demand-controlled ventilation for commercial kitchens

Upload: anescu-veronica

Post on 04-Apr-2018

224 views

Category:

Documents


0 download

TRANSCRIPT

  • 7/30/2019 Demand-Controlled Ventilation for Commercial Kitchens

    1/13

    3 6 A S H R A E J o u r n a l a s h r a e . o r g N o v e m b e r 2 0 1 2

    Food service facilities have high energy consumption with equipment

    and commercial kitchen ventilation (CKV) being the primary energy

    consumers in a restaurant. Exhaust hood airow drives HVAC energy

    consumption for CKV, so the rst step in reducing this exhaust airow is

    designing high efciency hoods with low capture and containment (C&C)

    airow rates. The next step is using demand control ventilation (DCV) to

    further reduce exhaust airow when cooking is not taking place under

    the hood, but when appliances are hot and ready for food preparation.

    Airow reduction is not the sole ob-

    jective o a DCV system; it also must

    ensure exhaust airow and the corre-

    sponding supply airows are increased

    to C&C levels as soon as cooking starts

    (to avoid spillage o convective heat and

    cooking euent into the kitchen space).

    The current NFPA-96 Standard1 and In-

    ternational Mechanical Code

    2

    require

    that a hood operate at ull design air-

    ows whenever ull-load cooking activ-

    ity occurs underneath an exhaust hood.

    DCV has evolved rom simple two-

    speed an control systems to proportion-

    al control with variable requency drives

    (VFDs) based on exhaust temperature.

    This improvement allowed or varying

    airows throughout the day. Then, an

    optical sensor was added to the temper-

    ature-based control to detect cooking

    activity taking place under the exhaust

    hood to urther enhance perormance.

    The latest system introduced to the

    market added measurement o exhaust

    airow and automated balancing o mul-

    tiple exhaust hoods connected to a single

    an (or a dedicated an) and modulation

    o replacement air or the space. Future

    systems need to be designed to consider

    the entire kitchen status to maximize en-ergy savings.

    Laboratory testing was conducted or

    common appliances in the commercial

    kitchen to evaluate system perormance

    when equipped with various DCV al-

    gorithms: operating at a fxed exhaust

    About the Authors

    Derek Schrock is U.S. research director and Jimmy

    Sandusky is research engineer at Halton Company

    in Scottsville, Ky. Andrey Livchak, Ph.D. is direc-

    tor of global research and development at Halton

    Group Americas in Bowling Green, Ky.

    By Derek Schrock, Member ASHRAE; Jimmy Sandusky, Associate Member ASHRAE; Andrey Livchak, Ph.D., Member ASHRAE

    Demand-Controlled Ventilation

    For Commercial KitchensT

    etraImages/Corbis

    This article was published in ASHRAE Journal, November 2012. Copyright 2012 ASHRAE. Posted at www.ashrae.org. This article may not be copied and/or

    distributed electronically or in paper orm without permission o ASHRAE. For more inormation about ASHRAE Journal, visit www.ashrae.org.

  • 7/30/2019 Demand-Controlled Ventilation for Commercial Kitchens

    2/13

    N o v e m b e r 2 0 1 2 A S H R A E J o u r n a l 3 7

    setpoint temperature, operating on a temperature curve to in-

    crease exhaust airow proportional to the temperature dier-

    ence between exhaust and space temperature and operating on

    a temperature curve in combination with a cooking activity

    sensor (CAS) to drive the system to design when cooking is

    detected. Additionally, an evaluation was done to determineenergy savings or a DCV system with balancing dampers in-

    stalled on a our exhaust hood, island confguration.

    Test Setup

    The objective o the frst round o tests was to compare per-

    ormance o DCV systems that use temperature sensors only

    to those that incorporate cooking activity and temperature sen-

    sors. Currently, only two manuacturers oer the latter. One

    design uses optical opacity sensors to detect the presence o

    cooking euent in a hood cavity. Another design uses inrared

    (IR) temperature sensors to monitor the surace temperature

    o cooking appliances. Data rom these IR sensors along with

    space temperature and hood exhaust temperature sensors are

    analyzed to interpret the status o cooking appliances (idle,

    cooking or o) and adjust hood exhaust airow accordingly.

    A 72 in. (1.8 m) long wall canopy exhaust hood was confg-

    ured to simulate various DCV control algorithms available on

    the market: exhaust temperature-based system that operates at

    a fxed setpoint, exhaust temperature-based system that oper-

    ates on a curve and exhaust temperature coupled with a cook-

    ing activity sensor system (includes IR sensors).

    Fixed setpoint exhaust temperatures o 90F, 100F and

    130F (32C, 38C and 54C) were evaluated. For these con-

    fgurations, the minimum exhaust airow rate was 80% o de-

    sign airow rate (a common value or temperature only basedsystems due to the limited ability to detect when cooking

    starts and ramp-up o exhaust airow). Exhaust airow was

    varied by a VFD in an attempt to maintain the tested tempera-

    ture setpoint.

    For exhaust temperature systems that operated on a curve,

    the minimum exhaust airow rate was again 80% o design.

    When using the curve, exhaust airow was incrementally in-

    the timer expiration, i no new cooking activity is detected, the

    system returns to the curve control algorithm.

    The exhaust hood was installed at 80 in. (2 m) above fn-

    ished oor with a temperature sensor mounted in the exhaust

    collar. The inrared sensors were positioned in the ront, in-

    terior ace o the canopy to sense the cooking surace. The

    temperature sensor was installed so that it was centered in the

    hood collar.

    The test protocol included a range o appliances that all

    demonstrated similar trends, but due to space limitations only

    data or appliances most commonly seen in kitchens is pre-

    sented: a charbroiler, griddle and open-vat ryer.

    Airows in Table 1 represent hood C&C airow, and when-

    ever the hood operates below this value when cooking occurs,

    the hood is spilling. Details o appliance uel source and prod-

    uct cooked are shown as well.

    During testing, each combination was evaluated at the idle

    and cooking states. Exhaust airow rate and temperature wereplotted versus time. The onset o the cooking process was not-

    ed to determine system response time.

    Results and Discussions

    Charbroiler

    Figure 1 summarizes testing conducted with the charbroiler,

    which exhibited the highest exhaust temperatures o all tested

    Table 1: Cooking appliance and associated food product.

    ApplianceFuel

    SourceLoading

    Design/Capture

    And Containment

    Airfow

    600F

    Charbroiler

    Natural

    Gas

    Frozen

    Hamburger Patties1,800 cm

    400F Griddle,

    Thermostatically

    Controlled

    Natural

    Gas

    Frozen

    Hamburger Patties1,000 cm

    350F Open-Vat

    Fryer, Single Vat

    Natural

    Gas

    Frozen

    French Fries1,000 cm

    2,000

    1,900

    1,800

    1,700

    1,600

    1,500

    1,400

    150

    145

    140

    135130

    125

    120

    115

    110

    105

    100

    Airfow(cm)

    Temperature(F

    )

    10:04:00a

    10:07:22a

    10:10:34a

    10:13:16a

    10:16:41a

    10:19:25a

    10:22:04a

    10:24:42a

    10:27:17a

    10:29:50a

    10:32:24a

    10:34:59a

    10:37:35a

    10:40:11a

    10:42:50a

    10:46:25a

    10:48:58a

    10:51:33a

    10:54:11a

    10:56:51a

    10:59:29a

    11:02:06a

    11:04:47a

    11:07:25a

    11:10:03a

    11:12:43a

    11:15:20a

    11:17:58a

    11:20:37a

    11:23:16a

    11:25:55a

    11:28:35a

    11:31:17a

    11:34:01a

    Temperature+ CAS

    TemperatureCurve

    Patties On

    ConstantTemperature,

    SP = 90F

    ConstantTemperature,SP = 100F

    ConstantTemperature,SP = 130F

    Airfow Duct TemperatureDesign Airfow

    Figure 1: Charbroiler testing.

    creased as the temperature dierence

    between exhaust and kitchen space in-

    creased. This algorithm ensures C&C

    o convective heat rom appliances in-

    stalled under the hood.Minimum exhaust airow or the

    system with cooking activity sensors

    installed was limited to 40% o the de-

    sign rate to ensure that the exhaust ans

    were operated in their recommended

    range. This system used the curve

    temperature control as described previ-

    ously when appliances are in idle mode

    and transitioned to design exhaust air-

    ow or an adjustable period (which was

    set to seven minutes or this test) upon

    detection o cooking activity. Following

  • 7/30/2019 Demand-Controlled Ventilation for Commercial Kitchens

    3/13

    3 8 A S H R A E J o u r n a l N o v e m b e r 2 0 1 2

    appliances. With the exhaust temperature and cooking activity

    sensor (CAS) algorithm, there was a small dierence (approxi-

    mately 5%) in idle and cooking exhaust airow rates due to the

    elevated exhaust temperature. The cooking activity sensor was

    able to detect placement o patties on the cooking surace and

    orce the system to design exhaust airow, albeit a small change.Following expiration o the cooking timer at approximately

    10:13 a.m., the airow rate dropped, but was orced back to

    design value as the exhaust temperature rose. With the tested

    algorithm, when the exhaust temperature exceeded 120F

    (49C), the system went to design exhaust airow (regardless

    o the cooking activity sensor values signal) as this was the

    upper limit o the temperature curve.

    Comparable results were seen with the temperature only

    system operating on a curve and constant temperature systems

    with a setpoint o 90F and 100F (32C and 38C). Due to an

    elevated exhaust temperature, the exhaust airow remained at

    or near the design airow level or the entirety o the test due

    to the temperature dierence threshold o the operating curve

    being exceeded. When operated on the temperature curve,

    there was a small decrease in exhaust airow at approximately

    10:30 a.m. due to a decrease in exhaust temperature.

    When the setpoint or the constant temperature system was

    changed to 130F (54C) the exhaust airow dropped to 80%

    o design and remained there or the duration o the test as

    exhaust temperature did not exceed the setpoint. There was

    one exception where the exhaust temperature peaked at 134F

    (57C). Being 4F (2C) above the threshold, this value was

    within the deadband o the system. Had the temperature con-

    tinued to rise, the exhaust airow would have increased pro-portionally in an attempt to maintain a constant exhaust tem-

    perature.

    It should be noted that with the charbroiler, the exhaust tem-

    perature rose steadily throughout the test as buildup on the

    cooking surace occurred. I the test had lasted longer, the ex-

    haust airow would have likely increased to design airows

    or all tested systems.

    Griddle

    The results o the griddle testing are summarized in Fig-

    ure 2. The exhaust temperature with the CAS algorithm oper-

    ated at approximately 70% o design airow at idle. The ex-

    haust airow was greater than the minimum setpoint o 40%

    to maintain C&C o heat generated by the appliance. When

    hamburger patties were placed on the surace, a decrease in

    surace temperature was noted as a cooking signal, and airow

    was driven to design almost immediately, and ell back to idle

    ater the cooking timer expired.

    Advertisement formerly in this space. Advertisement formerly in this space.

  • 7/30/2019 Demand-Controlled Ventilation for Commercial Kitchens

    4/13

    Advertisement formerly in this space.

  • 7/30/2019 Demand-Controlled Ventilation for Commercial Kitchens

    5/13

    4 0 A S H R A E J o u r n a l N o v e m b e r 2 0 1 2

    This test showed that the constant temperature setpoints o

    90F and 130F (32C and 54C) were not suitable or the ap-

    plication. With a 90F (32C) setpoint the system remained at

    design airow at all times due to the setpoint being lower than

    the exhaust temperature, even at idle conditions. A site confg-

    ured to operate in this manner was no dierent than having a

    standard canopy hood without DCV. The opposite was true o

    the 130F (54C) setpoint. The system remained at idle airow

    as the exhaust temperature never exceeded the setpoint, result-

    ing in both heat and cooking euent spilling to the space.

    Open-Vat Fryer

    Figure 3 shows data taken or the open-vat ryer. When

    testing with the CAS, the idle airow rate uctuated between

    For an exhaust temperature-based sys-

    tem operating on a curve, exhaust airow

    increased to the minimum idle rate o

    80% o design. Ater patties were placed

    on the griddle, the airow increased grad-

    ually with the exhaust temperature andthen ell as the temperature decreased

    near the end o the cooking cycle. Note

    that airow was not at design or the en-

    tirety o the cooking process.

    When operating with a constant tem-

    perature setpoint o 100F (38C), the

    system was able to reach and maintain

    design airow ollowing placing patties

    on the cooking surace. However, the

    initial response was not as ast as ob-

    tained with the CAS.

    Figure 2: Griddle testing.

    1,200

    1,100

    1,000

    900

    800

    700

    600

    140

    130

    120

    110

    100

    90

    80

    70

    60

    Airfow(cm)

    Temperature(F)

    1:02:00p

    1:06:55p

    1:11:52p

    1:17:04p

    1:22:18p

    1:27:34p

    1:32:55p

    1:38:21p

    1:43:53p

    1:49:22p

    1:54:50p

    2:00:13p

    2:05:36p

    2:10:49p

    2:15:49p

    2:20:44p

    2:25:33p

    2:30:12p

    2:34:45p

    2:39:16p

    2:43:50p

    2:48:18p

    2:52:48p

    2:57:19p

    3:01:50p

    3:06:20p

    Temperature+ CAS

    TemperatureCurve

    Patties On

    ConstantTemperature,

    SP = 90F

    ConstantTemperature,SP = 100F

    ConstantTemperature,SP = 130F

    Airfow Duct TemperatureDesign Airfow

    Advertisement formerly in this space.

  • 7/30/2019 Demand-Controlled Ventilation for Commercial Kitchens

    6/13

    Advertisement formerly in this space.

  • 7/30/2019 Demand-Controlled Ventilation for Commercial Kitchens

    7/13

    4 2 A S H R A E J o u r n a l N o v e m b e r 2 0 1 2

    40% and 50% o design as the appli-

    ance fred to maintain oil temperature

    in the vat. Upon dropping the baskets

    o ries into the oil, the drop in temper-

    ature detected by the sensor indicated

    cooking was occurring and drove theexhaust an to design airow and then

    returned to idle ater the cooking timer

    expired.

    With the algorithm operating on a

    temperature curve, the system idled at

    the minimum prescribed 80% o design

    airow and increased proportionally as

    the exhaust temperature rose. The tem-

    perature dierence between exhaust and

    space did not exceed the upper limit to

    go to design airow.

    With the constant temperature setpoint confgurations, all

    systems idle at 80% o design. When the setpoint was 90F

    (32C), the system did reach design airow ater the initia-

    tion o the cooking process, but a signifcant time lag between

    onset o cooking and meeting design airow was noted. For

    100F and 130F (38C and 54C) confgurations, the system

    remained idle at all times due to exhaust temperature not ex-

    ceeding the setpoint. This was indicative o the requirement

    to be very amiliar with the given cooking process when con-

    fguring temperature-based DCV systems. For example, the

    open-vat ryer potentially could perorm better with a lower

    temperature setpoint value, but common practice dictates

    90F (32C) and above setpoints to achieve any measurable

    airow reductions.

    Figure 3: Open-vat fryer testing.

    1,200

    1,100

    1,000

    900

    800

    700600

    500

    400

    300

    200

    120

    110

    100

    90

    80

    70

    60

    Airfow

    (cm)

    Tempera

    ture(F)

    2:58:00p

    3:01:23p

    3:04:37p

    3:07:57p

    3:11:21p

    3:14:48p

    3:18:11p

    3:21:37p

    3:25:01p

    3:28:25p

    3:31:45p

    3:35:04p

    3:38:19p

    3:41:36p

    3:44:52p

    3:48:01p

    3:51:12p

    3:54:25p

    3:57:39p

    4:00:51p

    4:04:06p

    4:07:22p

    4:10:39p

    4:13:55p

    4:17:16p

    4:20:36p

    4:23:58p

    4:27:22p

    4:30:46p

    4:34:12p

    4:37:36p

    Baskets Dropped

    Temperature

    Curve

    ConstantTemperature,

    SP = 90F

    ConstantTemperature,SP = 100F

    ConstantTemperature,SP = 130F

    Temperature

    + CAS

    Airfow Duct TemperatureDesign Airfow

    Advertisement formerly in this space.

  • 7/30/2019 Demand-Controlled Ventilation for Commercial Kitchens

    8/13

    Advertisement formerly in this space.

  • 7/30/2019 Demand-Controlled Ventilation for Commercial Kitchens

    9/13

    4 4 A S H R A E J o u r n a l N o v e m b e r 2 0 1 2

    Response Time

    In addition to evaluating

    the exhaust airow achieved

    with dierent types o DCV

    systems, the response times

    o the systems were comparedas shown in Table 2. An entry

    o N/A indicates that the

    system either was not able to

    meet or remained at design

    airow during the test. Note

    or tested appliances. When using only the temperature sensor,

    system response is more dependent on the correct selection set-

    points and is always delayed. I improperly confgured, temper-

    ature-based systems can operate at either idle or design airow

    at all times, resulting in loss o C&C or no energy savings.

    Each appliance shown has dierent exhaust temperatures

    that represent the transition rom idle to cooking states. Rare-

    ly, appliances are confgured so that each has a dedicated ex-

    haust hood; the mixed lineup under a long hood is typical.

    Appliance lineups will vary rom site to site, making a generic

    temperature curve or setpoint nearly impossible to obtain.

    Some confgurations can perorm well without the CAS.

    For example, convection or conveyor ovens produce little to

    the response time o the systems with the CAS was substan-

    tially aster than the temperature-based systems. This is be-

    cause the sensor actively monitors what is occurring at the ap-

    pliance level, and can indicate when cooking occurs as soon as

    the product is placed in/on the appliance and drive the exhaust

    an to design airow or the entirety o the process; whereas,

    a temperature-based system can only react to a by-product o

    the cooking process: a change in temperature that takes longer

    to observe.

    Discussion

    The inclusion o the cooking activity sensor ensures the sys-

    tem goes to design airow at the onset o the cooking process

    Table 2: Response time comparison.

    Time From Start o Cooking (Seconds) When Design Airfow Reached

    Appliance Temperature

    + Cooking

    Activity Sensor

    Temperature

    Only Curve

    Constant

    Temperature,

    SP=90F

    Constant

    Temperature,

    SP=100F

    Constant

    Temperature,

    SP=130F

    Charbroiler 23 N/A N/A N/A N/A

    Griddle 35 174 N/A 181 N/A

    Open-Vat Fryer 23 N/A 297 N/A N/A

    Advertisement formerly in this space.

  • 7/30/2019 Demand-Controlled Ventilation for Commercial Kitchens

    10/13

    Advertisement formerly in this space.

  • 7/30/2019 Demand-Controlled Ventilation for Commercial Kitchens

    11/13

    4 6 A S H R A E J o u r n a l a s h r a e . o r g N o v e m b e r 2 0 1 2

    no smoke during the cooking process, which would be di-

    fcult or an optical opacity or inrared sensor to interpret. In

    some installations, a combination o temperature-based and

    temperature/CAS-based systems may be necessary or the

    system to perorm at an optimal level.

    Space temperature will vary during cooling and heating pe-riods, aecting exhaust temperature as well. As a result the ex-

    haust temperature setpoint must be adjusted rom one season

    to another or DCV systems with exhaust temperature sen-

    sors only. A space temperature sensor installed in the area to

    constantly evaluate the dierence between exhaust and room

    temperature maximizes energy savings potential o the DCV

    system.

    A an speed profle or each confguration was generated

    to compare energy savings, rather than using average percent

    reduction alone. These profles were used in conjunction with

    an outdoor air load calculator to determine savings associated

    with makeup air cooling and heating, as well as exhaust and

    supply an energy. Table 3 compares the annual energy sav-

    ings associated with both confgurations.

    Although both confgurations save energy, the installation o

    balancing dampers maximizes these savings by allowing thehoods to operate independently. Without dampers, when one

    hood is in the cooking state, all are orced to design airow

    regardless o state. The value o the balancing damper lies in

    the ability to lower the airows or hoods that are not cooking

    in single exhaust an, multiple exhaust hood confgurations.

    In this particular case with our hoods connected to a single

    exhaust an, the DCV system with balancing dampers saves

    nearly twice as much energy when compared to a similar sys-

    tem without balancing dampers. This is a conservative esti-

    mate because additional savings when all hoods are in idle

    mode are not accounted or. Indeed, when the DCV system

    is in idle mode (appliances are hot, but no cooking occurs),

    Case Study: DCV With and Without Balanc-

    ing Dampers

    For installations where the exhaust hoods each

    have a dedicated exhaust an, balancing dampers

    are not needed since the airows can be modu-

    lated by changing the an speed. However, when

    multiple exhaust hoods are connected to a single

    exhaust an, balancing dampers listed in accor-

    dance with the UL 710 standard can be installed

    on each exhaust hood section to maximize the

    energy savings o a DCV system. This is because

    each hood needs to have the ability to indepen-

    dently regulate airow based on its state (o,

    idle or cooking). To illustrate the energy savings

    that can be achieved with dampers installed, a

    site is evaluated with both confgurations.

    The examined site is in Seattle, and is a 24/7operation. The only time the kitchen exhaust

    hoods are shut down is or a daily water-wash

    operation (approximately 15 minutes). The ex-Figure 5: Case study with balancing dampers installed.

    120

    100

    80

    60

    40

    20

    0

    ExhaustFanSpeed(%)

    Average Airfow = 73% o Design

    5/13/12 5/14 5/15 5/16 5/17 5/18 5/19 5/20 5/21 5/22

    Exhaust Fan VFD Speed, %

    Figure 4: Examined site exhaust hood conguration.

    haust hoods are installed as back-to-back island style canopy

    hoods and are connected to a single exhaust an (Figure 4).

    Each hood is ftted with a balancing damper at the exhaust col-

    lar. The DCV system operates with cooking activity sensors

    installed on all hoods. The design airow or the site is 11,290

    cm (5328 L/s). Figure 4 shows monitored data or exhaust

    an speed. On average, the exhaust airow rate was 73% o

    design. Figure 5 shows the system rarely operated close to

    design airows because the our hoods did not have cookingoccurring at the same time.

    Figure 6shows the exhaust an speed or the same DCV sys-

    tem and time period without the dampers installed. To model

    the system without dampers installed, hood status was also

    monitored with the an speed and exhaust airow data. These

    ags are generated by the control algorithm based on the inputs

    rom the cooking activity, space and duct temperature sensor.

    I one o the our hoods was in cooking state, that an speed

    would increase to 100% to reach design airow or the par-

    ticular exhaust hood. I status was o or idle or all hoods,

    an speed was assumed to be equal to that o the system with

    balancing dampers.

  • 7/30/2019 Demand-Controlled Ventilation for Commercial Kitchens

    12/13

    Advertisement formerly in this space.

  • 7/30/2019 Demand-Controlled Ventilation for Commercial Kitchens

    13/13

    4 8 A S H R A E J o u r n a l a s h r a e o r g N o v e m b e r 2 0 1 2

    and the exhaust airow is controlled based on a

    hoods exhaust temperature (more accurately the

    temperature dierence between hood exhaust

    and space temperature) a dilemma is revealed:

    which exhaust temperature (or hood) should be

    used as a control signal or DCV without damp-ers?

    The hood with the highest exhaust temperature

    would be the saest bet, but this would require

    a more sophisticated control algorithm (not the

    case or many DCV suppliers) and will still end

    up with a higher total exhaust airow compared

    to DCV with dampers. In some cases, a fxed

    leading hood is assigned, and its exhaust tem-

    perature is used to control exhaust airow or the

    whole system in DCV systems without dampers.

    Future of DCV Systems

    As evidence shows, the cooking activity sensor

    is an important component o an efcient DCV

    system. However, this is not the most eective

    way to identiy appliance status. Taking a signal

    directly rom the cooking appliance is a more e-

    ective way to detect appliance status (cooking,

    idle or o). Most modern cooking appliances are

    equipped with programmable logic controllers

    Compared to DCV systems with cooking activity sensors,

    systems that use only temperature sensors can have signifcant

    lags in response time; more than two minutes in the evaluated

    cases o the open-vat ryer and griddle. Not detecting cooking

    in a timely manner results in loss o C&C, which allows heatand cooking euent to spill to the kitchen space. Any sav-

    ings associated with an energy can quickly be oset by an

    increased load on cooling and heating equipment.

    When temperature only systems are used, setpoints must

    be calibrated or a given application (appliance combination).

    This is key to ensuring the system operates as intended. In-

    appropriate setpoints can result in hoods that run at design

    airow constantly (an expensive exhaust-only hood) or idle

    continuously (allowing spillage to occur). The setpoints also

    should be reset or winter and summer to account or variation

    in kitchen space temperature, unless a space temperature sen-

    sor is used or automatic reset.Using automatic balancing dampers listed per UL Standard

    710 or DCV systems with multiple hoods connected to a single

    exhaust an signifcantly improves system energy efciency. The

    energy savings or a our-hood system can be double when com-

    pared to an identical DCV system without balancing dampers.

    References

    1. NFPA. 2011. NFPA Standard 96-2011, Standard for Ventilation

    Control and Fire Protection of Commercial Cooking Operations.

    National Fire Protection Association.

    2. ICC. 2012. 2012 International Mechanical Code. International

    Code Council.

    Figure 6: Case study without balancing dampers installed.

    120

    100

    80

    60

    40

    20

    0ExhaustFanSpeed(%)

    Average Airfow = 86% o Design

    5/13/12 5/14 5/15 5/16 5/17 5/18 5/19 5/20 5/21 5/22

    Exhaust Fan VFD Speed Without Dampers

    Table 3: Energy savings comparison with and without balancing dampers.

    Estimated Savings

    SystemHeating

    (Therms)

    Cooling

    (kWh)

    Exhaust Fan

    (kWh)

    Supply Fan

    (kWh)

    DCV With

    Dampers1,133 6,435 32,554 10,851

    DCV Without

    Dampers623 3,539 15,697 5,232

    Dierence 510 2,896 16,857 5,619

    (PLCs) that already know appliance status. Establishing com-

    munication between the appliance and DCV controller is all

    that is needed.

    As noted previously, cooking equipment and CKV are a

    kitchens primary energy consumers. The term demand con-trol ventilation implies that hood exhaust is modulated based

    on demand by cooking appliances under the hood. Cooking

    appliances defne overall kitchen energy consumption because

    CKV energy consumption is, to a large extent, driven by ap-

    pliances being used, and their status defning DCV exhaust

    airow. However, DCV doesnt optimize the energy consump-

    tion o the source: the cooking equipment.

    The next step in the development o an energy-efcient

    kitchen is implementing a demand-controlled kitchen (DCK)

    strategy, where appliances are controlled based on cooking

    demand and communicate their status to DCV to minimize

    CKV energy consumption. Indeed, how many times have youseen a range with all burners on and no pots on it or a triple-

    stack conveyer oven with all stacks on and just one conveyer

    being used? When we implement a DCK strategy with energy-

    efcient cooking appliances that are integrated with a DCV

    system (controlled based on cooking schedule and demand),

    we will have a truly energy-efcient kitchen.

    Conclusions

    Commercial kitchen DCV systems can oer great energy

    savings to the end user when properly implemented. Care

    should be taken to ensure the proper DCV system and sensor

    type are selected or a given appliance lineup.