Contactor, 3p, 55kW/400V/AC3
Part no. DILM115(RAC120)Catalog No. 239547Eaton Catalog No. XTCE115G00AEL-Nummer(Norway)
4110246
Delivery programProduct range Contactors
Application Contactors for Motors
Subrange Contactors up to 170 A, 3 pole
Utilization category AC-1: Non-inductive or slightly inductive loads, resistance furnacesNAC-3: Normal AC induction motors: starting, switch off during runningAC-4: Normal AC induction motors: starting, plugging, reversing, inching
Notes Also suitable for motors with efficiency class IE3.IE3-ready devices are identified by the logo on their packaging.
Connection technique Screw terminals
Number of poles 3 pole
Rated operational current
AC-3
380 V 400 V Ie A 115
AC-1
Conventional free air thermal current, 3 pole, 50 - 60 Hz
Open
at 40 °C Ith =Ie A 160
enclosed Ith A 115
Conventional free air thermal current, 1 pole
open Ith A 325
enclosed Ith A 285
Max. rating for three-phase motors, 50 - 60 Hz
AC-3
220 V 230 V P kW 37
380 V 400 V P kW 55
660 V 690 V P kW 90
AC-4
220 V 230 V P kW 17
380 V 400 V P kW 28
660 V 690 V P kW 43
Contact sequence
Instructions Contacts to EN 50 012.integrated suppressor circuit in actuating electronics
Can be combined with auxiliary contact DILM150-XHI(V)..DILM1000-XHI(V)..
Voltage AC/DC AC operation
Technical dataGeneralStandards IEC/EN 60947, VDE 0660, UL, CSA
Lifespan, mechanical
AC operated Operations x 106 10
12/22/2017 Eaton 239547 ED2017 V39.0 EN 1 / 13
Operating frequency, mechanical
AC operated Operations/h 3600
Climatic proofing Damp heat, constant, to IEC 60068-2-78Damp heat, cyclic, to IEC 60068-2-30
Ambient temperature
Open °C -25 - +60
Enclosed °C - 25 - 40
Storage °C - 40 - 80
Mounting position
Mechanical shock resistance (IEC/EN 60068-2-27)
Half-sinusoidal shock, 10 ms
Main contacts
N/O contact g 10
Auxiliary contacts
N/O contact g 7
N/C contact g 5
Mechanical shock resistance (IEC/EN 60068-2-27) when tabletop-mounted
Half-sinusoidal shock, 10 ms
Main contacts
N/O contact g 10
Auxiliary contacts
N/O contact g 7
N/C contact g 5
Degree of Protection IP00
Protection against direct contact when actuated from front (EN 50274) Finger and back-of-hand proof
Weight
AC operated kg 2.25
Screw connector terminals
Terminal capacity main cable
Flexible with ferrule mm2 1 x (10 - 95)2 x (10 - 70)
Stranded mm2 1 x (16 - 95)2 x (16 - 70)
Solid or stranded AWG single 8…3/0, double 8…2/0
Flat conductor Lamellenzahlx Breite xDicke
mm 2 x (6 x 16 x 0.8)
Stripping length mm 24
Terminal screw M10
Tightening torque Nm 14
Tool
Hexagon socket-head spanner SW mm 5
Terminal capacity control circuit cables
Solid mm2 1 x (0.75 - 4)2 x (0.75 - 2.5)
Flexible with ferrule mm2 1 x (0.75 - 2.5)2 x (0.75 - 2.5)
Solid or stranded AWG 18 - 14
Stripping length mm 10
Terminal screw M3.5
Tightening torque Nm 1.2
Tool
Pozidriv screwdriver Size 2
Standard screwdriver mm 0.8 x 5.5
12/22/2017 Eaton 239547 ED2017 V39.0 EN 2 / 13
1 x 6
Main conducting pathsRated impulse withstand voltage Uimp V AC 8000
Overvoltage category/pollution degree III/3
Rated insulation voltage Ui V AC 690
Rated operational voltage Ue V AC 690
Safe isolation to EN 61140
between coil and contacts V AC 690
between the contacts V AC 690
Making capacity (p.f. to IEC/EN 60947)
Up to 690 V A 1610
Breaking capacity
220 V 230 V A 1150
380 V 400 V A 1150
500 V A 1150
660 V 690 V A 1100
Short-circuit rating
Short-circuit protection maximum fuse
Type “2” coordination
400 V gG/gL 500 V A 250
690 V gG/gL 690 V A 250
Type “1” coordination
400 V gG/gL 500 V A 250
690 V gG/gL 690 V A 250
ACAC-1
Rated operational current
Conventional free air thermal current, 3 pole, 50 - 60 Hz
Open
at 40 °C Ith =Ie A 160
at 50 °C Ith =Ie A 142
at 55 °C Ith =Ie A 135
at 60 °C Ith =Ie A 130
enclosed Ith A 115
Conventional free air thermal current, 1 pole
open Ith A 325
enclosed Ith A 285
AC-3
Rated operational current
Open, 3-pole: 50 – 60 Hz
220 V 230 V Ie A 115
240 V Ie A 115
380 V 400 V Ie A 115
415 V Ie A 115
440V Ie A 115
500 V Ie A 115
660 V 690 V Ie A 93
380 V 400 V Ie A 115
Motor rating P kWh
220 V 230 V P kW 37
240V P kW 40
380 V 400 V P kW 55
415 V P kW 70
440 V P kW 75
12/22/2017 Eaton 239547 ED2017 V39.0 EN 3 / 13
500 V P kW 85
660 V 690 V P kW 90
AC-4
Open, 3-pole: 50 – 60 Hz
220 V 230 V Ie A 55
240 V Ie A 55
380 V 400 V Ie A 55
415 V Ie A 55
440 V Ie A 55
500 V Ie A 55
660 V 690 V Ie A 45
Motor rating P kWh
220 V 230 V P kW 17
240 V P kW 19
380 V 400 V P kW 28
415 V P kW 33
440 V P kW 35
500 V P kW 40
660 V 690 V P kW 43
DCRated operational current, open
DC-1
60 V Ie A 160
110 V Ie A 160
220 V Ie A 90
Current heat loss3 pole, at Ith (60°) W 24.2
Current heat loss at Ie to AC-3/400 V W 18.9
Impedance per pole mΩ 0.6
Magnet systemsVoltage tolerance
AC operated Pick-up x Uc 0.8 - 1.15
Drop-out voltage AC operated Drop-out x Uc 0.25 - 0.6
Power consumption of the coil in a cold state and 1.0 x US
50 Hz Pick-up VA 180
50 Hz Sealing VA 3.1
50 Hz Sealing W 2.3
60 Hz Pick-up VA 170
60 Hz Sealing VA 3.1
60 Hz Sealing W 2.3
Duty factor % DF 100
Changeover time at 100 % US (recommended value)
Main contacts
AC operated
Closing delay ms 28 - 33
Opening delay ms 35 - 41
Arcing time ms 15
Permissible residual current with actuation of A1 - A2 by the electronics (with0 signal).
mA ≦ 1
Electromagnetic compatibility (EMC)Emitted interference to EN 60947-1
Interference immunity to EN 60947-1
Rating data for approved typesSwitching capacity
Maximum motor rating
Three-phase
12/22/2017 Eaton 239547 ED2017 V39.0 EN 4 / 13
200 V208 V
HP 40
230 V240 V
HP 50
460 V480 V
HP 100
575 V600 V
HP 100
Single-phase
115 V120 V
HP 10
230 V240 V
HP 25
General use A 180
Short Circuit Current Rating SCCR
Basic Rating
SCCR kA 10
max. Fuse A 600
max. CB A 600
480 V High Fault
SCCR (fuse) kA 30/100
max. Fuse A 300/300 Class J
SCCR (CB) kA 65
max. CB A 250
600 V High Fault
SCCR (fuse) kA 30/100
max. Fuse A 300/300 Class J
SCCR (CB) kA 30
max. CB A 350
Special Purpose Ratings
Electrical Discharge Lamps (Ballast)
480V 60Hz 3phase, 277V 60Hz 1phase A 160
600V 60Hz 3phase, 347V 60Hz 1phase A 160
Incandescent Lamps (Tungsten)
480V 60Hz 3phase, 277V 60Hz 1phase A 160
600V 60Hz 3phase, 347V 60Hz 1phase A 160
Resistance Air Heating
480V 60Hz 3phase, 277V 60Hz 1phase A 160
600V 60Hz 3phase, 347V 60Hz 1phase A 160
Refrigeration Control (CSA only)
LRA 480V 60Hz 3phase A 540
FLA 480V 60Hz 3phase A 84
LRA 600V 60Hz 3phase A 540
FLA 600V 60Hz 3phase A 84
Definite Purpose Ratings (100,000 cycles acc. to UL 1995)
LRA 480V 60Hz 3phase A 690
FLA 480V 60Hz 3phase A 115
Elevator Control
200V 60Hz 3phase HP 30
200V 60Hz 3phase A 92
240V 60Hz 3phase HP 40
240V 60Hz 3phase A 104
480V 60Hz 3phase HP 75
480V 60Hz 3phase A 96
600V 60Hz 3phase HP 100
600V 60Hz 3phase A 99
12/22/2017 Eaton 239547 ED2017 V39.0 EN 5 / 13
Design verification as per IEC/EN 61439Technical data for design verification
Rated operational current for specified heat dissipation In A 115
Heat dissipation per pole, current-dependent Pvid W 6.3
Equipment heat dissipation, current-dependent Pvid W 18.9
Static heat dissipation, non-current-dependent Pvs W 2.3
Heat dissipation capacity Pdiss W 0
Operating ambient temperature max. °C -25
Operating ambient temperature max. °C 60
IEC/EN 61439 design verification
10.2 Strength of materials and parts
10.2.2 Corrosion resistance Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat Meets the product standard's requirements.
10.2.3.3 Verification of resistance of insulating materials to abnormal heatand fire due to internal electric effects
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation Meets the product standard's requirements.
10.2.5 Lifting Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions Meets the product standard's requirements.
10.3 Degree of protection of ASSEMBLIES Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances Meets the product standard's requirements.
10.5 Protection against electric shock Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections Is the panel builder's responsibility.
10.8 Connections for external conductors Is the panel builder's responsibility.
10.9 Insulation properties
10.9.2 Power-frequency electric strength Is the panel builder's responsibility.
10.9.3 Impulse withstand voltage Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material Is the panel builder's responsibility.
10.10 Temperature rise The panel builder is responsible for the temperature rise calculation. Eaton willprovide heat dissipation data for the devices.
10.11 Short-circuit rating Is the panel builder's responsibility. The specifications for the switchgear must beobserved.
10.12 Electromagnetic compatibility Is the panel builder's responsibility. The specifications for the switchgear must beobserved.
10.13 Mechanical function The device meets the requirements, provided the information in the instructionleaflet (IL) is observed.
Technical data ETIM 6.0Low-voltage industrial components (EG000017) / Power contactor, AC switching (EC000066)
Electric engineering, automation, process control engineering / Low-voltage switch technology / Contactor (LV) / Power contactor, AC switching ([email protected] [AAB718012])
Rated control supply voltage Us at AC 50HZ V 100 - 120
Rated control supply voltage Us at AC 60HZ V 100 - 120
Rated control supply voltage Us at DC V 0 - 0
Voltage type for actuating AC
Rated operation current Ie at AC-1, 400 V A 160
Rated operation current Ie at AC-3, 400 V A 115
Rated operation power at AC-3, 400 V kW 55
Rated operation current Ie at AC-4, 400 V A 55
Rated operation power Ie at AC-4, 400 V kW 28
Modular version No
Number of auxiliary contacts as normally open contact 0
Number of auxiliary contacts as normally closed contact 0
Type of electrical connection of main circuit Screw connection
Number of normally closed contacts as main contact 0
Number of main contacts as normally open contact 3
12/22/2017 Eaton 239547 ED2017 V39.0 EN 6 / 13
ApprovalsProduct Standards IEC/EN 60947-4-1; UL 60947-4-1; CSA - C22.2 No. 60947-4-1-14; CE marking
UL File No. E29096
UL Category Control No. NLDX
CSA File No. 012528
CSA Class No. 2411-03, 3211-04
North America Certification UL listed, CSA certified
Specially designed for North America No
Characteristics
1: Overload relay2: Suppressor3: Auxiliary contact modules
12/22/2017 Eaton 239547 ED2017 V39.0 EN 7 / 13
on the side: 2 x DILM820-XHI11(V)-SI; 2 x DILM820-XHI11-SA
Squirrel-cage motorOperating characteristicsStarting:from restStopping:after attaining full running speedElectrical characteristicsMake: up to 6 x rated motor currentBreak: up to 1 x rated motor currentUtilization category100 % AC-3Typical applications
12/22/2017 Eaton 239547 ED2017 V39.0 EN 8 / 13
CompressorsLiftsMixersPumpsEscalatorsAgitatorsFansConveyor beltsCentrifugesHinged flapsBucket-elevatorsAir conditioning systemGeneral drives in manufacturing and processing machines
Extreme switching dutySquirrel-cage motorOperating characteristicsInching, plugging, reversingElectrical characteristicsMake: up to 6 x rated motor currentBreak: up to 6 x rated motor currentUtilization category100 % AC-4Typical applicationsPrinting pressesWire-drawing machinesCentrifugesSpecial drives for manufacturing and processing machines
12/22/2017 Eaton 239547 ED2017 V39.0 EN 9 / 13
Switching conditions for non-motor consumers, 3 pole, 4 poleOperating characteristicsNon inductive and slightly inductive loadsElectrical characteristicsSwitch on: 1 x rated operational currentSwitch off: 1 x rated operational currentUtilization category100 % AC-1Typical examples of applicationElectric heat
12/22/2017 Eaton 239547 ED2017 V39.0 EN 10 / 13
distance at side to earthed parts: 10 mm
DILM80…DILM170DILMC80…DILMC150DILMF80…DILMF150
Additional product information (links)IL03407039Z (AWA2100-2286) Contactors
IL03407039Z (AWA2100-2286) Contactors ftp://ftp.moeller.net/DOCUMENTATION/AWA_INSTRUCTIONS/IL03407039Z2010_10.pdf
Switchgear of Power Factor CorrectionSystems
http://www.moeller.net/binary/ver_techpapers/ver934en.pdf
X-Start - Modern Switching InstallationsEfficiently Fitted and Wired Securely
http://www.moeller.net/binary/ver_techpapers/ver938en.pdf
Mirror Contacts for Highly-Reliable InformationRelating to Safety-Related Control Functions
http://www.moeller.net/binary/ver_techpapers/ver944en.pdf
Effect of the Cabel Capacitance of Long ControlCables on the Actuation of Contactors
http://www.moeller.net/binary/ver_techpapers/ver949en.pdf
12/22/2017 Eaton 239547 ED2017 V39.0 EN 12 / 13
Motor starters and "Special Purpose Ratings"for the North American market
http://www.moeller.net/binary/ver_techpapers/ver953en.pdf
Switchgear for Luminaires http://www.moeller.net/binary/ver_techpapers/ver955en.pdf
Standard Compliant and Functionally SafeEngineering Design with Mechanical AuxiliaryContacts
http://www.moeller.net/binary/ver_techpapers/ver956en.pdf
The Interaction of Contactors with PLCs http://www.moeller.net/binary/ver_techpapers/ver957en.pdf
Busbar Component Adapters for modernIndustrial control panels
http://www.moeller.net/binary/ver_techpapers/ver960en.pdf
12/22/2017 Eaton Industries GmbHhttp://www.eaton.eu
© 12/2017 by Eaton Industries GmbHEaton 239547 ED2017 V39.0 EN