energies Article Use of Discharge Resistor to Improve Transient De-Excitation in Brushless Synchronous Machines Emilio Rebollo 1 , Carlos A. Platero 1, * , David Talavera 1 and Ricardo Granizo 2 1 Department of Electrical Engineering, ETS Ingenieros Industriales, Universidad Politécnica de Madrid, C/José Gutierrez Abascal, 2, 28006 Madrid, Spain 2 Department of Electrical Engineering, ETS Ingeniería y Diseño Industrial, Universidad Politécnica de Madrid, C/Ronda de Valencia, 3, 28012 Madrid, Spain * Correspondence: [email protected]; Tel.: +34-91-06-76977 Received: 3 June 2019; Accepted: 27 June 2019; Published: 1 July 2019 Abstract: The discharge resistor is only used in case of electrical trip to reduce the field current as fast as possible and to minimize the damages produced by the short-circuit current supplied by the synchronous machine. The connection of the discharge resistor is done by opening the field breaker and it implies a large negative voltage in the field winding. This negative voltage is limited to 80% of the winding insulation voltage. On the other hand, in case of a transient de-excitation, at the first moment, the automatic voltage regulator (AVR) reduces the field voltage to the minimum. In case of one-quadrant rectifier type AVR, the minimum voltage is zero and in case of two-quadrant rectifier AVR, the minimum voltage is close to the ceiling voltage with negative polarity. In both cases, the minimum voltages are much smaller than the negative voltage produced by the connection of the discharge resistor. This paper presents a new system that improves the transient de-excitation of synchronous machines using the discharge resistor by an additional static field breaker (SFB). The control of the static field breaker and consequently the connection and disconnection of the discharge resistor is done based on the output field voltage supplied by the AVR. This allows the exciter field current to be reduced in a faster way and continue with the normal operation of the machine after the transient. In this study, the correct operation of the additional static field breaker (SFB) has been validated by computer simulations and experimental test in a 15 MVA generator comprising a commercial one-quadrant rectifier AVR type obtaining excellent results. Keywords: synchronous generator excitation; brushless rotating machines; synchronous machines; machine protection; de-excitation system; de-excitation time constant; protection system; brushless excitation; brushless synchronous machine testing 1. Introduction Nowadays there are mainly two excitation systems in the market, static and brushless [1]. The static excitation system directly feeds the field winding of the synchronous machine, hence requires slipping rings and brushes which creates problems for maintenance [2]. However, the control of the field current could be performed in a fast way, so the transient response is swift [3]. On the other hand, the brushless excitation systems require an additional electrical machine, called exciter, which feeds the field winding of the main machine [46]. This system does not require slipping rings or brushes; however, the field winding is not accessible for de-excitation [7,8]. One of the main disadvantages of brushless synchronous machines is that the rotating diodes do not allow a fast de-excitation, as the minimum voltage in the diode bridge is zero. Numerous systems have been developed to address this issue. One very common technique is the use of a rotating Energies 2019, 12, 2528; doi:10.3390/en12132528 www.mdpi.com/journal/energies

Upload: others

Post on 16-Nov-2021

14 views

Category:

Documents


3 download

TRANSCRIPT

Page 1: De-Excitation in Brushless Synchronous Machines

energies

Article

Use of Discharge Resistor to Improve TransientDe-Excitation in Brushless Synchronous Machines

Emilio Rebollo 1, Carlos A. Platero 1,* , David Talavera 1 and Ricardo Granizo 2

1 Department of Electrical Engineering, ETS Ingenieros Industriales, Universidad Politécnica de Madrid,C/José Gutierrez Abascal, 2, 28006 Madrid, Spain

2 Department of Electrical Engineering, ETS Ingeniería y Diseño Industrial,Universidad Politécnica de Madrid, C/Ronda de Valencia, 3, 28012 Madrid, Spain

* Correspondence: [email protected]; Tel.: +34-91-06-76977

Received: 3 June 2019; Accepted: 27 June 2019; Published: 1 July 2019

Abstract: The discharge resistor is only used in case of electrical trip to reduce the field current asfast as possible and to minimize the damages produced by the short-circuit current supplied bythe synchronous machine. The connection of the discharge resistor is done by opening the fieldbreaker and it implies a large negative voltage in the field winding. This negative voltage is limitedto 80% of the winding insulation voltage. On the other hand, in case of a transient de-excitation,at the first moment, the automatic voltage regulator (AVR) reduces the field voltage to the minimum.In case of one-quadrant rectifier type AVR, the minimum voltage is zero and in case of two-quadrantrectifier AVR, the minimum voltage is close to the ceiling voltage with negative polarity. In both cases,the minimum voltages are much smaller than the negative voltage produced by the connection ofthe discharge resistor. This paper presents a new system that improves the transient de-excitationof synchronous machines using the discharge resistor by an additional static field breaker (SFB).The control of the static field breaker and consequently the connection and disconnection of thedischarge resistor is done based on the output field voltage supplied by the AVR. This allows theexciter field current to be reduced in a faster way and continue with the normal operation of themachine after the transient. In this study, the correct operation of the additional static field breaker(SFB) has been validated by computer simulations and experimental test in a 15 MVA generatorcomprising a commercial one-quadrant rectifier AVR type obtaining excellent results.

Keywords: synchronous generator excitation; brushless rotating machines; synchronous machines;machine protection; de-excitation system; de-excitation time constant; protection system; brushlessexcitation; brushless synchronous machine testing

1. Introduction

Nowadays there are mainly two excitation systems in the market, static and brushless [1]. The staticexcitation system directly feeds the field winding of the synchronous machine, hence requires slippingrings and brushes which creates problems for maintenance [2]. However, the control of the field currentcould be performed in a fast way, so the transient response is swift [3].

On the other hand, the brushless excitation systems require an additional electrical machine,called exciter, which feeds the field winding of the main machine [4–6]. This system does not requireslipping rings or brushes; however, the field winding is not accessible for de-excitation [7,8].

One of the main disadvantages of brushless synchronous machines is that the rotating diodesdo not allow a fast de-excitation, as the minimum voltage in the diode bridge is zero. Numeroussystems have been developed to address this issue. One very common technique is the use of a rotating

Energies 2019, 12, 2528; doi:10.3390/en12132528 www.mdpi.com/journal/energies

Page 2: De-Excitation in Brushless Synchronous Machines

Energies 2019, 12, 2528 2 of 17

resistor [9–11]. Other techniques are based on rotating controlled bridges [12,13]. These methods havevery complex control systems which require trusted communication between the stator and the rotor.

Mixed excitation systems have also been developed and it is a very active research line [14] inorder to combine the static and brushless system advantages.

There are other research lines to improve the operation excitation system for synchronous machinesbased on the use of subharmonic excitation [15], improving the rotor design [16], or nonlinear excitationcontrol [17].

In a previous study, in order to solve the problem of the rotating diodes bridge, one of thede-excitation techniques based on a rotating resistor was developed by the authors [18,19]. This system,called high-speed brushless de-excitation system (HSBDS) for synchronous machines, is based on anovel brushless configuration that includes an autonomous control card mounted in the rotor whichgoverns series of static switches and a discharge resistor which accelerates the field current suppression.Originally the HSBDS was developed for reducing the short-circuit current supplied by the machineand it was tested in a 5-kVA laboratory bench where it has proven its operation.

Afterward, the HSBDS was improved and commissioned in real generation units. In Reference [20]the necessary changes needed to scale the HSBDS from 5 kVA of the laboratory bench until 20 MVA ofa hydro generator were detailed. In the 20 MVA generator, the no-load de-excitation time constant hadbeen decreased by 4 times from the conventional brushless operation.

The inverse voltage of the semiconductors used as static switches has been investigated toimprove the transient response of the HSBDS [21]. Moreover, thanks to a 15 MVA synchronouslaboratory machine, the HSBDS has been tested in a large size commercial generator under short-circuitconditions [22] with excellent results. In this 15 MVA generator, the three-phase internal short-circuitenergy (i2t) was reduced by 12.5 times thanks to the use of the HSBDS.

Another problem of brushless excitation system is the additional time constant imposed by theadditional machine, the exciter. This paper deals with this problem.

In this paper, a new research line is presented. It consists of the use of the discharge resistor intransient operation and not only in case of electrical trip, as it is normally done. The discharge resistorwill be connected for de-excitation purpose and afterward disconnected, and the machine will continuewith the normal operation. It is necessary for an additional static field breaker (SFB).

In this work, we present an autonomous system to control the discharge resistor, based on acommercial microcontroller. Moreover, as a static field breaker, we use a static DC relay joined tothe conventional field breaker. The experimental tests have been carried out in a brushless 15 MVAgenerator where the HSBDS was previously installed. So, we also present tests of both systemsworking together.

This paper is structured as follows: Section 2 summarizes the problem of the brushless de-excitation.Section 3 details the principles of the proposed de-excitation system based on the transient use ofthe discharge resistor and an additional static field breaker (SFB). Section 4 shows the results of thecomputer simulations of the new de-excitation system for a brushless hydro generator. Section 5presents the experimental results of the tests done in a 15 MVA synchronous generator. And finally,Section 6 concludes with the main contributions of the paper.

2. De-Excitation of Brushless Synchronous Machines. Description of the Problem and State ofthe Art

2.1. De-Excitation of Brushless Synchronous Machines Process

Despite its advantages, a brushless excitation system has a poorer transient response compared tothe static system as the exciter introduces an extra time constant to the main synchronous machineconstant. Another reason is the use of rotating diodes which does not allow the field winding to getnegative voltage feed.

In synchronous machines, the transient behavior of the field current is characterized by thetransient time constant (1), that depends on the field winding impedance (Rf, Lf), the rotor–stator

Page 3: De-Excitation in Brushless Synchronous Machines

Energies 2019, 12, 2528 3 of 17

coupling (Mf), and the stator winding inductance (Ld). At no-load condition, the time constant (2) onlydepends on the field winding impedance, that is the ratio between inductance (Lf) and resistance (Rf).In any case, the time constants are inversely proportional to the resistance of the field winding.

Td′ =

L f −M2

fLd

R f(1)

Td0′ =

L f

R f(2)

These time constants determine the de-excitation process in the event of a transient de-excitationor in case of internal failure in a synchronous machine. In case a discharge resistor (Rd) was connected,the time constant of the machine diminishes, as presented in (3) and (4).

Td′ =

L f −M2

fLd

R f + Rd(3)

Td0′ =

L f

R f + Rd(4)

The higher the value of the discharge resistor (Rd), the lower is the de-excitation time. However,the voltage in the rotor is proportional to the discharge resistor and the excitation current at thebeginning of the de-excitation. So, the maximum value of the discharge resistor (Rd) should not damagethe rotor insulation. In the case of the static excitation system, the connection of a discharge resistorcan be done easily, so the transient response in case of field suppression is excellent.

The behavior of the brushless synchronous machines is worse for three reasons: first, the exciter(another additional synchronous machine) that enlarges the time constants; second, the absence ofbrushes does not easily connect the auxiliary circuit for field suppression; and third, the rotating diodesprevent the rotor from negative voltage feed.

For brushless synchronous machines, the usual value of the time constant is in the range of 0.5–1 sfor T’d (1) and 5–9 s for T’d0 (2). So, in case of an internal failure in the machine, the damage willprobably be critical, even if the electrical protection system operates correctly, as the current suppliedby the machine will last several seconds.

2.2. Brushless De-Excitation System State of the Art

The de-excitation, in case of electrical trip, is done using a discharge resistor connected by thefield breaker. There are mainly two different configurations depending on the field breaker and type ofrectifier, as shown in Figures 1 and 2.

Energies 2019, 12, x FOR PEER REVIEW 4 of 17

resistor placed in the rotor. The connection of the resistor is done by complex systems to initiate the de-excitation. In the case of the Reference [9], the control of the discharge resistor is done by a semiconductor controlled by slipping rings and brushes. On the other hand, in the case of References [10,11], the control is done by a complex rotating transformer. Furthermore, there are some techniques based on rotating thyristor bridges [12,13].

Discharge Resistor

Exciter Diode bridge

Rotating Components

Main Synchronous Machine

AVR

AVRControl

Automatic Voltage Regulator

FieldBreaker

Figure 1. Conventional 1-quadrant automatic voltage regulator (AVR) brushless excitation system.

Discharge Resistor

FieldBreaker

Exciter Diode bridge

Rotating Components

Main Synchronous Machine

AVR

AVRControl

Automatic Voltage Regulator

Figure 2. Conventional 2-quadrant AVR brushless excitation system.

High-Speed Brushless De-Excitation System (HSBDS)

One method to improve the problem imposed by the rotating diodes bridge has been developed by the authors. It is a fast de-excitation system called high-speed brushless de-excitation system (HSBDS), the detailed principles of operation of the de-excitation system were described in Reference [19]. In this section, only a brief description of the HSBDS is presented because some tests of the new system SFB in combination with HSBDS are presented.

The HSBDS system comprises a discharge resistor connected between the rotating diodes and the field winding of the main generator by a static switch (Figure 3). The static switch is operated by the analysis of the voltage measured at the rotating diodes by a control circuit. Therefore, it is not necessary for any external signal via radio, special transformers, or slip rings. The excitation system and the AVR scheme should remain the same as in a conventional brushless machine. Only if field suppression was required, the static switch would be closed and the discharge resistor connected.

A simplified diagram of the HSBDS during normal operation is presented in Figure 3a. In this case, the AVR supplies a current (If exc) that flows through the exciter field winding. This induces an AC voltage in the armature windings of the exciter. Hence, a current flow through the rotating diodes and feeds the main synchronous generator field winding with (If). As a result, there is a positive polarity voltage at the diode bridge (Ubridge) and therefore at the field winding (Uf). The positive polarity voltage measured by control circuit close the static switch. Consequently, the field current goes from the diode bridge to the field winding through the static switch.

Figure 1. Conventional 1-quadrant automatic voltage regulator (AVR) brushless excitation system.

Page 4: De-Excitation in Brushless Synchronous Machines

Energies 2019, 12, 2528 4 of 17

Energies 2019, 12, x FOR PEER REVIEW 4 of 17

resistor placed in the rotor. The connection of the resistor is done by complex systems to initiate the de-excitation. In the case of the Reference [9], the control of the discharge resistor is done by a semiconductor controlled by slipping rings and brushes. On the other hand, in the case of References [10,11], the control is done by a complex rotating transformer. Furthermore, there are some techniques based on rotating thyristor bridges [12,13].

Discharge Resistor

Exciter Diode bridge

Rotating Components

Main Synchronous Machine

AVR

AVRControl

Automatic Voltage Regulator

FieldBreaker

Figure 1. Conventional 1-quadrant automatic voltage regulator (AVR) brushless excitation system.

Discharge Resistor

FieldBreaker

Exciter Diode bridge

Rotating Components

Main Synchronous Machine

AVR

AVRControl

Automatic Voltage Regulator

Figure 2. Conventional 2-quadrant AVR brushless excitation system.

High-Speed Brushless De-Excitation System (HSBDS)

One method to improve the problem imposed by the rotating diodes bridge has been developed by the authors. It is a fast de-excitation system called high-speed brushless de-excitation system (HSBDS), the detailed principles of operation of the de-excitation system were described in Reference [19]. In this section, only a brief description of the HSBDS is presented because some tests of the new system SFB in combination with HSBDS are presented.

The HSBDS system comprises a discharge resistor connected between the rotating diodes and the field winding of the main generator by a static switch (Figure 3). The static switch is operated by the analysis of the voltage measured at the rotating diodes by a control circuit. Therefore, it is not necessary for any external signal via radio, special transformers, or slip rings. The excitation system and the AVR scheme should remain the same as in a conventional brushless machine. Only if field suppression was required, the static switch would be closed and the discharge resistor connected.

A simplified diagram of the HSBDS during normal operation is presented in Figure 3a. In this case, the AVR supplies a current (If exc) that flows through the exciter field winding. This induces an AC voltage in the armature windings of the exciter. Hence, a current flow through the rotating diodes and feeds the main synchronous generator field winding with (If). As a result, there is a positive polarity voltage at the diode bridge (Ubridge) and therefore at the field winding (Uf). The positive polarity voltage measured by control circuit close the static switch. Consequently, the field current goes from the diode bridge to the field winding through the static switch.

Figure 2. Conventional 2-quadrant AVR brushless excitation system.

In Figure 1 an automatic voltage regulator (AVR) one-quadrant Insulated Gate Bipolar Transistor(IGBT) rectifier type is shown in combination with a single pole field breaker. In this configuration,the discharge resistor is connected when the field breaker is open in case of shutdown. While in case oftransient de-excitation the minimum voltage supply by the AVR is zero, consequently the de-excitationof the field winding of the exciter is not very fast.

In Figure 2 two-quadrant thyristors rectifier AVR type is shown in combination with a three polesfield breaker. The discharge resistor is connected by a normally closed pole of the field breaker. In caseof transient de-excitation, the thyristor bridge firing angle can raise 150 and supply negative voltage,this voltage is around 1.5 times the rated excitation voltage. In this case, the de-excitation of the fieldwinding of the exciter is faster.

The main problem of the de-excitation is related to the rotating diodes. In order to improvethe de-excitation time constant of synchronous machines, some techniques have been developed.Most of these techniques are based on the fast dissipation of the magnetic energy of the rotor ina rotating resistor placed in the rotor. The connection of the resistor is done by complex systemsto initiate the de-excitation. In the case of the Reference [9], the control of the discharge resistor isdone by a semiconductor controlled by slipping rings and brushes. On the other hand, in the case ofReferences [10,11], the control is done by a complex rotating transformer. Furthermore, there are sometechniques based on rotating thyristor bridges [12,13].

High-Speed Brushless De-Excitation System (HSBDS)

One method to improve the problem imposed by the rotating diodes bridge has been developed bythe authors. It is a fast de-excitation system called high-speed brushless de-excitation system (HSBDS),the detailed principles of operation of the de-excitation system were described in Reference [19]. In thissection, only a brief description of the HSBDS is presented because some tests of the new system SFBin combination with HSBDS are presented.

The HSBDS system comprises a discharge resistor connected between the rotating diodes andthe field winding of the main generator by a static switch (Figure 3). The static switch is operated bythe analysis of the voltage measured at the rotating diodes by a control circuit. Therefore, it is notnecessary for any external signal via radio, special transformers, or slip rings. The excitation systemand the AVR scheme should remain the same as in a conventional brushless machine. Only if fieldsuppression was required, the static switch would be closed and the discharge resistor connected.

A simplified diagram of the HSBDS during normal operation is presented in Figure 3a. In thiscase, the AVR supplies a current (If exc) that flows through the exciter field winding. This inducesan AC voltage in the armature windings of the exciter. Hence, a current flow through the rotatingdiodes and feeds the main synchronous generator field winding with (If). As a result, there is a positivepolarity voltage at the diode bridge (Ubridge) and therefore at the field winding (Uf). The positive

Page 5: De-Excitation in Brushless Synchronous Machines

Energies 2019, 12, 2528 5 of 17

polarity voltage measured by control circuit close the static switch. Consequently, the field currentgoes from the diode bridge to the field winding through the static switch.Energies 2019, 12, x FOR PEER REVIEW 5 of 17

Main Synchronous Machine Exciter

Rotating Components

HSBDS

Rd

ControlCircuit

Static Switch

Diode bridge

+

Uf

-

Ir ≈ 0

I ≠ 0+

-

Ubridge

If exc≠0

Rotating ComponentsRd

ControlCircuit

Static Switch

If exc ↓-

Uf

+

If

Ir = If

I = 0-

+

If/3If/3 If/3

a)

b)

If

Ubridge

Figure 3. Simplified diagram of a brushless synchronous generator with a high-speed brushless de-excitation system (HSBDS) (a) During normal operation; (b) During the de-excitation of the brushless synchronous generator.

A simplified diagram of the HSBDS during de-excitation process is displayed in Figure 3b. In case of electrical trip in the brushless synchronous generator, the field breaker will open. So, the current of the exciter field winding will be quickly reduced. Therefore, the diode bridge voltage will be also reduced. A voltage will be induced in the field winding of the main generator with inverse polarity, as the winding is very inductive. So, the current through the winding does not change suddenly, nor does the magnetic flux. This inverse voltage, in the main machine field winding, makes the voltage in the diode bridge becomes negative. At this moment, the control circuit will turn off the static switch. So, the field current will go through the discharge resistor (Rd) as presented in Figure 3b. By adding the discharge resistor in the circuit this system diminishes the de-excitation time constant of the main synchronous machine considerably as expressed in (3) and (4). By appropriate dimensioning of the discharge resistance, the resultant transient response of the brushless generator can thus be made comparable to that of a static excitation generator.

3. Operation Principle of Transient Use of the Discharge Resistor by Static Field Breaker (SFB)

A brushless excitation system comprises two synchronous machines, an exciter and a main synchronous machine, which rotate together at the same shaft. The exciter is small in comparison to the main machine, as it is only dimensioned to supply the power needed by the field winding of the main synchronous machine through a rotating diode bridge. The exciter has the field winding in the stator and the armature winding in the rotor, which is not the normal configuration for synchronous machines.

One of the main problems of the brushless configuration is the delay which the exciter introduces in case of field current change. The exciter behaves as a first-order system with typical time constants of 100–500 ms.

Most of the brushless excitation systems have an automatic voltage regulator (AVR) comprising one-quadrant rectifier as shown in Figure 4. So, it is not possible to feed the exciter field winding with negative voltage.

Figure 3. Simplified diagram of a brushless synchronous generator with a high-speed brushlessde-excitation system (HSBDS) (a) During normal operation; (b) During the de-excitation of thebrushless synchronous generator.

A simplified diagram of the HSBDS during de-excitation process is displayed in Figure 3b. In caseof electrical trip in the brushless synchronous generator, the field breaker will open. So, the currentof the exciter field winding will be quickly reduced. Therefore, the diode bridge voltage will be alsoreduced. A voltage will be induced in the field winding of the main generator with inverse polarity,as the winding is very inductive. So, the current through the winding does not change suddenly, nordoes the magnetic flux. This inverse voltage, in the main machine field winding, makes the voltage inthe diode bridge becomes negative. At this moment, the control circuit will turn off the static switch.So, the field current will go through the discharge resistor (Rd) as presented in Figure 3b. By addingthe discharge resistor in the circuit this system diminishes the de-excitation time constant of the mainsynchronous machine considerably as expressed in (3) and (4). By appropriate dimensioning of thedischarge resistance, the resultant transient response of the brushless generator can thus be madecomparable to that of a static excitation generator.

3. Operation Principle of Transient Use of the Discharge Resistor by Static Field Breaker (SFB)

A brushless excitation system comprises two synchronous machines, an exciter and a mainsynchronous machine, which rotate together at the same shaft. The exciter is small in comparison to themain machine, as it is only dimensioned to supply the power needed by the field winding of the mainsynchronous machine through a rotating diode bridge. The exciter has the field winding in the statorand the armature winding in the rotor, which is not the normal configuration for synchronous machines.

One of the main problems of the brushless configuration is the delay which the exciter introducesin case of field current change. The exciter behaves as a first-order system with typical time constantsof 100–500 ms.

Page 6: De-Excitation in Brushless Synchronous Machines

Energies 2019, 12, 2528 6 of 17

Most of the brushless excitation systems have an automatic voltage regulator (AVR) comprisingone-quadrant rectifier as shown in Figure 4. So, it is not possible to feed the exciter field winding withnegative voltage.Energies 2019, 12, x FOR PEER REVIEW 6 of 17

Discharge Resistor

Field Breaker

AVR

AVRControl

ExciterAutomatic Voltage Regulator

Figure 4. Conventional 1-quadrant AVR brushless excitation system.

In case of de-excitation in normal operation (not in case of machine trip), the AVR will reduce the voltage to feed the exciter field winding. In this case, the time constant will be the own time constant of the winding L/R, neglecting the voltage drop in the freewheel diode. The equivalent circuit is presented in Figure 5.

In order to get a faster de-excitation, the proposed solution is based on the transient use of the discharge resistor to decrease the time constant of the circuit. For that purpose, it has been necessary to install an additional static field breaker (SFB) (Figure 6). This SFB can connect and disconnect the discharge resistor quickly, as it is connected in series to the field breaker.

If

Figure 5. Conventional AVR brushless excitation system. Exciter field current in case of transient de-excitation (field breaker closed).

Discharge Resistor

Field Breaker

AVR

AVRControl

ExciterAutomatic Voltage Regulator

SFB

Figure 6. Proposed AVR brushless excitation system with an additional static field breaker (SFB).

In normal operation, the field breaker is closed as well as the SFB. This represents a small voltage drop across the SFB (typically around 1.5 V), and therefore some losses. However, if the SFB is open the discharge resistor can be connected transiently in the circuit. In case of transient de-excitation in normal operation, the AVR will reduce the exciter field winding voltage and the SFB will open. Therefore, the time constant will be reduced because the total resistance of the circuit will be the field winding resistance and the discharge resistor. In this case, the negative voltage in the field winding is proportional to the value of the discharge resistor and the excitation current (Rd × If). The normal practice is dimensioning the discharge resistor to reach 80% of the maximum insulation voltage of the winding for the maximum excitation current. There are some machines which use nonlinear

Figure 4. Conventional 1-quadrant AVR brushless excitation system.

In case of de-excitation in normal operation (not in case of machine trip), the AVR will reducethe voltage to feed the exciter field winding. In this case, the time constant will be the own timeconstant of the winding L/R, neglecting the voltage drop in the freewheel diode. The equivalent circuitis presented in Figure 5.

Energies 2019, 12, x FOR PEER REVIEW 6 of 17

Discharge Resistor

Field Breaker

AVR

AVRControl

ExciterAutomatic Voltage Regulator

Figure 4. Conventional 1-quadrant AVR brushless excitation system.

In case of de-excitation in normal operation (not in case of machine trip), the AVR will reduce the voltage to feed the exciter field winding. In this case, the time constant will be the own time constant of the winding L/R, neglecting the voltage drop in the freewheel diode. The equivalent circuit is presented in Figure 5.

In order to get a faster de-excitation, the proposed solution is based on the transient use of the discharge resistor to decrease the time constant of the circuit. For that purpose, it has been necessary to install an additional static field breaker (SFB) (Figure 6). This SFB can connect and disconnect the discharge resistor quickly, as it is connected in series to the field breaker.

If

Figure 5. Conventional AVR brushless excitation system. Exciter field current in case of transient de-excitation (field breaker closed).

Discharge Resistor

Field Breaker

AVR

AVRControl

ExciterAutomatic Voltage Regulator

SFB

Figure 6. Proposed AVR brushless excitation system with an additional static field breaker (SFB).

In normal operation, the field breaker is closed as well as the SFB. This represents a small voltage drop across the SFB (typically around 1.5 V), and therefore some losses. However, if the SFB is open the discharge resistor can be connected transiently in the circuit. In case of transient de-excitation in normal operation, the AVR will reduce the exciter field winding voltage and the SFB will open. Therefore, the time constant will be reduced because the total resistance of the circuit will be the field winding resistance and the discharge resistor. In this case, the negative voltage in the field winding is proportional to the value of the discharge resistor and the excitation current (Rd × If). The normal practice is dimensioning the discharge resistor to reach 80% of the maximum insulation voltage of the winding for the maximum excitation current. There are some machines which use nonlinear

Figure 5. Conventional AVR brushless excitation system. Exciter field current in case of transientde-excitation (field breaker closed).

In order to get a faster de-excitation, the proposed solution is based on the transient use of thedischarge resistor to decrease the time constant of the circuit. For that purpose, it has been necessaryto install an additional static field breaker (SFB) (Figure 6). This SFB can connect and disconnect thedischarge resistor quickly, as it is connected in series to the field breaker.

Energies 2019, 12, x FOR PEER REVIEW 6 of 17

Discharge Resistor

Field Breaker

AVR

AVRControl

ExciterAutomatic Voltage Regulator

Figure 4. Conventional 1-quadrant AVR brushless excitation system.

In case of de-excitation in normal operation (not in case of machine trip), the AVR will reduce the voltage to feed the exciter field winding. In this case, the time constant will be the own time constant of the winding L/R, neglecting the voltage drop in the freewheel diode. The equivalent circuit is presented in Figure 5.

In order to get a faster de-excitation, the proposed solution is based on the transient use of the discharge resistor to decrease the time constant of the circuit. For that purpose, it has been necessary to install an additional static field breaker (SFB) (Figure 6). This SFB can connect and disconnect the discharge resistor quickly, as it is connected in series to the field breaker.

If

Figure 5. Conventional AVR brushless excitation system. Exciter field current in case of transient de-excitation (field breaker closed).

Discharge Resistor

Field Breaker

AVR

AVRControl

ExciterAutomatic Voltage Regulator

SFB

Figure 6. Proposed AVR brushless excitation system with an additional static field breaker (SFB).

In normal operation, the field breaker is closed as well as the SFB. This represents a small voltage drop across the SFB (typically around 1.5 V), and therefore some losses. However, if the SFB is open the discharge resistor can be connected transiently in the circuit. In case of transient de-excitation in normal operation, the AVR will reduce the exciter field winding voltage and the SFB will open. Therefore, the time constant will be reduced because the total resistance of the circuit will be the field winding resistance and the discharge resistor. In this case, the negative voltage in the field winding is proportional to the value of the discharge resistor and the excitation current (Rd × If). The normal practice is dimensioning the discharge resistor to reach 80% of the maximum insulation voltage of the winding for the maximum excitation current. There are some machines which use nonlinear

Figure 6. Proposed AVR brushless excitation system with an additional static field breaker (SFB).

In normal operation, the field breaker is closed as well as the SFB. This represents a small voltagedrop across the SFB (typically around 1.5 V), and therefore some losses. However, if the SFB is openthe discharge resistor can be connected transiently in the circuit. In case of transient de-excitationin normal operation, the AVR will reduce the exciter field winding voltage and the SFB will open.

Page 7: De-Excitation in Brushless Synchronous Machines

Energies 2019, 12, 2528 7 of 17

Therefore, the time constant will be reduced because the total resistance of the circuit will be the fieldwinding resistance and the discharge resistor. In this case, the negative voltage in the field windingis proportional to the value of the discharge resistor and the excitation current (Rd × If). The normalpractice is dimensioning the discharge resistor to reach 80% of the maximum insulation voltage of thewinding for the maximum excitation current. There are some machines which use nonlinear dischargeresistors to reach always the maximum negative voltage with any value of excitation current.

In this way, the excitation current reduces in a very fast way (Figure 7). It is remarkable thatthe de-excitation speed is faster than in the case of a 2-quadrant AVR where the negative voltageonly reaches the ceiling voltage. Because the ceiling voltage is normally 1.5 times the rated excitationvoltage, for any field current.

Energies 2019, 12, x FOR PEER REVIEW 7 of 17

discharge resistors to reach always the maximum negative voltage with any value of excitation current.

In this way, the excitation current reduces in a very fast way (Figure 7). It is remarkable that the de-excitation speed is faster than in the case of a 2-quadrant AVR where the negative voltage only reaches the ceiling voltage. Because the ceiling voltage is normally 1.5 times the rated excitation voltage, for any field current.

Rd Discharge Resistor

If

Figure 7. AVR brushless excitation system with additional static field breaker (SFB). Exciter field current in case of transient de-excitation (field breaker closed SFB open).

The control of the SFB could be done by the AVR through a digital output which turns on or turns off the static field breaker. Another possibility is the use of an external controller, as we present in this work. It meters the voltage supply to the field winding from the AVR, in case the voltage was close to zero the controller will open the SFB. In both cases, the control of the SFB is based on measuring the AVR output and in case it is less than an adjustable value.

After the transient de-excitation, the static switch must be turned off, disconnecting the discharge resistor from the field winding circuit. Therefore, the machine will continue the normal operation.

It is also remarkable that a hysteresis comparator must be programmed in order to avoid unwanted rebounds in the connection and disconnection of the discharge resistor.

Operation of SFB and HSBDS

The use of the SFB system together with the HSBDS is interesting. As explained in the last section, the control of the HSBDS is made by a comparison between the diodes bridge voltage and a threshold value so the control of this voltage in the optimal way is important. Since the SFB significantly decreases the constant time in the exciter, the diodes bridge voltage decreases faster and consequently the HSBDS will operate before.

If an important reduction in the main generator magnetic flux is needed, the AVR reduces the voltage in the exciter field winding and the SFB connects the discharge resistor demagnetizing the exciter. Consequently, the rotating diode bridge voltage decreases quickly and the HSBDS inserts the discharge resistor in the main generator field winding, thus the response time of the brushless machine with SFB and HSBDS will be like the static excitation system.

4. Simulations of the Proposed Static Field Breaker (SFB) System

In order to verify the operation and the advantages previously presented, numerous simulations have been made by using the Simpower System® of Matlab® Version 9.2 (2018b) software. The generator model [23] and the exciter model [24] have been largely used. The simulation model comprises the main generator, the complete excitation system, including the exciter, the static circuit breaker, and the discharge resistor (Figure 8). All the data correspond to a 40 MVA brushless hydro generator. The characteristics are shown in Appendix A Tables A1 and A2 for the generator and the exciter, respectively.

Furthermore, the novel SFB which affects the excitation current in the exciter has been included, as well as the HSBDS.

Figure 7. AVR brushless excitation system with additional static field breaker (SFB). Exciter fieldcurrent in case of transient de-excitation (field breaker closed SFB open).

The control of the SFB could be done by the AVR through a digital output which turns on or turnsoff the static field breaker. Another possibility is the use of an external controller, as we present in thiswork. It meters the voltage supply to the field winding from the AVR, in case the voltage was close tozero the controller will open the SFB. In both cases, the control of the SFB is based on measuring theAVR output and in case it is less than an adjustable value.

After the transient de-excitation, the static switch must be turned off, disconnecting the dischargeresistor from the field winding circuit. Therefore, the machine will continue the normal operation.

It is also remarkable that a hysteresis comparator must be programmed in order to avoid unwantedrebounds in the connection and disconnection of the discharge resistor.

Operation of SFB and HSBDS

The use of the SFB system together with the HSBDS is interesting. As explained in the last section,the control of the HSBDS is made by a comparison between the diodes bridge voltage and a thresholdvalue so the control of this voltage in the optimal way is important. Since the SFB significantly decreasesthe constant time in the exciter, the diodes bridge voltage decreases faster and consequently the HSBDSwill operate before.

If an important reduction in the main generator magnetic flux is needed, the AVR reduces thevoltage in the exciter field winding and the SFB connects the discharge resistor demagnetizing theexciter. Consequently, the rotating diode bridge voltage decreases quickly and the HSBDS inserts thedischarge resistor in the main generator field winding, thus the response time of the brushless machinewith SFB and HSBDS will be like the static excitation system.

4. Simulations of the Proposed Static Field Breaker (SFB) System

In order to verify the operation and the advantages previously presented, numerous simulationshave been made by using the Simpower System® of Matlab®Version 9.2 (2018b) software. The generatormodel [23] and the exciter model [24] have been largely used. The simulation model comprises themain generator, the complete excitation system, including the exciter, the static circuit breaker,and the discharge resistor (Figure 8). All the data correspond to a 40 MVA brushless hydro

Page 8: De-Excitation in Brushless Synchronous Machines

Energies 2019, 12, 2528 8 of 17

generator. The characteristics are shown in Appendix A Tables A1 and A2 for the generator and theexciter, respectively.Energies 2019, 12, x FOR PEER REVIEW 8 of 17

Figure 8. Simulation model of the brushless SFB de-excitation of a 40 MVA synchronous generator.

The simulations for the 40 MVA hydro generator have been performed for four different excitation systems:

-Conventional brushless excitation system.

The excitation corresponds to a conventional brushless excitation system. It will be considered as the reference.

-SFB.

Beside the brushless excitation system, the additional SFB is included in the exciter field winding, so the exciter discharge resistor could be temporally connected to the exciter field winding.

-HSBDS.

In this case, the HSBDS is installed in the field winding of the main synchronous machine. So, a rotating discharge resistor could be connected in the field winding of the main generator in case of the magnetic flux reduction. The AVR is connected to the exciter field winding only with the conventional field breaker.

-SFB + HSBDS.

In the last case, both systems are installed in the 40 MVA generator, the SBF and the HSBDS in the exciter and in the main machine field windings, respectively. Therefore, in case of magnetic flux reduction, the SBF will insert the discharge resistor in the exciter field winding and the HSBDS will insert the rotating discharge resistor in the main machine field winding.

4.1. Rated Voltage No-Load De-Excitation Simulations

The first simulations correspond to a de-excitation from rated voltage and no-load conditions. In these simulations, the generator voltage setpoint is altered from rated voltage to zero.

In these simulations, one can observe that the greatest de-excitation time corresponds to the conventional brushless, as the stator voltage decrease to zero in more than 10 s (Figure 9). When using the SFB the de-excitation time is slightly reduced, around 500 ms. The use of HSBDS notably improves the de-excitation time, because a discharge resistor is inserted in the field winding of the main machine. In Figure 10, the negative rotor voltage can be seen when the rotating discharge resistor is connected, in case of use of the HSBDS.

The fastest response corresponds to the combination of HSBDS and SFB, thanks to the discharge resistors connected in the field winding of the exciter and main machine respectively. In this

Figure 8. Simulation model of the brushless SFB de-excitation of a 40 MVA synchronous generator.

Furthermore, the novel SFB which affects the excitation current in the exciter has been included,as well as the HSBDS.

The simulations for the 40 MVA hydro generator have been performed for four differentexcitation systems:

-Conventional brushless excitation system.The excitation corresponds to a conventional brushless excitation system. It will be considered as

the reference.-SFB.Beside the brushless excitation system, the additional SFB is included in the exciter field winding,

so the exciter discharge resistor could be temporally connected to the exciter field winding.-HSBDS.In this case, the HSBDS is installed in the field winding of the main synchronous machine. So,

a rotating discharge resistor could be connected in the field winding of the main generator in case of themagnetic flux reduction. The AVR is connected to the exciter field winding only with the conventionalfield breaker.

-SFB + HSBDS.In the last case, both systems are installed in the 40 MVA generator, the SBF and the HSBDS in

the exciter and in the main machine field windings, respectively. Therefore, in case of magnetic fluxreduction, the SBF will insert the discharge resistor in the exciter field winding and the HSBDS willinsert the rotating discharge resistor in the main machine field winding.

4.1. Rated Voltage No-Load De-Excitation Simulations

The first simulations correspond to a de-excitation from rated voltage and no-load conditions.In these simulations, the generator voltage setpoint is altered from rated voltage to zero.

In these simulations, one can observe that the greatest de-excitation time corresponds to theconventional brushless, as the stator voltage decrease to zero in more than 10 s (Figure 9). When usingthe SFB the de-excitation time is slightly reduced, around 500 ms. The use of HSBDS notably improvesthe de-excitation time, because a discharge resistor is inserted in the field winding of the main machine.

Page 9: De-Excitation in Brushless Synchronous Machines

Energies 2019, 12, 2528 9 of 17

In Figure 10, the negative rotor voltage can be seen when the rotating discharge resistor is connected,in case of use of the HSBDS.

Energies 2019, 12, x FOR PEER REVIEW 9 of 17

configuration, the discharge resistor of the main machine is connected by the HSBDS around 500 ms before that in the previous case. Figure 11 shows the voltage in the exciter field winding and how with the use of the SFB the voltage becomes negative when the exciter discharge resistor is connected, whereas the conventional AVR makes the excitation voltage zero. The value in these cases is close to −2.25 times the rated voltage.

Figure 9. De-excitation at rated voltage simulation results at no-load, for 40 MVA synchronous generator. Stator voltage.

Figure 10. De-excitation at rated voltage simulation results at no-load, for 40 MVA synchronous generator. Rotor voltage.

Figure 11. De-excitation at rated voltage simulation results at no-load, for 40 MVA synchronous generator. Excitation voltage.

24 25 26 27 28 29 30 31 32 33 34 35

Time [s]

0

0.2

0.4

0.6

0.8

1[p

u]

Stator Voltage

Brushless

SFB

SFB+HSBDS

HSBDS

24 25 26 27 28 29 30 31 32 33 34 35

Time [s]

-2.5

-2

-1.5

-1

-0.5

0

0.5

1

[pu]

Rotor Voltage

Brushless

SFB

SFB+HSBDS

HSBDS

24 25 26 27 28 29 30 31 32 33 34 35

Time [s]

-2

-1

0

1

2

[pu]

Excitation Voltage

Brushless

SFB

SFB+HSBDS

HSBDS

Figure 9. De-excitation at rated voltage simulation results at no-load, for 40 MVA synchronous generator.Stator voltage.

Energies 2019, 12, x FOR PEER REVIEW 9 of 17

configuration, the discharge resistor of the main machine is connected by the HSBDS around 500 ms before that in the previous case. Figure 11 shows the voltage in the exciter field winding and how with the use of the SFB the voltage becomes negative when the exciter discharge resistor is connected, whereas the conventional AVR makes the excitation voltage zero. The value in these cases is close to −2.25 times the rated voltage.

Figure 9. De-excitation at rated voltage simulation results at no-load, for 40 MVA synchronous generator. Stator voltage.

Figure 10. De-excitation at rated voltage simulation results at no-load, for 40 MVA synchronous generator. Rotor voltage.

Figure 11. De-excitation at rated voltage simulation results at no-load, for 40 MVA synchronous generator. Excitation voltage.

24 25 26 27 28 29 30 31 32 33 34 35

Time [s]

0

0.2

0.4

0.6

0.8

1

[pu]

Stator Voltage

Brushless

SFB

SFB+HSBDS

HSBDS

24 25 26 27 28 29 30 31 32 33 34 35

Time [s]

-2.5

-2

-1.5

-1

-0.5

0

0.5

1

[pu]

Rotor Voltage

Brushless

SFB

SFB+HSBDS

HSBDS

24 25 26 27 28 29 30 31 32 33 34 35

Time [s]

-2

-1

0

1

2

[pu]

Excitation Voltage

Brushless

SFB

SFB+HSBDS

HSBDS

Figure 10. De-excitation at rated voltage simulation results at no-load, for 40 MVA synchronousgenerator. Rotor voltage.

The fastest response corresponds to the combination of HSBDS and SFB, thanks to the dischargeresistors connected in the field winding of the exciter and main machine respectively. In thisconfiguration, the discharge resistor of the main machine is connected by the HSBDS around 500 msbefore that in the previous case. Figure 11 shows the voltage in the exciter field winding and howwith the use of the SFB the voltage becomes negative when the exciter discharge resistor is connected,whereas the conventional AVR makes the excitation voltage zero. The value in these cases is close to−2.25 times the rated voltage.

Energies 2019, 12, x FOR PEER REVIEW 9 of 17

configuration, the discharge resistor of the main machine is connected by the HSBDS around 500 ms before that in the previous case. Figure 11 shows the voltage in the exciter field winding and how with the use of the SFB the voltage becomes negative when the exciter discharge resistor is connected, whereas the conventional AVR makes the excitation voltage zero. The value in these cases is close to −2.25 times the rated voltage.

Figure 9. De-excitation at rated voltage simulation results at no-load, for 40 MVA synchronous generator. Stator voltage.

Figure 10. De-excitation at rated voltage simulation results at no-load, for 40 MVA synchronous generator. Rotor voltage.

Figure 11. De-excitation at rated voltage simulation results at no-load, for 40 MVA synchronous generator. Excitation voltage.

24 25 26 27 28 29 30 31 32 33 34 35

Time [s]

0

0.2

0.4

0.6

0.8

1

[pu]

Stator Voltage

Brushless

SFB

SFB+HSBDS

HSBDS

24 25 26 27 28 29 30 31 32 33 34 35

Time [s]

-2.5

-2

-1.5

-1

-0.5

0

0.5

1

[pu]

Rotor Voltage

Brushless

SFB

SFB+HSBDS

HSBDS

24 25 26 27 28 29 30 31 32 33 34 35

Time [s]

-2

-1

0

1

2

[pu]

Excitation Voltage

Brushless

SFB

SFB+HSBDS

HSBDS

Figure 11. De-excitation at rated voltage simulation results at no-load, for 40 MVA synchronousgenerator. Excitation voltage.

Page 10: De-Excitation in Brushless Synchronous Machines

Energies 2019, 12, 2528 10 of 17

4.2. Step-Down Voltage Setpoint Simulations

The second set of simulations corresponds to a step-down in the voltage setpoint of the AVR.This is the normal way to test the response in generators during commissioning. In this simulation, thereference voltage in the AVR has suddenly changed from rated voltage to 80% rated voltage.

Figure 12 illustrates stator voltage for the four cases. The conventional brushless has the slowestresponse. When using the SFB, the response is similar, though it occurs around 500 ms in advance dueto the insertion of the exciter discharge resistor.

Energies 2019, 12, x FOR PEER REVIEW 10 of 17

4.2. Step-Down Voltage Setpoint Simulations

The second set of simulations corresponds to a step-down in the voltage setpoint of the AVR. This is the normal way to test the response in generators during commissioning. In this simulation, the reference voltage in the AVR has suddenly changed from rated voltage to 80% rated voltage.

Figure 12 illustrates stator voltage for the four cases. The conventional brushless has the slowest response. When using the SFB, the response is similar, though it occurs around 500 ms in advance due to the insertion of the exciter discharge resistor.

The use of HSBDS allows reducing the voltage in a faster way because the insertion of the rotor discharge resistor reduces the field current quickly. The SFB + HSBDS has the fastest response because the exciter discharge resistor makes it possible for the HSBDS to operate around 500 ms in advance.

In Figure 13, the rotor voltages are presented. With the use of the HSBDS, the voltage becomes negative in the first part of the transient response.

Figure 14 shows the voltages supplied by the AVR to the exciter field winding. The transient responses of the regulator are different in the four cases because the stator voltages are also different.

In the cases where the SFB is used, the voltage becomes negative when the exciter discharge resistor is connected. The value in these cases is close to −2.25 times the rated voltage. In the other two cases, the exciter field voltage is zero.

Figure 12. Step-down voltage setpoint simulation results at no-load for 40 MVA synchronous generator. Stator voltage.

Figure 13. Step-down voltage setpoint simulation results at no-load for 40 MVA synchronous generator. Rotor voltage.

29 30 31 32 33 34 35 36 37 38 39

Time [s]

0.4

0.6

0.8

1

1.2

1.4

[pu]

Stator Voltage

Brushless

SFB

SFB+HSBDS

HSBDS

29 30 31 32 33 34 35 36 37 38 39

Time [s]

-2

-1

0

1

2

[pu]

Rotor Voltage

Brushless

SFB

SFB+HSBDS

HSBDS

Figure 12. Step-down voltage setpoint simulation results at no-load for 40 MVA synchronous generator.Stator voltage.

The use of HSBDS allows reducing the voltage in a faster way because the insertion of the rotordischarge resistor reduces the field current quickly. The SFB + HSBDS has the fastest response becausethe exciter discharge resistor makes it possible for the HSBDS to operate around 500 ms in advance.

In Figure 13, the rotor voltages are presented. With the use of the HSBDS, the voltage becomesnegative in the first part of the transient response.

Energies 2019, 12, x FOR PEER REVIEW 10 of 17

4.2. Step-Down Voltage Setpoint Simulations

The second set of simulations corresponds to a step-down in the voltage setpoint of the AVR. This is the normal way to test the response in generators during commissioning. In this simulation, the reference voltage in the AVR has suddenly changed from rated voltage to 80% rated voltage.

Figure 12 illustrates stator voltage for the four cases. The conventional brushless has the slowest response. When using the SFB, the response is similar, though it occurs around 500 ms in advance due to the insertion of the exciter discharge resistor.

The use of HSBDS allows reducing the voltage in a faster way because the insertion of the rotor discharge resistor reduces the field current quickly. The SFB + HSBDS has the fastest response because the exciter discharge resistor makes it possible for the HSBDS to operate around 500 ms in advance.

In Figure 13, the rotor voltages are presented. With the use of the HSBDS, the voltage becomes negative in the first part of the transient response.

Figure 14 shows the voltages supplied by the AVR to the exciter field winding. The transient responses of the regulator are different in the four cases because the stator voltages are also different.

In the cases where the SFB is used, the voltage becomes negative when the exciter discharge resistor is connected. The value in these cases is close to −2.25 times the rated voltage. In the other two cases, the exciter field voltage is zero.

Figure 12. Step-down voltage setpoint simulation results at no-load for 40 MVA synchronous generator. Stator voltage.

Figure 13. Step-down voltage setpoint simulation results at no-load for 40 MVA synchronous generator. Rotor voltage.

29 30 31 32 33 34 35 36 37 38 39

Time [s]

0.4

0.6

0.8

1

1.2

1.4

[pu]

Stator Voltage

Brushless

SFB

SFB+HSBDS

HSBDS

29 30 31 32 33 34 35 36 37 38 39

Time [s]

-2

-1

0

1

2

[pu]

Rotor Voltage

Brushless

SFB

SFB+HSBDS

HSBDS

Figure 13. Step-down voltage setpoint simulation results at no-load for 40 MVA synchronous generator.Rotor voltage.

Figure 14 shows the voltages supplied by the AVR to the exciter field winding. The transientresponses of the regulator are different in the four cases because the stator voltages are also different.

In the cases where the SFB is used, the voltage becomes negative when the exciter dischargeresistor is connected. The value in these cases is close to −2.25 times the rated voltage. In the other twocases, the exciter field voltage is zero.

Page 11: De-Excitation in Brushless Synchronous Machines

Energies 2019, 12, 2528 11 of 17

Energies 2019, 12, x FOR PEER REVIEW 11 of 17

Figure 14. Step-down voltage setpoint simulation results at no-load for 40 MVA synchronous generator. Excitation voltage.

5. Static Field Breaker (SFB) Laboratory Experimental Test in a 15 MVA Synchronous Machine

5.1. Experimental Setup

The tests were performed in a 15 MVA, 13 kV, 1000 rpm synchronous generator with an exciter and a commercial one-quadrant AVR. Figure 15 shows the experimental setup, comprising a main generator (15 MVA), the exciter, and a field breaker. The characteristics are shown in Appendix B Tables A3 and A4 for the generator and the exciter, respectively. Using special switch-disconnector equipment, the stator winding can be connected in four different configurations, so it is possible to test in different stator voltages. Moreover, in the experimental setup, there are voltage transformers and slipping ring for metering purpose.

The experimental setup has some special features compared to a conventional generator; a simplified schema is shown in Figure 16. Firstly, three slip rings are installed in order to take measurements. A copper bar (HSBDS disconnector Figure 16) could be connected in parallel to the static switch, in this condition, the machine operates as a conventional brushless.

During the test, the commercial AVR used does not allow to configure the digital output for special purpose. So, the SFB control is done externally by an Arduino Nano® V3.0 microcontroller (Figure 17a). This controller measures the excitation voltage supply by the AVR. In case the voltage is close to zero, the SFB should be open. When the AVR output is greater than an adjustable value the SFB will be close again.

Main Generator

Voltage transformers

Exciter

HSBDS

Disconnectors

Field Circuit Breaker

Slip rings

Slip rings

Figure 15. Experimental setup 15 MVA, 13 kV synchronous machine for HSBDS + SFB testing.

29 30 31 32 33 34 35 36 37 38 39

-4

-2

0

2

4

[pu]

Excitation Voltage

Brushless

SFB

SFB+HSBDS

HSBDS

Figure 14. Step-down voltage setpoint simulation results at no-load for 40 MVA synchronous generator.Excitation voltage.

5. Static Field Breaker (SFB) Laboratory Experimental Test in a 15 MVA Synchronous Machine

5.1. Experimental Setup

The tests were performed in a 15 MVA, 13 kV, 1000 rpm synchronous generator with an exciterand a commercial one-quadrant AVR. Figure 15 shows the experimental setup, comprising a maingenerator (15 MVA), the exciter, and a field breaker. The characteristics are shown in Appendix BTables A3 and A4 for the generator and the exciter, respectively. Using special switch-disconnectorequipment, the stator winding can be connected in four different configurations, so it is possible to testin different stator voltages. Moreover, in the experimental setup, there are voltage transformers andslipping ring for metering purpose.

Energies 2019, 12, x FOR PEER REVIEW 11 of 17

Figure 14. Step-down voltage setpoint simulation results at no-load for 40 MVA synchronous generator. Excitation voltage.

5. Static Field Breaker (SFB) Laboratory Experimental Test in a 15 MVA Synchronous Machine

5.1. Experimental Setup

The tests were performed in a 15 MVA, 13 kV, 1000 rpm synchronous generator with an exciter and a commercial one-quadrant AVR. Figure 15 shows the experimental setup, comprising a main generator (15 MVA), the exciter, and a field breaker. The characteristics are shown in Appendix B Tables A3 and A4 for the generator and the exciter, respectively. Using special switch-disconnector equipment, the stator winding can be connected in four different configurations, so it is possible to test in different stator voltages. Moreover, in the experimental setup, there are voltage transformers and slipping ring for metering purpose.

The experimental setup has some special features compared to a conventional generator; a simplified schema is shown in Figure 16. Firstly, three slip rings are installed in order to take measurements. A copper bar (HSBDS disconnector Figure 16) could be connected in parallel to the static switch, in this condition, the machine operates as a conventional brushless.

During the test, the commercial AVR used does not allow to configure the digital output for special purpose. So, the SFB control is done externally by an Arduino Nano® V3.0 microcontroller (Figure 17a). This controller measures the excitation voltage supply by the AVR. In case the voltage is close to zero, the SFB should be open. When the AVR output is greater than an adjustable value the SFB will be close again.

Main Generator

Voltage transformers

Exciter

HSBDS

Disconnectors

Field Circuit Breaker

Slip rings

Slip rings

Figure 15. Experimental setup 15 MVA, 13 kV synchronous machine for HSBDS + SFB testing.

29 30 31 32 33 34 35 36 37 38 39

-4

-2

0

2

4

[pu]

Excitation Voltage

Brushless

SFB

SFB+HSBDS

HSBDS

Figure 15. Experimental setup 15 MVA, 13 kV synchronous machine for HSBDS + SFB testing.

The experimental setup has some special features compared to a conventional generator;a simplified schema is shown in Figure 16. Firstly, three slip rings are installed in order to takemeasurements. A copper bar (HSBDS disconnector Figure 16) could be connected in parallel to thestatic switch, in this condition, the machine operates as a conventional brushless.

During the test, the commercial AVR used does not allow to configure the digital output forspecial purpose. So, the SFB control is done externally by an Arduino Nano® V3.0 microcontroller(Figure 17a). This controller measures the excitation voltage supply by the AVR. In case the voltage isclose to zero, the SFB should be open. When the AVR output is greater than an adjustable value theSFB will be close again.

Page 12: De-Excitation in Brushless Synchronous Machines

Energies 2019, 12, 2528 12 of 17Energies 2019, 12, x FOR PEER REVIEW 12 of 17

Exciter Rotating Bridge HSBDS Main Generator

SmartGen™

15 MVA 13 kV1000 rpm 50 Hz

(AVR)

Uf

Static Switch

UfExcRd_exc 71Ω 170W

1000A/60 mVIf

If_exc

Ubr

Shunt

Discharge Resistor

Rotating parts

400/50V

Disconnector HSBDS

Control circuit

Excitation transformer

FB

Static Field Breaker (SFB)

SFBController

SFB

Figure 16. Simplified diagram of the 15 MVA, 13 kV experimental setup for HSBDS + SFB testing.

(a) (b) (c)

Figure 17. Experimental setup for HSBDS + SFB testing. (a) External static field breaker controller based on Arduino® (b) Static field breaker (c) HSBDS components mounted in the rotor.

The SFB is shown in Figure 17b, it is based on a commercial static solid relay. The voltage drop in normal operation is less than 1.55 V, so the losses at rated operation conditions represent less than 14.4 Watts (<9.3 A × 1.55 V).

The maximum voltage and current of the SFB should be the same as the conventional field breaker. The maximum current corresponds to a short-circuit when the automatic voltage regulator goes to ceiling voltage. On the other hand, the maximum voltage is determinate by the product of the maximum current and the discharge resistor. The components of the HSBDS, rotating discharge resistor, control card, and static switches are shown in Figure 17c.

5.2. Tests Results

The laboratory setup has no possibility to be connected to the mains. For this reason, the tests performed correspond to step-down AVR voltage setpoint at no-load condition.

The configuration considered is as follow:

-Brushless.

The excitation corresponds to a conventional brushless excitation. In these tests, the disconnector of the HSBDS is closed and the SFB is closed.

-SFB.

An additional static field breaker (SFB) in series is installed in the main field breaker (FB). The control of the SFB is externally given to the AVR by a microcontroller.

Figure 16. Simplified diagram of the 15 MVA, 13 kV experimental setup for HSBDS + SFB testing.

Energies 2019, 12, x FOR PEER REVIEW 12 of 17

Exciter Rotating Bridge HSBDS Main Generator

SmartGen™

15 MVA 13 kV1000 rpm 50 Hz

(AVR)

Uf

Static Switch

UfExcRd_exc 71Ω 170W

1000A/60 mVIf

If_exc

Ubr

Shunt

Discharge Resistor

Rotating parts

400/50V

Disconnector HSBDS

Control circuit

Excitation transformer

FB

Static Field Breaker (SFB)

SFBController

SFB

Figure 16. Simplified diagram of the 15 MVA, 13 kV experimental setup for HSBDS + SFB testing.

(a) (b) (c)

Figure 17. Experimental setup for HSBDS + SFB testing. (a) External static field breaker controller based on Arduino® (b) Static field breaker (c) HSBDS components mounted in the rotor.

The SFB is shown in Figure 17b, it is based on a commercial static solid relay. The voltage drop in normal operation is less than 1.55 V, so the losses at rated operation conditions represent less than 14.4 Watts (<9.3 A × 1.55 V).

The maximum voltage and current of the SFB should be the same as the conventional field breaker. The maximum current corresponds to a short-circuit when the automatic voltage regulator goes to ceiling voltage. On the other hand, the maximum voltage is determinate by the product of the maximum current and the discharge resistor. The components of the HSBDS, rotating discharge resistor, control card, and static switches are shown in Figure 17c.

5.2. Tests Results

The laboratory setup has no possibility to be connected to the mains. For this reason, the tests performed correspond to step-down AVR voltage setpoint at no-load condition.

The configuration considered is as follow:

-Brushless.

The excitation corresponds to a conventional brushless excitation. In these tests, the disconnector of the HSBDS is closed and the SFB is closed.

-SFB.

An additional static field breaker (SFB) in series is installed in the main field breaker (FB). The control of the SFB is externally given to the AVR by a microcontroller.

Figure 17. Experimental setup for HSBDS + SFB testing. (a) External static field breaker controllerbased on Arduino® (b) Static field breaker (c) HSBDS components mounted in the rotor.

The SFB is shown in Figure 17b, it is based on a commercial static solid relay. The voltage drop innormal operation is less than 1.55 V, so the losses at rated operation conditions represent less than14.4 Watts (<9.3 A × 1.55 V).

The maximum voltage and current of the SFB should be the same as the conventional fieldbreaker. The maximum current corresponds to a short-circuit when the automatic voltage regulatorgoes to ceiling voltage. On the other hand, the maximum voltage is determinate by the product ofthe maximum current and the discharge resistor. The components of the HSBDS, rotating dischargeresistor, control card, and static switches are shown in Figure 17c.

5.2. Tests Results

The laboratory setup has no possibility to be connected to the mains. For this reason, the testsperformed correspond to step-down AVR voltage setpoint at no-load condition.

The configuration considered is as follow:-Brushless.The excitation corresponds to a conventional brushless excitation. In these tests, the disconnector

of the HSBDS is closed and the SFB is closed.-SFB.An additional static field breaker (SFB) in series is installed in the main field breaker (FB).

The control of the SFB is externally given to the AVR by a microcontroller.-HSBDS.

Page 13: De-Excitation in Brushless Synchronous Machines

Energies 2019, 12, 2528 13 of 17

In this case, the HSBDS disconnector is open and the HSBDS is in operation. The control of theSFB is closed.

-SFB + HSBDS.In this mode, both systems are in operation, the SBF and the HSBDS. Therefore, the control of SBF

is in operation and the disconnector is open.The results of the experimental tests are very similar to the simulations presented in the previous

section. The first set of tests was conducted by exciting the machine at rated voltage and speed with noload and after change the setpoint of the AVR from rated voltage to zero. Different de-excitation timeresponses were obtained.

The results are presented in Figure 18. As it was expected, the slowest de-excitation timecorresponds to the conventional brushless system. The use of SFB improves around 400 ms in theresponse time. Better improvements are obtained by using the HSBDS. However, the combination ofboth systems, SFB + HSBDS, makes the operation even faster.

Energies 2019, 12, x FOR PEER REVIEW 13 of 17

-HSBDS.

In this case, the HSBDS disconnector is open and the HSBDS is in operation. The control of the SFB is closed.

-SFB + HSBDS.

In this mode, both systems are in operation, the SBF and the HSBDS. Therefore, the control of SBF is in operation and the disconnector is open.

The results of the experimental tests are very similar to the simulations presented in the previous section. The first set of tests was conducted by exciting the machine at rated voltage and speed with no load and after change the setpoint of the AVR from rated voltage to zero. Different de-excitation time responses were obtained.

The results are presented in Figure 18. As it was expected, the slowest de-excitation time corresponds to the conventional brushless system. The use of SFB improves around 400 ms in the response time. Better improvements are obtained by using the HSBDS. However, the combination of both systems, SFB + HSBDS, makes the operation even faster.

The second set of tests was conducted by swiftly changing the set-point of the AVR from rated voltage to 80%. This situation is the same as the case of a transient de-excitation when the AVR should reduce the excitation voltage as fast as possible. The results are enclosed in Figure 19, where the stator voltages for the different configurations are displayed.

Figure 18. De-excitation at rated voltage tests results at no-load for 15 MVA synchronous generator. Stator voltage.

Figure 19. Step-down voltage setpoint tests results at no-load for 15 MVA synchronous generator. Stator voltage.

The slowest response corresponds to the conventional brushless configuration. In this case, the voltage raises the new set-point in a time greater than 2 s. When using the SFB, the response is similar, but it is advanced around 400 ms. In the cases where the HSBSD is used, the voltages raise the set-point in less than 2 s. It is remarkable that in the case of using the HSBDS, there are some rebounds in the connection of the static switch mounted in the rotor. However, with the combination of both system SFB-HSBDS, the response is really fast and with no large overshoot. In Figure 20 as example is presented a record from one of the numerous tests. In this test, the voltage setup is suddenly

0 1 2 3 4 5 6 7 8

Time [s]

0

0.2

0.4

0.6

0.8

1

[pu]

Stator Voltage

Brushless

SFB

HSBDS

SFB+HSBDS

0 1 2 3 4 5 6

Time [s]

0.75

0.8

0.85

0.9

0.95

1

1.05

[pu]

Stator Voltage

SetpointBrushless

HSBDS

SFB

SFB+HSBDS

Figure 18. De-excitation at rated voltage tests results at no-load for 15 MVA synchronous generator.Stator voltage.

The second set of tests was conducted by swiftly changing the set-point of the AVR from ratedvoltage to 80%. This situation is the same as the case of a transient de-excitation when the AVR shouldreduce the excitation voltage as fast as possible. The results are enclosed in Figure 19, where the statorvoltages for the different configurations are displayed.

Energies 2019, 12, x FOR PEER REVIEW 13 of 17

-HSBDS.

In this case, the HSBDS disconnector is open and the HSBDS is in operation. The control of the SFB is closed.

-SFB + HSBDS.

In this mode, both systems are in operation, the SBF and the HSBDS. Therefore, the control of SBF is in operation and the disconnector is open.

The results of the experimental tests are very similar to the simulations presented in the previous section. The first set of tests was conducted by exciting the machine at rated voltage and speed with no load and after change the setpoint of the AVR from rated voltage to zero. Different de-excitation time responses were obtained.

The results are presented in Figure 18. As it was expected, the slowest de-excitation time corresponds to the conventional brushless system. The use of SFB improves around 400 ms in the response time. Better improvements are obtained by using the HSBDS. However, the combination of both systems, SFB + HSBDS, makes the operation even faster.

The second set of tests was conducted by swiftly changing the set-point of the AVR from rated voltage to 80%. This situation is the same as the case of a transient de-excitation when the AVR should reduce the excitation voltage as fast as possible. The results are enclosed in Figure 19, where the stator voltages for the different configurations are displayed.

Figure 18. De-excitation at rated voltage tests results at no-load for 15 MVA synchronous generator. Stator voltage.

Figure 19. Step-down voltage setpoint tests results at no-load for 15 MVA synchronous generator. Stator voltage.

The slowest response corresponds to the conventional brushless configuration. In this case, the voltage raises the new set-point in a time greater than 2 s. When using the SFB, the response is similar, but it is advanced around 400 ms. In the cases where the HSBSD is used, the voltages raise the set-point in less than 2 s. It is remarkable that in the case of using the HSBDS, there are some rebounds in the connection of the static switch mounted in the rotor. However, with the combination of both system SFB-HSBDS, the response is really fast and with no large overshoot. In Figure 20 as example is presented a record from one of the numerous tests. In this test, the voltage setup is suddenly

0 1 2 3 4 5 6 7 8

Time [s]

0

0.2

0.4

0.6

0.8

1

[pu]

Stator Voltage

Brushless

SFB

HSBDS

SFB+HSBDS

0 1 2 3 4 5 6

Time [s]

0.75

0.8

0.85

0.9

0.95

1

1.05

[pu]

Stator Voltage

SetpointBrushless

HSBDS

SFB

SFB+HSBDS

Figure 19. Step-down voltage setpoint tests results at no-load for 15 MVA synchronous generator.Stator voltage.

Page 14: De-Excitation in Brushless Synchronous Machines

Energies 2019, 12, 2528 14 of 17

The slowest response corresponds to the conventional brushless configuration. In this case,the voltage raises the new set-point in a time greater than 2 s. When using the SFB, the response issimilar, but it is advanced around 400 ms. In the cases where the HSBSD is used, the voltages raise theset-point in less than 2 s. It is remarkable that in the case of using the HSBDS, there are some reboundsin the connection of the static switch mounted in the rotor. However, with the combination of bothsystem SFB-HSBDS, the response is really fast and with no large overshoot. In Figure 20 as example ispresented a record from one of the numerous tests. In this test, the voltage setup is suddenly changed.The channel 1 represents the diode bridge voltage, the channel 2 the voltage in the discharge resistor,the channel 3 represents the AVR output voltage, and the channel 4 represents the signal control forthe SFB.

Energies 2019, 12, x FOR PEER REVIEW 14 of 17

changed. The channel 1 represents the diode bridge voltage, the channel 2 the voltage in the discharge resistor, the channel 3 represents the AVR output voltage, and the channel 4 represents the signal control for the SFB.

Figure 20. Step-down voltage setpoint tests record. CH1: Diodes bridge voltage; CH2: Discharge resistor voltage; CH3: AVR output voltage; CH4: Control signal to the SFB.

6. Conclusions

The discharge resistor is normally used in case of electrical trip by opening the field breaker. The connection of the discharge resistor implies a large negative voltage in the field winding and consequently a very fast de-excitation is obtained.

The main novelty presented in this paper is the transient use of the discharge resistor to improve the response of a brushless synchronous machine. For this purpose, an additional static field breaker (SFB) should be installed to connect and afterward disconnect the discharge resistor and continue with the normal operation of the synchronous machine.

The proposed system has been successfully validated by simulations and experimental results in a brushless 15 MVA laboratory synchronous machine with a commercial automatic voltage regulator (AVR).

The main advantage of the transient use of the discharge resistor by a static field breaker (SFB) is the reduction of the exciter time constant. This indicates that the generator will respond before in case of transient de-excitation. According to the simulations and experimental results, the system operates around 500 ms in advance in comparison to the equivalent conventional brushless machine.

The high-speed brushless de-excitation system (HSBDS) for synchronous machines, previously developed by the authors, was originally designed to protect the machine against internal faults. It is based on the installation of a rotating discharge resistor controlled by a rotating card.

According to the results, the HSBDS can equally be used in transient operation to reduce the generator field current in a transient de-excitation. It is important to activate the HSBDS as fast as possible in order to improve the transient response of the brushless synchronous machine. Another important contribution is that the use of SFB has proved to be an efficient tool to accelerate the operation of the HSBDS in transient de-excitation. The combination of SFB with the HSBDS, also simulated and experimentally tested, improves even more the transient response even more in case of transient de-excitation.

The transient use of the discharge resistor and the control of the SFB could be implemented with an external controller, as in the tests presented in this paper, so it could be installed in existing machines. Another possibility is to use a programmable digital output of the AVR, if available, to control the SFB.

Although at the moment this new system has only been tested in brushless synchronous machines, a future research line is to use it in static excitation systems.

Figure 20. Step-down voltage setpoint tests record. CH1: Diodes bridge voltage; CH2: Dischargeresistor voltage; CH3: AVR output voltage; CH4: Control signal to the SFB.

6. Conclusions

The discharge resistor is normally used in case of electrical trip by opening the field breaker.The connection of the discharge resistor implies a large negative voltage in the field winding andconsequently a very fast de-excitation is obtained.

The main novelty presented in this paper is the transient use of the discharge resistor to improvethe response of a brushless synchronous machine. For this purpose, an additional static field breaker(SFB) should be installed to connect and afterward disconnect the discharge resistor and continue withthe normal operation of the synchronous machine.

The proposed system has been successfully validated by simulations and experimental resultsin a brushless 15 MVA laboratory synchronous machine with a commercial automatic voltageregulator (AVR).

The main advantage of the transient use of the discharge resistor by a static field breaker (SFB) isthe reduction of the exciter time constant. This indicates that the generator will respond before in caseof transient de-excitation. According to the simulations and experimental results, the system operatesaround 500 ms in advance in comparison to the equivalent conventional brushless machine.

The high-speed brushless de-excitation system (HSBDS) for synchronous machines, previouslydeveloped by the authors, was originally designed to protect the machine against internal faults. It isbased on the installation of a rotating discharge resistor controlled by a rotating card.

According to the results, the HSBDS can equally be used in transient operation to reducethe generator field current in a transient de-excitation. It is important to activate the HSBDS asfast as possible in order to improve the transient response of the brushless synchronous machine.Another important contribution is that the use of SFB has proved to be an efficient tool to acceleratethe operation of the HSBDS in transient de-excitation. The combination of SFB with the HSBDS,

Page 15: De-Excitation in Brushless Synchronous Machines

Energies 2019, 12, 2528 15 of 17

also simulated and experimentally tested, improves even more the transient response even more incase of transient de-excitation.

The transient use of the discharge resistor and the control of the SFB could be implemented withan external controller, as in the tests presented in this paper, so it could be installed in existing machines.Another possibility is to use a programmable digital output of the AVR, if available, to control the SFB.

Although at the moment this new system has only been tested in brushless synchronous machines,a future research line is to use it in static excitation systems.

7. Patents

Platero, C.A. et al.: “Rapid de-excitation system for synchronous machines with indirect excitation.”European Patent WO/2010/094818 PCT/ES2010/000058, 201.

Author Contributions: The authors have contributed to the completion of this paper according to the followinglist of tasks: Conceptualization, C.A.P.; methodology, C.A.P.; software, E.R.; validation, R.G. and D.T.; resources,E.R.; writing—original draft preparation, R.G., C.A.P., D.T., and E.R.; writing—review and editing, R.G., C.A.P.,and E.R.; supervision, C.A.P.

Funding: This research received no external funding.

Acknowledgments: The authors wish to acknowledge the technical support of ALSTOM Renovables, S.A. andENDESA Generación, S.A., and especially Martínez, J.A., Puigmal, F., Villarejo, M., Alvarez, M. and Diago, J.R.

Conflicts of Interest: The authors declare no conflict of interest.

Appendix A

Table A1. Simulation main generator ratings.

Manufacturer Alstom, Bilbao (Spain) Type SAH 500/120/26

Total power 40 MVA Speed 230.77 rpmFrequency 50 Hz Max. runaway speed 535 rpm

Rated voltage 13.8 kV Rated power factor 0.85Rated current 1673 A Rated active power 34 MW

Xd 1.008 pu Xq 0.689 puX’d 0.316 pu X”q 0.254 puX”d 0.275 pu Xl 0.172 pu

Stator resistance 0.005 pu T’d 1.681 sT”d 0.0649 s T’d0 5.451 sUfn 203 V Ifn 693.4 A

Table A2. Simulation exciter ratings.

Manufacturer Alstom, Bilbao (Spain) Type WE 11330 20 /26

Nominal voltage 165.2 V Total power 162 kVAFrequency 38.46 Hz Power factor 0.96

Speed 230.77 rpm Phase number 3Excitation voltage 167 V Excitation current 9.4 A

Page 16: De-Excitation in Brushless Synchronous Machines

Energies 2019, 12, 2528 16 of 17

Appendix B

Table A3. Experimental results main generator ratings.

Manufacturer Metropolitan Vickers Type G50/C1

Total power 15 MVA Speed 1000 rpmFrequency 50 Hz Rated power factor 0.85

Configuration A Configuration C

Rated voltage 4 kV ∆ Parallel Rated voltage 7 kV ҮParallelRated current 2144 A Rated current 1237 A

Configuration B Configuration D

Rated voltage 13 kV ҮSeries Rated voltage 7.5 kV ∆ SeriesRated current 666 A Rated current 1155 A

Xd 2.203 pu Xq 2.203 puX’d 0.642 pu X”q 0.350 puX”d 0.542 pu Xl 0.172 pu

Stator resistance 0.0017 pu T’d 2.397 sT”d 0.315 s T’d0 6.02 sUfN 105 V IfN 340 A

Table A4. Experimental results exciter ratings.

Manufacturer Alstom, Bilbao (Spain) Type WE 5615 10/6

Nominal voltage 26 V Total power 4 kVAFrequency 83.33 Hz Power factor 0.96

Speed 1000 rpm Phase number 3Excitation voltage 77.1 V Excitation current 9.3 A

References

1. Eshraghnia, R.; Kleen, R.J. Modeling and simulation of the transient response of 138.75 MVA synchronousgenerator with rotating and static excitation systems. In Proceedings of the 2014 IEEE PES T&D Conferenceand Exposition, Chicago, IL, USA, 14–17 April 2014; pp. 1–5.

2. Schaefer, R.C. Brushless rotating exciter conversion to main field static exciter system. In Proceedings of theConference Record of 2013 Annual IEEE Pulp and Paper Industry Technical Conference (PPIC), Charlotte,NC, USA, 23–27 June 2013; pp. 186–191.

3. Taborda, J. Modern technical aspects of Field Discharge equipment for excitation systems. In Proceedings ofthe 2008 IEEE Power and Energy Society General Meeting—Conversion and Delivery of Electrical Energy inthe 21st Century, Pittsburgh, PA, USA, 20–24 July 2008; pp. 1–8.

4. Zhang, Y.; Cramer, A.M. Numerical Average-Value Modeling of Rotating Rectifiers in Brushless ExcitationSystems. IEEE Trans. Energy Convers. 2017, 32, 1592–1601. [CrossRef]

5. Taborda, J. Comparison between detailed and simplified AC exciter models. In Proceedings of the IEEE PESGeneral Meeting, Providence, RI, USA, 25–29 July 2010; pp. 1–8.

6. Ruuskanen, V.; Niemela, M.; Pyrhonen, J.; Kanerva, S.; Kaukonen, J. Modelling the brushless excitationsystem for a synchronous machine. IET Electr. Power Appl. 2009, 3, 231–239. [CrossRef]

7. Shahnazari, M.; Vahedi, A. Improved dynamic average modelling of brushless excitation system in allrectification modes. IET Electr. Power Appl. 2010, 4, 657–669. [CrossRef]

8. Gunes, M.; Dogru, N. Fuzzy Control of Brushless Excitation System for Steam Turbogenerators. IEEE Trans.Energy Convers. 2010, 25, 844–852. [CrossRef]

9. Boveri, A.B. A Method and Device for Demagnetizing Brushless Synchronous Machines. InternationalPatent WO 93/20614, 14 October 1993.

10. Schneider. Entregungsschaltung für Bürstenios über Rotierende Dionen Erregte Synchronmaschinen.German Patent DE 1763299, 21 October 1971.

Page 17: De-Excitation in Brushless Synchronous Machines

Energies 2019, 12, 2528 17 of 17

11. Siemens. Anordnung zur Schnellentregung von Bürstenlosen Synchronmachinen, die über UmlaufendeUngesteuerte Gleichrichter Erregt Warden. German Patent DE 2127497, 28 May 1971.

12. Nøland, J.K.; Hjelmervik, K.B.; Lundin, U. Comparison of Thyristor-Controlled Rectification Topologies fora Six-Phase Rotating Brushless Permanent Magnet Exciter. IEEE Trans. Energy Convers. 2016, 31, 314–322.[CrossRef]

13. Westinghouse. Fast De-excitation Brushless Exciter. U.S. Patent 4152,636, 1 May 1979.14. Mudhigollam, U.K.; Choudhury, U.; Hatua, K. Wide regulated series hybrid excitation alternator. IET Electr.

Power Appl. 2018, 12, 439–446. [CrossRef]15. Hussain, A.; Atiq, S.; Kwon, B. Optimal Design and Experimental Verification of Wound Rotor Synchronous

Machine Using Subharmonic Excitation for Brushless Operation. Energies 2018, 11, 554. [CrossRef]16. Yuan, T.; Yang, N.; Zhang, W.; Cao, W.; Xing, N.; Tan, Z.; Li, G. Improved Synchronous Machine Rotor

Design for the Easy Assembly of Excitation Coils Based on Surrogate Optimization. Energies 2018, 11, 1311.[CrossRef]

17. Li, J.; Liu, Y.; Li, C.; Chu, B. Passivity-Based Nonlinear Excitation Control of Power Systems with StructureMatrix Reassignment. Information 2013, 4, 342–350. [CrossRef]

18. Platero Gaona, C.A.; García, F.B.; Marín, P.F.; Cuevas, M.R.; Arrabé, R.G.; López, C.C. RapidDe-excitation System for Synchronous Machines with Indirect Excitation. European Patent WO/2010/094818PCT/ES2010/000058, 8 December 2012.

19. Rebollo, E.; Blanquez, F.R.; Platero, C.A.; Blazquez, F.; Redondo, M. High-speed de-excitation system forbrushless synchronous machines. IET Electr. Power Appl. 2012, 6, 156–161.

20. Rebollo, E.; Blanquez, F.R.; Platero, C.A.; Blazquez, F.; Redondo, M. Improved high-speed de-excitationsystem for brushless synchronous machines tested on a 20 MVA hydro-generator. IET Electr. Power Appl.2015, 9, 405–411. [CrossRef]

21. Platero, C.A.; Blázquez, F.; Rebollo, E.; Blánquez, F.R.; Martínez, J.A.; Redondo, M. Enhancement of a highspeed de-excitation system for brushless synchronous machines by large blocking voltage semiconductors.In Proceedings of the 2015 IEEE 10th International Symposium on Diagnostics for Electrical Machines, PowerElectronics and Drives (SDEMPED), Guarda, Portugal, 1–4 September 2015; pp. 50–55.

22. Rebollo, E.; Platero, C.A.; Blazquez, F.; Granizo, R. Internal sudden short-circuit response of a new HSBDSfor brushless synchronous machines tested on a 15 MVA generator. IET Electr. Power Appl. 2017, 11, 495–503.[CrossRef]

23. Blánquez, F.R.; Revuelta, P.; Rebollo, E.; Platero, C.A. Validation study of the use of MATLAB/Simulinksynchronous-machine block for accurate power-plant stability studies. In Proceedings of the 2014 14thInternational Conference on Environment and Electrical Engineering, Krakow, Poland, 10–12 May 2014;pp. 122–126.

24. Sybille, G.; Doyon, J.-F. Mechanical Coupling of Synchronous Generator with Exciter System Usingthe Simscape Mechanical Rotational Port. Available online: https://es.mathworks.com/help/physmod/

sps/examples/mechanical-coupling-of-synchronous-generator-with-exciter-system-using-the-simscape-mechanical-rotational-port.html (accessed on 28 April 2019).

© 2019 by the authors. Licensee MDPI, Basel, Switzerland. This article is an open accessarticle distributed under the terms and conditions of the Creative Commons Attribution(CC BY) license (http://creativecommons.org/licenses/by/4.0/).