Appointment of Construction and Maintenance Agency - Regional Science Museum at Patan, Gujarat Page 1 Department of Science and Technology, Government of Gujarat Responses to Pre- Bid Queries- II(B) Engagement of Construction and Maintenance Agency (CMA) for Regional Science Museum at Patan, Gujarat Council on Science and Technology Department of Science & Technology, Govt. of Gujarat Block B, 7 th Floor, M.S Building, Sector 11, Gandhinagar 382 011 Gujarat, India

Upload: phamquynh

Post on 28-Jun-2018

213 views

Category:

Documents


0 download

TRANSCRIPT

Appointment of Construction and Maintenance Agency - Regional Science Museum at Patan, Gujarat

Page 1

Department of Science and Technology, Government of Gujarat

Responses to Pre- Bid Queries- II(B)

Engagement of Construction and Maintenance Agency (CMA)

for

Regional Science Museum at Patan,

Gujarat Council on Science and Technology

Department of Science & Technology, Govt. of Gujarat

Block B, 7th Floor, M.S Building, Sector 11, Gandhinagar – 382 011

Gujarat, India

Appointment of Construction and Maintenance Agency - Regional Science Museum at Patan, Gujarat

Page 2

S.

No

Page

No. Part of RFP Clause No. Clarification sought with justification, if any Response

1 94 Voulme II -

Schedule 11

I. SEWAGE

TREATMEN

T PLANT

We request authority to clarify the scope of Civil Works

and MEP for Sewage Treatment Plant This will be in Contractor’s scope.

2 Voulme II -

Schedule 11

Sec - C ,

SL.No 5

We request you to confirm the type of stone to be used

for making of facia. Kindly confirm.

Kindly refer Architectural BOQ for the

description mentions Marble/ Granite.

3 Schedule 2 Scope of

Works

We request Authority to Take Permission from all such

Concern department.

Please refer Schedule 2 and Schedule 9 for

all approvals to be taken by DTA and CMA

4 General Reinforceme

nt Details

We request Authority to provide reinforcement details

for Building for calculating quantities.

Reinforcement details shall be provided

during execution stage.

5 General

We request Authority to Provide BOQ in Excel Format No change

6 2

Scope of

Works

We request Authority that kindly Considered the

Tapping/outfall point 1 m Outside the Boundary of

RSM.

Kindly refer schedule 2 & schedule 3,

7 Autocad

Drawing

Autocad

Drawing Kindly Provide Details of D5 - Door type

Please refer description mentioned in BOQ,

3.1 & 3.2 of internal partition and false

ceiling

8

Autocad

Drawing

Autocad

Drawing We Consider it to Single leaf Aluminium glazed Door in

the same area.

Please refer Door Window Schedule in

drawing sheet no. 10741A-AC-1013-AC-

10101

9

Autocad

Drawing

Autocad

Drawing We request authority to kindly provide details/Schedule

of Ventilator

The ventilator details are Width – 1000mm,

Height-1200mm, Cill-1000mm, Lintel –

2250mm

10

Autocad

Drawing

Autocad

Drawing We request Authority to provide Finishing Details at

Ground floor Auditorium Central lobby.

Finishing Details will be same as that of the

corridor.

11

Autocad

Drawing

Autocad

Drawing We request Authority to provide Finishing Details at

ground Floor Room For Services

Finishing Details will be same as that of

AHU.

Appointment of Construction and Maintenance Agency - Regional Science Museum at Patan, Gujarat

Page 3

S.

No

Page

No. Part of RFP Clause No. Clarification sought with justification, if any Response

12

Autocad

Drawing

Autocad

Drawing We request Authority to provide details for Double

Height Entrance Lobby with Cutout Above

Please refer finishing details of double

height atrium in drawing sheet no.

TCE.10741A-AC-1013-AF-10003.

13

Autocad

Drawing

Autocad

Drawing

We request Authority to Kindly provide Finishing

Details for Given Areas for Ground Floor -

1.IBMS ROOM

2. Circulation And Fire Exit Lobby - Grid 3-4 &A-B

3. Circulation And Fire Exit Lobby - Grid 11-12 &A-B

4. Jurassic Theatre

1. Finishing details of IBMS room is same

as that of the control room.

2. Finishing details of Circulation And Fire

Exit Lobby - Grid 3-4 &A-B is same as that

of corridors.

3. Finishing details of Circulation And Fire

Exit Lobby - Grid 11-12 &A-B

Will be same as that of corridors.

4. Finishing details of Jurassic Theater will

be same as that of short documentary

theater.

14

Autocad

Drawing

Autocad

Drawing

Near Office and Central Exhibit Area: Partition Wall of

Various Lenghts have been showed in CAD Drawing,

We request Authority to Kindly Clarify Details such as

Section and Relevant BOQ item to be referred.

Please refer sl. No. 1 of internal partition &

false ceiling for the partitions in central

exhibit area and sl.no.1 & 2 of internal

partition & false ceiling for office area

partition

15

3 Technical

Specification

s 5.2.2 We request you to kindly follow IS 456. IS 10262 can be followed alongwith IS 456.

16

42 Technical

Specification

s 11.5.1

We Request Authority to follow IS code for removal of

formwork. No change

Appointment of Construction and Maintenance Agency - Regional Science Museum at Patan, Gujarat

Page 4

S.

No

Page

No. Part of RFP Clause No. Clarification sought with justification, if any Response

17

44 Technical

Specification

s 13.5 We request authority to Consider as per IS Code No change

18

49-51 Technical

Specification

s

14.8.1,

14.8.2 We request Authority to kindly Follow IS 383-2016. IS 383-2016 can be followed

19

Autocad

Drawing

Autocad

Drawing

We request Authority to Provide footing Layout and

Footing Section for main Building and Boundary Wall

for Quantity Calculation

The details of the same will be provided

during execution stage.

20

In Gujarat state cement used is Abuja, Ultratech, saghi,

JK Lakshmi, sidhee and Hathi brand,but in list of

Approved Makes only Ultratech is given. All these brands

are I.S.I approved makes, hence it is desirable that above

said brands may be added in approved make list please.

A.C.C. and Ultratech are already part of

approved make list. In addition to the brands

mentioned in approved make list, Ambuja,

Ultratech, Sanghi and JK Lakshmi cement

are included

21 NA

TCE

10741A-EL-

4000-AU-

40001

Drawing

40 KVA UPS with ACDB is shown but the UPS panel is

missing. Kindly Calrify is the UPS Panel needs to be

consider or not? If Needs to Consider, Kindly Provide

the SLD for the same.

UPS along with distribution board already

been shown in SLD. Please refer

TCE.10741A-EL-4000-AU-40001 sheet 3

of 3

22 NA

TCE

10741A-EL-

4000-AU-

40001

Drawing SLD for Fire Panel, WTP Panel is not Shown in SLD.

Kindly Confirm the consideration.

Fire Panel and WTP Panel shall be as per

Package requirements. In present scheme,

only SINGLE POINT supply to these panels

considered.

Appointment of Construction and Maintenance Agency - Regional Science Museum at Patan, Gujarat

Page 5

S.

No

Page

No. Part of RFP Clause No. Clarification sought with justification, if any Response

23 NA

TCE 10741A-

EL-4000-AU-

40001 Drawing

SLD for HVAC Panel is not Shown in SLD. Kindly

Confirm the consideration.

HVAC Panel shall be as per Package

requirements. Only SINGLE POINT supply

is considered in Electrical Single Line

Diagrams.

24 NA

TCE 10741A-

EL-4000-AU-

40001 Drawing

Kindly Clarify the Purpose of 12 Nos 40A FP MCB &

10 Nos 16A DP MCB shown at the outgoing terminal of

UPS and also the Size of cable to be used for the same.

40A, 4P MCBs will feed downstream

Emergency Lighting Distribution Boards.

Other DP MCBs will be used to supply UPS

power to various requirments during

detailing. (like BMS, exhibit, Workstation

etc. )

Cable Sizes: 40A 4P MCB - 4C X 25

sq.mm. Cable, DP MCB's - Upto 16 sq.mm.

25 NA General

NA Kindly Provide the Details of DB to be Provided for Lift

Purpose.

Lift Panel (DB) shall be as per Lift's

requirement. Only Single point supply

considered for Lift Panel.

26 NA General

NA Light Fixture for Lift is missing in Drg, Kindly confirm

the consideration. Light Fixture in Lift, will be part of lift car.

27 NA General

NA

Kindly Provide the Size of Wire/Cables used for 70W

Flood Lights, 50W Down Lighters, Up Lighters, Object

Focus Lights, 22W Down Lighters, Special Light

Fixtures

For Flood Lights - upto 6 sq.mm. Wire /

cable. For others 2.5 / 4 sq.mm. wires.

28 NA

TCE 10741A-

EL-4000-AU-

40003 Drawing

Please Provide the Specification/Model Cat Ref for

Below Mentioned Lights

1. Down Lightes

2. Ceiling Suspension Lights

3. Uplighters, Floor/Base Mounting

4. Object Focus Lights (Ceiling Mounted)

For these items, refer description mentioned

in Architecture BOQ for Lighting fixtures. It

is clearly mentions the suggested vendors

for the same. These are general lighting and

there cannot be particular specifications for

the same. Model/ Cat Ref no are vendor

specific and depends on vendor to vendor.

29 NA

BOQ,

Schedule 11

15.1.6, 16.1,

16.2, 16.4,

16.6, 16.7

Please Provide the Use of Following Items.

Item 15.1.6, 16.1, 16.2, 16.4, 16.6, 16.7

15.1.6 - is EXIT Light. Already shown in

Lighting Layout.

Appointment of Construction and Maintenance Agency - Regional Science Museum at Patan, Gujarat

Page 6

S.

No

Page

No. Part of RFP Clause No. Clarification sought with justification, if any Response

16.1 to 16.7 are Street Lighting items. -

They are shown in Drawing Number

TCE.10741A-EL-4000-GL-40013

30 NA General

Please Provide Drg for Special Light Fixtures

Please refer TCE.10741A-EL-4000-GL-

40002-03-04-05-06 - LIGHTING LAYOUT

provided in tender drawings.

31 NA

Technical

Specification

& BOQ NA

The BOQ Items shows the capacity of DO Fuse to be

install is 11KKKV but as per technical specs it is 33 KV,

Please confirm the size of fuse to be considered.

Kindly note that electrical system is 11kV

system so all equipment shall be 11kV rated

only.

32 NA General

NA Kindly Provide the Details of DB to be Provided for Lift

Purpose. Refer response to query 25.

33 NA General

NA Light Fixture for Lift is missing in Drg, Kindly confirm

the consideration. Refer response to query 26.

34 NA

TCE-

10741A-EL-

4000-AU-

40001

Drawing

Kindly Clarify the Purpose of 12 Nos 40A FP MCB &

10 Nos 16A DP MCB shown at the out going terminal of

UPS and also the Size of cable to be used for the same.

Refer response to query 24.

35 NA General

NA Please Provide the Cable Route and Earthling Route, for

Calculation of Quantities of Cable & Earthing Items.

Please refer TCE.10741A-EL-4000-SE-

40014 - FLOOR EARTHING &

LIGHTNING PROTECTION LAYOUT

provided in tender drawings.

36 NA

Technical

Specification Specificatio

n Kindly Provide the specification for Distribution Boards.

We believe you are referring to LDB /

PDBs. They shall be as per Manufacturer's

standard. List of approved makes already

given. Please refer it to schedule 3.

Appointment of Construction and Maintenance Agency - Regional Science Museum at Patan, Gujarat

Page 7

S.

No

Page

No. Part of RFP Clause No. Clarification sought with justification, if any Response

37 NA

Technical

Specification

& BOQ

Specificatio

n

The Technical specification of BMS System is included

in Schedule 3 but the same is not consider in BOQ,

Kindly Confirm the consideration.

Please consider the specifications mentioned

in the Schedule 3 for BMS

38 NA

Technical

Specification

& BOQ

Specificatio

n

Please Provide Technical Specification of Ticket

Counter Software if any.

As such there are no technical specifications

for Ticketing software. Generally they have

data sheets which are vendor specific. Data

sheets from the vendor can be provided

which will be approved by Authority/DTA.

39

BOQ &

Drawing

DSR Item

No 4.6 In

Electrical &

TCE-

10739A-EL-

4026-GL-

40020

In Drg the height is mentionede as 75mm but in BOQ

item is of 50mm. Kindly confirm which size is to be

considered.

The dwg no. mentioned is not for RSM

Patan. Pls Clarify. Pls follow description

mentioned in BOQ for cable tray details.

40 BOQ

DSR Item

No. 17.1,

17.2, 17.3,

17.4, 17.5,

17.6

Kindly Provide the area where 3Cx2.5Sqmm Cu FR

PVC Insulated Cabel to be used and where

2x2.5+1x1.5Sqmm FRLS PVC Circuit is to be used.

3Cx2.5Sqmm Cu FR PVC- Primary Points-

Lighting

2x2.5+1x1.5Sqmm FRLS PVC- Secondary

points-Lighting

41 Annexure 5

Annexure 5 Themic Blue Lighting is not visible; Provide the Auto

cad Drg for the same.

Autocad dwgs will be provided against

submission of NDA. Please refer

TCE.10741A-EL-4000-GL-40002 for the

same.

42 General

General Please provide auto cad drawing for special lights

Autocad dwgs will be provided against

submission of NDA. Please refer

TCE.10741A-EL-4000-GL-40002 for the

same.

Appointment of Construction and Maintenance Agency - Regional Science Museum at Patan, Gujarat

Page 8

S.

No

Page

No. Part of RFP Clause No. Clarification sought with justification, if any Response

43 Page no

51

5-RFP-

Volume-I-

Draft-

Contract-

Schedule-11

BOQ-2.00-

Centrifugal

Pumps:

Shall we consider pump with thermal insulation with

cladding ? Please confirm

Yes, Pump shall have thermal insulation

with cladding as per the relevant piping

insulation thickness

44 Page no

51

5-RFP-

Volume-I-

Draft-

Contract-

Schedule-11

BOQ- 3.0 -

Cooling

Tower

CTI Certified cooling tower Required or Not? Please

confirm. Not Required

45 Page no

52 to 55

5-RFP-

Volume-I-

Draft-

Contract-

Schedule-11

BOQ- 4.0-

Canteen Air

Handling

Units:

BOQ- 5.0-

Kitchen Air

Handling

Unit (100%

Fresh Air):

BOQ- 6.0-

Ceiling

Suspended

Air

Handling

Unit

BOQ-

7.0,8.0-

Floor

Mentioned static pressure is Esp or TSP ?please confirm.

(ESP- External static pressure

TSP- Total Static pressure)

TSP.

Appointment of Construction and Maintenance Agency - Regional Science Museum at Patan, Gujarat

Page 9

S.

No

Page

No. Part of RFP Clause No. Clarification sought with justification, if any Response

Mounted

Air

Handling

Units

46 Page no

55

5-RFP-

Volume-I-

Draft-

Contract-

Schedule-11

BOQ- 9.0

Floor

Mounted

Heat

Recovery

AirHandling

Unitsfor

FreshAir:

Please provide the unit selection conditions :-

a) Fresh air condition for the summer and Monsoon.

B) return Air condition

Refer Technical Specification Clause No-5

for Outdoor Design Conditions And Clause

No-6.01 for Indoor Design Conditions

47 Page no

57

5-RFP-

Volume-I-

Draft-

Contract-

Schedule-11

BOQ- 12.0

High Wall

Split AC

Units:

Hi wall units are inverter type or non inverter type ?

Please confirm Inverter Type

48 Page no

59

5-RFP-

Volume-I-

Draft-

Contract-

Schedule-11

B) Ducting:

1.00 GSS

Factory

Fabricated

Ducting:

Ducting is 180 GSM or 120GSM ? Please confirm.

As per Technical Specification for Duct

work, Clause for Air Distribution Point No-

3.01-C & 4.01-C ,

The GSM Value shall be 120

49 Page no

59

5-RFP-

Volume-I-

Draft-

B) Ducting:

1.04

QTY shown for 18G is R/O but amount is shown. Please

confirm?

The quantity shown in item description is

Rate only. Refer Corrigendum V(b)

attached..

Appointment of Construction and Maintenance Agency - Regional Science Museum at Patan, Gujarat

Page 10

S.

No

Page

No. Part of RFP Clause No. Clarification sought with justification, if any Response

Contract-

Schedule-11

50 Page no

64

5-RFP-

Volume-I-

Draft-

Contract-

Schedule-11

E)Insulation

Works

6.03(a)

6.04(c)

6.05(c)

Amount is not reflecting for the item.

The total amount for these items comes out

to be Rs. 21414. Refer Corrigendum V (b)

attached.. Please note that the BOQ is

indicative in nature and the project is

awarded on a lump sump basis.

51 Page no

21

5-RFP-

Volume-I-

Draft-

Contract-

Schedule-11

GRAND

TOTAL ACTUAL VALUE - 39960375.83

Please consider the actual value. Refer

Corrigendum V (b) attached

52 Schedule 3-

Exhibits

As per the discussion over the pre bid meeting, it is

suggested by the Authority to use the specified videos

from Youtube for the main content source for the

interactive exhibits as an edited version for the same.

We would like to know that who will take the ownership

for the copyrights of the same videos. Kindly clari

Refer Corrigendum V(b) attached for RFP

Volume II, Schedule 2 -Scope of Work

53 Schedule 3-

Exhibits

We would request to upload detailed design & AV BOQ

for three museums for our detailing of the appropriate

propositions

Please Refer Corrigendum V(b) Annexure 1

Exhibit report(Schedule 3- RFP Volume II).

AV design and BOQ is part of scope of

CMA

54 Schedule-3

Exhibit

Report

Chapter 8/7

– Theming

Lack of clarity/ text readability is an issue and hence

can’t comprehend what’s written

This section has been removed and detailed

3D views are attached as Annexure 1. Please

Refer Corrigendum V(b) Annexure 1

Exhibit report(Schedule 3- RFP Volume II)

Appointment of Construction and Maintenance Agency - Regional Science Museum at Patan, Gujarat

Page 11

S.

No

Page

No. Part of RFP Clause No. Clarification sought with justification, if any Response

55 Schedule-3

Exhibit

Report

Annexure 1: Titling of gallery is missing Please Refer Corrigendum V(b) Annexure 1

Exhibit report(Schedule 3- RFP Volume II)

56 Schedule-3

Exhibit

Report

Annexure 1: No details in Projector Room except make/brand of

Projector

Details of the projector room have been

updated in the exhibit list. Please Refer

Corrigendum V(b) Annexure 1 Exhibit

report(Schedule 3- RFP Volume II)

57 Schedule-3

Exhibit

Report

Detail brief of Video content required wherever video is

to be developed

Video content details have been updated.

Please Refer Corrigendum V(b) Annexure 1

Exhibit report(Schedule 3- RFP Volume II)

58 Schedule-3

Exhibit

Report

Simulator have been suggested at many places, details of

the same are missing

Simulators details have been updated. Please

Refer Corrigendum V(b) Annexure 1

Exhibit report(Schedule 3- RFP Volume II)

59 Schedule-3

Exhibit

Report

B10_EX 01 & 02: POP & FRP has been jointly

suggested – are you sure on this?

Either of the two can be used.

60 Schedule-3

Exhibit

Report

B10_EX 13: Details required with ref to number of seats 4 seats

61 Schedule-3

Exhibit

Report

B10_EX 14: Clarity needed

12 models shall be placed

Appointment of Construction and Maintenance Agency - Regional Science Museum at Patan, Gujarat

Page 12

S.

No

Page

No. Part of RFP Clause No. Clarification sought with justification, if any Response

62 Schedule-3

Exhibit

Report

B10_EX 15: Number of Pods? Number of animals?

Should they be real or fabricated

Bottled animals shall be real. The count of

animals has been specified in the exhibit list

63 Schedule-3

Exhibit

Report

Touch Screen Kiosks - size and technical specifications

needed

17” touch screen kiosk shall be used.

64 Schedule-3

Exhibit

Report

Content Brief for Touch screen kiosk missing

Content brief has been specified at various

places

65 Schedule-3

Exhibit

Report

For installations/models/statics/hardware – certain

vendors are suggested, do we have to only source from

them/ is it compulsory to only buy from these identified

vendors? Or can we procure from elsewhere with

equivalent specs or customize our self

The exhibits shall be procured from the

suggested vendors only. In eventuality of

non-availability of specific exhibit with

suggested vendor, same shall be dealt on

case to case basis at the time of execution

with prior approval from Authority/DTA

66 Schedule-3

Exhibit

Report

Content/copy curation has to be done by the agency or the

content will be given by the consultant? In case the

content has to be curated by the agency who will be the

approving authority of the same and the timelines?

The theme of content shall be specified by

DTA. Actual development of content/ copy

curation shall be done by the CMA and it

shall be approved by DTA/Authority

67 RFP-Volume-

II, Schedule3 Tender Drawings No. TCE.10741A-1019-LP-16413,

Quantity of 60mm thick interlocking concrete pavers is

Please consider volume of 2025 sqm. Also

refer Annexure 3.0 for updated BOQ.

Appointment of Construction and Maintenance Agency - Regional Science Museum at Patan, Gujarat

Page 13

S.

No

Page

No. Part of RFP Clause No. Clarification sought with justification, if any Response

2410 SQMT given whereas 2025 SQMT given in BOQ.

Please confirm.

68

RFP-Volume-

II

BOQ Item No. D3 and D4 in Landscape, Unpolished kota

tile (25mm thick) and Mirror kota in outdoor (40mm

thick) given whereas not given. Please provide the

location for the same on drawing.

This is shown in the drawing near the

sundial area, please check legend and

drawing.

69

RFP-Volume-

II, Schedule3

Tender Drawings No. TCE.10741A-AC-1013-AC-

10101, Door & Window schedule, Ref. RFP-Volume-I,

BOQ Item No. D15.1 pg no. 6. Please provide

specification and separate item in BOQ for all types of

fire rated door.

Please refer Annexure 3.0 for description in

BOQ. BOQ item no. D-15.1 shall be

applicable for all other fire doors.

70 RFP-Volume-

II, Schedule3

Tender Drawings, DRG no. TCE.10741A-AC-1013-DW-

10141 (Door and Window schedule) given in list. Please

provide the same.

Door window schedule is provided in Drg

no. TCE.10741A-AC-1013-AC-10101.

Hence no separate drawing for door window

schedule is required. Please ignore the Drg

No. provided in list.

71

RFP-Volume-

II, Schedule3

Tender Drawings No. TCE.10741A-AC-1013-AC-

10101, Door & Window schedule, Quantity of Automatic

Glazed sliding door (GD1) 14 No. Given whereas 13No.

given in BOQ Arch. Items No. D5. Please confirm.

Please refer Annexure 4.0 Drawings No.

TCE.10741A-AC-1013-AC-10101 for

revised drawing. Number of GD1 are 13 and

the same is incorporated in revised drawing.

72 RFP-Volume-

II, Schedule3

Tender Drawings No. TCE.10741A-AC-1013-AC-

10101, Door & Window schedule, Quantity of FD4 is not

match on provided floor plan. Pease confirm.

Please refer Annexure 4.0 Drawings No.

TCE.10741A-AC-1013-AC-10101 for

revised drawing. Quantity of FD-4 has been

revised in drawing.

Appointment of Construction and Maintenance Agency - Regional Science Museum at Patan, Gujarat

Page 14

S.

No

Page

No. Part of RFP Clause No. Clarification sought with justification, if any Response

73 RFP-Volume-

II, Schedule3

Tender Drawings No. TCE.10741A-AC-1013-AC-10101

to 10104, 1000mm and 950+250mm High SS railing

given whereas same item given in kg in BOQ. Please

provide detail drawings of same item.

The item for SS railing is considered in kg.

Please refer Annexure 4.0 Drg No.

TCE.10741A-AC-1013-AC-10002 revised

for all types of railing. In the revised Tender

drawings different types of railings are

indicated. The length of the railing may be

calculated by bidder as per tender drawings.

74

Please provide detail drawings of connecting bridge

Details of connecting bridge are already

given in Tender Drawing No. TCE.10741A-

CV-3000-RC-30059 & 30060.

75 RFP-Volume-

II, Schedule3

Tender Drawings No. TCE.10741A-AC-1013-AC-10215

(Partition wall layout), vinyl wall paper mentioned

whereas same item not given in BOQ. Please provide

BOQ for the same.

All such partitions walls shall be “Gypsum

board partition” as per BOQ item no. F-1.1.

Vinyl wall paper is considered in BOQ of

‘Exhibits’

76

Please provide BOQ for Toilet cubical and location for

the same in drawing.

All the toilet partitions are made of masonry

wall, having tiles finish. Hence there is no

separate item for toilet cubicle.

77 RFP-Volume-

I BOQ

For Civil and Structural works, Grand total is not match

with actual amount. For Example: SOQ Item No. L 30

(Water Proofing), = 480 sqm x 505.90Rs/sqm =

2,42,832.00 Rs. Amount whereas 2,59,830.24 Rs given in

BOQ. Please correct arithmetic error.

Please consider the final amount in BOQ.

Contingencies are added in the final amount.

Kindly note that the estimates are only for

reference

78 RFP-Volume-

II, Schedule3

Tender Drawings No. TCE.10741A-AC-1013-AC-

10103, L shaped sofa not shown but quantity is

considered in BOQ. Please confirm.

For sofa and all other furniture tender drg

no. TCE.10741A-AC-1013-IW-10201 to

10204 to be referred.

Appointment of Construction and Maintenance Agency - Regional Science Museum at Patan, Gujarat

Page 15

S.

No

Page

No. Part of RFP Clause No. Clarification sought with justification, if any Response

79 RFP-Volume-

II, Schedule3

Tender Drawings No. TCE.10741A-AC-1013-AC-

10101, 4 chair per table shown for canteen chair, hence

total NO. of chairs shall be 4x12= 48 No. while 96 No.

chairs are considered in BOQ. Please confirm.

For furniture, tender drg no. TCE.10741A-

AC-1013-IW-10201 to 10204 to be referred.

80 RFP-Volume-

I

BOQ of signage and furniture Item No.B5, B24 to B30,

Please provide the location else confirm whether quantity

to be executed as per BOQ.

Please refer tender drg no. TCE.10741A-

AC-1013-AC-10208 to 10211 for tentative

location of signage

81 RFP-Volume-

II, Schedule-2

Part A (Scope

of Work- D.

landscape

works)

Please provide BOQ, Specification and Details DRGs of

above mentioned scope.

Sr. No. 1 - Outdoor Furniture- We have used

brick and plastering and this quantity is

taken in the BOQ, location of the same will

be given in the GFC.

Sr. No. 2,3,4,8,10 - These are not there in

the design and thus not given BOQ, spec

and Drawing for the same.

Sr. No. 5 - Pump/Gardeners room will be

provided in the Utility Building and thus not

given separately.

Sr. No. 9 - Drip irrigation System- No drip

irrigation will be provided but manual

irrigation will be done on the site.

Sr. No. 6 & 7- Not Required.

Please note that the BOQ qualities are only

for reference

82 RFP-Volume-

II, Schedule3 Tender Drawings No. TCE.10741A-AC-1013-AC-

10102, Details No. 1.1 and 1.2 for terrace. Details shows

The coping item is already taken in the

BOQ. Please refer Sr. No. 17(b), 19(b) & 22

in the BOQ.

Appointment of Construction and Maintenance Agency - Regional Science Museum at Patan, Gujarat

Page 16

S.

No

Page

No. Part of RFP Clause No. Clarification sought with justification, if any Response

RCC coping. Please provide the BOQ for the same item

in RNMT.

83 RFP-Volume-

II, Schedule3

Tender Drawings No. TCE.10741A-AC-1013-AC-10103

and 10104, Finishing Schedule, wall finish shows gypsum

plaster e.g. At lift lobby & corridor. The quantity is

mentioned in BOQ is 10 SQMT only. Please revise the

quantity in BOQ.

The gypsum plaster has been revised to

cement plaster and wall putty finish. The

revised finish schedule drawing to be

referred. A nominal quantity for gypsum

plaster is kept as alternative item.

84 RFP-Volume-

II, Schedule3

Tender Drawings No. TCE.10741A-CV-3000-RC-30001

(General Note), concrete note no. 8 shows HDPE sheet

applicable and mentioned in BOQ. Please provide the

BOQ for HDPE sheet.

HDPE sheet not required. Please ignore.

85 RFP-Volume-

II, Schedule3

Tender Drawings, reinforcement details are not provided

in all Structural drawings. Please provide the

reinforcement details for all structural members. No Change. Please refer schedule 2.