manager - IEEE Region 5...Simple Protective Relay Auxiliary input (ac or dc) Settings Output (dry contact) Contact used to energiz e circuit breaker

Signal Path for Microprocessor-Based Relays

Analog

low-pass

filter

A/D

conversion

Digital

cosine

filter and

phasor

Magnitude

and

impedance

Current

transformer

(CT)

Potential

transformer

(PT)

Page 43: Derrick Haas Regional Technical Manager - IEEE Region 5...Simple Protective Relay Auxiliary input (ac or dc) Settings Output (dry contact) Contact used to energiz e circuit breaker

A/D Conversion

A/D

Analog signal Digital signal

00000001

00000101

00001001

00100100

10010000

:.

Input Output

Page 44: Derrick Haas Regional Technical Manager - IEEE Region 5...Simple Protective Relay Auxiliary input (ac or dc) Settings Output (dry contact) Contact used to energiz e circuit breaker

Nonfiltered signal

(samples)

Filtered signal

(samples)

Digital Filtering

Digital filtering

Page 45: Derrick Haas Regional Technical Manager - IEEE Region 5...Simple Protective Relay Auxiliary input (ac or dc) Settings Output (dry contact) Contact used to energiz e circuit breaker

Phasor samples:

magnitude and angle

versus reference

| I |

qReference

Phasor Calculation

Filtered signal

(samples)

Phasor calculation

Page 46: Derrick Haas Regional Technical Manager - IEEE Region 5...Simple Protective Relay Auxiliary input (ac or dc) Settings Output (dry contact) Contact used to energiz e circuit breaker

Sinusoid-to-Phasor Conversion

0 t

A 2

A

0

v(t)

q

Page 47: Derrick Haas Regional Technical Manager - IEEE Region 5...Simple Protective Relay Auxiliary input (ac or dc) Settings Output (dry contact) Contact used to energiz e circuit breaker

Sinusoid to PhasorsCurrent Channels Are Sampled

IA

t

IA

1559

–69

–1656

–2274

–1558

70

1656

2273

1cycles

8

Page 48: Derrick Haas Regional Technical Manager - IEEE Region 5...Simple Protective Relay Auxiliary input (ac or dc) Settings Output (dry contact) Contact used to energiz e circuit breaker

• Pick quadrature samples (1/4-cycle apart)

• Pick current sample (x sample)

• Pick previous sample 1/4-cycle old (y sample)

Sinusoid to Phasors

y sample (1/4-cycle old)

x sample (present)

IA

1559

–69

–1656

–2274

–1558

70

1656

2273

Page 49: Derrick Haas Regional Technical Manager - IEEE Region 5...Simple Protective Relay Auxiliary input (ac or dc) Settings Output (dry contact) Contact used to energiz e circuit breaker

Sinusoid to Phasors

2274

70

2275

X

Y

IA

t

Ia(t)

–88.2

1cycles

8

=

70

2274–arctanAngle

=

x

yarctanAngle

22 )2274(–70M agnitude +=

22 yxMagnitude +=

= + = IA 70 –2274j 2275 – 88.2

Page 50: Derrick Haas Regional Technical Manager - IEEE Region 5...Simple Protective Relay Auxiliary input (ac or dc) Settings Output (dry contact) Contact used to energiz e circuit breaker

Relay OperationRelay Word Bits and Logic

Page 51: Derrick Haas Regional Technical Manager - IEEE Region 5...Simple Protective Relay Auxiliary input (ac or dc) Settings Output (dry contact) Contact used to energiz e circuit breaker

• Instantaneous

overcurrent

• Time overcurrent

• Voltage elements

• Inputs

• Internal relay logic –

SELOGIC® variable (SV)

and latches

• Outputs

Relay Word Bits

Assert to logical 1 when conditions are true,

deassert to logical 0 when conditions are false

Page 52: Derrick Haas Regional Technical Manager - IEEE Region 5...Simple Protective Relay Auxiliary input (ac or dc) Settings Output (dry contact) Contact used to energiz e circuit breaker

• 50P1P = instantaneous phase overcurrent setting

• IA = Phase A measured current

• 50A1 = 1 if IA ≥ 50P1P; 50A1 = 0 if IA < 50P1P

Instantaneous Overcurrent Element

When b (+) terminal is greater than a (–) terminal, c is logical 1

+

_

ca

b

Comparator

+

_

50A150P1P setting

IA

Page 53: Derrick Haas Regional Technical Manager - IEEE Region 5...Simple Protective Relay Auxiliary input (ac or dc) Settings Output (dry contact) Contact used to energiz e circuit breaker

• 50P1 = 1 if 50A1, 50B1, or 50C1 = 1

• 50P1 = 0 if 50A1, 50B1, and 50C1 = 0

Instantaneous Overcurrent Element

When a, b, or c terminal is logical 1, output d is logical 1

50A150B150C1

OR 50P1

ORabc

d

Page 54: Derrick Haas Regional Technical Manager - IEEE Region 5...Simple Protective Relay Auxiliary input (ac or dc) Settings Output (dry contact) Contact used to energiz e circuit breaker

51P1T Phase

Time-Overcurrent Element

Curve Timing and Reset Timing

51P1P

51P1C

51P1TD

51P1RS

51P1CT

51P1MR

Settings

Relay Word Bits

51P1P

51P1T

51P1R

Controls the Torque Control Switch

Pickup

Curve

Timeout

Reset

Torque Control Switch

Setting

51P1P

IP

SELOGIC

Torque Control

Reset TimingSetting

51P1RS=

Electromechanical

1 Cycle

Y

N

51P1TC

State

Torque Control

Switch Position

Logical 1

Logical 0Closed

Open

Min. Response

Const. Time Add.

Electromechanical

Reset? (Y/N)

Time Dial

Curve Type

Pickup

51P1TC

SELOGIC

Setting

Phase Time-Overcurrent ElementSEL-751 Feeder Protection Relay

Page 55: Derrick Haas Regional Technical Manager - IEEE Region 5...Simple Protective Relay Auxiliary input (ac or dc) Settings Output (dry contact) Contact used to energiz e circuit breaker

Phase Time-Overcurrent

ElementSEL-651R-2

Page 56: Derrick Haas Regional Technical Manager - IEEE Region 5...Simple Protective Relay Auxiliary input (ac or dc) Settings Output (dry contact) Contact used to energiz e circuit breaker

p 0.02

0.0104t TD • 0.0226

M – 1

= +

r 2

1.08t TD •

1– M

=

p 2

5.95t TD • 0.180

M – 1

= +

r 2

5.95t TD •

1– M

=

p 2

3.88t TD • 0.0963

M – 1

= +

r 2

3.88t TD •

1– M

=

p 2

5.67t TD • 0.0352

M – 1

= +

r 2

5.67t TD •

1– M

=

p 0.02

0.00342t TD • 0.00262

M – 1

= +

r 2

0.323t TD •

1– M

=

Standard Time-Current CharacteristicsIEEE C37.112-1996

Curve Type Operating Time Reset Time

U1 (moderately inverse)

U2 (inverse)

U3 (very inverse)

U4 (extremely inverse)

U5 (short-time inverse)

Page 57: Derrick Haas Regional Technical Manager - IEEE Region 5...Simple Protective Relay Auxiliary input (ac or dc) Settings Output (dry contact) Contact used to energiz e circuit breaker

U1 Moderately Inverse Curve

M = multiples of pickup

IP = max phase current

M = IP / 51P1P

Time dial shifts curve up

/ down (slower / faster)

Page 58: Derrick Haas Regional Technical Manager - IEEE Region 5...Simple Protective Relay Auxiliary input (ac or dc) Settings Output (dry contact) Contact used to energiz e circuit breaker

• Standard U.S. curves (U1–U5)

• Standard IEC curves (C1–C5)

• Recloser curve:

SEL-651R Time-Overcurrent Curves

A/101 H/122 R/105 2/135 8+/111 16/139

B/117 J/164 T/161 3/140 9/131 17/103

C/133 KP/162 V/137 4/106 KG/165 18/105

D/166 L/107 W/138 5/114 11/141

E/132 M/118 Y/120 6/136 13/142

F/163 N/104 Z/134 7/152 14/119

G/121 P/115 1/102 8/113 15/112

Page 59: Derrick Haas Regional Technical Manager - IEEE Region 5...Simple Protective Relay Auxiliary input (ac or dc) Settings Output (dry contact) Contact used to energiz e circuit breaker

Relay Word Bit Tables8 Relay Word Bits Per Numbered Row

Row Relay Word Bits

1 TLED_08 TLED_07 TLED_06 TLED_05 TLED_04 TLED_03 TLED_02 TLED_01

2 TLED_16 TLED_15 TLED_14 TLED_13 TLED_12 TLED_11 TLED_10 TLED_09

3 TLED_24 TLED_23 TLED_22 TLED_21 TLED_20 TLED_19 TLED_18 TLED_17

4 50A1 50B1 50C1 50P1 50A2 50B2 50C2 50P2

5 50A3 50B3 50C3 50P3 50A4 50B4 50C4 50P4

6 50G1 50G2 50G3 50G4 50Q1 50Q2 50Q3 50Q4

Page 60: Derrick Haas Regional Technical Manager - IEEE Region 5...Simple Protective Relay Auxiliary input (ac or dc) Settings Output (dry contact) Contact used to energiz e circuit breaker

Logic

Page 61: Derrick Haas Regional Technical Manager - IEEE Region 5...Simple Protective Relay Auxiliary input (ac or dc) Settings Output (dry contact) Contact used to energiz e circuit breaker

• Mathematics of logical variables (Relay Word bits)

• Operators – AND, OR, NOT, rising and falling edge,

and parentheses

• SELOGIC control equation Boolean operators

▪ Defined symbols

▪ Application rules

Boolean Logic

Page 62: Derrick Haas Regional Technical Manager - IEEE Region 5...Simple Protective Relay Auxiliary input (ac or dc) Settings Output (dry contact) Contact used to energiz e circuit breaker

SELOGIC Control Equation Operators

Operator Symbol Functionality

Parentheses ( ) Group terms

Negation – Change sign of numerical value

NOT NOT (!) Invert the logic

Rising edge R_TRIG (/)Assert output for one processing interval on

input rising-edge transition

Falling edge F_TRIG (\)Assert output for one processing interval on

input falling-edge transition

Multiply * Multiply numerical values

Page 63: Derrick Haas Regional Technical Manager - IEEE Region 5...Simple Protective Relay Auxiliary input (ac or dc) Settings Output (dry contact) Contact used to energiz e circuit breaker

SELOGIC Control Equation Operators

Operator Symbol Functionality

Divide / Divide numerical values

Add + Add numerical values

Subtract – Subtract numerical values

Comparison<, >, <=,

>=, =, <>Compare numerical values

AND AND (*) Multiply Boolean values

OR OR (+) Add Boolean values

Page 64: Derrick Haas Regional Technical Manager - IEEE Region 5...Simple Protective Relay Auxiliary input (ac or dc) Settings Output (dry contact) Contact used to energiz e circuit breaker

SELOGIC Control Equation Examples

A

A

A

B

B

BC

C

C C = A OR B

C = A AND B

C = A AND NOT B

A B

A B

OR

1

AND

1

AND

1 A B

Page 65: Derrick Haas Regional Technical Manager - IEEE Region 5...Simple Protective Relay Auxiliary input (ac or dc) Settings Output (dry contact) Contact used to energiz e circuit breaker

E = A AND B OR C OR NOT D

Equation implemented

Programmable Logic

Logic

A

B

C

D

E

A

B

DC

E

(–)

(+)

Page 66: Derrick Haas Regional Technical Manager - IEEE Region 5...Simple Protective Relay Auxiliary input (ac or dc) Settings Output (dry contact) Contact used to energiz e circuit breaker

SELOGIC Control Equation Examples

50P1P 50G1P

TR

TRIP

OUT103Normally open;

closes when

OUT103 asserts

When TR equation

asserts, TRIP Relay

Word bit asserts

Page 67: Derrick Haas Regional Technical Manager - IEEE Region 5...Simple Protective Relay Auxiliary input (ac or dc) Settings Output (dry contact) Contact used to energiz e circuit breaker

SEL-387A Internal Trip Logic

Relay

Word

Bit

SELOGIC Control

Equation Settings

TRIP1

TRGTR

TDURD

0(In) (Out)

TR1

ULTR1

TARGET

RESET PB

TAR R Serial

Port Command

TRIP1TRIP2TRIP3TRIP4TRIP5

TRIPL

Minimum Trip

Duration TimerRising

Edge

Detect

Page 68: Derrick Haas Regional Technical Manager - IEEE Region 5...Simple Protective Relay Auxiliary input (ac or dc) Settings Output (dry contact) Contact used to energiz e circuit breaker

SELOGIC Control Equation Example

OUT101 = (51PT OR OUT101) AND NOT TRGTR

!TRGTR

OUT

101

51PT OUT101OUT101 =

Page 69: Derrick Haas Regional Technical Manager - IEEE Region 5...Simple Protective Relay Auxiliary input (ac or dc) Settings Output (dry contact) Contact used to energiz e circuit breaker

• Relay Word bits IN101 and IN102 monitor physical

state inputs

• Debounce timer is built in and settable

Optoisolated Inputs

0–2 s

IN101

IN102

de-energized

energized

logical 0

logical 1

IN101

IN102

0–2 s

0–2 s

0–2 s

Page 70: Derrick Haas Regional Technical Manager - IEEE Region 5...Simple Protective Relay Auxiliary input (ac or dc) Settings Output (dry contact) Contact used to energiz e circuit breaker

Latching Control Logic

SET01 = CLOSE RST01 = TRIP LT01 = 52A

SELOGIC Latch

Equation

Relay

Word Bit

LTnSETn

RSTn

n = 1, 2, 3, etc.

Page 71: Derrick Haas Regional Technical Manager - IEEE Region 5...Simple Protective Relay Auxiliary input (ac or dc) Settings Output (dry contact) Contact used to energiz e circuit breaker

• Set as logic placeholder and timer

• Example settings

▪ SV05 = 50P1

▪ SV05PU = 6 cycles

▪ SV05DO = 60 cycles

• Operation

▪ SV05 asserts when 50P1 asserts

▪ SV05T asserts 0.1 s after 50P1 asserts

▪ SV05T deasserts 1 s after 50P1 deasserts

SV Timer

SV05PU

SV05D0

SV05 SV05

SV05T

Page 72: Derrick Haas Regional Technical Manager - IEEE Region 5...Simple Protective Relay Auxiliary input (ac or dc) Settings Output (dry contact) Contact used to energiz e circuit breaker

• When OUT101 equation is true (logical 1), OUT101 closes

• Example setting: OUT101 = SV05T

• Operation: OUT101 closes after 50P1 has been asserted

for 0.1 s

Outputs

OUT101

OUT102

OUT101

OUT102

logical

0

logical

1

de-energize

energize

OUT101(a)

OUT102(a)

Open

Closed

Page 73: Derrick Haas Regional Technical Manager - IEEE Region 5...Simple Protective Relay Auxiliary input (ac or dc) Settings Output (dry contact) Contact used to energiz e circuit breaker

Track Relay Word Bit State Change With Sequential Events Records (SER)

Example: 50P1 = 4 A; CTR = 1,000; Primary PU = 4,000 A

Page 74: Derrick Haas Regional Technical Manager - IEEE Region 5...Simple Protective Relay Auxiliary input (ac or dc) Settings Output (dry contact) Contact used to energiz e circuit breaker

• Event reports are helpful in fault analysis

• Relays collect 15-cycle (settable) event reports when ER or

any TRIP Relay Word bit asserts, or whenever TRI or PUL

serial port command is executed

• HIS command provides summary of events

Event Reporting

Page 75: Derrick Haas Regional Technical Manager - IEEE Region 5...Simple Protective Relay Auxiliary input (ac or dc) Settings Output (dry contact) Contact used to energiz e circuit breaker

Event Reporting

Page 76: Derrick Haas Regional Technical Manager - IEEE Region 5...Simple Protective Relay Auxiliary input (ac or dc) Settings Output (dry contact) Contact used to energiz e circuit breaker

Event Reporting

Page 77: Derrick Haas Regional Technical Manager - IEEE Region 5...Simple Protective Relay Auxiliary input (ac or dc) Settings Output (dry contact) Contact used to energiz e circuit breaker
Page 78: Derrick Haas Regional Technical Manager - IEEE Region 5...Simple Protective Relay Auxiliary input (ac or dc) Settings Output (dry contact) Contact used to energiz e circuit breaker

• How do microprocessor-based relays create phasors?

• What tools do microprocessor-based relays offer for

fault analysis?

• How do SEL relays create control circuits?

• What are Relay Word bits used for in SEL relays?

Review Questions

Page 79: Derrick Haas Regional Technical Manager - IEEE Region 5...Simple Protective Relay Auxiliary input (ac or dc) Settings Output (dry contact) Contact used to energiz e circuit breaker

• Microprocessor-based relays create phasors from

sinusoid (waveform) inputs

• Relay Word bits control relay I/O

• Microprocessor-based relays offer many

troubleshooting and fault analysis tools

• SELOGIC control equations provide programming

flexibility to create virtual control circuits

Summary

Page 80: Derrick Haas Regional Technical Manager - IEEE Region 5...Simple Protective Relay Auxiliary input (ac or dc) Settings Output (dry contact) Contact used to energiz e circuit breaker

Questions?