Deep Green Retrofits Rob Dumont Dumont and Associates [email protected]

Upload: nguyennguyet

Post on 01-Feb-2018

216 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Deep Green Retrofits - BC Building · PDF fileDeep Green Retrofits Rob Dumont ... House with Boiler System ... another expt. Windows R2 R3 1.5 Air Tightness 2.95 ac/h @50 Pa 0.29 ac/h

Deep Green

Retrofits

Rob Dumont

Dumont and Associates

[email protected]

Page 2: Deep Green Retrofits - BC Building · PDF fileDeep Green Retrofits Rob Dumont ... House with Boiler System ... another expt. Windows R2 R3 1.5 Air Tightness 2.95 ac/h @50 Pa 0.29 ac/h

Why Deep Green?

1. We currently have a climate crisis. Climate scientists are calling for a reduction in carbon emissions of at least 2 times from current levels.

2. World population is expected to increase by a factor of 1.5 by 2050

3. Because there are so many people in poor countries, it is expected that average consumption per person in the world will increase by a factor of 3 before stabilizing.

Page 3: Deep Green Retrofits - BC Building · PDF fileDeep Green Retrofits Rob Dumont ... House with Boiler System ... another expt. Windows R2 R3 1.5 Air Tightness 2.95 ac/h @50 Pa 0.29 ac/h

Multiply these three factors together:

2 x 1.5 x 3 = 9

In other words, with that amount of growth in people and consumption, and the need to reduce carbon emissions, the only way to address the problem is reduce the carbon emissions of all buildings, transportation, industry and agriculture by a factor of 9.

Page 4: Deep Green Retrofits - BC Building · PDF fileDeep Green Retrofits Rob Dumont ... House with Boiler System ... another expt. Windows R2 R3 1.5 Air Tightness 2.95 ac/h @50 Pa 0.29 ac/h

What would sustainable

buildings look like?

Page 5: Deep Green Retrofits - BC Building · PDF fileDeep Green Retrofits Rob Dumont ... House with Boiler System ... another expt. Windows R2 R3 1.5 Air Tightness 2.95 ac/h @50 Pa 0.29 ac/h

Discovery 3 Home in Red

Deer, Alberta

One of Canada’s EQuilibrium Homes

Projected Net Zero Energy on an annual basis

Energy Conservation Features:

R87 Roof, R70 Walls, R60 Floor, R5 Windows, air tightness goal of 0.5 ac/h @ 50 pascals, Heat Recovery Ventilator

Energy Supply:

Passive solar, Active solar, 8.3 kilowatt PV system

Page 6: Deep Green Retrofits - BC Building · PDF fileDeep Green Retrofits Rob Dumont ... House with Boiler System ... another expt. Windows R2 R3 1.5 Air Tightness 2.95 ac/h @50 Pa 0.29 ac/h

Effect of Conservation and Renewable Energy Measures

259

138

0

42

5857

87

0

50

100

150

200

250

300

Base Case Hse 1. Reduce Space

Heat

2. Reduce Water

Heat

3. Reduce Lights

and Appliances

4. Space Cooling 5. Install Solar

Water Heat

6. Install

Photovoltaics

Conservation and Renewable Energy Measures

An

nu

al P

urch

ased

En

erg

y C

on

su

mp

tio

n (

kW

h/s

q.m

.)

Page 7: Deep Green Retrofits - BC Building · PDF fileDeep Green Retrofits Rob Dumont ... House with Boiler System ... another expt. Windows R2 R3 1.5 Air Tightness 2.95 ac/h @50 Pa 0.29 ac/h

Observations

1. Space Heating Load is the greatest single load

2. Water Heating Load is the second greatest load

3. LAME (Lights, Appliances and Misc) is the third greatest load

Reducing these three has the greatest impact on the house performance

Page 8: Deep Green Retrofits - BC Building · PDF fileDeep Green Retrofits Rob Dumont ... House with Boiler System ... another expt. Windows R2 R3 1.5 Air Tightness 2.95 ac/h @50 Pa 0.29 ac/h

Comparison of Inuvik and

Red Deer Climates

Inuvik Red Deer

Annual Heating

Degree Days

(C-days)

10,040 5550

Outdoor Design

Temp for heating

systems

-40.1 C -35.0 C

Annual Solar

Radiation on a

horizontal Surface

(GJ/m2)

3.3 4.9

Page 9: Deep Green Retrofits - BC Building · PDF fileDeep Green Retrofits Rob Dumont ... House with Boiler System ... another expt. Windows R2 R3 1.5 Air Tightness 2.95 ac/h @50 Pa 0.29 ac/h

Comparison of Inuvik and

Red Deer Climates

Inuvik Red Deer

Latitude Angle

(degrees)

68 52

Annual Solar

Radiation on a

South Facing

Surface tilted at

the latitude angle

(Gigajoules/m2)

4.7 6.5

Page 10: Deep Green Retrofits - BC Building · PDF fileDeep Green Retrofits Rob Dumont ... House with Boiler System ... another expt. Windows R2 R3 1.5 Air Tightness 2.95 ac/h @50 Pa 0.29 ac/h

Classic Analysis of Optimum

Amount of Insulation

Optimum amount of insulation is that

amount which minimizes the combined

cost of the installed insulation and the

cost of the fuel to heat the space

Consider only the cost of insulation and

cost of fuel

Page 11: Deep Green Retrofits - BC Building · PDF fileDeep Green Retrofits Rob Dumont ... House with Boiler System ... another expt. Windows R2 R3 1.5 Air Tightness 2.95 ac/h @50 Pa 0.29 ac/h
Page 12: Deep Green Retrofits - BC Building · PDF fileDeep Green Retrofits Rob Dumont ... House with Boiler System ... another expt. Windows R2 R3 1.5 Air Tightness 2.95 ac/h @50 Pa 0.29 ac/h

Cost of Batt Insulation

In southern Canada

Approximately

3 cents per square foot per R value

Thus R100 in a 1000 square foot attic

would cost about $3000

Page 13: Deep Green Retrofits - BC Building · PDF fileDeep Green Retrofits Rob Dumont ... House with Boiler System ... another expt. Windows R2 R3 1.5 Air Tightness 2.95 ac/h @50 Pa 0.29 ac/h

Cost of Rigid Insulation

Page 14: Deep Green Retrofits - BC Building · PDF fileDeep Green Retrofits Rob Dumont ... House with Boiler System ... another expt. Windows R2 R3 1.5 Air Tightness 2.95 ac/h @50 Pa 0.29 ac/h

Cost of Rigid Insulation

In southern Canada

Approximately

15 cents per square foot per R value

Thus R100 in a 1000 square foot attic

would cost about $15000

Page 15: Deep Green Retrofits - BC Building · PDF fileDeep Green Retrofits Rob Dumont ... House with Boiler System ... another expt. Windows R2 R3 1.5 Air Tightness 2.95 ac/h @50 Pa 0.29 ac/h

Optimum R value

= Square root( Cost of fuel x annual

heating degree days x present worth

factor x internal heat gain factor / cost of

insulation)

(This approach was used in the

development of the Model National

Energy Code for Houses for Canada)

Page 16: Deep Green Retrofits - BC Building · PDF fileDeep Green Retrofits Rob Dumont ... House with Boiler System ... another expt. Windows R2 R3 1.5 Air Tightness 2.95 ac/h @50 Pa 0.29 ac/h

Optimum R values for Inuvik

Heating Degree Days

Cost of Fuel

Can. $/litre

Cost of

Insulation

$/ft2 per R

value

Optimum R

value

English Units

H-ft2-F/BTU

0.50 0.03 44

1.00 0.03 63

0.50 0.06 31

1.00 0.06 44

Page 17: Deep Green Retrofits - BC Building · PDF fileDeep Green Retrofits Rob Dumont ... House with Boiler System ... another expt. Windows R2 R3 1.5 Air Tightness 2.95 ac/h @50 Pa 0.29 ac/h

Recommended Revised

Analysis of Optimum

Insulation Levels

Optimum amount of insulation is that amount

which minimizes the combined cost of the

installed insulation and the cost of the fuel

to heat the space

PLUS

the cost of the heating system.

PLUS the cost of the environmental damage

(Estimated at $200 per tonne of CO2)

Page 18: Deep Green Retrofits - BC Building · PDF fileDeep Green Retrofits Rob Dumont ... House with Boiler System ... another expt. Windows R2 R3 1.5 Air Tightness 2.95 ac/h @50 Pa 0.29 ac/h

What does a heating system

cost for a modest house

install?

Cheap: Electric baseboards ($1k -$2k)

Cheap: Point source heating ($2k-$5k)

Intermediate: Forced air with fossil fuel ($10k-15k)

High: Boiler system with fossil fuel ($15k -$30k)

Page 19: Deep Green Retrofits - BC Building · PDF fileDeep Green Retrofits Rob Dumont ... House with Boiler System ... another expt. Windows R2 R3 1.5 Air Tightness 2.95 ac/h @50 Pa 0.29 ac/h

Example of a Point Source

Oil Fired Space Heater

Toyotomi Space Heater

22,000 BTU/hr (6.4 kilowatts)

90% Efficient AFUE

$2600 Cdn including

Thru-wall vent kit

Page 20: Deep Green Retrofits - BC Building · PDF fileDeep Green Retrofits Rob Dumont ... House with Boiler System ... another expt. Windows R2 R3 1.5 Air Tightness 2.95 ac/h @50 Pa 0.29 ac/h

Comparison of Capital Costs

of Insulation plus Heating

Standard Code

House with Boiler

System

Insulation $5,000

Heating System

$20,000

$25,000

Superinsulated

House with Point

Source Heating

Insulation

$15,000

Heating System

$5,000

$20,000

Page 21: Deep Green Retrofits - BC Building · PDF fileDeep Green Retrofits Rob Dumont ... House with Boiler System ... another expt. Windows R2 R3 1.5 Air Tightness 2.95 ac/h @50 Pa 0.29 ac/h

Observation:

Consider the total cost of the thermal

comfort system including the heating

system, and not just the cost of the

insulation

Use an integrated design

Talk to Juergen Korn of Yukon Housing

Page 22: Deep Green Retrofits - BC Building · PDF fileDeep Green Retrofits Rob Dumont ... House with Boiler System ... another expt. Windows R2 R3 1.5 Air Tightness 2.95 ac/h @50 Pa 0.29 ac/h

Techniques for Super-

insulated Retrofits

Source Books:

The Super-insulated Retrofit Book by

Robert Argue (1982, Firefly Books,

available from www.amazon.com)

Keeping the Heat In by Natural

Resources Canada

Page 23: Deep Green Retrofits - BC Building · PDF fileDeep Green Retrofits Rob Dumont ... House with Boiler System ... another expt. Windows R2 R3 1.5 Air Tightness 2.95 ac/h @50 Pa 0.29 ac/h

Case Study

Double-Wall Double Roof

Retrofit

Location: Saskatoon

Annual Heating Degree Days: 5950 HDD

Celsius

1968 Bungalow

Page 24: Deep Green Retrofits - BC Building · PDF fileDeep Green Retrofits Rob Dumont ... House with Boiler System ... another expt. Windows R2 R3 1.5 Air Tightness 2.95 ac/h @50 Pa 0.29 ac/h
Page 25: Deep Green Retrofits - BC Building · PDF fileDeep Green Retrofits Rob Dumont ... House with Boiler System ... another expt. Windows R2 R3 1.5 Air Tightness 2.95 ac/h @50 Pa 0.29 ac/h

Pre-Retrofit

Page 26: Deep Green Retrofits - BC Building · PDF fileDeep Green Retrofits Rob Dumont ... House with Boiler System ... another expt. Windows R2 R3 1.5 Air Tightness 2.95 ac/h @50 Pa 0.29 ac/h

Post Retrofit

Page 27: Deep Green Retrofits - BC Building · PDF fileDeep Green Retrofits Rob Dumont ... House with Boiler System ... another expt. Windows R2 R3 1.5 Air Tightness 2.95 ac/h @50 Pa 0.29 ac/h

Pre-Retrofit

Page 28: Deep Green Retrofits - BC Building · PDF fileDeep Green Retrofits Rob Dumont ... House with Boiler System ... another expt. Windows R2 R3 1.5 Air Tightness 2.95 ac/h @50 Pa 0.29 ac/h

Comparison of Pre and Post

Pre-Retrofit Post-

Retrofit

Ratio

Post/Pre

Attic Insulation R20

RSI 3.5

R60

RSI 10.7

3.6

Wall Insulation

(Nominal)

R 7

RSI 1.2

R 47

RSI 8.3

4.3

Bsmt Floor

Insulation

R 0 No change ;

Later R20 was

added in

another expt.

Windows R2 R3 1.5

Air Tightness 2.95 ac/h @50

Pa

0.29 ac/h

@50 Pa

0.10

Page 29: Deep Green Retrofits - BC Building · PDF fileDeep Green Retrofits Rob Dumont ... House with Boiler System ... another expt. Windows R2 R3 1.5 Air Tightness 2.95 ac/h @50 Pa 0.29 ac/h

Energy Results

Peak Heat Loss reduced from 13.1 kW to

5.5 kW

Page 30: Deep Green Retrofits - BC Building · PDF fileDeep Green Retrofits Rob Dumont ... House with Boiler System ... another expt. Windows R2 R3 1.5 Air Tightness 2.95 ac/h @50 Pa 0.29 ac/h

Step 1. Cut off eaves and wrap roof

and walls with poly

(sometimes called the ―chainsaw

retrofit‖)

Page 31: Deep Green Retrofits - BC Building · PDF fileDeep Green Retrofits Rob Dumont ... House with Boiler System ... another expt. Windows R2 R3 1.5 Air Tightness 2.95 ac/h @50 Pa 0.29 ac/h

Step 2. Add second roof

Page 32: Deep Green Retrofits - BC Building · PDF fileDeep Green Retrofits Rob Dumont ... House with Boiler System ... another expt. Windows R2 R3 1.5 Air Tightness 2.95 ac/h @50 Pa 0.29 ac/h

Step 3. Add exterior wall

system

Page 33: Deep Green Retrofits - BC Building · PDF fileDeep Green Retrofits Rob Dumont ... House with Boiler System ... another expt. Windows R2 R3 1.5 Air Tightness 2.95 ac/h @50 Pa 0.29 ac/h

Step 4. Finish details

around windows & doors

Page 34: Deep Green Retrofits - BC Building · PDF fileDeep Green Retrofits Rob Dumont ... House with Boiler System ... another expt. Windows R2 R3 1.5 Air Tightness 2.95 ac/h @50 Pa 0.29 ac/h

Insulation of walls & bsmt

walls

Page 35: Deep Green Retrofits - BC Building · PDF fileDeep Green Retrofits Rob Dumont ... House with Boiler System ... another expt. Windows R2 R3 1.5 Air Tightness 2.95 ac/h @50 Pa 0.29 ac/h

R40 on Roof ; R40 on

Walls; R40 in Bsmt Walls

Page 36: Deep Green Retrofits - BC Building · PDF fileDeep Green Retrofits Rob Dumont ... House with Boiler System ... another expt. Windows R2 R3 1.5 Air Tightness 2.95 ac/h @50 Pa 0.29 ac/h

Post Retrofit—Asphalt

Shingles, Stucco Walls

Page 37: Deep Green Retrofits - BC Building · PDF fileDeep Green Retrofits Rob Dumont ... House with Boiler System ... another expt. Windows R2 R3 1.5 Air Tightness 2.95 ac/h @50 Pa 0.29 ac/h

February 2010 View of

House

Page 38: Deep Green Retrofits - BC Building · PDF fileDeep Green Retrofits Rob Dumont ... House with Boiler System ... another expt. Windows R2 R3 1.5 Air Tightness 2.95 ac/h @50 Pa 0.29 ac/h
Page 39: Deep Green Retrofits - BC Building · PDF fileDeep Green Retrofits Rob Dumont ... House with Boiler System ... another expt. Windows R2 R3 1.5 Air Tightness 2.95 ac/h @50 Pa 0.29 ac/h

Comparison of Pre and Post

Pre-Retrofit Post-

Retrofit

Ratio

Post/Pre

Attic Insulation R20

RSI 3.5

R63

RSI 12.5

3.6

Wall Insulation

(Nominal)

R 7

RSI 1.2

R 47

RSI 8.3

4.3

Bsmt Floor

Insulation

R 0 No change ;

Later R20 was

added

Windows R2 R3 1.5

Air Tightness 2.95 ac/h @50

Pa

0.29 ac/h

@50 Pa

0.10

Page 40: Deep Green Retrofits - BC Building · PDF fileDeep Green Retrofits Rob Dumont ... House with Boiler System ... another expt. Windows R2 R3 1.5 Air Tightness 2.95 ac/h @50 Pa 0.29 ac/h
Page 41: Deep Green Retrofits - BC Building · PDF fileDeep Green Retrofits Rob Dumont ... House with Boiler System ... another expt. Windows R2 R3 1.5 Air Tightness 2.95 ac/h @50 Pa 0.29 ac/h

The Super Insulated Retrofit

Book by Robert Argue &

Brian Marshall

Page 42: Deep Green Retrofits - BC Building · PDF fileDeep Green Retrofits Rob Dumont ... House with Boiler System ... another expt. Windows R2 R3 1.5 Air Tightness 2.95 ac/h @50 Pa 0.29 ac/h

Saskatchewan Examples

of Deep Green Retrofits

Page 43: Deep Green Retrofits - BC Building · PDF fileDeep Green Retrofits Rob Dumont ... House with Boiler System ... another expt. Windows R2 R3 1.5 Air Tightness 2.95 ac/h @50 Pa 0.29 ac/h

Before: 1950s Wood Frame

building with concrete block

foundation walls

Page 44: Deep Green Retrofits - BC Building · PDF fileDeep Green Retrofits Rob Dumont ... House with Boiler System ... another expt. Windows R2 R3 1.5 Air Tightness 2.95 ac/h @50 Pa 0.29 ac/h

Double wall, double roof

retrofit

1950s 4 Plex in Regina, Saskatchewan

Harold Orr was designer of the retrofit

Achieved an 82% reduction in air leakage

Achieved an 85% reduction in space heating

Former single forced air furnace with one thermostat for 4 suites was replaced by thermostatically controlled point source natural gas fireplaces (1 per suite)

Page 45: Deep Green Retrofits - BC Building · PDF fileDeep Green Retrofits Rob Dumont ... House with Boiler System ... another expt. Windows R2 R3 1.5 Air Tightness 2.95 ac/h @50 Pa 0.29 ac/h

Post-Retrofit

Page 46: Deep Green Retrofits - BC Building · PDF fileDeep Green Retrofits Rob Dumont ... House with Boiler System ... another expt. Windows R2 R3 1.5 Air Tightness 2.95 ac/h @50 Pa 0.29 ac/h

Use of point source heating

(fireplace) in each of the 4

suites.

Page 47: Deep Green Retrofits - BC Building · PDF fileDeep Green Retrofits Rob Dumont ... House with Boiler System ... another expt. Windows R2 R3 1.5 Air Tightness 2.95 ac/h @50 Pa 0.29 ac/h

New primary heating system

consisted of 4 fireplaces

Cost of new primary heating system:

4 fireplaces x $2500 = $10,000

Back bedrooms also each had one 500

watt electric baseboard heater (rarely

used, as the tenant pays for electricity,

while the landlord pays for natural gas)

Page 48: Deep Green Retrofits - BC Building · PDF fileDeep Green Retrofits Rob Dumont ... House with Boiler System ... another expt. Windows R2 R3 1.5 Air Tightness 2.95 ac/h @50 Pa 0.29 ac/h

Further information on the

entire sequence of the

retrofit

http://solaralberta.ca/power%20point

/Harold%20Orr.ppt

Page 49: Deep Green Retrofits - BC Building · PDF fileDeep Green Retrofits Rob Dumont ... House with Boiler System ... another expt. Windows R2 R3 1.5 Air Tightness 2.95 ac/h @50 Pa 0.29 ac/h

Roof retrofit

Page 50: Deep Green Retrofits - BC Building · PDF fileDeep Green Retrofits Rob Dumont ... House with Boiler System ... another expt. Windows R2 R3 1.5 Air Tightness 2.95 ac/h @50 Pa 0.29 ac/h

Roof Retrofit

Page 51: Deep Green Retrofits - BC Building · PDF fileDeep Green Retrofits Rob Dumont ... House with Boiler System ... another expt. Windows R2 R3 1.5 Air Tightness 2.95 ac/h @50 Pa 0.29 ac/h

First Double Wall Retrofit-

1978, Saskatoon House

Page 52: Deep Green Retrofits - BC Building · PDF fileDeep Green Retrofits Rob Dumont ... House with Boiler System ... another expt. Windows R2 R3 1.5 Air Tightness 2.95 ac/h @50 Pa 0.29 ac/h

Small House Retro – 1988

Double Wall Retrofit

Page 53: Deep Green Retrofits - BC Building · PDF fileDeep Green Retrofits Rob Dumont ... House with Boiler System ... another expt. Windows R2 R3 1.5 Air Tightness 2.95 ac/h @50 Pa 0.29 ac/h

Shed Roof on back of House was Double-Roofed

to address Condensation Problem

Custom Solar Builders, Saskatoon, did the work

Page 54: Deep Green Retrofits - BC Building · PDF fileDeep Green Retrofits Rob Dumont ... House with Boiler System ... another expt. Windows R2 R3 1.5 Air Tightness 2.95 ac/h @50 Pa 0.29 ac/h

Advantages of Double

Wall/Double Roof Retrofits

1. Conduction losses can be greatly reduced

2. Air leakage can be greatly reduced

3. Heating system can be greatly simplified in many cases because of the reduced heat loss. (e.g. Fireplace is sufficient to heat a modest space.)

4. Provides opportunity to address simultaneous need for upgraded roofing and siding.

5. Space on the interior is not lost.

6. House can be occupied while work is in progress

Page 55: Deep Green Retrofits - BC Building · PDF fileDeep Green Retrofits Rob Dumont ... House with Boiler System ... another expt. Windows R2 R3 1.5 Air Tightness 2.95 ac/h @50 Pa 0.29 ac/h

Summary

1. Because of global warming concerns, deep retrofits are needed for our existing housing stock.

2. Deep green double wall, double roof retrofits have a track record of proven performance dating back up to 30 years.

3. Optimum insulation levels depend on more than just the cost of fuel and the cost of insulation. Consider also the capital cost of the heating system

4.Let’s get on with it.

Page 56: Deep Green Retrofits - BC Building · PDF fileDeep Green Retrofits Rob Dumont ... House with Boiler System ... another expt. Windows R2 R3 1.5 Air Tightness 2.95 ac/h @50 Pa 0.29 ac/h

Acknowledgements:

Staff of the Institute for Research in

Construction of the National Research

Council of Canada

Harold Orr, who conceived the retrofit

strategy and guided its development

Private contractors, including Rod Gibson

of Custom Solar Builders, Saskatoon