SS-DCG3 www.daikinac.com 7/17 Supersedes 4/17 6 Ton Packaged Gas/ Electric Units up to 15.5 IEER 80% AFUE DCG Commercial Contents Nomenclature........................................ 2 Product Specificaons ........................... 4 Expanded Cooling Data ......................... 7 Airflow Data ......................................... 11 Crankcase Heater................................. 12 Electrical Data ...................................... 13 Dimensions .......................................... 14 Wiring Diagrams ................................. 18 – for Models with DDC Controls .............. 23 Accessories .......................................... 32 Standard Features • Patented tubular heat exchanger High-efficiency scroll compressor High and low-pressure switches Copper tube / aluminum fin coils Contactor with lugs High-capacity, steel-cased filter drier 24-volt terminal strip Converble airflow orientaon Easy to service Built-in filter rack with standard 2" filters Boom ulity entry Cabinet Features Heavy-gauge, galvanized-steel cabinet with UV-resistant powder-paint finish • Full Perimeter Rail • Sloped drain pan Complies with California Low NOx emissions standards Single speed blower motor units meet the performance specified in Table 6.8.1A of ASHRAE Standard 90.1-2010 AHRI Cerfied; ETL Listed Two-speed blower motor, TXV and two-stage compressor meet the performance specified as of 1/1/2016 in Table 6.8.1-1 of ASHRAE Standard 90.1-2013 * Complete warranty details available from your local distributor or manufacturer’s representave or at www.daikincomfort.com. Cooling Capacity: Up to 71,000 BTU/h Heating Input: 138,000 BTU/h

Upload: others

Post on 28-Mar-2021

1 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: DCG Commercialwebtest.daikinac.com/content/assets/LightCommercial... · 2017. 8. 16. · •ase Monitor: Phase monitor (3 phase only), available for 3 - 25 ton DS, DC and DT series

SS-DCG3 www.daikinac.com 7/17Supersedes 4/17

DRAFT

6 Ton Packaged Gas/ Electric Units up to 15.5 IEER

80% AFUE

DCG Commercial

■ ContentsNomenclature ........................................ 2Product Specifications ........................... 4Expanded Cooling Data ......................... 7Airflow Data ......................................... 11 Crankcase Heater................................. 12 Electrical Data ...................................... 13Dimensions .......................................... 14Wiring Diagrams ................................. 18 – for Models with DDC Controls .............. 23Accessories .......................................... 32

■ Standard Features• Patented tubular heat exchanger• High-efficiency scroll compressor• High and low-pressure switches• Copper tube / aluminum fin coils• Contactor with lugs• High-capacity, steel-cased filter drier• 24-volt terminal strip• Convertible airflow orientation• Easy to service• Built-in filter rack with standard 2" filters• Bottom utility entry

■ Cabinet Features• Heavy-gauge, galvanized-steel cabinet

with UV-resistant powder-paint finish• Full Perimeter Rail• Sloped drain pan

• Complies with California Low NOx emissions standards• Single speed blower motor units meet the performance

specified in Table 6.8.1A of ASHRAE Standard 90.1-2010• AHRI Certified; ETL Listed• Two-speed blower motor, TXV and two-stage

compressor meet the performance specified as of 1/1/2016 in Table 6.8.1-1 of ASHRAE Standard 90.1-2013

* Complete warranty details available from your local distributor or manufacturer’s representative or at www.daikincomfort.com.

Cooling Capacity: Up to 71,000 BTU/hHeating Input: 138,000 BTU/h

Page 2: DCG Commercialwebtest.daikinac.com/content/assets/LightCommercial... · 2017. 8. 16. · •ase Monitor: Phase monitor (3 phase only), available for 3 - 25 ton DS, DC and DT series

2 www.daikinac.com SS-DCG3

Nomenclature

D C G 060 090 3 B * * * A *1 2 3 4,5,6 7,8,9 10 11 12 13 14 15 16

Revision LevelsMajor & Minor

Brand Factory-Installed OptionsD Daikin X No Options

A Non-powered convenience outletConfiguration B Powered convenience outletC Standard Efficiency (6 - 25 Tons) C Low-ambient kitS Standard Efficiency (3 - 5 Tons) D Return air smoke detectorT High Efficiency (3 - 5 Tons) E Supply air smoke detector

F Non-powered convenience outlet; Application Low-ambient kitC Cooling1 G Non-powered convenience outlet; G Gas Heat Return air smoke detectorH Heat Pump1 H Non-powered convenience outlet;

Supply air smoke detectorNominal Cooling Capacity J Non-powered convenience outlet;036 3 Tons 102 8½ Tons 300 25 Tons Return & Supply air smoke detectors048 4 Tons 120 10 Tons K Non-powered convenience outlet;060 5 Tons 150 12½ tons Low-ambient kit; Supply air smoke detector072 6 Tons 180 15 Tons L Non-powered convenience outlet; 090 7½ Tons 240 20 Tons Low-ambient kit

Return & Supply air smoke detectorsNominal Heating Capacity M Powered convenience outlet;

Gas/Electric A/C H/P Factory-Installed Electric Heat Low-ambient kit045 45,000 BTU/h XXX No Heat N Powered convenience outlet;070 70,000 BTU/h 010 10 kW 030 30 kW Return air smoke detector090 90,000 BTU/h 015 15 kW 031 30 kW O Powered convenience outlet;115 115,000 BTU/h 016 15 kW 045 45 kW Return & Supply air smoke detectors140 140,000 BTU/h 018 18 kW 046 45 kW P Powered convenience outlet;210 210,000 BTU/h 020 20 kW 060 60 kW Supply air smoke detector350 350,000 BTU/h 025 25 kW Q Powered convenience outlet; Low-ambient400 400,000 BTU/h kit; Return air smoke detector

See product specifications for heat size(s) available for each capacity. R Powered convenience outlet; Low-ambientVoltage kit; Supply air smoke detector1 208-230/1/60 4 460/3/60 T Powered convenience outlet; Low-ambient3 208-230/3/60 7 575/3/60 kit; Return & Supply air smoke detectors

U Non-powered convenience outlet;Supply Fan/Drive Type/Motor Low-ambient kit; Return air smoke detectorB Belt Drive (single speed) V Two-Speed Belt Drive (also designates 6-Ton V Low-ambient kit; Return air smoke detectorD Direct Drive (3-5 Tons) with two-stage compressor) W Low-ambient kit; Supply air smoke detector

H High Static (single-speed Belt Drive models only) Y Low-ambient kit; Return & SupplyFactory-Installed Options air smoke detectorsA Ultra Low-Leak Downflow Economizer R Ultra Low-Leak Downflow Economizer; Z Return & Supply air smoke detectorsB DDC-BACnet protocol DDC-BACnet protocol; F Ultra Low-Leak Downflow Economizer; Disconnect Switch (non-fused)

DDC-BACnet protocol V Low-Leak Downflow Economizer Factory-Installed OptionsH Disconnect Switch (non-fused) W Low-Leak Downflow Economizer X Standard Aluminized Heat ExchangerJ Ultra Low-Leak Downflow Economizer; Disconnect Switch (non-fused) S Stainless-Steel Heat Exchanger

Disconnect Switch (non-fused) X No Options D Hinged PanelsM Disconnect Switch (non-fused); DDC-BACnet protocol K Stainless-Steel Heat Exchanger;

Hinged PanelsNote: Not all options available for all products. B Phase Monitor

1X= No Options in character 13th J Stainless Steel Heat Exchanger; Phase MonitorM Hinged Panel; Phase MonitorL Stainless-Steel Heat Exchanger;

Hinged Panels; Phase Monitor

Page 3: DCG Commercialwebtest.daikinac.com/content/assets/LightCommercial... · 2017. 8. 16. · •ase Monitor: Phase monitor (3 phase only), available for 3 - 25 ton DS, DC and DT series

SS-DCG3 www.daikinac.com 3

Factory-Installed Options• Stainless-Steel Heat Exchanger (Gas only units): A tubular heat exchanger made of 409-type stainless steel is installed in the unit.• Low-Ambient Kit: Allows for cooling operation at lower outdoor temperatures. On the 3- to 6-ton units, cooling operation is extended

from 60°F ambient temperature to 35°F outside air temperature. On 7½ -20 ton units, cooling operation is extended from 35°F ambient temperature to 0°F outside air temperature. For 25 ton units, cooling operation is extended from 24°F ambient temperature to 0°F outside air temperature.

• Economizers (Downflow): Based on air conditions, can provide outside air to cool the space.• Electric Heat Kits (heat pump and cooling units only): Available in all voltage options.• Non-powered Convenience Outlet: A 120V, 15A, GFCI outlet makes it easier for technicians to service the unit once an electrician runs

power to the outlet.• Powered Convenience Outlet: A 120V, 15A, GFCI outlet powered with a transformer built into the unit. When a factory-installed powered

convenience outlet is installed in the equipment, the unit MCA (Min. Circuit Ampacity) will increase by 7.5A for 208/230V units, increase by 3.75A for 460V units, and by 3A for 575V units. The MOP (Max. Overcurrent Protection) device must be sized accordingly.

• Disconnect Switch (non-fused; 3-phase units only): A disconnect switch is installed in the unit and factory wiring will be complete from the switch to the unit. Please note that for air conditioning and heat pump models, the appropriate electric heat kit must be ordered to be factory-installed along with the disconnect switch (non-fused) when it is ordered. Please note that for models with a powered con-venience outlet option and a disconnect switch (non-fused) option, the power to the powered convenience outlet will be shut off when the disconnect switch (non-fused) is in the off position.

• Return Air and/or Supply Air Smoke Detectors: Return air and/or supply air smoke detectors are installed in the unit.• Hinged Access Panels: Allows access to unit’s major components. Combined with latches for easy access to control box, compressor,

filters and blower motor. Available on all units.• Two-speed indoor fan blower models are available on 6, 7½, 8½, 10, 12½, 15, 20 & 25 ton units. Section 6.4.3.10.b of ASHRAE Standard

90.1-2010 and Section 6.5.3.2.1.a of ASHRAE Standard 90.1-2013 require a minimum of two fan speeds. Section 140.4(m)1 of California Energy Commission Title 24 2013 contains a similar provision. When the units with the two-speed indoor fan blowers operate on a call for the first stage of cooling, the fan operates at low speed, which is 66% of full speed. When the units operate on a call for the second stage of cooling, the fan operates at full speed. In heating operation, the fan operates at full speed. During ventilation operation, the fan operates at low speed.

• Return Air and/or Supply Air Smoke Detectors: Return air and/or supply air smoke detectors are installed in the unit.• Hinged Access Panels: Allows access to unit’s major components. Combined with latches for easy access to control box, compressor,

filters and blower motor. Available on all models.• Phase Monitor: Phase monitor (3 phase only), available for 3 - 25 ton DS, DC and DT series models. Phase monitor shall provide protection

for motors and compressors against problems caused by phase loss, phase reversal and phase unbalance. Phase monitor is equipped with an LED that provides an ON or FAULT indicator.

• DDC Controller: DDC communicating controller, available for 3 - 25 ton DS, DC and DT series models with on-board BACnet® communication interface.

Page 4: DCG Commercialwebtest.daikinac.com/content/assets/LightCommercial... · 2017. 8. 16. · •ase Monitor: Phase monitor (3 phase only), available for 3 - 25 ton DS, DC and DT series

4 www.daikinac.com SS-DCG3

Product Specifications — 6 Tons

DCG0720903V***A*

DCG0720904V***A*

DCG0720907V***A*

Cooling CapacityTotal BTU/h 69,000 69,000 69,000

Sensible BTU/h 51,000 51,000 51,000

EER / IEER 11.2/15.5 11.2/15.5 11.2/15.5

Decibels 78 78 78

AHRI Number 8952850 8952850 8952850

Heating CapacityHigh Input / Output KBTU/h 92 / 73.6 92 / 73.6 92 / 73.6

Low Input/ Output KBTU/h 69 / 55 69 / 55 69 / 55

Steady State Efficiency 80 80 80

Temperature Rise Range (°F) 20-50 / 5-35 20-50 / 5-35 20-50 / 5-35

No. of Burners 4 4 4

Evaporator Motor / CoilMotor Type 2-speed Belt Drive 2-speed Belt Drive 2-speed Belt Drive

# of Wheels (D x W) 1 (11" x 10") 1 (11" x 10") 1 (11" x 10")

Indoor Nominal CFM 2,350 2,350 2,350

Indoor Motor FLA (Cooling) 6.0 2.9 2.4

Horsepower - RPM 2.0-1,725 2.0-1,725 2.0-1,725

Piston Size (Cooling) TXV TXV TXV

Filter Size (Qty) (4) 16" x 20" x 2" (4) 16" x 20" x 2" (4) 16" x 20" x 2"

Drain Size (NPT) ¾" ¾" ¾"

R-410A Refrigerant Charge (oz.) 146.0 146.0 146.0

Evaporator Coil Face Area (ft²) 8.9 8.9 8.9

Rows Deep/ Fins per Inch 4/16 4/16 4/16

Motor Sheave VL44 X 7/8 VL44 X 7/8 VL44 X 7/8

Blower Sheave AK59 X 1 AK59 X 1 AK59 X 1

Condenser Fan / CoilQuantity of Condenser Fan Motors 1 1 1

Horsepower - RPM ⅓ - 1,075 ⅓ - 1,075 ⅓ - 1,075

Fan Diameter/ # Fan Blades 22/ 4 22/ 4 22/ 4

Outdoor Nominal CFM 4,200 4,200 4,200

Face Area (ft²) 19 19 19

Rows Deep/ Fins per Inch 2/27 2/27 2/27

CompressorQuantity / Stage 1 / Two 1 / Two 1 / Two

Type Scroll Scroll Scroll

Compressor RLA / LRA 17.6/136 8.5/66.1 6.3/55.3

Electrical DataVoltage/ Phase/ Frequency 208-230/ 3/ 60 460/ 3/ 60 575/ 3/ 60

Outdoor Fan FLA 2.0 0.85 0.67

Total Unit Amps 25.6 12.3 9.4

Min. Circuit Ampacity¹ 30.0 14.3 11.0

Max. Overcurrent Protection² 45.0 20.0 15.0

Entrance Power Supply 1.125" 1.125" 1.125"

Entrance Control Voltage ½" ½" ½"

Operating Weight (lbs) 680 680 680Ship Weight (lbs) 695 695 695

¹ Wire size should be determined in accordance with National Electrical Codes. Extensive wire runs will require larger wire sizes.² May use fuses or HACR-type circuit breakers of the same size as noted.Notes• Always check the S&R plate for electrical data on the unit being installed. • When a factory-installed powered convenience outlet is installed in the equipment, the unit MCA (Min. Circuit Ampacity) will increase by

7.5A for 208/230V units, increase by 3.75A for 460V units, and by 3A for 575V units. The MOP (Max. Overcurrent Protection) device must be sized accordingly.

Page 5: DCG Commercialwebtest.daikinac.com/content/assets/LightCommercial... · 2017. 8. 16. · •ase Monitor: Phase monitor (3 phase only), available for 3 - 25 ton DS, DC and DT series

SS-DCG3 www.daikinac.com 5

Product Specifications — 6 Tons (cont.)

DCG0721153V***A*

DCG0721154V***A*

DCG0721157V***A*

Cooling CapacityTotal BTU/h 69,000 69,000 69,000

Sensible BTU/h 51,000 51,000 51,000

EER / IEER 11.2/15.5 11.2/15.5 11.2/15.5

Decibels 78 78 78

AHRI Number 8952850 8952850 8952850

Heating CapacityHigh Input / Output KBTU/h 115 / 92 115 / 92 115 / 92

Low Input/ Output KBTU/h 86 / 69 86 / 69 86 / 69

Steady State Efficiency 80 80 80

Temperature Rise Range (°F) 25-55 / 10-40 25-55 / 10-40 25-55 / 10-40

No. of Burners 5 5 5

Evaporator Motor / CoilMotor Type 2-speed Belt Drive 2-speed Belt Drive 2-speed Belt Drive

# of Wheels (D x W) 1 (11" x 10") 1 (11" x 10") 1 (11" x 10")

Indoor Nominal CFM 2,350 2,350 2,350

Indoor Motor FLA (Cooling) 6.0 2.9 2.4

Horsepower - RPM 2.0-1,725 2.0-1,725 2.0-1,725

Piston Size (Cooling) TXV TXV TXV

Filter Size (Qty) (4) 16" x 20" x 2" (4) 16" x 20" x 2" (4) 16" x 20" x 2"

Drain Size (NPT) ¾" ¾" ¾"

R-410A Refrigerant Charge (oz.) 146.0 146.0 146.0

Evaporator Coil Face Area (ft²) 8.9 8.9 8.9

Rows Deep/ Fins per Inch 4/16 4/16 4/16

Motor Sheave VL44 X 7/8 VL44 X 7/8 VL44 X 7/8

Blower Sheave AK59 X 1 AK59 X 1 AK59 X 1

Condenser Fan / CoilQuantity of Condenser Fan Motors 1 1 1

Horsepower - RPM ⅓ - 1,075 ⅓ - 1,075 ⅓ - 1,075

Fan Diameter/ # Fan Blades 22/ 4 22/ 4 22/ 4

Outdoor Nominal CFM 4,200 4,200 4,200

Face Area (ft²) 19 19 19

Rows Deep/ Fins per Inch 2/27 2/27 2/27

CompressorQuantity / Stage 1 / Two 1 / Two 1 / Two

Type Scroll Scroll Scroll

Compressor RLA / LRA 17.6/136 8.5/66.1 6.3/55.3

Electrical DataVoltage/ Phase/ Frequency 208-230/ 3/ 60 460/ 3/ 60 575/ 3/ 60

Outdoor Fan FLA 2.0 0.85 0.67

Total Unit Amps 25.6 12.3 9.4

Min. Circuit Ampacity¹ 30.0 14.3 11.0

Max. Overcurrent Protection² 45.0 20.0 15.0

Entrance Power Supply 1.125" 1.125" 1.125"

Entrance Control Voltage ½" ½" ½"

Operating Weight (lbs) 685 685 685Ship Weight (lbs) 700 700 700

¹ Wire size should be determined in accordance with National Electrical Codes. Extensive wire runs will require larger wire sizes.² May use fuses or HACR-type circuit breakers of the same size as noted.Notes• Always check the S&R plate for electrical data on the unit being installed. • When a factory-installed powered convenience outlet is installed in the equipment, the unit MCA (Min. Circuit Ampacity) will increase by

7.5A for 208/230V units, increase by 3.75A for 460V units, and by 3A for 575V units. The MOP (Max. Overcurrent Protection) device must be sized accordingly.

Page 6: DCG Commercialwebtest.daikinac.com/content/assets/LightCommercial... · 2017. 8. 16. · •ase Monitor: Phase monitor (3 phase only), available for 3 - 25 ton DS, DC and DT series

6 www.daikinac.com SS-DCG3

Product Specifications — 6 Tons (cont.)

DCG0721403B***A*

DCG0721403V***A*

DCG0721404B***A*

DCG0721404V***A*

DCG0721407B***A*

DCG0721407V***A*

Cooling CapacityTotal BTU/h 71,000 69,000 71,000 69,000 71,000 69,000

Sensible BTU/h 49,800 51,000 49,800 51,000 49,800 51,000

EER / IEER 11.0 / 11.2 11.2/15.5 11.0 / 11.2 11.2/15.5 11.0 / 11.2 11.2/15.5

Decibels 78 78 78 78 78 78

AHRI Number 6345695 8952850 6345695 8952850 6345695 8952850

Heating CapacityHigh Input / Output KBTU/h 138 / 110.4 138 / 110.4 138 / 110.4 138 / 110.4 138 / 110.4 138 / 110.4

Low Input/ Output KBTU/h 103 / 83 103 / 83 103 / 83 103 / 83 103 / 83 103 / 83

Steady State Efficiency 80 80 80 80 80 80

Temperature Rise Range (°F) 30-60 / 15-45 30-60 / 15-45 30-60 / 15-45 30-60 / 15-45 30-60 / 15-45 30-60 / 15-45

No. of Burners 6 6 6 6 6 6

Evaporator Motor / CoilMotor Type Belt Drive 2-speed Belt Drive Belt Drive 2-speed Belt Drive Belt Drive 2-speed Belt Drive

# of Wheels (D x W) 1 (11" x 10") 1 (11" x 10") 1 (11" x 10") 1 (11" x 10") 1 (11" x 10") 1 (11" x 10")

Indoor Nominal CFM 2,350 2,350 2,350 2,350 2,350 2,350

Indoor Motor FLA (Cooling) 5.0 6.0 2.5 2.9 2.3 2.4

Horsepower - RPM 1.5-1,725 2.0-1,725 1.5-1,725 2.0-1,725 1.5-1,725 2.0-1,725

Piston Size (Cooling) 0.094 TXV 0.094 TXV 0.094 TXV

Filter Size (Qty) (4) 16" x 20" x 2" (4) 16" x 20" x 2" (4) 16" x 20" x 2" (4) 16" x 20" x 2" (4) 16" x 20" x 2" (4) 16" x 20" x 2"

Drain Size (NPT) ¾" ¾" ¾" ¾" ¾" ¾"

R-410A Refrigerant Charge (oz.) 146.0 146.0 146.0 146.0 146.0 146.0

Evaporator Coil Face Area (ft²) 8.9 8.9 8.9 8.9 8.9 8.9

Rows Deep/ Fins per Inch 4/ 16 4/ 16 4/ 16 4/ 16 4/ 16 4/ 16

Motor Sheave VL44 X 7/8 VL44 X 7/8 VL44 X 7/8 VL44 X 7/8 VL44 X 7/8 VL44 X 7/8

Blower Sheave AK59 X 1 AK59 X 1 AK59 X 1 AK59 X 1 AK59 X 1 AK59 X 1

Belt AX53 AX53 AX53 AX53 AX53 AX53

Condenser Fan / CoilQuantity of Condenser Fan Motors 1 1 1 1 1 1

Horsepower - RPM ⅓ - 1,075 ⅓ - 1,075 ⅓ - 1,075 ⅓ - 1,075 ⅓ - 1,075 ⅓ - 1,075

Fan Diameter/ # Fan Blades 22/ 4 22/ 4 22/ 4 22/ 4 22/ 4 22/ 4

Outdoor Nominal CFM 4,200 4,200 4,200 4,200 4,200 4,200

Face Area (ft²) 19 19 19 19 19 19

Rows Deep/ Fins per Inch 2/ 27 2/ 27 2/ 27 2/ 27 2/ 27 2/ 27

CompressorQuantity / Stage 1 / Single 1 / Two 1 / Single 1 / Two 1 / Single 1 / Two

Type Scroll Scroll Scroll Scroll Scroll Scroll

Compressor RLA / LRA 19/ 123 17.6/136 9.7/ 62 8.5/66.1 7.4/ 50 6.3/55.3

Electrical DataVoltage/ Phase/ Frequency 208-230/ 3/ 60 208-230/ 3/ 60 460/ 3/ 60 460/ 3/ 60 575/ 3/ 60 575/ 3/ 60

Outdoor Fan FLA 1.90 2.00 1.20 0.90 0.90 0.70

Total Unit Amps 25.9 25.6 13.4 12.3 10.6 9.4

Min. Circuit Ampacity¹ 31 30 16 14.4 12 11.0

Max. Overcurrent Protection² 45 45 25 20 15 15

Entrance Power Supply 1.125" 1.125" 1.125" 1.125" 1.125" 1.125"

Entrance Control Voltage ½" ½" ½" ½" ½" ½"

Operating Weight (lbs) 690 690 690 690 690 690Ship Weight (lbs) 715 715 715 715 715 715

¹ Wire size should be determined in accordance with National Electrical Codes. Extensive wire runs will require larger wire sizes.² May use fuses or HACR-type circuit breakers of the same size as noted.Notes• Always check the S&R plate for electrical data on the unit being installed. • When a factory-installed powered convenience outlet is installed in the equipment, the unit MCA (Min. Circuit Ampacity) will increase by 7.5A for 208/230V units, increase by

3.75A for 460V units, and by 3A for 575V units. The MOP (Max. Overcurrent Protection) device must be sized accordingly.

Page 7: DCG Commercialwebtest.daikinac.com/content/assets/LightCommercial... · 2017. 8. 16. · •ase Monitor: Phase monitor (3 phase only), available for 3 - 25 ton DS, DC and DT series

SS-DCG3 www.daikinac.com 7

Expanded Cooling Data — 6 Tons Single Speed

Out

door

Am

bien

t Te

mpe

ratu

re65

7585

9510

511

5En

teri

ng In

door

Wet

Bul

b Te

mpe

ratu

reID

BAi

rflo

w59

6367

7159

6367

7159

6367

7159

6367

7159

6367

7159

6367

71

70

2650

MBh

69.6

72.1

79.0

-68

.070

.477

.2-

66.3

68.8

75.3

-64

.767

.173

.5-

61.5

63.7

69.8

-57

.059

.064

.7-

S/T

0.75

0.63

0.44

-0.

780.

650.

45-

0.80

0.67

0.46

-0.

830.

690.

48-

0.86

0.72

0.50

-0.

860.

720.

50-

∆T18

1612

-18

1612

-18

1612

-19

1612

-18

1612

-17

1511

-

kW5.

105.

205.

35-

5.47

5.58

5.75

-5.

795.

916.

09-

6.08

6.21

6.40

-6.

326.

466.

66-

6.53

6.67

6.89

-

HI P

R23

525

326

7-

263

283

299

-29

932

234

0-

341

367

388

-38

441

343

6-

424

456

482

-LO

PR

108

115

125

-11

412

113

2-

118

126

137

-12

413

214

4-

130

138

151

-13

514

315

6-

2350

MBh

67.5

70.0

76.7

-66

.068

.474

.9-

64.4

66.8

73.1

-62

.865

.171

.4-

59.7

61.9

67.8

-55

.357

.362

.8-

S/T

0.72

0.60

0.42

-0.

740.

620.

43-

0.76

0.64

0.44

-0.

790.

660.

46-

0.82

0.68

0.47

-0.

820.

690.

48-

∆T19

1612

-19

1713

-19

1713

-19

1713

-19

1713

-18

1512

-

kW5.

065.

165.

31-

5.43

5.54

5.70

-5.

755.

876.

05-

6.03

6.16

6.35

-6.

276.

416.

61-

6.48

6.62

6.83

-

HI P

R23

225

026

4-

261

281

296

-29

731

933

7-

338

363

384

-38

040

943

2-

420

452

477

-LO

PR

107

113

124

-11

312

013

1-

117

125

136

-12

313

114

3-

129

137

150

-13

314

215

5-

2050

MBh

62.3

64.6

70.8

-60

.963

.169

.2-

59.4

61.6

67.5

-58

.060

.165

.9-

55.1

57.1

62.6

-51

.052

.958

.0-

S/T

0.69

0.58

0.40

-0.

720.

600.

42-

0.74

0.61

0.43

-0.

760.

630.

44-

0.79

0.66

0.46

-0.

800.

660.

46-

∆T19

1713

-20

1713

-20

1713

-20

1713

-19

1713

-18

1612

-

kW4.

955.

055.

19-

5.30

5.41

5.57

-5.

615.

735.

90-

5.89

6.01

6.20

-6.

126.

256.

45-

6.33

6.46

6.67

-

HI P

R22

524

325

6-

253

272

287

-28

831

032

7-

328

353

372

-36

939

741

9-

407

438

463

-LO

PR

103

110

120

-10

911

612

7-

114

121

132

-11

912

713

9-

125

133

145

-12

913

815

0-

75

2650

MBh

70.8

72.8

78.9

84.6

69.1

71.2

77.0

82.7

67.5

69.5

75.2

80.7

65.8

67.8

73.3

78.7

62.5

64.4

69.7

74.8

57.9

59.6

64.5

69.3

S/T

0.86

0.77

0.58

0.37

0.89

0.79

0.60

0.39

0.91

0.81

0.62

0.40

0.94

0.84

0.64

0.41

0.97

0.87

0.66

0.42

0.98

0.88

0.67

0.43

∆T21

1916

1121

2016

1121

2016

1121

2016

1121

1916

1120

1815

10

kW5.

145.

245.

405.

565.

515.

625.

795.

975.

845.

966.

146.

346.

136.

266.

456.

666.

376.

516.

726.

936.

596.

736.

947.

17

HI P

R23

725

526

928

126

628

630

231

530

332

634

435

934

537

139

240

838

841

744

145

942

846

148

750

8LO

PR

109

116

126

135

115

122

133

142

119

127

139

148

125

133

146

155

131

140

153

163

136

145

158

168

2350

MBh

68.7

70.7

76.6

82.2

67.1

69.1

74.8

80.3

65.5

67.4

73.0

78.3

63.9

65.8

71.2

76.4

60.7

62.5

67.7

72.6

56.2

57.9

62.7

67.3

S/T

0.82

0.73

0.55

0.36

0.85

0.76

0.57

0.37

0.87

0.78

0.59

0.38

0.90

0.80

0.61

0.39

0.93

0.83

0.63

0.40

0.94

0.84

0.63

0.41

∆T22

2017

1122

2017

1222

2017

1222

2117

1222

2017

1221

1916

11

kW5.

105.

205.

365.

525.

475.

585.

755.

935.

795.

916.

106.

296.

086.

216.

406.

616.

326.

466.

666.

886.

546.

686.

897.

11

HI P

R23

525

326

727

826

328

329

931

230

032

234

035

534

136

7.1

388

404

384

413

436

455

424

456

482

503

LO P

R10

811

512

513

311

412

113

214

111

812

613

714

612

413

214

415

413

013

815

116

113

514

315

616

7

2050

MBh

63.4

65.3

70.7

75.8

61.9

63.8

69.0

74.1

60.5

62.2

67.4

72.3

59.0

60.7

65.7

70.5

56.0

57.7

62.4

67.0

51.9

53.4

57.8

62.1

S/T

0.79

0.70

0.53

0.34

0.82

0.73

0.55

0.36

0.84

0.75

0.57

0.36

0.86

0.77

0.58

0.38

0.90

0.80

0.61

0.39

0.90

0.81

0.61

0.39

∆T22

2117

1223

2117

1223

2117

1223

2117

1223

2117

1221

1916

11

kW4.

995.

085.

235.

395.

345.

455.

615.

795.

665.

775.

956.

145.

946.

066.

256.

456.

176.

306.

506.

716.

386.

516.

726.

94

HI P

R22

824

525

927

025

527

529

030

329

131

333

034

433

135

637

639

237

240

142

344

141

144

346

748

8L O

PR

104

111

121

129

110

117

128

136

115

122

133

142

120

128

140

149

126

134

147

156

131

139

152

162

IDB

= En

terin

g In

door

Dry

Bul

b Te

mpe

ratu

reSh

aded

are

a re

flect

s AC

CA (T

VA) R

ating

con

ditio

nskW

= T

otal

sys

tem

pow

erH

igh

and

low

pre

ssur

es a

re m

easu

red

at th

e liq

uid

and

sucti

on s

ervi

ce v

alve

s.Am

ps =

out

door

uni

t am

ps (c

omp.

+fan

)

Page 8: DCG Commercialwebtest.daikinac.com/content/assets/LightCommercial... · 2017. 8. 16. · •ase Monitor: Phase monitor (3 phase only), available for 3 - 25 ton DS, DC and DT series

8 www.daikinac.com SS-DCG3

Expanded Cooling Data — 6 Tons Single Speed (cont.)

Out

door

Am

bien

t Te

mpe

ratu

re65

7585

9510

511

5En

teri

ng In

door

Wet

Bul

b Te

mpe

ratu

reID

BAi

rflo

w59

6367

7159

6367

7159

6367

7159

6367

7159

6367

7159

6367

71

80

2650

MBh

72.0

73.6

78.6

84.0

70.3

71.9

76.8

82.1

68.7

70.2

75.0

80.1

67.0

68.4

73.1

78.2

63.6

65.0

69.5

74.3

58.9

60.2

64.4

68.8

S/T

0.94

0.88

0.72

0.54

1.00

0.91

0.74

0.56

1.00

0.94

0.76

0.57

1.00

0.97

0.79

0.59

1.00

1.00

0.82

0.61

1.00

1.00

0.82

0.62

∆T23

2220

1624

2320

1624

2320

1623

2320

1622

2320

1620

2118

15

kW5.

185.

285.

445.

605.

555.

675.

846.

025.

886.

016.

196.

396.

186.

316.

516.

716.

436.

566.

776.

996.

646.

787.

007.

23

HI P

R23

925

827

228

426

928

930

531

830

632

934

736

234

837

539

641

339

242

144

546

443

346

649

251

3LO

PR

110

117

128

136

116

123

135

144

121

128

140

149

127

135

147

157

133

141

154

164

137

146

160

170

2350

MBh

69.9

71.4

76.3

81.6

68.3

69.8

74.6

79.7

66.7

68.1

72.8

77.8

65.0

66.5

71.0

75.9

61.8

63.1

67.5

72.1

57.2

58.5

62.5

66.8

S/T

0.90

0.84

0.68

0.51

0.93

0.87

0.71

0.53

0.95

0.89

0.73

0.54

0.98

0.92

0.75

0.56

1.00

0.96

0.78

0.58

1.00

0.96

0.78

0.59

∆T24

2320

1625

2421

1725

2421

1725

2421

1724

2421

1622

2219

15

kW5.

145.

245.

405.

565.

515.

625.

795.

975.

845.

966.

146.

346.

136.

266.

456.

666.

386.

516.

726.

936.

596.

736.

947.

17

HI P

R23

725

526

928

126

628

630

231

530

332

634

435

934

537

139

240

838

841

744

145

942

846

148

750

8LO

PR

109

116

126

135

115

122

133

142

119

127

139

148

125

133

146

155

131

140

153

163

136

145

158

168

2050

MBh

64.5

65.9

70.4

75.3

63.0

64.4

68.8

73.6

61.5

62.9

67.2

71.8

60.0

61.3

65.5

70.1

57.0

58.3

62.3

66.6

52.8

54.0

57.7

61.6

S/T

0.86

0.81

0.66

0.49

0.89

0.84

0.68

0.51

0.92

0.86

0.70

0.52

0.95

0.89

0.72

0.54

0.98

0.92

0.75

0.56

0.99

0.93

0.76

0.57

∆T25

2421

1725

2421

1725

2421

1726

2421

1725

2421

1723

2320

16

kW5.

025.

125.

275.

435.

385.

495.

665.

835.

705.

826.

006.

195.

986.

116.

306.

506.

226.

356.

556.

766.

436.

576.

776.

99

HI P

R23

024

726

127

325

827

829

330

629

331

633

434

833

436

038

039

637

640

542

744

641

544

747

249

2LO

PR

106

112

123

130

111

119

129

138

116

123

135

143

122

129

141

151

128

136

148

158

132

140

153

163

85

2650

MBh

73.3

74.7

78.2

83.5

71.6

73.0

76.4

81.5

69.9

71.2

74.6

79.6

68.2

69.5

72.8

77.6

64.7

66.0

69.1

73.7

60.0

61.1

64.0

68.3

S/T

0.98

0.95

0.86

0.7

1.00

0.98

0.89

0.7

1.00

1.00

0.91

0.7

1.00

1.00

0.94

0.8

1.00

1.00

0.98

0.8

1.00

1.00

0.98

0.8

∆T25

2523

2025

2524

2024

2524

2024

2424

2122

2323

2021

2122

18.9

kW5.

215.

325.

485.

65.

595.

715.

886.

15.

936.

056.

246.

46.

236.

366.

566.

86.

486.

626.

837.

06.

696.

847.

067.

3

HI P

R24

226

027

528

6.7

271

292

308

321.

730

933

235

136

5.8

352

378

399

416.

639

542

644

946

8.7

437

470

497

517.

9LO

PR

111

118

129

137.

211

712

513

614

5.0

122

130

141

150.

712

813

614

915

8.3

134

143

156

165.

913

914

816

117

1.6

2350

MBh

71.1

72.5

75.9

81.0

69.5

70.8

74.2

79.1

67.8

69.1

72.4

77.3

66.2

67.5

70.6

75.4

62.9

64.1

67.1

71.6

58.2

59.4

62.2

66.3

S/T

0.94

0.91

0.82

0.7

0.97

0.94

0.85

0.7

1.00

0.96

0.87

0.7

1.00

0.99

0.90

0.7

1.00

1.00

0.93

0.8

1.00

1.00

0.94

0.8

∆T26

2624

2126

2625

2126

2625

2126

2625

2125

2524

2123

2323

19.8

kW5.

185.

285.

445.

65.

555.

675.

846.

05.

886.

016.

196.

46.

186.

316.

516.

76.

436.

566.

777.

06.

646.

787.

007.

2

HI P

R23

925

827

228

3.8

269

289

305

318.

530

632

934

736

2.2

348

375

396

412.

539

242

144

546

4.1

433

466

492

512.

8LO

PR

110

117

128

135.

911

612

313

514

3.6

121

128

140

149.

212

713

514

715

6.7

133

141

154

164.

213

714

616

016

9.9

2050

MBh

65.7

66.9

70.1

74.8

64.1

65.4

68.5

73.0

62.6

63.8

66.8

71.3

61.1

62.3

65.2

69.6

58.0

59.1

61.9

66.1

53.7

54.8

57.4

61.2

S/T

0.91

0.87

0.79

0.6

0.94

0.91

0.82

0.7

0.96

0.93

0.84

0.7

0.99

0.96

0.86

0.7

1.00

0.99

0.90

0.7

1.00

1.00

0.91

0.7

∆T27

2625

2127

2725

2227

2725

2227

2725

2226

2625

2224

2523

20.2

kW5.

065.

165.

315.

55.

425.

535.

705.

95.

755.

876.

056.

26.

036.

166.

356.

66.

276.

416.

616.

86.

486.

626.

837.

1

HI P

R23

225

026

427

5.3

261

280

296

308.

929

631

933

735

1.3

338

363

384

400.

138

040

943

245

0.2

420

452

477

497.

4L O

PR

107

113

124

131.

811

312

013

113

9.3

117

124

136

144.

712

313

114

315

2.0

129

137

150

159.

313

314

215

516

4.8

IDB

= En

terin

g In

door

Dry

Bul

b Te

mpe

ratu

reSh

aded

are

a re

flect

s AH

RI R

ating

con

ditio

nskW

= T

otal

sys

tem

pow

erH

igh

and

low

pre

ssur

es a

re m

easu

red

at th

e liq

uid

and

sucti

on s

ervi

ce v

alve

s.Am

ps =

out

door

uni

t am

ps (c

omp.

+fan

)

Page 9: DCG Commercialwebtest.daikinac.com/content/assets/LightCommercial... · 2017. 8. 16. · •ase Monitor: Phase monitor (3 phase only), available for 3 - 25 ton DS, DC and DT series

SS-DCG3 www.daikinac.com 9

Expanded Cooling Data — 6 Tons (2 Speed)

Out

door

Am

bien

t Te

mpe

ratu

re65

7585

9510

511

5En

teri

ng In

door

Wet

Bul

b Te

mpe

ratu

reID

BAi

rflo

w59

6367

7159

6367

7159

6367

7159

6367

7159

6367

7159

6367

71

70

2525

MBh

67.6

70.1

76.8

-66

.068

.575

.0-

64.5

66.8

73.2

-62

.965

.271

.4-

59.8

61.9

67.9

-55

.357

.462

.9-

S/T

0.72

0.60

0.42

-0.

750.

630.

43-

0.77

0.64

0.44

-0.

790.

660.

46-

0.82

0.69

0.48

-0.

830.

690.

48-

Del

ta T

1815

12-

1816

12-

1816

12-

1816

12-

1816

12-

1714

11-

KW4.

894.

985.

13-

5.23

5.34

5.50

-5.

545.

655.

82-

5.81

5.93

6.11

-6.

046.

166.

36-

6.24

6.37

6.57

-

HI P

R23

124

826

2-

259

279

294

-29

431

733

5-

335

361

381

-37

740

642

9-

417

449

474

-LO

PR

110

117

128

-11

612

413

5-

121

129

140

-12

713

514

7-

133

142

155

-13

814

616

0-

2250

MBh

65.6

68.0

74.5

-64

.166

.572

.8-

62.6

64.9

71.1

-61

.163

.369

.3-

58.0

60.1

65.9

-53

.755

.761

.0-

S/T

0.69

0.58

0.40

-0.

710.

600.

41-

0.73

0.61

0.42

-0.

760.

630.

44-

0.79

0.66

0.45

-0.

790.

660.

46-

Del

ta T

1916

12-

1916

12-

1916

12-

1916

12-

1916

12-

1715

11-

KW4.

854.

955.

09-

5.19

5.30

5.46

-5.

505.

615.

78-

5.76

5.88

6.06

-5.

996.

126.

31-

6.19

6.32

6.51

-H

I PR

228

246

260

-25

627

629

1-

292

314

331

-33

235

737

7-

374

402

424

-41

344

446

9-

LO P

R10

911

612

7-

115

123

134

-12

012

713

9-

126

134

146

-13

214

015

3-

136

145

158

-

1991

MBh

62.4

64.6

70.8

-60

.963

.169

.2-

59.5

61.6

67.5

-58

.060

.165

.9-

55.1

57.1

62.6

-51

.152

.958

.0-

S/T

0.66

0.55

0.38

-0.

680.

570.

40-

0.70

0.59

0.41

`0.

720.

610.

42-

0.75

0.63

0.44

-0.

760.

630.

44-

Del

ta T

1916

12-

1917

13-

1917

13-

1917

13-

1917

13-

1815

12-

KW4.

784.

875.

01-

5.12

5.22

5.37

-5.

415.

525.

69-

5.67

5.79

5.97

-5.

906.

026.

21-

6.09

6.22

6.41

-

HI P

R22

424

125

4-

251

270

285

-28

630

732

5-

325

350

370

-36

639

441

6-

404

435

460

-L O

PR

107

114

124

-11

312

013

1-

117

125

136

-12

313

114

3-

129

137

150

-13

414

215

5-

75

2525

MBh

68.8

70.8

76.6

82.2

67.2

69.1

74.8

80.3

65.6

67.5

73.1

78.4

64.0

65.9

71.3

76.5

60.8

62.6

67.7

72.7

56.3

58.0

62.7

67.3

S/T

0.82

0.74

0.56

0.36

0.85

0.76

0.58

0.37

0.87

0.78

0.59

0.38

0.90

0.81

0.61

0.39

0.94

0.84

0.63

0.41

0.94

0.84

0.64

0.41

Del

ta T

2119

1611

2119

1611

2119

1611

2119

1611

2119

1611

1918

1510

KW4.

925.

025.

175.

325.

275.

385.

545.

715.

585.

705.

876.

055.

855.

986.

166.

356.

096.

216.

416.

616.

296.

426.

626.

83

HI P

R23

325

126

527

626

228

129

731

029

732

033

835

333

936

538

540

238

141

043

345

242

145

347

949

9LO

PR

111

118

129

138

118

125

136

145

122

130

142

151

128

136

149

159

134

143

156

166

139

148

161

172

2250

MBh

66.8

68.7

74.4

79.8

65.2

67.1

72.7

78.0

63.7

65.5

70.9

76.1

62.1

63.9

69.2

74.3

59.0

60.7

65.7

70.6

54.6

56.3

60.9

65.4

S/T

0.78

0.70

0.53

0.34

0.81

0.73

0.55

0.35

0.83

0.75

0.56

0.36

0.86

0.77

0.58

0.37

0.89

0.80

0.60

0.39

0.90

0.81

0.61

0.39

Del

ta T

2120

1611

2220

1611

2220

1611

2220

1611

2220

1611

2019

1510

KW4.

894.

985.

135.

285.

235.

345.

505.

665.

545.

655.

826.

005.

815.

936.

116.

306.

046.

166.

366.

566.

246.

376.

576.

78

HI P

R23

124

826

227

425

927

929

430

729

431

733

534

933

536

138

139

837

740

642

944

741

744

947

449

4LO

PR

110

117

128

136

116

124

135

144

121

129

140

150

127

135

148

157

133

142

155

165

138

146

160

170

1991

MBh

63.4

65.3

70.7

75.9

61.9

63.8

69.0

74.1

60.5

62.3

67.4

72.3

59.0

60.7

65.7

70.6

56.0

57.7

62.5

67.0

51.9

53.5

57.9

62.1

S/T

0.75

0.67

0.51

0.33

0.78

0.70

0.53

0.34

0.80

0.71

0.54

0.35

0.82

0.74

0.56

0.36

0.86

0.76

0.58

0.37

0.86

0.77

0.58

0.38

Del

t a T

2220

1711

2220

1712

2221

1712

2221

1712

2220

1712

2119

1611

KW4.

824.

915.

055.

205.

165.

265.

415.

585.

465.

575.

735.

915.

725.

846.

026.

205.

946.

076.

266.

456.

146.

276.

466.

67

AMPS

10.5

10.8

11.1

11.4

11.3

11.5

11.9

12.3

12.2

12.4

12.8

13.3

12.9

13.2

13.6

14.1

13.7

14.0

14.5

15.0

14.5

14.8

15.3

15.8

HI P

R22

624

325

726

825

427

328

830

128

931

132

834

232

935

437

439

037

039

842

043

840

944

046

448

4LO

PR

108

115

125

133

114

121

132

141

118

126

138

147

124

132

145

154

130

139

151

161

135

144

157

167

IDB

= En

terin

g In

door

Dry

Bul

b Te

mpe

ratu

reLO

PR

Shad

ed a

rea

refle

cts

ACCA

(TVA

) Rati

ng c

ondi

tions

kW =

Tot

al s

yste

m p

ower

Hig

h an

d lo

w p

ress

ures

are

mea

sure

d at

the

liqui

d an

d su

ction

ser

vice

val

ves.

Amps

= o

utdo

or u

nit a

mps

(com

p.+f

an)

Page 10: DCG Commercialwebtest.daikinac.com/content/assets/LightCommercial... · 2017. 8. 16. · •ase Monitor: Phase monitor (3 phase only), available for 3 - 25 ton DS, DC and DT series

10 www.daikinac.com SS-DCG3

Expanded Cooling Data — 6 Tons (2 Speed) (cont.)

Out

door

Am

bien

t Te

mpe

ratu

re65

7585

9510

511

5En

teri

ng In

door

Wet

Bul

b Te

mpe

ratu

reID

BAi

rflo

w59

6367

7159

6367

7159

6367

7159

6367

7159

6367

7159

6367

71

80

2525

MBh

70.0

71.5

76.4

81.7

68.4

69.8

74.6

79.8

66.7

68.2

72.8

77.9

65.1

66.5

71.1

76.0

61.8

63.2

67.5

72.2

57.3

58.5

62.5

66.9

S/T

0.90

0.85

0.69

0.51

0.93

0.88

0.71

0.53

0.96

0.90

0.73

0.55

1.00

0.93

0.75

0.56

1.00

0.96

0.78

0.59

1.00

0.97

0.79

0.59

Del

ta T

2322

1915

2322

1915

2322

1916

2422

2016

2322

1915

2121

1814

KW4.

965.

065.

215.

365.

315.

425.

585.

755.

635.

745.

916.

105.

906.

026.

216.

406.

136.

266.

466.

666.

346.

476.

676.

89

HI P

R23

525

326

827

926

428

430

031

330

032

334

135

634

236

838

940

638

541

443

745

642

545

848

350

4LO

PR

112

120

130

139

119

126

138

147

123

131

143

153

130

138

150

160

136

144

158

168

140

149

163

174

2250

MBh

67.9

69.4

74.2

79.3

66.4

67.8

72.5

77.4

64.8

66.2

70.7

75.6

63.2

64.6

69.0

73.8

60.0

61.4

65.6

70.1

55.6

56.8

60.7

64.9

S/T

0.86

0.81

0.66

0.49

0.89

0.84

0.68

0.51

0.91

0.86

0.70

0.52

0.94

0.88

0.72

0.54

0.98

0.92

0.75

0.56

0.99

0.93

0.75

0.56

Del

ta T

2423

2016

2423

2016

2423

2016

2423

2016

2423

2016

2222

1915

KW4.

925.

025.

175.

325.

275.

385.

545.

715.

585.

705.

876.

055.

855.

986.

166.

356.

096.

216.

416.

616.

296.

426.

626.

83

HI P

R23

325

126

527

626

228

129

731

029

732

033

835

333

936

538

540

238

141

043

345

242

145

347

949

9LO

PR

111

118

129

138

118

125

136

145

122

130

142

151

128

136

149

159

134

143

156

166

139

148

162

172

1991

MBh

64.5

66.0

70.5

75.3

63.0

64.4

68.8

73.6

61.5

62.9

67.2

71.8

60.0

61.4

65.6

70.1

57.0

58.3

62.3

66.6

52.8

54.0

57.7

61.7

S/T

0.82

0.77

0.63

0.47

0.85

0.80

0.65

0.49

0.88

0.82

0.67

0.50

0.90

0.85

0.69

0.52

0.94

0.88

0.72

0.54

0.95

0.89

0.72

0.54

Del

ta T

2524

2016

2524

2117

2524

2117

2524

2117

2524

2116

2322

1915

KW4.

854.

955.

095.

245.

195.

305.

465.

625.

505.

615.

785.

965.

765.

886.

066.

255.

996.

126.

316.

506.

196.

326.

516.

72

HI P

R22

824

626

027

125

627

629

130

429

231

433

134

633

235

737

739

437

440

242

444

341

344

446

948

9LO

PR

109

116

127

135

115

123

134

142

120

127

139

148

126

134

146

156

132

140

153

163

136

145

158

169

85

2525

MBh

71.2

72.6

76.0

81.1

69.5

70.9

74.3

79.2

67.9

69.2

72.5

77.3

66.2

67.5

70.7

75.4

62.9

64.1

67.2

71.7

58.3

59.4

62.2

66.4

S/T

0.95

0.91

0.82

0.67

0.98

0.95

0.85

0.69

1.00

0.97

0.87

0.71

1.00

1.00

0.90

0.73

1.00

1.00

0.94

0.76

1.00

1.00

0.94

0.77

Del

ta T

2524

2320

2524

2320

2524

2320

2425

2320

2323

2320

2122

2119

KW5.

005.

095.

245.

405.

355.

465.

625.

805.

675.

785.

966.

155.

956.

076.

266.

466.

186.

316.

516.

726.

396.

526.

736.

94

HI P

R23

825

627

028

226

728

730

331

630

332

734

536

034

637

239

341

038

941

844

246

143

046

248

850

9LO

PR

113

121

132

140

120

128

139

148

125

133

145

154

131

139

152

162

137

146

159

170

142

151

165

175

2250

MBh

69.1

70.5

73.8

78.7

67.5

68.8

72.1

76.9

65.9

67.2

70.4

75.1

64.3

65.6

68.7

73.2

61.1

62.3

65.2

69.6

56.6

57.7

60.4

64.5

S/T

0.90

0.87

0.79

0.64

0.93

0.90

0.81

0.66

0.96

0.92

0.83

0.68

0.99

0.95

0.86

0.70

1.00

0.99

0.89

0.73

1.00

1.00

0.90

0.73

Del

ta T

2525

2420

2625

2421

2625

2421

2626

2421

2525

2421

2324

2219

KW4.

965.

065.

215.

365.

315.

425.

585.

755.

635.

745.

916.

105.

906.

026.

216.

406.

136.

266.

466.

666.

346.

476.

676.

89

HI P

R23

525

326

827

926

428

430

031

330

032

334

135

634

236

838

940

638

541

443

745

642

545

848

350

4LO

PR

112

120

130

139

119

126

138

147

123

131

143

153

130

138

150

160

136

144

158

168

140

149

163

174

1991

MBh

65.7

66.9

70.1

74.8

64.1

65.4

68.5

73.1

62.6

63.8

66.9

71.3

61.1

62.3

65.2

69.6

58.0

59.2

62.0

66.1

53.8

54.8

57.4

61.2

S/T

0.86

0.83

0.75

0.61

0.89

0.86

0.78

0.63

0.92

0.89

0.80

0.65

0.95

0.91

0.82

0.67

0.98

0.95

0.86

0.69

0.99

0.96

0.86

0.70

Del

t a T

2626

2421

2726

2521

2726

2521

2726

2522

2626

2421

2524

2320

KW4.

894.

985.

135.

285.

235.

345.

505.

665.

545.

655.

826.

005.

815.

936.

116.

306.

046.

166.

366.

566.

246.

376.

576.

78

HI P

R23

124

826

227

325

927

929

430

729

431

733

534

933

536

138

139

737

740

642

944

741

744

947

449

4LO

PR

110

117

128

136

116

124

135

144

121

129

140

150

127

135

147

157

133

142

155

165

138

146

160

170

IDB

= En

terin

g In

door

Dry

Bul

b Te

mpe

ratu

reSh

aded

are

a re

flect

s AH

RI R

ating

con

ditio

nskW

= T

otal

sys

tem

pow

erH

igh

and

low

pre

ssur

es a

re m

easu

red

at th

e liq

uid

and

sucti

on s

ervi

ce v

alve

s.Am

ps =

out

door

uni

t am

ps (c

omp.

+fan

)

Page 11: DCG Commercialwebtest.daikinac.com/content/assets/LightCommercial... · 2017. 8. 16. · •ase Monitor: Phase monitor (3 phase only), available for 3 - 25 ton DS, DC and DT series

SS-DCG3 www.daikinac.com 11

Airflow Data — 6 Tons

DCG072 Standard Belt Drive and Two-Speed Standard Belt Drive At High Speed - Horizontal

ESP (In W.C.)

0 Turns 1 Turn 2 Turns 3 Turns 4 Turns 5 Turns CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP

0.2 --- --- --- --- --- --- 2749 1.18 2573 0.96 2402 0.79

0.4 --- --- --- --- 2680 1.22 2544 1.06 2346 0.84 2164 0.68

0.6 --- --- 2655 1.31 2498 1.10 2306 0.92 2094 0.72 1890 0.57

0.8 2703 1.47 2486 1.20 2263 0.97 2076 0.81 --- --- --- ---

1 2515 1.34 2272 1.07 2002 0.83 --- --- --- --- --- ---

1.2 2253 1.16 2028 0.93 --- --- --- --- --- --- --- ---

DCG072 Standard Belt Drive and Two-Speed Standard Belt Drive At High Speed - Down Shot

ESP (In W.C.)

0 Turns 1 Turn 2 Turns 3 Turns 4 Turns 5 Turns CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP

0.2 --- --- --- --- 2625 1.18 2486 1.02 2322 0.83 2152 0.68

0.4 2765 1.52 2596 1.28 2476 1.09 2327 0.94 2159 0.75 1938 0.59

0.6 2650 1.43 2452 1.18 2325 1.00 2070 0.80 1898 0.64 --- ---

0.8 2443 1.29 2251 1.06 2068 0.86 1868 0.71 --- --- --- ---

1 2258 1.17 2040 0.94 1806 0.73 --- --- --- --- --- ---

1.2 2021 1.02 --- --- --- --- --- --- --- --- --- ---

High Static Belt Drive — Horizontal

ESP (In W.C.)

0 Turns 1 Turn 2 Turns 3 Turns 4 Turns 5 Turns CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP

0.6 --- --- --- --- --- --- --- --- 2677 1.29 2486 1.07

0.8 --- --- --- --- --- --- 2690 1.42 2529 1.20 2263 0.94

1 --- --- --- --- 2740 1.60 2471 1.27 2246 1.02 1972 0.79

1.2 --- --- 2748 1.74 2518 1.44 2255 1.13 1970 0.87 --- ---

1.4 2797 1.87 2562 1.59 2273 1.27 2025 0.99 --- --- --- ---

1.6 2556 1.67 2314 1.40 2035 1.11 --- --- --- --- --- ---

1.8 2342 1.50 2037 1.21 --- --- --- --- --- --- --- ---

2 2137 1.35 --- --- --- --- --- --- --- --- --- ---

High Static Belt Drive — Down Shot

ESP (In W.C.)

0 Turns 1 Turn 2 Turns 3 Turns 4 Turns 5 Turns CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP

0.6 --- --- --- --- 2793 1.64 2575 1.37 2407 1.15 2250 0.96

0.8 --- --- 2775 1.76 2638 1.53 2407 1.25 2226 1.04 2011 0.84

1 2821 1.89 2660 1.67 2407 1.36 2194 1.12 2012 0.92 --- ---

1.2 2696 1.79 2497 1.54 2228 1.23 1977 0.98 --- --- --- ---

1.4 2455 1.59 2236 1.35 2013 1.10 --- --- --- --- --- ---

1.6 2262 1.44 2032 1.20 --- --- --- --- --- --- --- ---

1.8 2069 1.30 --- --- --- --- --- --- --- --- --- ---

Note: Tables represent dry coil without filter; to compensate for filter, add 0.08" to measured E.S.P.

Air Flow Pressure Drop of Down Flow Economizer

Airflow Pressure Drop of Downflow Economizer for 3 to 6 Ton Rofftop Units (100% Return Air)

SCF, 800 1000 1200 1400 1600 1800 2000 2200 2400 2600 2800

in WG 0.02 0.04 0.05 0.07 0.09 0.12 0.14 0.17 0.21 0.24 0.28

Page 12: DCG Commercialwebtest.daikinac.com/content/assets/LightCommercial... · 2017. 8. 16. · •ase Monitor: Phase monitor (3 phase only), available for 3 - 25 ton DS, DC and DT series

12 www.daikinac.com SS-DCG3

Crankcase Heater Selection TableZP/ZPS… Compressor Diameter Compressor Voltage Crankcase

Heater Watts230V 460V 575V16-31 5.5" 0163R00002S 0163R00031S 0163R00032S 40

39-83 6.58/7.3" 0130L00017S 0130L00018S 0130L00019S 70

103-137 9.14” 0130L00020S 0130L00021S 0130L00022S 90

DC*,DT* & DS* Tonnage Compressor Voltage Crankcase Heater Watts230V 460V 575V

3 Ton 0163R00002S 0163R00031S 0163R00032S 40

4 Ton-12.5 Ton 0130L00017S 0130L00018S 0130L00019S 70

15-20 Ton** 0130L00017S 0130L00018S 0130L00019S 70

25 Ton 0130L00020S 0130L00021S 0130L00022S 90

*Includes C,G&H models. **If Compressor Diameter is 9.14” then use 25 Ton Crankcase heaters.

0.00

0.05

0.10

0.15

0.20

0.25

0.30

0.35

0.40

0.45

0.50

0 700600500400300200100

Air Velocity (FPM)

Resi

stan

ce (i

n. w

.g.)

2" Deep

Flanders Pre Pleat M13Air Velocity vs Resistance

(Test Size: 24" x 24" x 2" High Capacity)

Tonnage: Filter Nominal Size: Part Number: Order QTY:

3 24 x 24 x 2 0160L00203 1

4 14 x 20 x 2 0160L00204 4

5, 6, 7.5 16 x 20 x 2 0160L00205 4

7.5(HP), 8.5, 10 16 X 24 X 2 0160L00206 4

12.5 20 x 25 x 2 0160L00202 4

15, 20 20 x 25 x 2 0160L00202 6

25 20 X 20 X 2 0160L00201 8

High Efficiency MERV 13 Air Filter Option

Crankcase Heater, High Efficiency MERV 13 Air Filter Option

Page 13: DCG Commercialwebtest.daikinac.com/content/assets/LightCommercial... · 2017. 8. 16. · •ase Monitor: Phase monitor (3 phase only), available for 3 - 25 ton DS, DC and DT series

SS-DCG3 www.daikinac.com 13

Electrical Data - 6 ton

Model Number Electrical Rating

Compressor Circuit 1 Compressor Circuit 2 Outdoor Fan Motor Indoor Fan Motor Optional Powered Convienience Outlet Power Supply

RLA LRA RLA LRA QTY HP FLA Type HP FLA FLA MCA MOP

DCG072XXX3B 208/230-3-60 19.0 123.0 1 0.33 2.00Standard - Belt

Drive1.50 4.80

- 30.6 / 30.6 45 / 45

7.2 / 6.5 37.8 / 37.1 50 / 50

DCG072XXX3H 208/230-3-60 19.0 123.0 1 0.33 2.00High Static - Belt

Drive2.00 6.40

- 32.2 / 32.2 50 / 50

7.2 / 6.5 39.4 / 38.7 50 / 50

DCG072XXX3V 208/230-3-60 17.6 136.0 1 0.33 2.00Standard - Belt

Drive (High Speed)

2.00 6.00- 30.0 / 30.0 45 / 45

7.2 / 6.5 37.2 / 36.5 50 / 50

DCG072XXX4B 460-3-60 9.7 62.0 1 0.33 0.85Standard - Belt

Drive1.50 2.40

- 15.4 25

3.3 18.7 25

DCG072XXX4H 460-3-60 9.7 62.0 1 0.33 0.85High Static - Belt

Drive 2.00 3.00

- 16.0 25

3.3 19.3 25

DCG072XXX4V 460-3-60 8.5 66.1 1 0.33 0.85Standard - Belt

Drive (High Speed)

2.00 2.90- 14.3 20

3.3 17.6 25

DCG072XXX7B 575-3-60 7.4 50.0 1 0.33 0.90Standard - Belt

Drive1.50 2.30

- 12.5 15

2.6 15.1 20

DCG072XXX7H 575-3-60 7.4 50.0 1 0.33 0.90High Static - Belt

Drive2.00 2.50

- 12.7 20

2.6 15.3 20

DCG072XXX7V 575-3-60 6.3 55.3 1 0.33 0.90Standard - Belt

Drive (High Speed)

2.00 2.40- 11.2 15

2.6 13.8 20

Page 14: DCG Commercialwebtest.daikinac.com/content/assets/LightCommercial... · 2017. 8. 16. · •ase Monitor: Phase monitor (3 phase only), available for 3 - 25 ton DS, DC and DT series

14 www.daikinac.com SS-DCG3

Dimensions

11.2

65

33.8

05

73.9

4548

.196

6.19

610

.060

12.0

00

7.16

517

.000

31.5

4011

.000

20.8

53

4.47

5

ALL

DIM

EN

SIO

NS

GIV

EN

AR

E IN

INC

HE

SA

LL D

IME

NS

ION

S A

ND

SP

EC

IFIC

AT

ION

S A

RE

SU

BJE

CT

TO

CH

AN

GE

WIT

HO

UT

NO

TIC

E

DC

G07

2***

6 T

ON

CO

MM

ER

CIA

L

GA

S L

INE

EN

TR

AN

CE

CO

MB

US

TIO

N A

IR IN

LET

(G

AS

UN

ITS

)

FLU

E/V

EN

T O

UT

LET

FR

ON

T V

IEW

TO

P V

IEW

FO

RK

HO

LES

BO

TH

SID

ES

A

ND

BO

TH

EN

DS

CO

ND

EN

SA

TE

DR

AIN

OU

TLE

T

LIF

TIN

G S

HA

CK

LE

HO

LES

BO

TH

SID

ES

A

ND

EN

DS

SU

PP

LY A

IR D

UC

T

RE

TU

RN

AIR

DU

CT

RIG

HT

EN

D V

IEW

Page 15: DCG Commercialwebtest.daikinac.com/content/assets/LightCommercial... · 2017. 8. 16. · •ase Monitor: Phase monitor (3 phase only), available for 3 - 25 ton DS, DC and DT series

SS-DCG3 www.daikinac.com 15

Dimensions (cont.)

7.984

"C"

"B"

10.372

5.872

8.55511.000

17.000

6.192

23.442

48.312

20.905

5.104 12.000

19.470

5.558 25.000

74.061

"A"

LINE WIRE ENTRANCE

TSTAT WIRE ENTRANCE

LEFT END VIEW

SUPPLY AIR DUCT

CONDENSATEDRAINBOTTOM EXIT

RETURN AIR DUCT

BASE PAN VIEW(VIEWED FROM TOP)

MODEL TONNAGES "A" "B" "C"3 TON COMMERCIAL

GAS, HT PUMP, AIR CONDITIONER 38.840 16.555 26.055

4 TON COMMERCIALGAS, HT PUMP, AIR CONDITIONER 38.840 16.555 26.055

5 TON COMMERCIALGAS, HT PUMP, AIR CONDITIONER 38.840 16.555 26.055

6 TON COMMERCIALGAS, HT PUMP, AIR CONDITIONER 42.840 20.555 30.055

7.984

30.055

20.555

10.372

5.872

8.55511.000

17.000

6.192

23.442

48.312

20.905

5.104 12.000

19.470

5.558 25.000

74.061

42.840

LINE WIRE ENTRANCE

TSTAT WIRE ENTRANCE

LEFT END VIEW

SUPPLY AIR DUCT

CONDENSATEDRAINBOTTOM EXIT

RETURN AIR DUCT

BASE PAN VIEW(VIEWED FROM TOP)

Page 16: DCG Commercialwebtest.daikinac.com/content/assets/LightCommercial... · 2017. 8. 16. · •ase Monitor: Phase monitor (3 phase only), available for 3 - 25 ton DS, DC and DT series

16 www.daikinac.com SS-DCG3

Unit Clearances

Maintain an adequate clearance around the unit for safety, service, maintenance, and proper unit operation. Leave a total clearance of 75” on the main control panel side of the unit for possible removal of fan shaft, coil, electric heat, and gas furnace. Leave a clearance of 48” on all other sides of the unit for possible compressor removal or service access, and to ensure proper ventilation and condenser airflow. Do not install the unit Beneath any obstruction. Install the unit away from all building exhausts to inhibit ingestion of exhaust air into the unit’s fresh-air intake.

Electrical Entrance Locations

30¼”

12⅜”

Low-Voltage Entrance

(Remove Plug)High-Voltage Entrance

3½” Dia.

47½”7½”

Power Thru the Curb

Low-Voltage Entrance

Corner & Center-of-Gravity Locations

30”

Compressor

Return

Evaporator Coil

Supply

CondenserCoil

37”

Unit Weights

6-Ton Weights

Corner Weight (A) 130

Corner Weight (B) 215

Corner Weight (C) 130

Corner Weight (D) 215

Unit Shipping Weight 715

Unit Operating Weight 690

Note: Weights are calculated without accessories installed.

Page 17: DCG Commercialwebtest.daikinac.com/content/assets/LightCommercial... · 2017. 8. 16. · •ase Monitor: Phase monitor (3 phase only), available for 3 - 25 ton DS, DC and DT series

SS-DCG3 www.daikinac.com 17

Roof Curb Installation — Rigging

Provisions for forks have been included in the unit base frame. No other fork locations are approved.

• Unit must be lifted by the four lifting holes located at the base frame corners.

• Lifting cables should be attached to the unit with shackles.

• The distance between the crane hook and the top of the unit must not be less than 60”.

• Two spreader bars must span over the unit to prevent damage to the cabinet by the lift cables. Spreader bars must be of sufficient length so that cables do not come in contact with the unit during transport. Remove wood struts mounted beneath unit base frame before setting unit on roof curb. These struts are in-tended to protect unit base frame from fork lift damage. To remove the struts, ex-tract the sheet metal retainers and pull the struts through the base of the unit. Refer to rigging label on the unit.

Important: If using bottom discharge with roof curb, duct-work should be attached to the curb prior to installing the unit. Duct-work dimensions are shown in Roof Curb Installation Instructions Manual.

Refer to the Roof Curb Installation Instructions for proper curb installation. Curbing must be installed in compliance with the National Roofing Contractors Association Manual.

Lower unit carefully onto roof mounting curb. While rigging the unit, the center of gravity will cause the condenser end to be lower than the supply air end.

Bring condenser end of unit into alignment with the curb. With condenser end of the unit resting on curb member and using curb as a fulcrum, lower opposite end of the unit until entire unit is seated on the curb. When a rectangular cantilever curb is used, take care to center the unit. Check for proper alignment and orientation of supply and return openings with duct.

To assist in determining rigging requirements, unit weights are shown below.

Curb installations must comply with local codes and should follow the established guidelines of the National Roofing Contractors Association.Proper unit installation requires that the roof curb be firmly and permanently attached to the roof structure. Check for adequate fastening method prior to setting the unit on the curb.Full perimeter roof curbs are available from the factory and are shipped unassembled. The installing contractor is responsible for field assembly, squaring, leveling, and mounting on the roof structure. All required hardware necessary for the assembly of the sheet metal curb is included in the curb accessory package.• Determine sufficient structural support before locating and mounting the curb and package unit.• Duct-work must be constructed using industry guidelines. The duct-work must be placed into the roof curb before mounting

the package unit. Our full perimeter curbs include duct connection frames to be assembled with the curb. Cantilevered-type curbs are not available from the factory.

• Contractor furnishes curb insulation, cant strips, flashing, and general roofing material.• Support curbs on parallel sides with roof members. To prevent damage to the unit, the roof members cannot penetrate supply

and return duct openings.Note: The unit and curb accessories are designed to allow vertical duct installation before unit placement. Duct installation after unit placement is not recommended.See the manual shipped with the roof curb for assembly and installation instructions.

3-D View

14 x 20Supply Opening

31⅝ x 14Return Opening

70¾ 40¼

14

15⁄6

¾

14

1⅜

Insulated Panels

Top View

Page 18: DCG Commercialwebtest.daikinac.com/content/assets/LightCommercial... · 2017. 8. 16. · •ase Monitor: Phase monitor (3 phase only), available for 3 - 25 ton DS, DC and DT series

18 www.daikinac.com SS-DCG3

Wiring Diagram — DCG 6 Tons (230V, Three-Phase, Belt Drive)

Wiri

ng i

s su

bjec

t to

cha

nge.

Alw

ays

refe

r to

the

wiri

ng d

iagr

am o

n th

e un

it fo

r th

e m

ost

up-t

o-da

te w

iring

.⚠

War

ning

High

Vol

tage

: D

isco

nnec

t al

l po

wer

bef

ore

serv

icin

g or

ins

talli

ng t

his

unit.

Mul

tiple

pow

er

sour

ces

may

be

pres

ent.

Failu

re to

do

so m

ay c

ause

pro

pert

y da

mag

e, p

erso

nal i

njur

y, o

r de

ath.⚡

INSTALLER/SERVICEMAN

TROUBLESHOOTING THIS APPLIANCE. STATUS LIGHT CODES ARE AS FOLLOWS:THE STATUS LIGHT ON THE FURNACE CONTROL MAY BE USED AS A GUIDE TO

FALSE FLAME SENSED

OPEN LIMIT SWITCHWITHOUT INDUCER ON

PRESSURE SWITCH CLOSED

PRESSURE SWITCH

NORMAL OPERATION

3 BLINKS

6 BLINKS

4 BLINKS

5 BLINKS

OUTPUT DELAYCOMPRESSOR

OFF

ON

1 BLINK

2 BLINKS

STATUS LIGHT

OPEN AUX. LIMIT

IGNITION FAILURE

OPEN ROLLOUT

SWITCH

OPEN

SWITCH

NO POWER ORINTERNAL CONTROL

EQUIP. STATUS

CHECK

ANTI-CYCLE TIMER

MAIN LIMIT OPEN

STICKING GAS VALVEBAD SWITCH

3 MIN. COMP.

PRESSURE SWITCH

GAS PRESSURE

FLAME ROLLOUT

AUX. LIMIT OPEN

FLAME SENSOR

BAD SWITCH

GAS VALVE

REPLACE CONTROLGAS FLOW

PRESSURE SWITCHCHECK

CHECK FUSE ON CONTROLCHECK INPUT POWER

-

CHECK

TRANSFORMERTR

ALS

COMP

COMPONENT LEGEND

COMPRESSOR

EM

IICIGN

GNDFS

GV

C

F FUSEFC

EVAPORATOR MOTOR

FLAME SENSOREQUIPMENT GROUND

IGNITOR

GAS VALVE

CONTACTOR

FAN CAPACITOR

RSTB1

PLFPS

VMVMR

ROLLOUT SWITCHTERMINAL BLOCK (24V SIGNAL)

PRESSURE SWITCH

VENT MOTORVENT MOTOR RELAY

LIMIT SWITCHLS

CONDENSER MOTORCM

INTEGRATED IGNITION CONTROL

FEMALE PLUG/CONNECTOR

AUXILIARY LIMIT SWITCH

IBR INDOOR BLOWER RELAY

GND

T3

RD

L3

POWER SUPPLY

YL

BK

208-240/3/60

YL

IIC

T1 T2BKPU

YL

BK

RD

CL1 L2BL

BL

RD RD

BK

T3 T2 T1

PU

COMP

CM

BR BK

RD

RDLS

WH

GR

1079 12

8 11

ECON

BLPU

RDRD

13

26

54

WH

L1BR

FS

YL

RDDI

BL

RDYL

YL

GR

YL

PU

YLPU

PS

541

2

NOTE 2PLF

63

YL

RS

ALS

GR

HEATCOOLUNUSED

BL

BL L2

BL

YL

MV

MV

PU

PU W. R.GAS VALVE

GV

BR

BL

(ALT.) HONEYWELLGAS VALVE

GV

GR

OR

RD

BK

OR

EM

WH

VMR

BL

24VTR

BLBL

1240

2 3C

BK

OR

RD

OR

BL

GR

BC BLOWER CONTACTOR

SEENOTE 3

BC

FS

IGN

BK

VM

OR

RD

L2 L3

C

L2

L3

CMT3

C

FC

208-240/3/60

T2

T3

T2T1

T1 COMP

L1

CL1

SUPPLY VOLTAGE

3VMR

BCIIC

VMR

FSIGN

NOTE 3L2

C

RSGV

3

6

PLF2

5

NOTE 2

1

EM

LS

H CD1

FSF

5

4

L1NOTE 3

ALS

PS

10ECON

3

6

8

12

11

9

IIC

7

TR

FCRDBR

1

4

208-240/3/60 0140L05401-A

LPS HPS

LPS LOW PRESSURE SWITCH

HPS HIGH PRESSURE SWITCH

RD

T2T3

T1

C

BC

BK

BC

BC

208

L3L2

L1

YL

HPS

LPS

3. L1 AND L2 ON IIC CONTROL IS 24V INPUT.

USE NEC CLASS 2 WIRE.

2. ACCESSORY ECONOMIZER PLUG ADJACENT TO BLOWER HOUSING IN RETURN AIR COMPARTMENT. REMOVE MALE PLUG AND ATTACH FEMALE PLUG TO THE ECONOMIZER ACCESSORY.

1. REPLACEMENT WIRE MUST BE THE SAME SIZE AND TYPE OF INSULATION AS ORIGINAL. (USE COPPER CONDUCTOR ONLY).

NOTES

PK

SMOKE/FIREDETECTORREPLACESJUMPER WIRE

BR

LOW VOLTAGE

LINE VOLTAGE

FIELD WIRING

LOW VOLTAGE OPTIONAL HIGH VOLTAGE

FACTORY WIRING

HIGH VOLTAGE

BL

RDY1

YL

W

BL

GR

W

NO ECONOMIZER

G

YL

RD

Y2

Y1

PK

WH

W

R RD

WHGR

C

RYL

GR

Y1

GWH

WITH ECONOMIZER OPTION

C

GR

THERMOSTATFIELD WIRING

BL

C

2 STAGE COOLING

TB1

GR

W

Y

C

TB1

TB1

Y

W

RG

C

W

Y2

GR

C

Y1

STAT

STAT

STAT

YL/PK

BL/PK

BL/PK BLUE WITH PINK STRIPYL/PK YELLOW WITH PINK STRIP

GR GREEN

WIRE CODE

BL BLUE

PU PURPLEPK PINK

WH WHITE

BK BLACK

RD RED

BR BROWN

OR ORANGE

YL YELLOW

GR

SEE UNIT RATING PLATE FOR TYPE AND SIZEOF OVER CURRENT PROTECTION

4. USE COPPER CONDUCTORS ONLY.

6. FOR LOW STAGE OPERATION ONLY, REMOVE WHITE JUMPER. FOR 2 STAGE OPERATION, REMOVE JUMPER AND CONNECT W2 TO W2 ON THERMOSTAT.

BL

RD

YL

RD

TO THERMOSTAT

GR

BL

PU

WH

BR

SEE NOTE 6

3

1

2

OR

OR

WH

SEE NOTE 4

3 1 VM

BK

BK

BK

5. FOR 208 VOLT TRANSFORMER OPERATION, MOVE BLACK WIRE FROM TERMINAL 3 TO TERMINAL 2 ON TRANSFORMER.

87

9

BL

9 8 7

GR Y2Y1 CGR W1 Y1 CW2S1 S2

TO THERMOSTATTERMINAL BLOCK

Y2Y1S1S2 RC W1 GW2

WH

PUPK

RD

GR

Y2

Y2

Page 19: DCG Commercialwebtest.daikinac.com/content/assets/LightCommercial... · 2017. 8. 16. · •ase Monitor: Phase monitor (3 phase only), available for 3 - 25 ton DS, DC and DT series

SS-DCG3 www.daikinac.com 19

Wiri

ng i

s su

bjec

t to

cha

nge.

Alw

ays

refe

r to

the

wiri

ng d

iagr

am o

n th

e un

it fo

r th

e m

ost

up-t

o-da

te w

iring

.⚠

War

ning

High

Vol

tage

: D

isco

nnec

t al

l po

wer

bef

ore

serv

icin

g or

ins

talli

ng t

his

unit.

Mul

tiple

pow

er

sour

ces

may

be

pres

ent.

Failu

re to

do

so m

ay c

ause

pro

pert

y da

mag

e, p

erso

nal i

njur

y, o

r de

ath.⚡

Wiring Diagram — DCG 6 Ton (460V/ 575V, Three-Phase, Belt Drive)

3. L1 AND L2 ON IIC CONTROL IS 24V INPUT.

USE NEC CLASS 2 WIRE.4. USE COPPER CONDUCTORS ONLY.

2. ACCESSORY ECONOMIZER PLUG ADJACENT TO BLOWER HOUSING IN RETURN AIR COMPARTMENT. REMOVE MALE PLUG AND ATTACH FEMALE PLUG TO THE ECONOMIZER ACCESSORY.

1. REPLACEMENT WIRE MUST BE THE SAME SIZE AND TYPE OF INSULATION AS ORIGINAL. (USE COPPER CONDUCTOR ONLY).

INSTALLER/SERVICEMAN

TROUBLESHOOTING THIS APPLIANCE. STATUS LIGHT CODES ARE AS FOLLOWS:THE STATUS LIGHT ON THE FURNACE CONTROL MAY BE USED AS A GUIDE TO

FALSE FLAMESENSED

OPEN LIMIT SWITCHWITHOUT INDUCER ONPRESSURE SWITCH CLOSED

PRESSURE SWITCH

NORMAL OPERATION

INTERNAL CONTROL

3 BLINKS

6 BLINKS

4 BLINKS5 BLINKS

OUTPUT DELAYCOMPRESSOR

OFF

ON

1 BLINK

2 BLINKS

STATUS LIGHT

OPEN AUX. LIMIT

IGNITION FAILUREOPEN ROLLOUT

SWITCH

OPEN

SWITCH

NO POWER OR

EQUIP. STATUS

CHECK

ANTI-CYCLE TIMER

MAIN LIMIT OPEN

STICKING GAS VALVEBAD SWITCH

3 MIN. COMP.

PRESSURE SWITCH

GAS PRESSURE

FLAME ROLLOUT

AUX. LIMIT OPEN

FLAME SENSOR

BAD SWITCH

GAS VALVE

REPLACE CONTROLGAS FLOW

PRESSURE SWITCHCHECK

CHECK FUSE ON CONTROLCHECK INPUT POWER

-CHECK

NOTES

TRANSFORMERTR

LOW VOLTAGE

FACTORY WIRING LINE VOLTAGE

LOW VOLTAGE

FIELD WIRING HIGH VOLTAGE

OPTIONAL HIGH VOLTAGE

ALS

COMP

COMPONENT LEGEND

COMPRESSOR

EM

IICIGN

GNDFS

GV

C

F FUSEFC

EVAPORATOR MOTOR

FLAME SENSOREQUIPMENT GROUND

IGNITOR

GAS VALVE

CONTACTOR

FAN CAPACITOR

RSTB1

PLFPS

VMVMR

ROLLOUT SWITCHTERMINAL BLOCK (24V SIGNAL)

PRESSURE SWITCH

VENT MOTORVENT MOTOR RELAY

LIMIT SWITCHLS

CONDENSER MOTORCM

INTEGRATED IGNITION CONTROL

FEMALE PLUG/CONNECTOR

AUXILLARY LIMIT SWITCH

IBR INDOOR BLOWER RELAY

GND

T3

RD

OR

L3

YL

BK

GR

YL

IIC

T1 T2BKPU

YL

BKRD

CL1 L2BL

BL

RD

ORBK

BK

T3 T2 T1

PU

COMP

CM

BR BK

RD

RDLS

WH

GR

1079 12

8 11

ECON

BLPU

RDRD

RD

13

26

54

WH

L1BR

FSYL

RDDI

BL

YL

YL

BL

YL

PU

YLPUPS

541

2

NOTE 2PLF

63

YL

RS

ALS

GR

HEATCOOLUNUSED

BL

BL L2

BL

YL

MV

MV

PU

PU W. R.GAS VALVE

GV

BL

BL

(ALT.) HONEYWELLGAS VALVE

GV

GR

OR

RD

BK

OR

EM

RD WH

2

1

3

VMR

BL

24VTR

BLBL

1460

2 3C

460/575TR240

BK OR

BC BLOWER CONTACTOR

PUSEENOTE 3

BC

FS

IGN

BK

VM

OR

RD

L2 L3

C

L2

L3

CMT3

C

FC

T2

T3

T2T1

T1 COMP

L1

CL1

13

3

VMR

BC IIC

VMR

FSIGN

NOTE 3L2

C

RSGV

3

6

PLF 2

5

NOTE 2

1

EM

VM

LS

H CD1

FSF

5

4

L1NOTE 3

ALS

PS

10ECON

3

6

8

12

11

9

IIC

7

TR

FCRDBR

1

4

460-575/3/60 0140L05402-A

LPS HPS

LPS LOW PRESSURE SWITCH

HPS HIGH PRESSURE SWITCH

SMOKE/FIRE DETECTORREPLACES JUMPER WIRE

RD

PK

T2T1

T3

C

BC

BK

BC

BC

RD

OR

HPS

LPS

L1L2

L3

ORBK

WH

ORBKRD

OR

BL

RDY1

YL

W

BL

GR

W

NO ECONOMIZER

G

YL

RD

Y2

Y1

PK

WH

W

R RD

WHGR

C

RYL

GR

Y1

GWH

WITH ECONOMIZER OPTION

C

GR

THERMOSTATFIELD WIRING

BL

C

2 STAGE COOLING

TB1

GR

W

Y

C

TB1

TB1

Y

W

RG

C

W

Y2

GR

C

Y1

STAT

STAT

STAT

BL/PK

YL/PK

BL/PK BLUE WITH PINK STRIPYL/PK YELLOW WITH PINK STRIP

GR GREEN

WIRE CODE

BL BLUE

PU PURPLEPK PINK

WH WHITE

BK BLACK

RD RED

BR BROWN

OR ORANGE

YL YELLOW

GR

POWER SUPPLY

SEE NOTE 4

460/3/60575/3/60

575

TO THERMOSTAT

YL BL RDWH

GR

SEENOTE 5

BR

BR

5. FOR LOW STAGE OPERATION ONLY, REMOVE WHITE JUMPER. FOR 2 STAGE OPERATION, REMOVE JUMPER AND CONNECT W2 TO W2 ON THERMOSTAT.

460-575/3/60SUPPLY VOLTAGE

SEE UNIT RATING PLATE FOR TYPE AND SIZEOF OVER CURRENT PROTECTION.

OR

RD

BL

BK

87

9

9 8 7

TO THERMOSTATTERMINAL BLOCK

GR Y1 CGR W1 Y2Y1 CW2S1 S2

Y2Y1S1S2 RC W1 GW2

GR

WH

PU

RD

Y2

Y2

Page 20: DCG Commercialwebtest.daikinac.com/content/assets/LightCommercial... · 2017. 8. 16. · •ase Monitor: Phase monitor (3 phase only), available for 3 - 25 ton DS, DC and DT series

20 www.daikinac.com SS-DCG3

Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.

⚠ Warning High Voltage: Disconnect all power before servicing or installing this unit. Multiple power sources may be present. Failure to do so may cause property damage, personal injury, or death. ⚡

Wiring Diagram — DCG Control Diagram DCG072 - 2 Speed (All Voltages)

BL

PU

BL

BLYL

BLBK

BLBR

YL BL

BL

1. REPLACEMENT WIRE MUST BE SAME SIZE AND TYPE OF INSULATION AS ORIGINAL (USE COPPER CONDUCTORS ONLY).

2 IF OPTIONAL ECONOMIZER IS INSTALLED, REMOVE ECON SHRT PLM AND CONNECT ECON PLM TO ECON PLF.

3 WHEN SPEED-UP PINS ARE SHORTED, THE COMPRESSOR DELAY IS BYPASSED; BYPASS FOR TESTING/TROUBLESHOOTING ONLY

4 CONNECTIONS SHOWN ARE FOR 1-STAGE HEAT OPERATION. WHEN 2-STAGE OPERATION IS REQIRED REMOVE JUMPER WIRE CONNECTING W2 TO W1 ON TB1.

5 IF OPTIONAL SMOKE DETECTOR(S) ARE INSTALLED, REMOVE JUMPER WIRE CONNECTING S1 TO S2 ON TB1. WIRE CONNECTIONS FROM ACCESSORY KIT: CONNECT RD WIRE TO TB1-S1. CONNECT BR WIRE TO TB1-S2. CONNECT BL TO TB1-C (24V COM).

6 IIC FAN OFF-DELAY: - COOL OFF-DELAY IS 60 SECONDS AFTER COOL OR FAN CALL IS REMOVED - HEAT OFF-DELAY IS SELECTABLE, A MOVABLE JUMPER IS PROVIDED; 120, 135, OR 150 SECOND DELAY MAY BE SELECTED. THE FACTORY SETTING IS 150 SEC

CO

NT

RO

LS

DIA

GR

AM

DC

G0

72

2 S

PE

ED

EM

2 S

TA

GE

CO

MP

BL

CC

BC1

BC2

CSPU

PK

AU

X B

AU

X A

8187

YYRB

SE

NS

OR

2

YYRB

SE

N2

PK

OPTIONAL SMOKE DETECTOR

YYRB

24

VA

C/D

C

SE

NS

OR

1

910

YYRB

166

17

SE

N1

RD

BR

BL

5

BL

CRS2S1

RDBK RD

RDCLASS 2

Y1W2 Y2W1G O

YL PUWHGR BR

WH4

FIELDCONTROL WIRING

TR1 SUPPLY (LINE) VOLTAGE

24 VAC

GR

BK BL

5

BKBLBR

RD

GR

HEAT FANCOOL FAN

3A

PS IN

COM

456

123

4

56

1

23

LMT OUTGV

LMT IN

24V

IIC

L1L1

12

987

1110

12

987

1110

R

COMP IN

GPS OUT

W

COMP OUT

YL

WH

YLYL

RD

GR

GR

GR

YL RDYLPU

PU

PU

YL

YL

YL

WH

WH

WH

RD

RD

RD RD

GR

GR

WH

YL

YLYL

YL

GR

RD

RDRD

RD

RD

BL

BLPU

FSD1

L2L2L2L2 BL

BRGY

PU PUALS

PUPU

RS

RD

LSRD

RD

PS

YL

YL

YL

BR

BR

FSVMR

GY

GY

BL

BL

TB1

BR

BR

YL

PU

YL

WH

BLYL1 3

42

5 6

BR2

YLWHPU

GR

YL

RD

YL

GR

YL

RD

YL

BL

BR1

GR

BL

BRBK

BR

BK

YL

BR

1 3

42

5 6

GRBK

YL

BKBR

BK

BR

BL

BR

BL

BR

BL

BL

BL

BL BL

BL BLCOMHIGH

LOW

GV

123

123

PU

PU

GRWH

YL

PU

2

RDECON PLF

ECON SHRTPLM

YL

321

PUPU

4YLBL

765

GR

8WH

9RD

YL

321

4 YL

765

PUPU

89

BL

YL BLYL

WH

PU

YL

RD

BL

PU

BL

BLBL

BL/PK

YL/PK

BL/PK

HP

S

YL/PK

LP

S

YL

MATMAT

IAQ 2-10IAQ COM

IAQ 24V

ACT COMACT 24V

ECON PLM

AUX1-O

OCCAUX2-I

E-GND

EXH1

OPTIONAL ECONOMIZER

OAT

Y2-I

S-BUS

321

4

Y1-IY2-O

Y1-O32

4

1

21

RC

21 6

54321

654321

S-BUS

OAT-t°

MAS

YLYL

PUPU

RD

ORGR

BL

PKPK

MAS

ENTH

WH

WHWH

BR

GRD

24V-PWR24V-COM

4321

S-BUSS-BUS

ECON ACT

BK

BKRD

BLGR

ORRD

PUPU

YL

YL

98

567

4

123

2

SPEED-UP

12

01

35

15

0

P3

3

6

0140L04969-A

Page 21: DCG Commercialwebtest.daikinac.com/content/assets/LightCommercial... · 2017. 8. 16. · •ase Monitor: Phase monitor (3 phase only), available for 3 - 25 ton DS, DC and DT series

SS-DCG3 www.daikinac.com 21

Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.

⚠ Warning High Voltage: Disconnect all power before servicing or installing this unit. Multiple power sources may be present. Failure to do so may cause property damage, personal injury, or death. ⚡

Wiring Diagram — DCG Power Diagram DCG072 - 2 Speed (230v)

RDBK

POWER DIAGRAMDCG072***32 SPEED EM

2 STAGE COMP

5. SEE ACCESSORY KIT LITERATURE FOR OPTIONAL CONVENIENCE OUTLET WIRING DIAGRAM.

4 SEE CONTROL DIAGRAM FOR CONTROL TRANSFORMER LOW VOLTAGE CONNECTIONS

3 208/230V SUPPLY POWER UNITS ARE FACTORY CONNECTED TO THE CONTROL TRANSFORMER 240V TAP. MOVE WIRE CONNECTION FROM 240V TAP TO 208V TAP WHEN 208V POWER SUPPLY IS USED.

2 THE CONTROL TRANSFORMER HAS MULTIPLE HIGH VOLTAGE TAPS. ENSURE WIRE CONNECTIONS ARE CORRECT FOR UNIT SUPPLY VOLTAGE RATING

1. REPLACEMENT WIRE MUST BE SAME SIZE AND TYPE OF INSULATION AS ORIGINAL (USE COPPER CONDUCTORS ONLY). UNIT TERMINALS ARE NOT DESIGNED FOR OTHER CONDUCTORS THE USE OF OTHER TYPE CONDUCTORS MAY CAUSE DAMAGE TO THE UNIT

NOTES:

0140L04973-A

GND

L1 L2 L3

LINE VOLTAGE

BK

RD

RD

RD

PU

BK

RD

OR

BK

RD

BK

YL

FC

BK(12)

BK(13)

BK(11)

BK

OR

RD

BK

RD

BK

OR

RD

OR

BK

RDOR

L1

L2

L3

T1

T2

T3

BC1

BK

BK

WH

OR

WHRD1 3

WH

BK

RD

L1

L2

L3

T1

T2

T3

BC2

RD OR

L1

L2

L3

T1

T2

T3

CC

OR

RD

BK

OR

RD

YL

BKT1

T3

COMPT2

EM

OR

RD

BK

WH

OR

BL

GY

BL

YL

GY

BL

YL

VMR

RD

OR

RD

VM

GR

GR

RD BK

2,3

4

24V CNTLVOLTAGE

LINEVOLTAGE

TR1

IIC DIAGNOSTIC BLINK CODES

-------

ANTI-CYCLE TIMER3 MIN. COMP.

STICKING GAS VALVE

BAD SWITCHMAIN LIMIT OPEN

SWITCHCHECK PRESSURE

SWITCHCHECK PRESSURE

AUX.LIMIT OPENBAD SWITCH

FLAME ROLLOUTFLAME SENSER

GAS VALVEGAS PRESSURE

GAS FLOWREPLACE CONTROL

CHECK FUSE ON CONTROLCHECK INPUT POWER

DELAYCOMPRESSOR OUTPUT

FALSE FLAME SENSED

OPEN LIMIT SWITCH

WITHOUT INDUCER ONPRESSURE SWITCH CLOSED

PRESSURE SWITCH OPEN

OPEN AUX LIMIT SWITCHOPEN ROLLOUT SWITCH

IGNITION FAILURE

INTERNAL CONTROLNO POWER OR

NORMAL OPERATION

6 BLINKS

5 BLINKS

4 BLINKS

3 BLINKS

2 BLINKS

1 BLINK

OFF

ON

CHECKEQUIPMENT STATUSSTATUS LIGHT

LOW VOLTAGE

FIELD WIRING

HIGH VOLTAGE

Y22ND STAGECOOL CALL(OUTPUT)

Y11ST STAGECOOL CALL(OUTPUT)

W22ND STAGEHEAT CALL(OUTPUT)

W11ST STAGEHEAT CALL(OUTPUT)

G

C

R

TB1 CONNECTION

24VAC-PWR(INPUT)

THERMOSTATIN / OUT

24VAC - COM(INPUT)

FAN CALL(OUTPUT)

THERMOSTAT CONNECTIONS

YELLOW/PINK STRIPE

YELLOW

YL/PK

BL/PK

BK

WIRE CODE

BLACKBL BLUEBR BROWNGR GREENGY GRAYOR ORANGEPK PINKPU PURPLERD REDWH WHITEYL

BLUE/PINK STRIPE

FACTORY WIRING

LOW VOLTAGE

HIGH VOLTAGE

HIGH VOLTAGEOPTIONAL

BK

RD

OR

BK

RD

OR

COMPRESSOR 2ND STAGE SOLENOIDCS

TERMINAL BLOCK 3, LOW VOLTAGE

PLUG / CONNECTOR, MALEPLM

ECONOMIZER

EVAPORATOR MOTOR

HIGH PRESSURE SWITCH

LOW PRESSURE SWITCH

PLUG / CONNECTOR, FEMALE

TERMINAL BLOCK 1, LOW VOLTAGE

TRANSFORMER 1, CONTROLS(LINE VOLTAGE / 24VAC)

ECON

EM

HPS

LPS

PLF

TB1

TR1

TB3

INTEGRATED IGNITION CONTROL

IGNITOR

GAS VALVE

IIC

IGN

GV

LIMIT SWITCH

EQUPIMENT GROUND

LS

GND

ROLLOUT SWITCHRS

TRANSFORMER 2, PWR - VENT MOTOR(LINE VOLTAGE / 230VAC)

TR2

VENT MOTOR

IIC 24V POWER FUSEF7

VENT MOTOR RELAYVMR

FLAME SENSORFS

VM

BLOWER CONTACTORBC

BLOWER RELAY

COMPRESSOR CONTACTOR

CONDENSER MOTOR

COMPRESSOR

CC

CM

COMP

COMPONENT LEGEND

CRANK CASE HEATER

BR

CCH

CONDENSER MOTOR CONTACTORCMC

CONDENSER MOTOR RELAYCMR

AUXILLARY LIMIT SWITCHALS

IIC

IGN IGN

6

6 2 SPEED EVAPORATOR MOTOR: BLACK LEADS FOR HIGH SPEED OPERATION, AND WHITE / BLUE / ORANGE LEADS FOR LOW SPEED OPERATION.

PU

CM

PU

BR

BK

PU

BR

BK

GRBR

BK

Page 22: DCG Commercialwebtest.daikinac.com/content/assets/LightCommercial... · 2017. 8. 16. · •ase Monitor: Phase monitor (3 phase only), available for 3 - 25 ton DS, DC and DT series

22 www.daikinac.com SS-DCG3

Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.

⚠ Warning High Voltage: Disconnect all power before servicing or installing this unit. Multiple power sources may be present. Failure to do so may cause property damage, personal injury, or death. ⚡

Wiring Diagram — DCG Power Diagram DCG072 - 2 Speed (460/575v)

RD

BK

POWER DIAGRAMDCG072***(4/7)2 SPEED EM

2 STAGE COMP

4. SEE ACCESSORY KIT LITERATURE FOR OPTIONAL CONVENIENCE OUTLET WIRING DIAGRAM.

3 SEE CONTROL DIAGRAM FOR CONTROL TRANSFORMER LOW VOLTAGE CONNECTIONS

2 THE CONTROL TRANSFORMER HAS MULTIPLE HIGH VOLTAGE TAPS. ENSURE WIRE CONNECTIONS ARE CORRECT FOR UNIT SUPPLY VOLTAGE RATING

1. REPLACEMENT WIRE MUST BE SAME SIZE AND TYPE OF INSULATION AS ORIGINAL (USE COPPER CONDUCTORS ONLY). UNIT TERMINALS ARE NOT DESIGNED FOR OTHER CONDUCTORS THE USE OF OTHER TYPE CONDUCTORS MAY CAUSE DAMAGE TO THE UNIT

NOTES:

0140L04974-B

GND

L1 L2 L3

LINE VOLTAGE

BK

RD

RD

RD

PU

BK

RD

OR

BK

RD

BK

YL

FC

BK(12)

BK(13)

BK(11)

BK

OR

RD

BK

RD

BK

OR

RD

OR

BK

RD

OR

L1

L2

L3

T1

T2

T3

BC1

BK

BK

WH

OR

WHRD1 3

WH

BK

RD

L1

L2

L3

T1

T2

T3

BC2

RD OR

L1

L2

L3

T1

T2

T3

CC

OR

RD

BK

OR

RD

YL

BKT1

T3

COMPT2

EM

BR

OR

RD

BK

WH

OR

BL

GY

BL

YL

GY

BL

YL

VMR

RD

RD

VM

GR

GR

RD BK

2

3

24V CNTLVOLTAGE

LINEVOLTAGE

TR1

IIC DIAGNOSTIC BLINK CODES

-------

ANTI-CYCLE TIMER3 MIN. COMP.

STICKING GAS VALVE

BAD SWITCHMAIN LIMIT OPEN

SWITCHCHECK PRESSURE

SWITCHCHECK PRESSURE

AUX.LIMIT OPENBAD SWITCH

FLAME ROLLOUTFLAME SENSER

GAS VALVEGAS PRESSURE

GAS FLOWREPLACE CONTROL

CHECK FUSE ON CONTROLCHECK INPUT POWER

DELAYCOMPRESSOR OUTPUT

FALSE FLAME SENSED

OPEN LIMIT SWITCH

WITHOUT INDUCER ONPRESSURE SWITCH CLOSED

PRESSURE SWITCH OPEN

OPEN AUX LIMIT SWITCHOPEN ROLLOUT SWITCH

IGNITION FAILURE

INTERNAL CONTROLNO POWER OR

NORMAL OPERATION

6 BLINKS

5 BLINKS

4 BLINKS

3 BLINKS

2 BLINKS

1 BLINK

OFF

ON

CHECKEQUIPMENT STATUSSTATUS LIGHT

LOW VOLTAGE

FIELD WIRING

HIGH VOLTAGE

Y22ND STAGECOOL CALL(OUTPUT)

Y11ST STAGECOOL CALL(OUTPUT)

W22ND STAGEHEAT CALL(OUTPUT)

W11ST STAGEHEAT CALL(OUTPUT)

G

C

R

TB1 CONNECTION

24VAC-PWR(INPUT)

THERMOSTATIN / OUT

24VAC - COM(INPUT)

FAN CALL(OUTPUT)

THERMOSTAT CONNECTIONS

YELLOW/PINK STRIPE

YELLOW

YL/PK

BL/PK

BK

WIRE CODE

BLACKBL BLUEBR BROWNGR GREENGY GRAYOR ORANGEPK PINKPU PURPLERD REDWH WHITEYL

BLUE/PINK STRIPE

FACTORY WIRING

LOW VOLTAGE

HIGH VOLTAGE

HIGH VOLTAGEOPTIONAL

BK

RD

OR

BK

RD

OR

IIC

IGN IGN

OR

RD

TR2 COM230V

460V OR575V

ORBK

RD

RD

BK

RD

BK

RD

OR

OR

OR

COMPRESSOR 2ND STAGE SOLENOIDCS

TERMINAL BLOCK 3, LOW VOLTAGE

PLUG / CONNECTOR, MALEPLM

ECONOMIZER

EVAPORATOR MOTOR

HIGH PRESSURE SWITCH

LOW PRESSURE SWITCH

PLUG / CONNECTOR, FEMALE

TERMINAL BLOCK 1, LOW VOLTAGE

TRANSFORMER 1, CONTROLS(LINE VOLTAGE / 24VAC)

ECON

EM

HPS

LPS

PLF

TB1

TR1

TB3

INTEGRATED IGNITION CONTROL

IGNITOR

GAS VALVE

IIC

IGN

GV

LIMIT SWITCH

EQUPIMENT GROUND

LS

GND

ROLLOUT SWITCHRS

TRANSFORMER 2, PWR - VENT MOTOR(LINE VOLTAGE / 230VAC)

TR2

VENT MOTOR

IIC 24V POWER FUSEF7

VENT MOTOR RELAYVMR

FLAME SENSORFS

VM

BLOWER CONTACTORBC

BLOWER RELAY

COMPRESSOR CONTACTOR

CONDENSER MOTOR

COMPRESSOR

CC

CM

COMP

COMPONENT LEGEND

CRANK CASE HEATER

BR

CCH

CONDENSER MOTOR CONTACTORCMC

CONDENSER MOTOR RELAYCMR

AUXILLARY LIMIT SWITCHALS

5

5 2 SPEED EVAPORATOR MOTOR: BLACK LEADS FOR HIGH SPEED OPERATION, AND WHITE / BLUE / ORANGE LEADS FOR LOW SPEED OPERATION.

CM

PU

BR

BKGR

PU

BR

BK

Page 23: DCG Commercialwebtest.daikinac.com/content/assets/LightCommercial... · 2017. 8. 16. · •ase Monitor: Phase monitor (3 phase only), available for 3 - 25 ton DS, DC and DT series

SS-DCG3 www.daikinac.com 23

WIRING DIAGRAMS FOR MODELS WITH DDC CONTROLSFor complete information and installation instructions for models

with DDC controls, see manual DK-DDC-TGD-XXX

Page 24: DCG Commercialwebtest.daikinac.com/content/assets/LightCommercial... · 2017. 8. 16. · •ase Monitor: Phase monitor (3 phase only), available for 3 - 25 ton DS, DC and DT series

24 www.daikinac.com SS-DCG3

Wiri

ng i

s su

bjec

t to

cha

nge.

Alw

ays

refe

r to

the

wiri

ng d

iagr

am o

n th

e un

it fo

r th

e m

ost

up-t

o-da

te w

iring

.⚠

War

ning

High

Vol

tage

: D

isco

nnec

t al

l po

wer

bef

ore

serv

icin

g or

ins

talli

ng t

his

unit.

Mul

tiple

pow

er

sour

ces

may

be

pres

ent.

Failu

re to

do

so m

ay c

ause

pro

pert

y da

mag

e, p

erso

nal i

njur

y, o

r de

ath.⚡

Wiring Diagram with DDC — DCG072140 (208-230V/3/60) B***

412 5

3 6

GN

D

LDS

BPSW

BI1

BI2

BI3

RS

S

AI1

CO2VO

UT

DC

GN

D

24V

AC

CO

M

GN

D

VO

UT

DC

EC

ON

24V

TR1

124

02

3C

208

TR2

12

3

CEM

L3

BK

CO

MP

SMK

/EM

G

PO

WE

R S

UPP

LY20

8-24

0/3/

60SE

E N

OTE

4

CFS

YL/P

KB

L/PK

BKB

R

RD

PK

GR

YL

GR

GR

BL

BC

CC

OARH SPCRH

STPT

OFF

SET

GN

D

TEM

P

SPCTEMP

BL

BL

BL/ PK

DA

T

OA

T

BI4

BI5

BI6

BI7

BI8

AI2

AI3

AI4

AI5 AI6

AI7

AI8 GN

D

AG

ND

24V

AC

AG

ND

GN

DG

ND

CO

M3-

8R

L8 AO

4

CO

M2

AO

3

AO

2

AO

1

CO

M3-

8

RL7

RL6RL5

RL4

RL3

RL2

RL1CO

M1

AG

C

VO

UT

DC

GN

D

BL

WH

WH

WH

WH

+ - + -HG

RH

EXF

GR

ALR

M+ -

RD YL

T3 T2 T1

L2 L1

BL

RD B

K

BL

BL

RD

BK

BK R

D

WH

PK

L3T3 T2 T1

L2 L1 C

YL RD

SEE

NO

TE 4

240

C20

8

24V

RD

24V

T5T4

T3T2

T1

SEE

NO

TE 5

CS

PS

ES

XS

RD

RD

HP

SLP

S

TB1

RD

BK

YL

PU

PU

PK

YLPK

VM

VMR 3 1

2

PS

RS

ALS

MV

MV

PU

W.R

.G

AS

VA

LVE

GV

BL(A

LT.)

HO

NEY

WE

LLG

AS

VA

LVE

GV

FS IGN

SE

E N

OTE

6

IIC

LS

10

7 9

12

8

11

ECO

N

1 32654

L1FS

DIHEAT COOLUNUSED

L2

SE

EN

OTE

3

CM

BR

RC

CF

PU

BK

BK

RD

FC

OR

GR

OR

RD

BK

WH

BK

BK

BK

PK

RD

PU

PU

BR

RD

OR

BL

BL

BL

BL

BL

BLPK

WH

YL

YLYLP

UBL

RD

RD

RD

RD

RD

OR

RD

GR

GR

PU

RD

WH

BR

BKB

L

BL

WH

BR

OR

WH B

L

PU

RD

BK

BL

BL

WH

BL

BK

GR

BK

GR

BR

YL/

PK

YL

GR

TB2

0140

L050

12-A

208-

240/

3/60

OR

OR

DA

PU

RD

PU

WH

RD

BKR

D

BK

24 V

AC

Page 25: DCG Commercialwebtest.daikinac.com/content/assets/LightCommercial... · 2017. 8. 16. · •ase Monitor: Phase monitor (3 phase only), available for 3 - 25 ton DS, DC and DT series

SS-DCG3 www.daikinac.com 25

Wiring Diagram with DDC —DCG072140 (208-230V/3/60) B***

0140

L051

33-A

208-

240/

3/60

BL/

PK

B

LUE

WIT

H P

INK

STR

IP

PK

P

INK

YL/

PK

Y

ELLO

W W

ITH

PIN

K S

TRIP

WIR

E C

OD

ELIN

E V

OLT

AG

E

OP

TIO

NAL

HIG

H V

OLT

AG

E

LOW

VO

LTA

GE

RD

R

EDFAC

TOR

Y W

IRIN

G

LOW

VO

LTA

GE

BL

BLU

EB

K

BLA

CK

NO

TES

:

1. R

EPL

AC

EM

EN

T W

IRE

MU

ST

BE

SA

ME

SIZ

E A

ND

T

YP

E IN

SULA

TIO

N A

S O

RIG

INAL

(AT

LEA

ST

105°

C)

U

SE

CO

PP

ER

CO

ND

UC

TOR

ON

LY.

2. U

SE

CO

PP

ER

CO

ND

UC

TOR

S O

NLY

+

+ U

SE

N.E

.C. C

LAS

S 2

WIR

E3.

EC

ON

OM

IZE

R P

LUG

LO

CA

TED

IN T

HE

RET

UR

N A

IR

CO

MP

AR

TME

NT.

RE

MO

VE

MAL

E P

LUG

AN

D A

TTA

CH

F

EM

ALE

PLU

G T

O T

HE

EC

ON

OM

IZE

R A

CC

ES

SOR

Y.

4. F

OR

208

VO

LT T

RA

NS

FOR

ME

R O

PE

RAT

ION

MO

VE

B

LAC

K W

IRE

FR

OM

TE

RM

INAL

3 T

O T

ER

MIN

AL 2

O

N

TR

AN

SFO

RM

ER

.5.

RE

MO

VE J

UM

PE

R IF

SM

OK

E D

ETE

CTO

R O

R E

MER

GE

NC

Y

SH

UTD

OW

N D

EV

ICE

IS IN

STA

LLE

D.

6. C

RA

NK

CA

SE H

EAT

ER

AN

D C

RAN

KC

ASE

HEA

TER

S

WIT

CH

FA

CTO

RY

EQ

UIP

PE

D W

HE

N R

EQ

UIR

ED

.

OR

O

RA

NG

E

AGN

DAI

LAL

RM

BC BCC

BHS

BIL

BLS

BPSW

C CC

CC

RC

FC

FCC

FSC

HC

HR

CH

SC

MC

OM

CO

MP

CS

DFT

ECO

NE

MES EX

FG

ND

HG

RH

HP S

LDS

LPS

OAT

OAR

HPL

FPS R

CC

FR

LR

SSR

VCSA

T/D

A TSM

K/EM

GSP

CTE

MP

SPC

RH

T1-T

5TB

1-2

TR1-

2XS

DC

GR

OU

ND

FO

R A

NAL

OG

SEN

SOR

S ("

AG" O

N T

B2)

8 AN

ALO

G IN

P UTS

ALAR

MBL

OW

ER C

ON

TAC

TOR

BLO

WER

CO

NTA

CTO

RBL

OW

ER H

I GH

SPE

E D8

BIN

A RY

INP U

TSBL

OW

ER L

OW

SP

EED

BLO

WER

PR

OVI

NG

SW

ITC

HC

ON

TAC

TOR

CO

MPR

ESSO

R C

ON

TAC

TOR

CO

MPR

ESSO

R C

ON

TAC

TOR

REL

AYC

ON

DEN

SOR

FAN

CO

ND

ENSO

R F

A N C

ON

TAC

TOR

CLO

GG

ED

FIL

TER

SW

ITC

HC

RAN

KCA S

E H

EATE

RC

RAN

KCA S

E H

EATE

R R

ELA Y

CR

ANKC

A SE

HEA

TER

SW

ITC

HC

ON

DEN

SER

MO

TOR

CO

MM

ON

("C

" ON

TB

2)C

OM

PR

ESS

OR

CO

M1

AND

SM

OK E

DET

ECTO

RD

EFR

OST

TH

ERM

OST

ATEC

ON

OM

IZE

REV

APO

RAT

OR

MO

TOR

ECO

N C

OM

3 -8

AND

SM

OKE

DET

ECT O

REX

HA U

ST F

A NEQ

UIP

MEN

T G

RO

UN

DH

OT

GAS

REH

EAT

HIG

H P

RE S

SUR

E SW

ITC

HLO

AD S

HE D

DIN

GLO

W P

RES

S UR

E SW

ITC

HO

UTD

OO

R A

I R T

EM

PER

ATU

RE

OU

TDO

OR

AIR

REL

ATIV

E H

UM

IDIT

YFE

MAL

E P

L UG

/ C

ON

NEC

TOR

HPS

, LPS

& S

MO

KE D

ETEC

T OR

RU

N C

APA

CIT

OR

FO

RC

ON

DE N

SER

FAN

REL

AY

RE M

OTE

STA

RT

STO

PR

EVE

RSI

NG

VAL

V E C

OIL

SUPP

L Y /

DIS

CH

ARG

E AI

R T

EMPE

RAT

UR

ESM

OKE

OR

EM

ERG

E NC

Y SH

UTD

OW

NSP

ACE

TEM

PER

ATU

RE

SPAC

E R

ELAT

IVE

HU

MID

ITY

MO

T OR

SP E

ED T

APS

1-5

(DIR

E CT

DR

IVE N

MO

TOR

ON

LY)

TER

MI N

AL B

LOC

K (2

4V S

IGN

AL)

TRA N

SFO

RM

ER

24 V

AC T

RAN

SFO

RM

ER &

SM

OKE

DET

ECTO

RS

EE

UN

IT R

ATIN

G P

LATE

FO

RTY

PE

AN

D S

IZE

OF

OV

ER

CU

RR

EN

T P

RO

TEC

TIO

N

YL

YEL

LOW

GR

G

RE

EN

WH

W

HIT

E

BR

B

RO

WN

CO

MPO

NE

NT

LEG

EN

D

FIEL

D W

IRIN

G

HIG

H V

OLT

AG

E

PU

P

UR

PLE

FIEL

D S

PLIC

E

SW

ITC

H (T

EM

P)

OP

TIO

NAL

LO

W V

OLT

AG

E

SW

ITC

H (P

RE

SS

.)

OV

ER

CU

RR

EN

TP

RO

T. D

EV

ICE

TER

MIN

AL

PLU

G C

ON

NE

CTI

ON

FIEL

D G

RO

UN

D

IGN

ITE

R

JUN

CTI

ON

INTE

RN

AL T

OIN

TEG

RA

TED

CO

NTR

OL

SC

HE

MAT

IC S

YM

BO

L

LDS

RS

S

BPS

W

3

24V

TR

1

BC

C/B

LS

HPS

3

24V

TR

1

LPS

BI1

BI2

BI3 BI5

BI6 BI7

BI8 AI1 AI2 AI4

AI5

AI6 AI7

AI8 AG

ND

OA

TD

AT

OA

RH

431 2

CO

2

SP

CTE

MP

CO

M

SEN

SOR

OFF

SET

SPC

RH

CO

M1

RL1

RL2

CO

M2

CO

M3-

8

AI3

RL3

RL4

RL5

CC

1

RL6 RL7

RL8

24VA

CG

ND

EC

ON

PLF

+ - + - + -HG

RH

EX

F

ALR

M

SMK

/EM

G

AO

1

AO

2

AO

3A

O4

VM

R

FSIGN

NO

TE 3

L2

RS

GV

LS

H

D1

FSF

54L1N

OTE

3

ALS

PS

103 6 8

IIC

D D C

L2

T1C

OM

P

T2

SU

PPL

Y V

OLT

AG

E

CM

EM

L1

CC

T3

BC

208-

240/

3/60

BC

BC

CC

CC

VM

R3

1V

M

BI4

208-

240/

3/60

208-

240/

3/60

SE

E N

OTE

5

RC

CF

FC

CFS

L3

Wiri

ng i

s su

bjec

t to

cha

nge.

Alw

ays

refe

r to

the

wiri

ng d

iagr

am o

n th

e un

it fo

r th

e m

ost

up-t

o-da

te w

iring

.⚠

War

ning

High

Vol

tage

: D

isco

nnec

t al

l po

wer

bef

ore

serv

icin

g or

ins

talli

ng t

his

unit.

Mul

tiple

pow

er

sour

ces

may

be

pres

ent.

Failu

re to

do

so m

ay c

ause

pro

pert

y da

mag

e, p

erso

nal i

njur

y, o

r de

ath.⚡

Page 26: DCG Commercialwebtest.daikinac.com/content/assets/LightCommercial... · 2017. 8. 16. · •ase Monitor: Phase monitor (3 phase only), available for 3 - 25 ton DS, DC and DT series

26 www.daikinac.com SS-DCG3

Wiring Diagram with DDC — DCG072140 (460V,575V/3/60) B***

Wiri

ng i

s su

bjec

t to

cha

nge.

Alw

ays

refe

r to

the

wiri

ng d

iagr

am o

n th

e un

it fo

r th

e m

ost

up-t

o-da

te w

iring

.⚠

War

ning

High

Vol

tage

: D

isco

nnec

t al

l po

wer

bef

ore

serv

icin

g or

ins

talli

ng t

his

unit.

Mul

tiple

pow

er

sour

ces

may

be

pres

ent.

Failu

re to

do

so m

ay c

ause

pro

pert

y da

mag

e, p

erso

nal i

njur

y, o

r de

ath.⚡

GN

D

LDS

BI1

BI2

BI3

RS

S

AI1

24V

TR1

157

52

3C

460

TR2

12

3

CE

M

L3

BK

CO

MP

SM

K/E

MG

PO

WE

R S

UP

PLY

460/

575/

3/60

SE

E N

OTE

4

CFS BK

BR

RD

PK

GR

GR

BL

BC

CC

BL

BL

DA

T

OA

T

BI4

BI5

BI6

BI7

BI8

AI2

AI3

AI4

AI5

AI6

AI7

AI8

GN

D

AGN

D

24V

AC

AGN

D

GN

DG

ND

CO

M3-

8R

L8 AO

4

CO

M2

AO

3

AO

2

AO

1

CO

M3-

8

RL7

RL6RL5

RL4

RL3

RL2

RL1CO

M1

AG

CB

L

+ - + -HG

RH

EXF

GR

ALR

M+ -

RD YL

T3 T2 T1

L2 L1

BL

RD B

K

BL

BL

RD BK

BK R

D

WH

PK

L3T3 T2 T1

L2 L1 C

YL RD

SE

E N

OTE

4

575

C46

0 BL

24V

RD

24V

T5T4

T3T2

T1

SE

E N

OTE

5

CS

PS

ES

XS

RD

TB1

RD

BK

PU

PU

PK

YL

PK

VM

VM

R 3 1

2

PS

RS

ALS

MV

MV

PU

W.R

.G

AS

VA

LVE

GV

BL(A

LT.)

HO

NE

YW

ELL

GA

S V

ALV

E

GV

FS IGN

SEE

NO

TE 6

IIC

LS

10

7 9

12

8

11

ECO

N

1 32654

L1FS

DIHEAT COOLUNUSED

L2

SEE

NO

TE 3

OR

GR

OR

RD

BK

WH

BK

BK

PK

RD

PU

PU

BR

RD

OR

BL

BL

BL

BL

BL

BLPK

WH

YL

YL

YL

PUBL

RD

RD

RD

RD

RD

OR

RD

GR

GR

PU

WH

BK

BL

BL

WH

BR

OR

WH B

L

RD

BK

BL

BL

460/

575

TR 240O

RB

KO

RB

K

RD

RD

YL/

PK

BL/

PK

BL/ PK

WH

WH

WH

HP

SLP

SR

D

YL

BK

GR

YL/

PK

YL

BL

GR

CM

BR

RC

CF

PU

BK

BK

RD

FC

PU

BR

GN

D

VO

UT

DC

OARH SPCRH

STP

TO

FFS

ET

GN

D

TEM

P

SPCTEMP VO

UT

DC

GN

D

CO2VO

UT

DC

GN

D24

VA

C

CO

M

0140

L050

13-A

460/

575/

3/60

GR

RD

BP

SW

GR

BK

TB2

DA

PU

PU

WH

412 5

3 6

EC

ON

BK

BR

WH

RD

RD

WH

YL

RD

BK

RD

BK

24 V

AC

Page 27: DCG Commercialwebtest.daikinac.com/content/assets/LightCommercial... · 2017. 8. 16. · •ase Monitor: Phase monitor (3 phase only), available for 3 - 25 ton DS, DC and DT series

SS-DCG3 www.daikinac.com 27

Wiring Diagram with DDC—DCG072140 (460V,575V/3/60) B***

Wiri

ng i

s su

bjec

t to

cha

nge.

Alw

ays

refe

r to

the

wiri

ng d

iagr

am o

n th

e un

it fo

r th

e m

ost

up-t

o-da

te w

iring

.⚠

War

ning

High

Vol

tage

: D

isco

nnec

t al

l po

wer

bef

ore

serv

icin

g or

ins

talli

ng t

his

unit.

Mul

tiple

pow

er

sour

ces

may

be

pres

ent.

Failu

re to

do

so m

ay c

ause

pro

pert

y da

mag

e, p

erso

nal i

njur

y, o

r de

ath.⚡

0140

L051

34-A

460/

575/

3/60

BL/

PK

B

LUE

WIT

H P

INK

STR

IP

PK

PIN

K

YL/P

K

YELL

OW

WIT

H P

INK

STR

IP

WIR

E C

OD

ELIN

E V

OLT

AG

E

OP

TIO

NA

L H

IGH

VO

LTA

GE

LOW

VO

LTA

GE

RD

R

ED

F AC

TOR

Y W

IRIN

G

LOW

VO

LTA

GE

BL

BLU

EBK

BL

AC

K

NO

TES

:

1. R

EP

LAC

EM

EN

T W

IRE

MU

ST

BE

SAM

E S

IZE

AN

D

TYP

E IN

SU

LATI

ON

AS

OR

IGIN

AL

(AT

LEA

ST 1

05°C

)

US

E C

OP

PE

R C

ON

DU

CTO

R O

NLY

.2.

US

E C

OP

PE

R C

ON

DU

CTO

RS

ON

LY

++

US

E N

.E.C

. CLA

SS 2

WIR

E3.

EC

ON

OM

IZE

R P

LUG

LO

CA

TED

IN T

HE

RE

TUR

N A

IR

CO

MP

AR

TME

NT.

RE

MO

VE

MA

LE P

LUG

AN

D A

TTA

CH

F

EMAL

E P

LUG

TO

TH

E E

CO

NO

MIZ

ER

AC

CE

SSO

RY.

4. F

OR

460

VO

LT T

RA

NS

FOR

ME

R O

PE

RA

TIO

N M

OV

E

BLA

CK

WIR

E F

RO

M T

ER

MIN

AL

3 T

O T

ER

MIN

AL

2

ON

T

RA

NS

FOR

ME

R.

5.R

EM

OV

E J

UM

PER

IF S

MO

KE

DE

TEC

TOR

OR

EM

ER

GE

NC

Y

SH

UTD

OW

N D

EV

ICE

IS IN

STA

LLE

D.

6. C

RA

NK

CA

SE

HE

ATE

R A

ND

CR

AN

KC

AS

E H

EA

TER

S

WIT

CH

FA

CTO

RY

EQ

UIP

PE

D W

HE

N R

EQ

UIR

ED

.

OR

O

RA

NG

E

AG

ND

AIL

ALR

MB

CB

CC

BH

SB

ILB

LSB

PSW

C CC

CC

RC

FC

FCC

FSC

HC

HR

CH

SC

MC

OM

CO

MP

CS

DFT

EC

ON

EM

ES

EXF

GN

DH

GR

HH

PS

LDS

LPS

OA

TO

AR

HP

LFP

SR

CC

FR

LR

SS

RV C

SA

T/D

AT

SM

K/E

MG

SPC

TEM

PS

PCR

HT1

-T5

TB1-

2TR

1-2

XS

DC

GR

OU

ND

FO

R A

NA

L OG

SE N

SOR

S("

AG" O

N T

B2)

8 A

NA

L OG

INP

UTS

ALA

RM

BLO

WER

CO

NTA

CTO

RB

LOW

ER

CO

NTA

CTO

RB

LOW

ER

HIG

H S

PEE

D8

BIN

AR

Y IN

PU

TSB

LOW

ER L

OW

SP

EE

DB

LOW

ER

PR

OVI

NG

SW

ITC

HC

ON

TAC

TOR

CO

MP

RE

SS

OR

CO

NTA

CT O

RC

OM

PR

ES

SO

R C

ON

TAC

T OR

RE

LAY

CO

ND

ENS

OR

FA

NC

ON

DEN

SO

R F

AN

CO

NTA

CTO

RC

LOG

GE

D F

ILTE

R S

WIT

CH

CR

AN

KC

A SE

HE

ATE

RC

RA

NK

CA S

E H

EA

TER

RE

LAY

CR

AN

KC

A SE

HE

ATE

R S

WIT

CH

CO

ND

ENS

ER

MO

TOR

CO

MM

ON

("C

" ON

TB

2)C

OM

PR

ES

SO

RC

OM

1 A

ND

SM

OK

E D

ETE

CTO

RD

EFR

OS

T TH

ER

MO

STA

TE

CO

NO

MIZ

E RE

VAP

OR

ATO

R M

OTO

RE

CO

N C

OM

3-8

AND

SM

OK

E D

ET E

CTO

RE

XHA

US

T FA

NE

QU

IPM

ENT

GR

OU

ND

HO

T G

AS

RE

HE

AT

HIG

H P

RE S

SUR

E S

WIT

CH

LOA

D S

HE

DD

ING

LOW

PR

ESS

UR

E SW

ITC

HO

UTD

OO

R A

IR T

EM

PER

ATU

RE

OU

TDO

OR

AIR

RE

LAT I

VE H

UM

IDIT

YFE

MAL

E P

LUG

/ C

ON

NE

CTO

RH

PS

, LP

S &

SM

OKE

DE

TEC

TOR

RU

N C

AP

ACIT

OR

FO

RC

ON

DEN

SE

R F

AN

RE

LAY

RE

MO

TE S

TAR

T S

TOP

RE

VE

RS

ING

VA

LVE

CO

ILS

UP

PL Y

/ D

ISC

HA

RG

E A

IR T

EM

PER

ATU

RE

SM

OK

E O

R E

ME R

GE

NC

Y S

HU

TDO

WN

SPA

CE

TEM

PER

ATU

RE

SPA

CE

RE

LATI

VE

HU

MID

ITY

MO

TOR

SP

EED

TA

PS

1-5

(DI R

EC

T D

RIV

EN

MO

TOR

ON

LY)

TER

MIN

AL

BLO

CK

(24 V

SIG

NAL

)TR

AN

S FO

RM

E R24

VA

C T

RA

NS F

OR

ME

R &

SM

OK

E D

ET E

CTO

RS

EE

UN

IT R

ATI

NG

PLA

TE F

OR

TYP

E A

ND

SIZ

EO

F O

VE

RC

UR

RE

NT

PR

OTE

CTI

ON

YL

YELL

OW

GR

G

RE

EN

WH

W

HIT

E

BR

B

RO

WN

CO

MP

ON

EN

T LE

GE

ND

FIE

LD W

IRIN

G

HIG

H V

OLT

AG

E

PU

P

UR

PLE

FIE

LD S

PLIC

E

SW

ITC

H (T

EM

P)

OP

TIO

NA

L LO

W V

OLT

AG

E

SW

ITC

H (P

RE

SS

.)

OV

ER

CU

RR

EN

TP

RO

T. D

EV

ICE

TER

MIN

AL

PLU

G C

ON

NE

CTI

ON

FIEL

D G

RO

UN

D

IGN

ITE

R

JUN

CTI

ON

INTE

RN

AL

TOIN

TEG

RA

TED

CO

NTR

OL

SC

HE

MA

TIC

SYM

BO

L

LDS

RS

S

BP

SW

3

24V

TR

2

BC

C/B

LS

HP

S

3

24V

TR

1

LPS

BI1

BI2

BI3 BI5

BI6 BI7

BI8 AI1 AI2 AI4 AI 5

AI6

AI7

AI8 AG

ND

OA

TD

AT

431 2

CO

M1

RL1

RL2

CO

M2

CO

M3-

8

AI3

RL3

RL4

RL5

CC

1

RL6

RL7

RL8

24V

AC

GN

D

EC

ON

PLF

+ - + - + -HG

RH

EX

F

ALR

M

SMK

/EM

G

AO

1

AO

2

AO

3A

O4

VM

R

FSIGN

NO

TE 3

L2

RS

GV

LS

H

D1

FSF

54L1N

OTE

3

ALS

PS

103 6 8

IIC

D D C

L2

T1C

OM

P

T2

SU

PP

LY V

OLT

AG

E

CM

EM

L1

CC

T3

BC

460/

575/

3/60

BC

BC

CC

CC

BI4

460/

575/

3/60

460/

575/

3/60

SEE

NO

TE 5

RC

CF

FC

CFS

L3

VM

R3

1V

M

31

12

OA

RH

CO

2

SP

CTE

MP

CO

M

SE

NS

OR

OFF

SE

T

SP

CR

H

Page 28: DCG Commercialwebtest.daikinac.com/content/assets/LightCommercial... · 2017. 8. 16. · •ase Monitor: Phase monitor (3 phase only), available for 3 - 25 ton DS, DC and DT series

28 www.daikinac.com SS-DCG3

Wiring Diagram with DDC - DCG072140 (208-230/3/60)V***

Wiri

ng i

s su

bjec

t to

cha

nge.

Alw

ays

refe

r to

the

wiri

ng d

iagr

am o

n th

e un

it fo

r th

e m

ost

up-t

o-da

te w

iring

.⚠

War

ning

High

Vol

tage

: D

isco

nnec

t al

l po

wer

bef

ore

serv

icin

g or

ins

talli

ng t

his

unit.

Mul

tiple

pow

er

sour

ces

may

be

pres

ent.

Failu

re to

do

so m

ay c

ause

pro

pert

y da

mag

e, p

erso

nal i

njur

y, o

r de

ath.⚡

412 5

3 6

GN

D

LDS

BPSW

BI1

BI2

BI3

RSS

AI1

CO2VOUT

DC

GN

D

24VA

C

CO

M

GN

D

VOUT

DC

ECO

N

24V

TR1

124

02

3C

208

TR2

12

3C

EM

L3

BK

COM

P

SMK/

EMG

POW

ER S

UPP

LY20

8-24

0/3/

60SE

E NO

TE 4

CFS

YL/P

KBL

/PK

BKBR

PK

GR

YL

GR

GR

BL

BC1

CC

OARH SPCRH

STPT

OFF

SET

GN

D

TEM

P

SPCTEMP

BL

BL

BL/

PK

DAT

OAT

BI4

BI5

BI6

BI7

BI8

AI2

AI3

AI4

AI5

AI6

AI7

AI8

GN

D

AGND

24VA

C

AGND

GND

GND

COM

3-8

RL8 A

O4

COM

2

AO

3

AO

2 A

O1

COM

3-8

RL7

RL6

RL5

RL4

RL3

RL2

RL1

CO

M1

AGC

VOUT

DC

GN

D

BL

WH

WH

WH

WH

+ - + -HGRH EX

F

GR

ALRM

+ -

RD YL

T3 T2 T1

L2 L1

BL

RD

BK

BLBL RD

BK

BK

RD

WHPK

L3T3 T2 T1

L2 L1

C

YL

RD

SEE

NOTE

4

240

C20

8

24V

RD

24V

T5T4

T3T2

T1

SEE

NOTE

5

CS

PSES

XS

RD

RD

HPS

LPS

TB1

RD

BK

YL

PU

PUPK

YLPK

VMVM

R 3 1

2

PS RS

ALS

MV MV

PU

W.R

.G

AS V

ALVE

GV

BL

(ALT

.) H

ON

EYW

ELL

GAS

VAL

VE

GV

FS IGN

SEE

NOTE

6

IICLS

107 9

12811EC

ON

1 32654

L1FS

DIHEAT COOLUNUSED

L2

SEE

NOTE

3

CM

BR

RCCF

PU B

KBK

RD

FC

GR

OR

RD

BK

WH BK

BK

BK

PK

RD

PU

PU

BR

RD OR

BL

BLBL

BL

BLBLPKWH

YLYLYLPUBLRDRD

RD

OR

RD GR

GR

PU

RD

WH

BRBK

BL

BL

WH

BR

OR

WH

BL

PU

RDBK BL

BL

WH

BL

BK GR

BK

GR

BR

YL/

PKYL

GR

TB2

0140

L066

19-A

208-

240/

3/60

OR

OR

DA

PU

RDPU

WH

RD

BKR

D

BK

24 V

AC

L3L2

L1

PHAS

E M

ONI

TOR

C

BC2

L3T3 T2 T1

L2 L1

PU

OR

BK R

D OR

BL

BL

RD

RD

PUBL

OR

RD

BK

BK

YL

YL

YL

BR

BR

BRPU

RD

PU

YL

GR

GR

GR

GR

BR

WH

GR

BL

WH

WH

WH

BL BL

BL

OR

OR

BR

PK

WH

GR

GR

WH

RD

BL

PK

GR

POW

ER &

CO

NTR

OL

WIR

ING

DIA

GR

AMDC

G 0

72**

*(3)

(V) B

DDC

NO

TES:

1. R

EPLA

CEM

ENT

WIR

E M

UST

BE

SAM

E

SIZ

E AN

D T

YPE

INSU

LATI

ON

AS

OR

IGIN

AL

(AT

LEA

ST 1

05°C

) USE

CO

PPER

C

OND

UCTO

R O

NLY

. 2

. USE

CO

PPER

CO

NDU

CTO

RS

ONL

Y

++

USE

N.E

.C. C

LASS

2 W

IRE.

3. E

CONO

MIZ

ER P

LUG

LO

CAT

ED IN

TH

E

RET

URN

AIR

CO

MPA

RTM

ENT.

REM

OVE

M

ALE

PLUG

AND

ATT

ACH

FEM

ALE

PLUG

T

O T

HE

ECO

NOM

IZER

AC

CES

SORY

. 4

. FO

R 2

08 V

OLT

TR

ANSF

OR

MER

OPE

RAT

ION

,

MO

VE B

LAC

K W

IRE

FRO

M T

ERM

INAL

3

TO

TER

MIN

AL 2

ON

TR

ANSF

ORM

ER.

5. R

EMO

VE J

UMPE

R IF

SM

OKE

D

ETEC

TOR

/EM

ERG

ENCY

SHU

TDO

WN

D

EVIC

E O

R P

HAS

E M

ON

ITO

R IS

INST

ALLE

D.

BK

BL

BL

PU

GY

BL

YL

OR

RD B

K

BK

BK

BK B

L WH

OR

RD

CS

YLG

R

YL

GR

YL

Page 29: DCG Commercialwebtest.daikinac.com/content/assets/LightCommercial... · 2017. 8. 16. · •ase Monitor: Phase monitor (3 phase only), available for 3 - 25 ton DS, DC and DT series

SS-DCG3 www.daikinac.com 29

Wiring Diagram with DDC - DCG072140 (208-230/3/60)V***

Wiri

ng i

s su

bjec

t to

cha

nge.

Alw

ays

refe

r to

the

wiri

ng d

iagr

am o

n th

e un

it fo

r th

e m

ost

up-t

o-da

te w

iring

.⚠

War

ning

High

Vol

tage

: D

isco

nnec

t al

l po

wer

bef

ore

serv

icin

g or

ins

talli

ng t

his

unit.

Mul

tiple

pow

er

sour

ces

may

be

pres

ent.

Failu

re to

do

so m

ay c

ause

pro

pert

y da

mag

e, p

erso

nal i

njur

y, o

r de

ath.⚡

0140

L066

20-A

208-

240/

3/60

BL/P

K B

LUE

WIT

H P

INK

STR

IP

PK

PIN

K

YL/P

K Y

ELLO

W W

ITH

PIN

K ST

RIP

WIR

E C

OD

ELIN

E VO

LTAG

E

OPT

ION

AL H

IGH

VO

LTAG

E

LOW

VO

LTAG

E

RD

R

EDFAC

TOR

YW

IRIN

G

LOW

VO

LTAG

E

BL

BLU

EBK

BL

ACK

NO

TES :

1. R

EPLA

CEM

ENT

WIR

E M

UST

BE

SAM

E SI

ZE A

ND

TYPE

INSU

LATI

ON

AS

OR

IGIN

AL (A

T LE

AST

105°

C)

USE

CO

PPER

CO

NDU

CTO

R O

NLY

.2.

USE

CO

PPER

CO

NDU

CTO

RS

ON

LY +

+ U

SE N

.E.C

. CLA

SS 2

WIR

E3.

EC

ON

OM

IZER

PLU

G L

OC

ATED

IN T

HE

RET

UR

N A

IR C

OM

PAR

TMEN

T. R

EMO

VE M

ALE

PLU

G A

ND

ATT

ACH

FEM

ALE

PLU

G T

O T

HE

ECO

NO

MIZ

ER A

CC

ESSO

RY.

4. F

OR

208

VO

LT T

RAN

SFO

RM

ER O

PER

ATIO

N M

OVE

BLAC

K W

IRE

FRO

M T

ERM

INAL

3 T

O T

ERM

INAL

2

ON

TRAN

SFO

RM

ER.

5.R

EMO

VE J

UM

PER

IF S

MO

KE D

ETEC

TOR

OR

EM

ERG

ENC

Y

SHU

TDO

WN

DEV

ICE

IS IN

STAL

LED

.

OR

O

RAN

GE

AGND

AIL

ALR

MBC

1BC

2BI

LBP

SWCC C

SC

FC

FCC

FSCH C

HR

CHS

CM CO

MC

OM

PD

FTEC

ON

EM ES EXF

GN

DH

GR H

HPS

LDS

LPS

OAT

OAR

HPL

FPS RC

C FR

LR

SSR

V CSA

T/D

ATSD SM

K/EM

GSP

CTE

MP

SPC

R HTB

1-2

TB1-

T3TR

1-2

XS PM

DCG

ROUN

DFO

RAN

ALO

GSE

NSO

RS("A

G"O

NTB

2)8

ANAL

OG

INPU

T SAL

ARM

BLO

WER

HIG

HSP

EED

CON

TAC

TOR

BLO

WER

LOW

SPEE

DC O

NTAC

TOR

8BI

NAR

YIN

PUT S

BLO

WER

PRO

VIN

GS W

ITC

HC

OM

P RES

SOR

CON

TAC

T OR

CO

MPR

ESSO

R2N

DST

AGE

SOLE

N OID

CON

DE N

SER

F AN

CO

ND

ENSE

RF A

NC

ON

TAC

TOR

CLO

GG

EDFI

LTER

S WIT

CH

CRAN

KCAS

EH

EATE

RC R

ANKC

ASE

HEA

TER

REL

A YC

RAN

KCAS

EH

EATE

RSW

I TC

HC

ON D

ENSE

RM

OTO

RC

OM

MO

N(" C

"ON

T B2)

CO

MP R

ESSO

RD

EFR

OST

THER

MO

STAT

ECO

NO

MIZ

EREV

APO

RATO

RM

OT O

REC

ON

C OM

3 -8

AND

SMO

KED

E TEC

TOR

EXH

AUS T

FAN

EQUI

PMEN

TG

RO

UN

DH

OT

GAS

RE H

EAT

HIG

HP R

ESSU

RE

SWIT

CH

LOAD

SHE D

DIN

GLO

WPR

ESSU

RE

S WIT

CH

OU

TDO

OR

AIR

TEM

PER

A TU

RE

OU

TDO

OR

AIR

REL

A TIV

EH

UMID

ITY

FEM

ALE

PLU

G/C

ONN

ECTO

RPR

ESS U

RE

SWIT

CH

R UN

CAPA

CI T

OR

FOR

CO

NDE N

SER

F AN

REL

AYR

EMO

T EST

ART

STO

PR

EVER

SIN

GVA

LVE

COI L

SUPP

L Y/D

ISC

HA R

GE

AIR

TEM

PER

ATU

RE

SMO

KED

ETEC

TOR

SMO

KEO

REM

ERG

ENCY

SHU

TDO

WN

SPAC

ETE

MPE

RAT

URE

SPAC

ER

E LAT

IVE

HUM

IDIT

YTE

RM

INA L

BLO

CK(2

4VSI

GN

AL)

PHAS

EM

ON

ITO

RTE

RM

INAL

(PM

)TR

ANSF

ORM

ER24

VAC

TRAN

S FO

RM

ER&

SMO

KED

E TEC

TOR

PHAS

EM

ON

ITO

RSE

E U

NIT

RAT

ING

PLA

TE F

OR

TYPE

AN

D S

IZE

OF

OVE

RCU

RREN

T PR

OTE

CTI

ON

YL

YELL

OW

GR

G

REE

N

WH

W

HIT

E

BR

BRO

WN

CO

MP O

NEN

T LE

GEN

D

FIEL

DW

IRIN

GH

IGH

VO

LTAG

E

PU

PUR

PLE

FIEL

D S

PLIC

E

SWIT

CH

(TEM

P)

OPT

ION

AL L

OW

VO

LTAG

E

SWIT

CH

(PR

ESS.

)

OVE

RCUR

REN

TPR

OT.

DEV

ICE

TER

MIN

AL

PLU

G C

ON

NEC

TIO

N

FIEL

D G

RO

UND

IGN

ITER

JUNC

TIO

N

INTE

RN

AL T

OIN

TEG

RAT

EDC

ON

TRO

L

SCH

EMAT

IC S

YMBO

L

LDS

RSS

BPSW

3

24V

TR

1

BC2

HPS

3

24V

TR

1

LPS

BI1

BI2

BI3

BI5

BI6

BI7

BI8

AI1

AI2

AI4

AI5

AI6

AI7

AI8

AGN

D

OAT

DAT

OAR

H

431 2

CO2

SPC

TEM

PC

OM

SEN

SOR

OFF

SET

SPCR

H

COM

1RL

1

RL2

COM

2

COM

3-8

AI3

RL3

RL4

RL5

CC

RL6

RL7

RL8

24VA

CG

ND

ECO

NPL

F

+ - + - + -HGR

H

EXF

ALRM

SMK/

EM

G

AO1

AO2

AO3

AO4

VMR

FSIGN

NO

TE 3

L2

RSG

V

LS

H

D1

FSF

54L1N

OTE

3

ALS

PS

103 6 8

IIC

D D C

L2

T1CO

MP

T2

SUPP

LY V

OLT

AGE

CM

EM

L1

CC

T3

208-

240/

3/60

BC1

CC

CC

VMR

31

VM

BI4

208-

240/

3/60

208-

240/

3/60

SEE

NO

TE 5

RC

CF

FC

CFS

L3

POW

ER &

CO

NTR

OL

WIR

ING

DIA

GR

AMDC

G 0

72**

*(3)

(V) B

DDC

PMSD

CS BC

1

BC1

BC1

BC2

BC2

BC2

Page 30: DCG Commercialwebtest.daikinac.com/content/assets/LightCommercial... · 2017. 8. 16. · •ase Monitor: Phase monitor (3 phase only), available for 3 - 25 ton DS, DC and DT series

30 www.daikinac.com SS-DCG3

Wiring Diagram with DDC - DCG072140 (460, 575/3/60)V***

Wiri

ng i

s su

bjec

t to

cha

nge.

Alw

ays

refe

r to

the

wiri

ng d

iagr

am o

n th

e un

it fo

r th

e m

ost

up-t

o-da

te w

iring

.⚠

War

ning

High

Vol

tage

: D

isco

nnec

t al

l po

wer

bef

ore

serv

icin

g or

ins

talli

ng t

his

unit.

Mul

tiple

pow

er

sour

ces

may

be

pres

ent.

Failu

re to

do

so m

ay c

ause

pro

pert

y da

mag

e, p

erso

nal i

njur

y, o

r de

ath.⚡

GN

D

LDS

BI1

BI2

BI3

RSS

AI1

24V

TR1

157

52

3C

460

TR2

12

3

L3

BK

CO

MP

SMK/

EMG

POW

ER S

UPP

LY46

0/57

5/3/

60

CFS BK

BR

RD

PK

GR

GR

BL

BC1

CC

BL

BL

DAT

OAT

BI4

BI5

BI6

BI7

BI8

AI2

AI3

AI4

AI5

AI6

AI7

AI8

GN

D

AGN

D

24VA

C

AGN

D

GN

DG

ND

CO

M3-

8R

L8 AO

4

COM

2

AO

3

AO

2

AO

1

COM

3-8

RL7

RL6

RL5

RL4

RL3

RL2

RL1

COM

1

AGC

BL

+ - + -HG

RH EXF

GR

ALR

M+ -

RD YL

T3 T2 T1

L2 L1

BL

RD BK

BKRD BL

BKRD

WH

PK

C

YL RD

SEE

NO

TE 4

575

C46

0 BL24V

RD

24V

T5T4

T3T2

T1

SEE

NO

TE 5

CS

PSES

XS

RD

TB1

RDBK

PU

PUPK

YLPK

PS RS

ALS

MV MV

PU

W.R

.G

AS V

ALVE

GV

BL

(ALT

.) HO

NEY

WEL

LG

AS V

ALVE

GV

FS IGN

IIC

LS

10

7 912

8

11

ECON

1 32654

L1FS

DIHEAT COOLUNUSED

L2

SEE

NO

TE 3

OR

GR

OR

PK

RD

PU PU

BR

RD

OR

BL

BLBL

BL

BLBLPKWH

YL

YLYLPUBLRDRD

RD

RD

RD

OR

RD GR

GR

PU

WH

BKBL

BL

WH

BR

OR

RDBK BL

BL

460/

575

TR 240O

RBK

OR

BK

RD

RD

YL/P

KBL

/PK

BL/

PK

WH

WH

WH

HPS

LPS

RD

YL

BK GR

YL/

PKYL

BL

GR

GN

D

VOUT

DC

OARH SPCRH

STPT

OFF

SET

GN

D

TEM

P

SPCTEMP VOUT

DC

GN

D

CO2VOUT

DC

GN

D24

VAC

CO

M

0140

L066

07-A

460/

575/

3/60

GR

RD

BPSW

GR

BK

TB2

DA

PU

PU

WH

412 5

3 6EC

ON

BKBR

WH

RD

RD

WH

YL

RDBK

RD

BK

24 V

AC

CM

BRRC

CF

PU

BK

BK

RD

FC

PU

BR

CS

GR

GR

GR

GR

YL

YL

GR

BR

BR

Yout

YC

L1L2

L3 OR

BKR

D

BLR

DPU

VMR 3 1

2

WH

BKBK

WH BL

L3T3 T2 T1

L2 L1C

BC2

L3T3 T2 T1

L2 L1C

EMRD

BK

RD

VM

BLBL

BL

BL

BL

OR

RD BK

GY BL YL

WH

BLO

RBR

BL

BRO

R

RD

BK

YL

YL

BL

YL

Page 31: DCG Commercialwebtest.daikinac.com/content/assets/LightCommercial... · 2017. 8. 16. · •ase Monitor: Phase monitor (3 phase only), available for 3 - 25 ton DS, DC and DT series

SS-DCG3 www.daikinac.com 31

Wiring Diagram with DDC - DCG072140 (460, 575/3/60)V***

Wiri

ng i

s su

bjec

t to

cha

nge.

Alw

ays

refe

r to

the

wiri

ng d

iagr

am o

n th

e un

it fo

r th

e m

ost

up-t

o-da

te w

iring

.⚠

War

ning

High

Vol

tage

: D

isco

nnec

t al

l po

wer

bef

ore

serv

icin

g or

ins

talli

ng t

his

unit.

Mul

tiple

pow

er

sour

ces

may

be

pres

ent.

Failu

re to

do

so m

ay c

ause

pro

pert

y da

mag

e, p

erso

nal i

njur

y, o

r de

ath.⚡

0140

L066

08-A

460/

575/

3/60

BL/P

K B

LUE

WIT

H P

INK

STR

IP

PK

PIN

K

YL/P

K Y

ELLO

W W

ITH

PIN

K ST

RIP

WIR

E C

OD

ELIN

E VO

LTAG

E

OPT

ION

AL H

IGH

VO

LTAG

E

LOW

VO

LTAG

E

RD

R

EDFAC

TOR

YW

IRIN

G

LOW

VO

LTAG

E

BL

BLU

EBK

BL

ACK

NO

TES:

1.R

EPLA

CEM

ENT

WIR

E M

UST

BE

SAM

E SI

ZE A

ND

TYP

E IN

SULA

TIO

N A

S O

RIG

INAL

(AT

LEAS

T 10

5°C

)U

SE C

OPP

ER C

ON

DUC

TOR

ON

LY.

2.U

SE C

OPP

ER C

ON

DUC

TOR

S O

NLY

++ U

SE N

.E.C

. CLA

SS 2

WIR

E3.

ECO

NO

MIZ

ER P

LUG

LO

CAT

ED IN

TH

E R

ETU

RN

AIR

CO

MPA

RTM

ENT.

REM

OVE

MAL

E PL

UG

AN

D A

TTAC

H F

EMAL

E PL

UG

TO

TH

E EC

ON

OM

IZER

AC

CES

SOR

Y.4.

FOR

460

VO

LT T

RAN

SFO

RM

ER O

PER

ATIO

N M

OVE

BLA

CK

WIR

E FR

OM

TER

MIN

AL 3

TO

TER

MIN

AL 2

O

N T

RAN

SFO

RM

ER.

5.R

EMO

VE J

UM

PER

IF S

MO

KE D

ETEC

TOR

OR

EM

ERG

ENC

Y S

HU

TDO

WN

DEV

ICE

IS IN

STAL

LED

.

OR

O

RAN

GE

AGND

AIL

ALR

MBC

1BC

2BI

LBP

SWCC C

FCC

FC

FCC

FSCH C

HR

CH

SC M C

OM

CO

MP

CS

DFT

ECO

NEM ES E X

FG

ND

HG

R HH

PSLD

SLP

SO

A TO

ARH

PLF

PM PS RC

CFR

LR

SSR

VCSA

T/D

A TSD SM

K/EM

GSP

CTE

MP

SPC

RH

TB1-

2TR

1-2

TB1-

T3XS

DC

GRO

UND

FOR

ANAL

OG

SEN

SORS

("AG

" ON

TB2)

8AN

ALO

GIN

P UTS

ALAR

MBL

OW

ERH

IGH

SPEE

DC

ONT

ACTO

RBL

OW

ERL O

WSP

EED

CO

NTA

CTO

R8

BINA

RY

INPU

T SBL

OW

ERPR

OVI

NG

S WIT

CH

CO

MPR

ESSO

RC

ON T

ACT O

RC

ON

DEN

SER

FAN

COIL

CO

NDEN

SER

FAN

CO

N DEN

SER

FAN

CON

TAC

TOR

CLO

GG

EDFI

LTER

SWIT

CH

CR

ANKC

ASE

HEA

TER

CR

ANKC

ASE

HE A

TER

REL

A YC R

ANKC

ASE

HEA

TER

SWIT

CH

CO

NDEN

SER

MO

T OR

CO

MM

ON

("C"O

NTB

2)C

OM

PRES

SOR

CO

MPR

ESSO

R2N

DS T

AGE

SOLE

N OID

DEF

RO

STTH

ERM

OST

ATEC

ON

OM

IZER

EVAP

ORA

TOR

MO

TOR

ECO

NC

OM

3-8

A ND

SMO

KEDE

TEC

TOR

EXH

AUS T

FAN

EQUI

PMEN

TG

RO

UND

HO

TG

ASR

EHEA

TH

IGH

P RES

SUR

ES W

ITC

HLO

ADSH

E DD

ING

LOW

PRES

SUR

ESW

ITC

HO

UTD

OO

RAI

RT E

MPE

RAT

UR

EO

UTD

OO

RAI

RRE

LATI

VEH

UMID

ITY

FEM

ALE

PLU

G/ C

ONN

ECTO

RPH

ASE

MO

NIT

OR

PRES

SUR

ES W

I TC

HR U

NC

APAC

ITO

RFO

RC

ON

DEN

SER

FAN

REL

AYR

EMO

T EST

ART

STO

PR

EVER

SIN

GVA

L VE

COIL

SUPP

L Y/D

I SC

HAR

GE

A IR

TEM

P ER

ATU

RE

SMO

KED

ETEC

T OR

SMO

KEO

REM

ERG

ENC Y

SHU

TDO

WN

SPAC

ETE

MPE

RAT

UR

ESP

ACE

RE L

ATIV

EHU

MID

ITY

TER

MIN

A LBL

OC

K(2

4VSI

GN

AL)

TRAN

SFO

RMER

PHAS

EM

ON

ITO

RTE

RM

INAL

(PM

)24

VAC

TRAN

S FO

RM

ER&

SMO

KED

ETEC

T OR

SEE

UN

IT R

ATIN

G P

LATE

FO

RTY

PE A

ND

SIZ

EO

F O

VER

CUR

REN

T PR

OTE

CTI

ON

YL

YELL

OW

GR

G

REE

N

WH

W

HIT

E

BR

BRO

WN

CO

MP O

NEN

TLE

GEN

D

FIEL

DW

IRIN

GH

IGH

VO

LTAG

E

PU

PUR

PLE

FIEL

D S

PLIC

E

SWIT

CH

(TEM

P)

OPT

ION

AL L

OW

VO

LTAG

E

SWIT

CH

(PR

ESS.

)

OVE

RCU

RREN

TPR

OT.

DEV

ICE

TER

MIN

AL

PLU

G C

ON

NEC

TIO

N

FIEL

D G

RO

UND

IGN

ITER

JUNC

TIO

N

INTE

RN

AL T

OIN

TEG

RAT

EDC

ON

TRO

L

SCH

EMAT

ICSY

MBO

L

LDS

RSS

BPSW

3

24V

TR

2

BC2

HPS

3

24V

TR

1

LPS

BI1

BI2

BI3

BI5

BI6

BI7

BI8

AI1

AI2

AI4

AI5

AI6

AI7

AI8

AGN

D

OAT

DAT

431 2

COM

1R

L1 RL2

COM

2

COM

3-8

AI3

RL3

RL4

RL5

CC

RL6 RL7

RL8

24VA

CG

ND

ECO

NPL

F

+ - + - + -HG

RH

EXF

ALRM

SMK/

EMG

AO1

AO2

AO3

AO4

VMR

FSIGN

NO

TE 3

L2

RSG

V

LS

H

D1

FSF

54L1N

OTE

3

ALS

PS

103 6 8

IIC

D D C

L2

T1CO

MP

T2

SUPP

LY V

OLT

AGE C

M

L1

CC

T3

460/

575/

3/60

CC

CC

BI4

460/

575/

3/60

460/

575/

3/60

SEE

NO

TE 5

RCC

FFC

CFS

L3

VMR

31

VM

31

12

OAR

HCO

2

SPC

TEM

PCO

M

SENS

OR

OFF

SET

SPCR

H

CS

BC1PM

BC2

BC2

SD

EMBC

1

BC1

BC1

BC2

Page 32: DCG Commercialwebtest.daikinac.com/content/assets/LightCommercial... · 2017. 8. 16. · •ase Monitor: Phase monitor (3 phase only), available for 3 - 25 ton DS, DC and DT series

32 www.daikinac.com SS-DCG3

Accessories

Daikin MasterItem # Description Fits

Model SizesField-

InstalledFactory-Installed

Operating Weight (lbs)

Curb14CURB3672B 14” Roof Curb 3-6 tons √ 86

18CURB3672B 18” Roof Curb 3-6 tons √ 100

24CURB3672B 24” Roof Curb 3-6 tons √ 128

GHRC-3672 Hurricane Restraint Clips 3-6 tons √ 2

Ultra Low-Leak Economizer & Power Exhaust110-365-09C Ultra Low-Leak Downflow Economizer w/ Dry Bulb 3-6 tons √ 71

10-366-09C Ultra Low-Leak Downflow Economizer w/ Enthalpy 3-6 tons √ √ 71

10-395-09 Ultra Low-Leak Horizontal Economizer w/ Dry Bulb 3-6 tons √ 71

10-396-09 Ultra Low-Leak Horizontal Economizer w/ Enthalpy 3-6 tons √ 71

10-455-09*-23 Centrifugal Power Exhaust 230v 3-6 tons √ 55

10-455-09*-33 Centrifugal Power Exhaust 460v 3-6 tons √ 55

10-455-09*-43 Centrifugal Power Exhaust 575v 3-6 tons √ 55

10-457-09xA-23 Modulating Power Exhaust 208-230v 3-6 tons √ 55

10-457-09xA-33 Modulating Power Exhaust 460v 3-6 tons √ 55

10-465-09-21 Prop Power Exhaust 230v 3-6 tons √ 55

10-465-09-31 Prop Power Exhaust 460v 3-6 tons √ 55

10-465-09-41 Prop Power Exhaust 575v 3-6 tons √ 55

Low-Leak Economizer & Power Exhaust2DDNECNJ3672C Low-Leak Downflow Economizer 3-6 tons √ √ 82

DPE36722 Downflow Power Exhaust (208/230 Volt) 3-6 tons √ 55

DPE36724 Downflow Power Exhaust (460 Volt) 3-6 tons √ 55

DPE36727 Downflow Power Exhaust (575v) 3-6 tons √ 55

DHZECNJ3672 Horizontal Economizer 3-6 tons √ 70

DHPE36722 Horizontal Power Exhaust (208/230 Volt) 3-6 tons √ 55

DHPE36724 Horizontal Power Exhaust (460 Volt) 3-6 tons √ 55

DHPE36727 Horizontal Power Exhaust (575 Volt) 3-6 tons √ 55

Downflow AccessoriesD25FD3672 25% Manual Fresh Air Damper 3-6 tons √ 12

D25MFD3672 25% Motorized Fresh Air Damper 3-6 tons √ 16

DDNBBS3672 Burglar Bar Sleeves with Supply & Return 3-6 tons √ 30

DDNECNJ3672NR Downflow Economizer2 w/o Barometric Relief 3-6 Tons √ 77

DDNSQRD3616 Downflow Square-to-Round Adapter (16” Round) 3 tons √ 45

DDNSQRD487218 Downflow Square-to-Round Adapter (18” Round) 4-6 tons √ 35

Horizontal AccessoriesDBRD3672 Barometric Relief Damper 3-6 tons √ 15

Concentrics

CDK36 Concentric Duct Kit 3 tons √ 27

CDK4872 Concentric Duct Kit 4-6 tons √ 27

DDC Accessories3DDC communicating controller (built-in BACnet® MS/TP) includes Standard Room Sensor to be installed in field

3-6 tons √ 2

Page 33: DCG Commercialwebtest.daikinac.com/content/assets/LightCommercial... · 2017. 8. 16. · •ase Monitor: Phase monitor (3 phase only), available for 3 - 25 ton DS, DC and DT series

SS-DCG3 www.daikinac.com 33

Accessories

Daikin MasterItem # Description Fits

Model SizesField-

InstalledFactory-Installed

Operating Weight (lbs)

10366D09C DDC Ultra Low-Leak Downflow Economizer 3-6 tons √ √ 71

10366D09 DDC Ultra Low-Leak Horizontal Economizer 3-6 tons √ 71

10465DDC Power Exhaust kit used with DDC Ultra Low-Leak Economizer

3-6 tons √ 1

DLAKT01 Low-Ambient 3-6 tons √ √ 2

LONKT01 LonWorks® card 3-6 tons √ 1

3PMK01 Phase Monitor (3-Phase Only) 3-6 tons √ √ 2

DFSKT01 Dirty Filter Switch 3-6 tons √ 1

High-Static Kits4HSKT036B High-Static Kit (230/460v) 3 tons √ √ 41

HSKT036B-7 High-Static Kit (575v) 3 tons √ √ 5

HSKT048B High-Static Kit (230/460v) 4 tons √ √ 38

HSKT048B-7 High-Static Kit (575v) 4 tons √ √ 27

HSKT060B High-Static Kit (230/460v) 5 tons √ √ 38

HSKT060B-7 High-Static Kit (575v) 5 tons √ √ 28

HSKT072B High-Static Kit (230/460v) 6 tons √ √ 38

HSKT072B-7 High-Static Kit (575v) 6 tons √ √ 15

Crankcase Heater Kits0163R00002S 40W 230V 3 tons √ 1

0163R00031S 40W 460V 3 tons √ 1

0163R00032S 40W 575V 3 tons √ 1

0130L00017S 70W 230V 4 - 6 tons √ 1

0130L00018S 70W 460V 4 - 6 tons √ 1

0130L00019S 70W 575V 4 - 6 tons √ 1

High Efficiency Filters0160L00203 High Efficiency MERV 13 Air Filter Nom.

Size: 24x24x2; (Order Qty 1)3 tons √ 2

0160L00204 High Efficiency MERV 13 Air Filter Nom. Size: 14x20x2; (Order Qty 4)

4 tons √ 4

0160L00205 High Efficiency MERV 13 Air Filter Nom. Size: 16x20x2; (Order Qty 4)

5 & 6 tons √ 4

Misc AccessoriesHAILGD03D Condenser Coil Hail Guard 3-5 tons √ 19

HAILGD04D Condenser Coil Hail Guard 6 tons √ 22

Convenience Outlet: Non Powered 3-6 Tons √ 2

Convenience Outlet: Powered 3-6 Tons √ 42

Disconnect Switch 3-6 Tons √ 5

HA-02 High-Altitude Kit 3-6 tons √ 1

LAKT12 Low Ambient Kit, 208-230V - non-DDC 3-6 tons √ √ 14

LAKT15 Low Ambient Kit, 460V - non-DDC 3-6 tons √ √ 14

LAKT16 Low Ambient Kit, 575V - non-DDC 3-6 tons √ √ 14

Page 34: DCG Commercialwebtest.daikinac.com/content/assets/LightCommercial... · 2017. 8. 16. · •ase Monitor: Phase monitor (3 phase only), available for 3 - 25 ton DS, DC and DT series

34 www.daikinac.com SS-DCG3

Our continuing commitment to quality products may mean a change in specifications without notice. © 2017 • Houston, Texas • Printed in the USA.

Accessories

Daikin MasterItem # Description Fits

Model SizesField-

InstalledFactory-Installed

Operating Weight (lbs)

LPM-07 LP Conversion Kit (For DCG036045 unit only) 3 Ton √ 1

LPM-08 LP Conversion Kit 3-6 Ton √ 1

3PMNDK01 Phase Monitor - Non DDC 3-6 tons √ √ 2

Smoke Detector (supply and/or return air) 3-6 tons √ 11

Hinged Panels 3-6 tons √ 101 Use Economizer & Power Exhaust listed within Ultra Low-Leak section 2 Use Economizer & Power Exhaust listed within Low-Leak section 3 For a full list of DDC accessories, please refer to DDC Controller Technical Guide manual (DK-DDC-TGD-01B)4 HSKT High-Static Kits are for use with standard single-speed belt-drive units only.

Note: Where multiple variations are available, the heaviest combination is listed.