DCCD - FLAME RETARDANT LOW SMOKE LABORATORY
DCCD Home
Electric cables are designed to carry power and communications for long
distances and can act as pathway along which fire can travel and spread. In addition
there are cable installations where large number of cables are installed vertically.
These can act as an area of significant fire hazard because of the medium of high fuel
loading represented by the insulating and sheathing materials. Fires involving these
cables may cause the loss of life as well as damage to the facilities and equipment. In
order to avoid such disasters the demand has arisen for improved flame-retardant
cables to reduce not only flame propagation but also smoke and toxic emission.
The Flame retardant low smoke cables laboratory carryout fire reaction tests on
electric cables and all polymeric materials according to various national and
International standards.
Test facilities at FRLS lab
TESTING/EQUIPMENT FACILITY :-
Some of the important test facilities are
Cone Calorimeter
Toxicity chamber
NBS Smoke Box Chamber
3 metre cube test chamber
Limiting Oxygen Index apparatus
HCl Emission apparatus
Fire Resistance test set-up
Test using Cone calorimeter
ACCREDITATIONS : -
The facility has been accredited for Flame Retardant Low Smoke testing as per
ISO/IEC 17025 by National Accreditation Board for Testing and Calibration
Laboratories (NABL) Govt of India.
TEST FACILITIES :-
Products/Apparatus Tests Conducted
§ Electric cables
§ Cable sheath materials
§ FRP composite materials
§ Cable trays
§ Channels
§ Feeder pillar boxes
§ Energy meter covers
§ Terminal blocks
§ Bushings
§ Supporting insulators
§ PVC conduit pipes
§ Flooring materials
§ Fabrics/curtain
§ Materials used in
aerospace/navy
§ Any other plastic material
Heat release measurements using Cone
Calorimeter
Toxicity Index test
Limiting Oxygen Index (Ignition property
of Plastics )
Temperature Index (Temp withstand
before ignition)
HCL (Acid gas content in plastics )
Zero Halogen evaluation
Smoke Density ( smoke evolved, and
light transmission, visibility under fire)
Fire resistance test (Circuit integrity
under fire conditions)
Flammability Test (The property of
propagating fire)
The lab will be augmented shortly for tests on Bunched cables.
FRLS TEST FACILITIES :-
Test Standard
(HRR) Heat Release Rate, Cumulative heat
released,
Effective heat combustion, Time to ignition,
ISO 5660
ASTM 1354
Mass loss rate, total mass loss, Smoke
obscuration
CO/CO2 production rate
Oxygen Index Test on Polymeric materials and
cable sheaths
ASTM D 2863-1997
NCD 1410
IS 10810(P-58)-1988
IS 13501-1992
Temperature Index Test on Polymeric materials
and cable sheaths
ASTM D 2863-1997
Halogen Acid Test on Polymeric materials and
cable sheaths
IEC 754(P-1)-1994
Flammability Test on Polymeric materials and
cable sheaths
UL 94-HB/VB-1980
ASTM D 635-1998
IS 11731(P-1,2)-1986
IS 6746-1972
Flammability Test on cables IS 10810(P-61)-1988
UL 1581-1991
IEC 332(P-1)-1979
IS 10810(P-53)-1984
IEC 332(P-3)-1991
IS 10810(P-62)-1993
IEEE 383-1974
Smoke density test on Polymeric materials and
cable sheaths
ASTM D 2843-1999
Smoke density test (3 Metre cube) on cables IEC 1034-2 1991
IS 10810 (P-63)-1993
Specific Optical density(NBS smoke box) on
Polymeric materials and cable sheaths
ASTM E-662-1983
NCD 1411
Fire survival Test on cables IEC 331 1970
CLIENTELE :-
Facilities are extensively used by Industrial Clients like RDSO, ICF, Tyco
Electronics, Lapp India, Reliance Engineers, Nicco Corporation, Whirlpool of India Ltd,
BIS and other utilities and manufacturers. Clients from countries like Dubai, UAE, etc.
are also widely using the test facilities
Products Wise Testing :
Protocol Test:
Energy Meter Data Concentrator IED Relay Protocol Convertor RTU
(The above Equipments are tested at ITID-Bangalore)
Cable Test :
Paper/PVC/XLPE/EPR Power cables of Voltage rating up to 220 kV Cable accessories, etc
(The above Equipments are tested at DCCD- Bangalore, STDS-Bhopal, and RTL-Noida)
Capacitor Test:
HV Shunt capacitors
HV Series capacitors
HV Capacitors for surge
LV Motor capacitors
LV fan motor Capacitors
LV Capacitors for Lighting
LV Power capacitors of self-healing type.
LV Shunt capacitors of non self - healing type.
(The above Equipments are tested at DCCD- Bangalore, STDS-Bhopal, and RTL-Noida)
Flame Retardant Low Smoke Test :
Electric cables
Cable sheath materials
FRP composite materials
Cable trays
Channels
Feeder pillar boxes
Energy meter covers
Terminal blocks
Bushings
Supporting insulators
PVC conduit pipes
Flooring materials
Fabrics/curtain
Materials used in aerospace/navy
Any other plastic material
(The above Equipments are tested at DCCD- Bangalore)
Temperature Rise Test :
Distribution, Transmission & Power equipment and accessories
Diagnostics Test on,
Power Transformer
Generators / Large motors
Power cables
EHV CTs, / CVTs
Resin Cast CTs
(The above Equipments are tested at DCCD- Bangalore)
High Power Test :
High voltage circuit breakers
High Voltage Switches
High Voltage Fuses
High Voltage Switch Boards
Terminal Boxes
MV Metal enclosed Switchgear
Power Transformers
Distribution Transformers
Traction Transformers
Potential Transformers
Current Transformers
Lightning Arresters
Insulator Strings
AC metal enclosed switch gear & control gear.
AC Disconnectors & Earth switches
Reactors
Line traps
Bus ducts, Bus bars, Generator Neutral Bus bar Compartment
Power connectors, ACSR conductors
LV Circuit Breaker
(The above Equipments are tested at HPL- Bangalore, STDS-Bhopal, and SCL-Bangalore)
Insulation / Impulse voltage Withstand Test :
Insulator ( Disc, Pin, Solid Core, Hollow)
Insulator Strings (all types)
Lightning Arrestor Housing & similar Insulating Materials
Battery Container
Rubber Mats
Insulating Tubes etc. Insulating Rod Isolator, Circuit Breaker Bus duct Cables Bushing AB Switch Panel P T /C V T / Coupling Capacitor/ Grading Capacitor / R.V.T.S / CT-PT Units Tap changer Voltage / Current / Power / Distribution Transformers Reactors HT Capacitors Thyristor Valves
(The above Equipments are tested at HV- Bangalore, STDS-Bhopal, UHVRL-Hyderabad and RTL-Noida)
Short Circuit / High Voltage / Synthetic Test :
Circuit Breakers (LV, HV)
Fuses
Switches
Starters
Control Switches
MCB / RCCB Switch Fuse units
Power Connectors
Spacers
Bus bars
Bus ducts
CT's conductors
Transformer
P T /C V T / Coupling /Tap Changers
Capacitors
Grading Capacitors
R.V.T.S
C.T – PT UNITS
Series & Shunt Reactors
Line Traps
Damping Reactors Tuning Reactors
Neutral Earthing Reactors
THYRISTOR VALVES
H.V. Circuit Breaker & Switchgear Panel with Circuit Breaker
HT switches/ Line sectionalizer
Isolators
Power & Distribution transformers & Traction transformers
HT fuses
Surge arresters
Reactors
Auto-reclosures
DC Breakers
HT switchgear panel
Motor terminal box
Spacers for Bundled conductor
HV Contactors
LT Air circuit breakers, MCCBs for voltage not exeeding 1000V
Circuit Breakers for Over current protection for household & similar installations
Miniature circuit breakers (MCB)
Low voltage fuses for voltage not exceeding 1000V
Low voltage fuse bases for voltage not exceeding 1000V
Air break switches, Air break disconnectors, air break switch disconnectors, fuse combinations
for voltage not exceeding 1000V
Carrier & Bases for Rewirable type fuses
Composite unit of air break switches for rewirable type switches for voltage not exceeding
650V, AC21, 100A
AC Miniature circuit breaker boards 1000V
Residual current operated circuit breaker
Factory build assemblies of switchgear & controlgears for 1000V
For enclosed distribution board & cutouts 1000V
Contactors & motor starters for voltages at exceeding 1000V
Electric power connectors above 200A
(The above Equipments are tested at HPL- Bangalore, STDS-Bhopal, and SCL-Bangalore)
Dielectric Materials Test :
Lubricating Oil
Transformer Oil
Polymers etc.
(The above Tests are Conducted at DMD- Bangalore)
Materials Test :
Coal
Analysis of coal, ash and water for thermal power stations
Lubrication oil and all other materials.
(The above Tests are Conducted at MTL- Bangalore)
Structural / Mechanical strength/ Vibration Test :
Transmission line towers
Line material
Transmission Line Conductors upto and including 800kV rating
Compression Clamps
Mid Span Joints
I&V Suspension Tension Strings upto and including 800kV rating
Structural Steel
Steel Wire ropes
Electrically Operated/ Hand Operated Winches
Chain Pulley Block upto 20 Tonnes
Load Cell
Line Material
Terminal Clamp
Structural Steel
Connecting Links for Brake Parachute/ Nylon Purchase Tape
Insulators & Insulator Strings of Single/ Twin/ Triple/ Quad-Tension or Suspension type upto and
including 800kV rating
Vibration Dampers upto and including 800kV
Spacer/ Spacer Dampers upto and including 800kV.
Transmission Line Conductors upto and including 800kV rating
Vibration Dampers upto and including 800kV
Spacer/ Spacer Dampers upto and including 800kV.
Transmission Line Conductors upto and including 800kV rating
Conductors
(These Products are tested at MED- Bangalore)
Seismic Qualification / Vibrations Test :
Energy Meter
Switchgear, Control Panel
All Equipments up to 10 Tons.
(The above Tests are Conducted at EVRC- Bangalore)
Calibration Tests :
Digital & Analog Voltmeters
Digital & Analog Ammeters
Multimeters
Digital & Analog Wattmeters
Digital Temperature indicators
Digital & Analog Panel meters
Electronic Thermometers
Data Loggers
Strip chart recorders
Power harmonic analysers
Process calibrators
Hot & Cold temperature baths
Current Clamps
Thermometers
Impulse measuring system
(The above Equipments calibration tests are conducted at ID- Bangalore, STDS-Bhopal)
Test :
Relay
UPS (Uninterrupted Power Supply) (1 KVA - 10 KVA & above)
Single Phase Electromechanical / kWh / Static / Electronic Energy Meters
Three Phase Four Wire / Three Phase Three Wire Electromechanical / kWh / TVM Static /
Electronic Energy Meters
Single phase / Three phase Static watt-hour meters
Electronic Trivector meters
Static protective relays
Smaller size UPS, SMPS, Inverters, Converters, Contactors etc
All Electronic equipments, like Static Relays, Breakers, contactors, starters, Electronic ballast,
Medical equipments
(The above Equipments are tested at ID- Bangalore, STDS-Bhopal)
Battery Testing :
Lead acid storage Batteries, VRLA, LMLA, NICAD Batteries, Tubular Batteries
(The above Tests are Conducted at EATD-Bangalore)
Flame Proof Testing :
All flame proof electrical equipment
(The above Tests are Conducted at EATD-Bangalore)
Ingress Protection Test:
All types of electrical equipment enclosures such as- Outdoor distribution boards Relay units/Panels Control Cubicles for PCVCB Switching & Control System enclosures RMV panels HT Metering & Switching Panel AC Distribution Board EWM Enclosures Platform Power Supply LT Panel Disconnecting Switch Assembly Junction Boxes LV switch Board AD/DC Panel weatherproof Switch Enclosures Dry type Transformer enclosures PCC Panel, MCC Panel, Bus Ducts DOL Starters Integral Starter Control Panel Electricity Metering Equipment Enclosures Actuators Telecommunication Equipment Enclosures Antennas
Cable Connector Assembly GPRS Equipment Enclosures Battery Charger Panels Medical Health Monitoring Equipment Enclosures Drive Mechanism Box Marshalling Kiosks Surge Monitors MOM's Belt sway Switch Enclosures Reactor assembly Enclosures Starter Motors Sot Starter Panels RAPCONS BAPCONS
Rotating Electrical Machinery Equipment Enclosures such as :
Enclosures of Induction Motors Valve Actuators DC Machines AC Machines Alternators Generators Vibratory Electric Motors Large Motors Automobile Electrical Motors Traction Motors Power Tool Motors Pumps (motors) Etc.
Luminaries and Light Fitting Equipment Enclosures such as :
Street light Fitting Enclosures Aviation Light Fitting Enclosures Domestic Industrial Light Fitting Enclosures Corridor/ Office Light Fitting Enclosures
Solar Operated Light Fitting Enclosures Etc.
(The above Tests are Conducted at EATD-Bangalore, STDS-Bhopal)
Luminaries :
Tubular fluorescent lamps with Starter
Self Ballasted Lamps for General Lighting Service (CFL)
Safety requirements and Performance requirements
Lamp Ballast
(The above Tests are Conducted at EATD-Bangalore)
Fan Testing :
Electrical Ceiling Fans and Regulator
Electrical Table Type Fans and Regulator
Electrical Pedestal Type Fans and Regulators
Propeller Type AC Ventilating Fans
(The above Tests are Conducted at EATD-Bangalore)
Refrigerators :
Direct cool and frost free refrigerators up to 600 lts. capacity.
(The above Tests are Conducted at EATD-Bangalore)
Air Conditioners :
Window air conditioner and split type air conditioner up to 3 TR.
(The above
Products Wise Testing :
Protocol Test:
Energy Meter Data Concentrator IED Relay Protocol Convertor RTU
(The above Equipments are tested at ITID-Bangalore)
Cable Test :
Paper/PVC/XLPE/EPR Power cables of Voltage rating up to 220 kV Cable accessories, etc (The above Equipments are tested at DCCD- Bangalore, STDS-Bhopal, and RTL-Noida)
Capacitor Test:
HV Shunt capacitors
HV Series capacitors
HV Capacitors for surge
LV Motor capacitors
LV fan motor Capacitors
LV Capacitors for Lighting
LV Power capacitors of self-healing type.
LV Shunt capacitors of non self - healing type.
(The above Equipments are tested at DCCD- Bangalore, STDS-Bhopal, and RTL-Noida)
Flame Retardant Low Smoke Test :
Electric cables
Cable sheath materials
FRP composite materials
Cable trays
Channels
Feeder pillar boxes
Energy meter covers
Terminal blocks
Bushings
Supporting insulators
PVC conduit pipes
Flooring materials
Fabrics/curtain
Materials used in aerospace/navy
Any other plastic material
(The above Equipments are tested at DCCD- Bangalore)
Temperature Rise Test :
Distribution, Transmission & Power equipment and accessories
Diagnostics Test on,
Power Transformer
Generators / Large motors
Power cables
EHV CTs, / CVTs
Resin Cast CTs
(The above Equipments are tested at DCCD- Bangalore)
High Power Test :
High voltage circuit breakers
High Voltage Switches
High Voltage Fuses
High Voltage Switch Boards
Terminal Boxes
MV Metal enclosed Switchgear
Power Transformers
Distribution Transformers
Traction Transformers
Potential Transformers
Current Transformers
Lightning Arresters
Insulator Strings
AC metal enclosed switch gear & control gear.
AC Disconnectors & Earth switches
Reactors
Line traps
Bus ducts, Bus bars, Generator Neutral Bus bar Compartment
Power connectors, ACSR conductors
LV Circuit Breaker
(The above Equipments are tested at HPL- Bangalore, STDS-Bhopal, and SCL-Bangalore)
Insulation / Impulse voltage Withstand Test :
Insulator ( Disc, Pin, Solid Core, Hollow)
Insulator Strings (all types)
Lightning Arrestor Housing & similar Insulating Materials
Battery Container
Rubber Mats
Insulating Tubes etc. Insulating Rod Isolator, Circuit Breaker Bus duct Cables Bushing AB Switch Panel P T /C V T / Coupling Capacitor/ Grading Capacitor / R.V.T.S / CT-PT Units Tap changer Voltage / Current / Power / Distribution Transformers Reactors HT Capacitors Thyristor Valves
(The above Equipments are tested at HV- Bangalore, STDS-Bhopal, UHVRL-Hyderabad and RTL-Noida)
Short Circuit / High Voltage / Synthetic Test :
Circuit Breakers (LV, HV)
Fuses
Switches
Starters
Control Switches
MCB / RCCB Switch Fuse units
Power Connectors
Spacers
Bus bars
Bus ducts
CT's conductors
Transformer
P T /C V T / Coupling /Tap Changers
Capacitors
Grading Capacitors
R.V.T.S
C.T – PT UNITS
Series & Shunt Reactors
Line Traps
Damping Reactors Tuning Reactors
Neutral Earthing Reactors
THYRISTOR VALVES
H.V. Circuit Breaker & Switchgear Panel with Circuit Breaker
HT switches/ Line sectionalizer
Isolators
Power & Distribution transformers & Traction transformers
HT fuses
Surge arresters
Reactors
Auto-reclosures
DC Breakers
HT switchgear panel
Motor terminal box
Spacers for Bundled conductor
HV Contactors
LT Air circuit breakers, MCCBs for voltage not exeeding 1000V
Circuit Breakers for Over current protection for household & similar installations
Miniature circuit breakers (MCB)
Low voltage fuses for voltage not exceeding 1000V
Low voltage fuse bases for voltage not exceeding 1000V
Air break switches, Air break disconnectors, air break switch disconnectors, fuse combinations
for voltage not exceeding 1000V
Carrier & Bases for Rewirable type fuses
Composite unit of air break switches for rewirable type switches for voltage not exceeding
650V, AC21, 100A
AC Miniature circuit breaker boards 1000V
Residual current operated circuit breaker
Factory build assemblies of switchgear & controlgears for 1000V
For enclosed distribution board & cutouts 1000V
Contactors & motor starters for voltages at exceeding 1000V
Electric power connectors above 200A
(The above Equipments are tested at HPL- Bangalore, STDS-Bhopal, and SCL-Bangalore)
Dielectric Materials Test :
Lubricating Oil
Transformer Oil
Polymers etc.
(The above Tests are Conducted at DMD- Bangalore)
Materials Test :
Coal
Analysis of coal, ash and water for thermal power stations
Lubrication oil and all other materials.
(The above Tests are Conducted at MTL- Bangalore)
Structural / Mechanical strength/ Vibration Test :
Transmission line towers
Line material
Transmission Line Conductors upto and including 800kV rating
Compression Clamps
Mid Span Joints
I&V Suspension Tension Strings upto and including 800kV rating
Structural Steel
Steel Wire ropes
Electrically Operated/ Hand Operated Winches
Chain Pulley Block upto 20 Tonnes
Load Cell
Line Material
Terminal Clamp
Structural Steel
Connecting Links for Brake Parachute/ Nylon Purchase Tape
Insulators & Insulator Strings of Single/ Twin/ Triple/ Quad-Tension or Suspension type upto
and including 800kV rating
Vibration Dampers upto and including 800kV
Spacer/ Spacer Dampers upto and including 800kV.
Transmission Line Conductors upto and including 800kV rating
Vibration Dampers upto and including 800kV
Spacer/ Spacer Dampers upto and including 800kV.
Transmission Line Conductors upto and including 800kV rating
Conductors
(These Products are tested at MED- Bangalore)
Seismic Qualification / Vibrations Test :
Energy Meter
Switchgear, Control Panel
All Equipments up to 10 Tons.
(The above Tests are Conducted at EVRC- Bangalore)
Calibration Tests :
Digital & Analog Voltmeters
Digital & Analog Ammeters
Multimeters
Digital & Analog Wattmeters
Digital Temperature indicators
Digital & Analog Panel meters
Electronic Thermometers
Data Loggers
Strip chart recorders
Power harmonic analysers
Process calibrators
Hot & Cold temperature baths
Current Clamps
Thermometers
Impulse measuring system
(The above Equipments calibration tests are conducted at ID- Bangalore, STDS-Bhopal)
Test :
Relay
UPS (Uninterrupted Power Supply) (1 KVA - 10 KVA & above)
Single Phase Electromechanical / kWh / Static / Electronic Energy Meters
Three Phase Four Wire / Three Phase Three Wire Electromechanical / kWh / TVM Static /
Electronic Energy Meters
Single phase / Three phase Static watt-hour meters
Electronic Trivector meters
Static protective relays
Smaller size UPS, SMPS, Inverters, Converters, Contactors etc
All Electronic equipments, like Static Relays, Breakers, contactors, starters, Electronic ballast,
Medical equipments
(The above Equipments are tested at ID- Bangalore, STDS-Bhopal)
Battery Testing :
Lead acid storage Batteries, VRLA, LMLA, NICAD Batteries, Tubular Batteries
(The above Tests are Conducted at EATD-Bangalore)
Flame Proof Testing :
All flame proof electrical equipment
(The above Tests are Conducted at EATD-Bangalore)
Ingress Protection Test:
All types of electrical equipment enclosures such as- Outdoor distribution boards Relay units/Panels Control Cubicles for PCVCB Switching & Control System enclosures RMV panels HT Metering & Switching Panel AC Distribution Board EWM Enclosures Platform Power Supply LT Panel Disconnecting Switch Assembly Junction Boxes LV switch Board AD/DC Panel weatherproof Switch Enclosures Dry type Transformer enclosures PCC Panel, MCC Panel, Bus Ducts DOL Starters Integral Starter Control Panel Electricity Metering Equipment Enclosures Actuators Telecommunication Equipment Enclosures Antennas Cable Connector Assembly GPRS Equipment Enclosures Battery Charger Panels Medical Health Monitoring Equipment Enclosures Drive Mechanism Box Marshalling Kiosks Surge Monitors MOM's Belt sway Switch Enclosures Reactor assembly Enclosures Starter Motors Sot Starter Panels RAPCONS BAPCONS
Rotating Electrical Machinery Equipment Enclosures such as :
Enclosures of Induction Motors Valve Actuators DC Machines AC Machines Alternators Generators Vibratory Electric Motors Large Motors Automobile Electrical Motors Traction Motors Power Tool Motors
Pumps (motors) Etc.
Luminaries and Light Fitting Equipment Enclosures such as :
Street light Fitting Enclosures Aviation Light Fitting Enclosures Domestic Industrial Light Fitting Enclosures Corridor/ Office Light Fitting Enclosures
Solar Operated Light Fitting Enclosures Etc.
(The above Tests are Conducted at EATD-Bangalore, STDS-Bhopal)
Luminaries :
Tubular fluorescent lamps with Starter
Self Ballasted Lamps for General Lighting Service (CFL)
Safety requirements and Performance requirements
Lamp Ballast
(The above Tests are Conducted at EATD-Bangalore)
Fan Testing :
Electrical Ceiling Fans and Regulator
Electrical Table Type Fans and Regulator
Electrical Pedestal Type Fans and Regulators
Propeller Type AC Ventilating Fans
(The above Tests are Conducted at EATD-Bangalore)
Refrigerators :
Direct cool and frost free refrigerators up to 600 lts. capacity.
(The above Tests are Conducted at EATD-Bangalore)
DCCD - FLAME RETARDANT LOW SMOKE LABORATORY
DCCD Home
Electric cables are designed to carry power and communications for long
distances and can act as pathway along which fire can travel and spread. In addition
there are cable installations where large number of cables are installed vertically.
These can act as an area of significant fire hazard because of the medium of high fuel
loading represented by the insulating and sheathing materials. Fires involving these
cables may cause the loss of life as well as damage to the facilities and equipment. In
order to avoid such disasters the demand has arisen for improved flame-retardant
cables to reduce not only flame propagation but also smoke and toxic emission.
The Flame retardant low smoke cables laboratory carryout fire reaction tests on
electric cables and all polymeric materials according to various national and
International standards.
Test facilities at FRLS lab
TESTING/EQUIPMENT FACILITY :-
Some of the important test facilities are
Cone Calorimeter
Toxicity chamber
NBS Smoke Box Chamber
3 metre cube test chamber
Limiting Oxygen Index apparatus
HCl Emission apparatus
Fire Resistance test set-up
Test using Cone calorimeter
ACCREDITATIONS : -
The facility has been accredited for Flame Retardant Low Smoke testing as per
ISO/IEC 17025 by National Accreditation Board for Testing and Calibration
Laboratories (NABL) Govt of India.
TEST FACILITIES :-
Products/Apparatus Tests Conducted
§ Electric cables
§ Cable sheath materials
§ FRP composite materials
§ Cable trays
§ Channels
§ Feeder pillar boxes
§ Energy meter covers
§ Terminal blocks
§ Bushings
§ Supporting insulators
§ PVC conduit pipes
§ Flooring materials
§ Fabrics/curtain
§ Materials used in
aerospace/navy
§ Any other plastic material
Heat release measurements using Cone
Calorimeter
Toxicity Index test
Limiting Oxygen Index (Ignition property
of Plastics )
Temperature Index (Temp withstand
before ignition)
HCL (Acid gas content in plastics )
Zero Halogen evaluation
Smoke Density ( smoke evolved, and
light transmission, visibility under fire)
Fire resistance test (Circuit integrity
under fire conditions)
Flammability Test (The property of
propagating fire)
The lab will be augmented shortly for tests on Bunched cables.
FRLS TEST FACILITIES :-
Test Standard
(HRR) Heat Release Rate, Cumulative heat
released,
Effective heat combustion, Time to ignition,
ISO 5660
ASTM 1354
Mass loss rate, total mass loss, Smoke
obscuration
CO/CO2 production rate
Oxygen Index Test on Polymeric materials and
cable sheaths
ASTM D 2863-1997
NCD 1410
IS 10810(P-58)-1988
IS 13501-1992
Temperature Index Test on Polymeric materials
and cable sheaths
ASTM D 2863-1997
Halogen Acid Test on Polymeric materials and
cable sheaths
IEC 754(P-1)-1994
Flammability Test on Polymeric materials and
cable sheaths
UL 94-HB/VB-1980
ASTM D 635-1998
IS 11731(P-1,2)-1986
IS 6746-1972
Flammability Test on cables IS 10810(P-61)-1988
UL 1581-1991
IEC 332(P-1)-1979
IS 10810(P-53)-1984
IEC 332(P-3)-1991
IS 10810(P-62)-1993
IEEE 383-1974
Smoke density test on Polymeric materials and
cable sheaths
ASTM D 2843-1999
Smoke density test (3 Metre cube) on cables IEC 1034-2 1991
IS 10810 (P-63)-1993
Specific Optical density(NBS smoke box) on
Polymeric materials and cable sheaths
ASTM E-662-1983
NCD 1411
Fire survival Test on cables IEC 331 1970
DCCD - HEAT RUN TEST LABORATORY
DCCD Home
Temperature rise test upto 3200 Amps Milli volt drop & resistance tests
(wherever applicable) from 1.o micro ohms to 20 kilo Ohms can be conducted on the
following equipment, as per Indian (BIS) IEC, ANSI of ASTA standards.
Pantograph Isolator
Isolated Phase BusDuct L.T Busduct
TEMPERATURE RISE TEST ON VARIOUS PRODUCTS :-
The Laboratory has facility to carry out Temperature rise test on Distribution,
Transmission & Power equipment and accessories as per relevant National &
International Specifications.
TESTING FACILITY FOR TEMPERATURE RISE TEST :-
Current source upto 3200 Amperes , 20 Volts, Three Phase and Neutral
DC Source 500 Amperes, 200 Volts
Temperature Monitoring equipment: Digital & Fiber Optics
Micro Ohm Meters
Milli Voltmeter/ Multimeter
On Load Tap Changer Circuit Breaker
Current Transformer Feeder Pillar
TEMPERATURE RISE TEST ON VARIOUS PRODUCTS :-
The facilities of Heat Run test laboratory, are being extensively used for testing
& certification, on number of Distribution, Transmission & Power equipment and
accessories. Apart from this the facilities are also used for product development,
mainly by manufacturers.
ACCREDITATION :-
The facility has been accredited for electrical testing as per ISO / IEC 17025 by
National Accreditation Board for testing and Calibration Laboratories (NABL), Govt. of
India and signatory to International Laboratory Accreditation Cooperation (ILCA)
Mutual Recognition Arrangement.
The facility is also been accredited by ASTA BEAB- UK, IECEE-CB –UK and BIS.
Feeder Piller L.T Panel Board
Outdoor Circuit Breaker SF6 Circuit Breker
TEMPERATURE RISE TEST ON VARIOUS PRODUCTS :-
TEST FACILITIES
Apparatus Type of Test Standard
Distribution Boards Temperature Rise upto
3200 A
IEC - 60439
Panel BoardTemperature Rise upto
3200 A
IS – 8623 / IEC 60439
Circuit BreakerTemperature Rise upto
3200 A
Resistance Measurement
IEC – 62271-100
IsolatorsTemperature Rise upto
3200 A
Resistance Measurement
IS-9921/ IEC – 62271-
200
Disconnect Switch-
HV
Temperature Rise upto
3200 A
Resistance Measurement
IEC – 60298
Current TransformerTemperature Rise upto
3200 A
Resistance Measurement
IS – 2705/ IEC – 60044
Busduct - HTTemperature Rise upto
3200 A
IS-8084
Busduct - LTTemperature Rise upto
3200 A
IS-8623 / IEC – 60439
Tap ChangerTemperature Rise upto
3200 A
IEC – 60214
Voltage TransformerTemperature Rise
Resistance Measurement
IS-3156
Power connectorTemperature Rise upto
3200 A
Resistance Measurement
IS-5561
LV FusesTemperature Rise upto
3200 A
IS-2086
AC Metal enclosed
Switchgear
Controlgear
Temperature Rise upto
3200 A
Resistance Measurement
IS-3427
HV Circuit BreakerTemperature Rise upto
3200 A
Resistance Measurement
IS – 13118 / IEC
62271-100
LV Circuit BreakerTemperature Rise upto
3200 A
Resistance Measurement
IS – 13947-2/ IEC
60947-2
RESEARCH:-
Facilities to undertake R & D, in the field of current carrying capabilities and its
effects on temperature rise on Switchgears, Panels, Distribution Boards, Bus duct
systems, disconnector Switches etc.
CONSULTANCY:-
Inspection of various equipment like switchgear, Control gear, Distribution Boards
Panels CTs, PTs, etc., for Temperature Rise performance, at the Manufacturers work,
as per relevant Specifications.
Mechanical Engineering Division
Upcoming Programmes
Two day workshop on ‘High Voltage
Testing & Measurement Techniques’- Sept 2-3, 2010
Five day Training Programme on ‘Test Facilities’- Sept 6-10, 2010
Five day residential Training Programme on ‘Protective Relays’ - Sept 13-17, 2010
Five day training programme on 'Real Time Digital Simulation of Power Systems' - Sept 21-25, 2010
view all programme
Central Power Research Institute (CPRI) is an autonomous society under Ministry of
Power, Government of India. Set up in 1960 by the Government of India, it functions as a
centre for applied research in electrical power engineering assisting the electrical industry in
product development, Consultancy and quality assurance. CPRI also serves as an independent
authority for testing and certification of power equipment. CPRI's governing body includes
eminent professionals from industries, utilities, prestigious academic and research institutions
and the government.
High Voltage Division :
Home
HV Division has dimension of 50(L)*40m(W)*35m(H) and an outdoor test bay which is equipped with
cascade transformer of two units, rated 600kV,2000kVA each. Facilities are available for taking supply in
to the main laboratory for indoor tests. A 600kV,2000kVA Power frequency testing transformer is located
indoor. Facilities for tensioning of horizontal insulator strings for conducting corona and RIV tests at
EHV/UHV test voltage are also available.
Laboratories Available :
High Voltage Laboratory
Impulse Current Laboratory
Pollution Laboratory
1200kv, 2 MVA Cascade Transformer
3 MV, 150 KJ Impulse Generator
Facilities Available for Testing :
Lightning impulse & switching impulse withstand and flashover tests both under dry and wet
conditions.
Power frequency voltage withstand & flashover test (Dry).
Power frequency voltage withstand & flashover test (Wet).
Visible corona inception/ extinction test with power frequency voltage under both dry and wet
conditions.
Radio interference voltage test under both wet and dry conditions.
Voltage distribution test on insulator strings.
Under oil puncture test on Disc, pin & post insulator units.
Steep front impulse puncture test on Disc, pin, & post insulator units.
Porosity tests on porcelain insulator fragments.
Temperature cycle tests on Disc, pin, & post insulator upto 33kV rating (indoor).
Dc withstand & flashover test under Dry and Wet conditions.
The tests are done as per National standards (IS) and International standards like BS, IEC,
ANSI etc.
It is worth mentioning here that the impulse and power frequency test facilities are of the
state of the art type and compare well with the facilities available at other International
laboratories like CESI, Italy, IREQ, Canada etc.
Further information contact us:
The Head of the Division
High Voltage Division
Central Power Research Institute
Prof. Sir C. V. Raman Road, P.B 8066,
Bangalore, India – 560 080.
Phone : +91-80-23601917(Off.)
E-mail : [email protected], [email protected]
High Voltage Division - Impulse Current Lab
HV Home
The Impulse Current Laboratory has been established in 1996 as a comprehensive test facility
considering the importance of ZnO arresters which are being increasingly used by several Utilities. Its
significance lies in the fact that, it has a unique Computer-controlled Impulse Current Generator
incorporating all conceivable features in a single consolidated design and is perhaps the only one of
its kind in this part of the world. All tests on ZnO blocks as per IEC 60099-4 and IS 3070 including
accelerated ageing test and loss measurement on ZnO blocks can be carried out.
Equipment available :
Impulse Current Generator 100 kV, 150 kJ
Types of Tests :
All type tests on Zno arrester blocks upto 11 kV As per National and International
Standards
Necessity Of Testing Arrester Blocks :
Lightning arresters, often called Surge Diverters, play a vital role in protecting expensive substation equipment from high voltage surges. These surge voltages originate from either switching operations of substation equipment or lightning strikes. In either case these over voltages have to be limited well below the insulation levels of the equipment. By R&D, new designs of lightning arresters have emerged, by which, it has become possible to bring down the insulation levels of the equipment resulting in significant savings to the power systems. Till recently gap type arresters were in use in the power system. Even in this type, new concepts were introduced in the design by which one to two step reduction of basic insulation level (BIL) of 145 and 220 kV systems were possible. These arresters are being now replaced by Zinc Oxide (ZnO) Gap-less arresters, (also known as Metal Oxide Surge Arresters). As reported in the literature, these were first developed in Japan and came into use from 1970. The replacement of conventional arresters by ZnO type initially started from system voltages above 145 kV class owing to their high initial cost. But now even distribution systems use ZnO arresters due to the present affordable cost. Considering the importance of tests on ZnO arresters which are being increasingly used by Powergrid, NTPC, State Electricity Boards and other power utilities. CPRI has established comprehensive test facility for undertaking tests on Zinc Oxide arresters as per IEC-60099-4 and other relevant standards. All tests prescribed by International/Indian Standards (IEC 60099-4) for Metal oxide arresters without gaps for AC systems can be undertaken. Following tests can be taken up with the newly commissioned Computer controlled Impulse Current Generator supplied by M/s. Haefely Trench, Switzerland with a capacity of 100 kV and 150 kJ
Residual Voltage Tests:
This test can be carried out for the following exponential waveforms:
a) Steep Current Impulse 1/<20 micro second.
Front time : 1 micro second ± 0.1 micro second.
Time to half value : <20 micro second.
Max. Current : 20 kA
Residual Voltage : Upto 40 kV
b) Lightning Current Impulse 8/20 micro second.
Front time : 8 micro second ± 1.0 micro second.
Time to half value : 20 micro second ±2.0 micro second.
Max. Current : 50 kA
Residual Voltage : Upto 50 kV
c) Switching Current Impulse 36/90 micro second.
Front time : > 30 micro second.
Time to half value : approx 2.5 T1.
Max. Current : 2 kA
Residual Voltage : Upto 30 kV
d) High Current Impulse 4/10 micro second
Front time : 4 micro second ± 0.5 micro second.
Time to half value : 10 micro second ± 1.0 micro second.
Max. Current : 120 kA
Residual Voltage : Upto 60 kV
Long duration rectangular Current Impulses : Transmission line class tests class I to V can be carried out as per IEC 60099-4.
Operating Duty Tests : Operating duty tests as per IEC 60099-4 can be carried out Power frequency voltage V/S Time curve : As per IEC 60099-4 can be carried out.
Ageing test : Ageing test can be carried out as per IEC 60099-4. The generator is exclusively designed as per the specifications drawn by CPRI. This is the first generator developed by M/s.Haefely with all the features combined in one and may be a unique generator in the world.
High Voltage Division - Impulse Current Lab
HV Home
The Impulse Current Laboratory has been established in 1996 as a comprehensive test facility
considering the importance of ZnO arresters which are being increasingly used by several Utilities. Its
significance lies in the fact that, it has a unique Computer-controlled Impulse Current Generator
incorporating all conceivable features in a single consolidated design and is perhaps the only one of its
kind in this part of the world. All tests on ZnO blocks as per IEC 60099-4 and IS 3070 including
accelerated ageing test and loss measurement on ZnO blocks can be carried out.
Equipment available :
High Voltage Division - Impulse Current Lab
HV Home
The Impulse Current Laboratory has been established in 1996 as a comprehensive test facility
considering the importance of ZnO arresters which are being increasingly used by several Utilities. Its
significance lies in the fact that, it has a unique Computer-controlled Impulse Current Generator
incorporating all conceivable features in a single consolidated design and is perhaps the only one of its
kind in this part of the world. All tests on ZnO blocks as per IEC 60099-4 and IS 3070 including
accelerated ageing test and loss measurement on ZnO blocks can be carried out.
Equipment available :
High Voltage Division - Pollution Laboratory
HV Home
The Pollution Laboratory has dimensions of 12M x 12M x 12M. An array of nozzles confirming to IEC specifications combined with a salt water pumping and air compressor provide the required salt fog. The power supply to the chamber is from one of the outdoor 600 kV, 2,000 kVA Cascade Transformers setup.
Pollution Test on InsulatorEquipment available :
600 kV, 3 Amperes AC source 100 kV, 6 Amperes AC source 150 kV, 1 Ampere DC source
With these equipment/facilities the Pollution Laboratory can carry out tests on insulators and insulator assemblies for systems upto and including 400 kV.
Types of Tests :
Pollution test on insulators by salt fog/solid layer method upto 400 kV AC & 150 kV DC SF6 Puncture withstand test facility for DC insulators Thermal runaway tests on insulators
This Laboratory can undertake these tests as per National & International Standards
Necessity Of Pollution Testing:
With the ever increasing demand for electrical power, there has been a steady growth in high voltage transmission lines required for optimum and economic transfer of large blocks of power over
long distances. As the level of transmission voltage is increased, switching and dynamic over voltages and withstand ability of the insulator under polluted conditions are important factors which determine the insulation level of the system. The reliability of the system mainly depends on the environmental and weather conditions which cause flashover on polluted insulators leading to system outages. It is generally recognized that the main events leading to flashover of polluted insulators under service voltage are the formation of a conductive layer on the insulator surface, leakage current surging with associated dry band formation and partial arc development and arc propagation along the insulator surface eventually spanning the whole insulator. The problem is more complex in case of DC systems because of large contamination due to electrostatic forces and longer duration of partial arc. Therefore the design of external insulation under polluted conditions is very critical and lot of investigations are under way to arrive at safe creepage distances for systems operating in different environments.
The pollution can be broadly classified into two types:
1. Marine pollution found in the immediate neighborhood of the sea and also at considerable distances from coast. 2. Industrial pollution caused by dust, smoke etcObjectives Pollution Investigation :
Collection of pollution flashover data under natural conditions Suitable artificial pollution test under conditions representing natural pollution Design of insulation for pollution conditions. Pollution ageing tests and investigation of causes of failures to arrive at suitable remedies. Pollution performance of composite insulators
Pollution Testing And Research At High Voltage Division : The High Voltage Division of CPRI has established a pollution chamber of size 12m x 12m x 12 m where pollution tests as per IEC BIS can be conducted on all types of external insulation for systems upto 400kV. The power source consists of testing transformers of 600kV, 3.3Amp & a 100kV, 6Amp rating. A DC source of 150kV, 1Amp with thyristorized feed back control system.
Two methods namely salt fog and solid layer are employed to test the insulators under pollution conditions.
In the case of salt fog method, the insulator is energised at the service voltage, which is kept throughout the test and the insulator is continuously subjected to the salt fog whose salinity (expressed in kg of Nacl per cubic meter of water) defines the severity of the test. The series of successive tests, each lasting for one hour, is carried out at the same applied voltage and for various salinities. This is carried out until highest salinity which the insulator withstands is achieved for atleast three tests out of four. The maximum degree of salinity is termed the withstand salinity of the test object.
In the case of solid layer method, the insulator is coated/dipped/sprayed/flowed on with a slurry containing Kaolin and sodium chloride.
1. Wetting before and during energisation, 2. Wetting after energisation
The object of the test is to confirm whether the specified withstand layer conductivity or the specified salt deposit density is withstood at the specified voltage. The insulator complies with this specification if three withstand tests out of four are obtained under the condition examined.
CPRI has been conducting research exhaustively on different aspects of pollution for the last ten years. Pollution level measurements have been carried out along the proposed route of a ± 500 kV DC transmission line of M/S. MSEB
Many research activities have been carried out in collaboration with CESI, Italy and the following are some of the important ones.
1. Effect of pollution flashover with respect to diameter of the porcelain shell 2. Pollution performance of composite insulators 3. Ageing studies on insulator of ceramic & non-ceramic material 4. Pollution test on lightning arrester
Mathematical models for pollution flashover of insulators are widely recognized as efficient tools, which could help in arriving at optimum insulator profiles for polluted areas. A mathematical model of arc under dynamic conditions has been formulated which can predict the safe withstand voltage for a given degree of pollution. Thus CPRI has the capability to study theoretically the pollution performance of insulators.
Pollution performance of insulators under DC voltages has been studied upto a voltage of about 140kV.
CPRI hopes that both the testing and research facilities now established will be used by manufacturers and utilities to solve the problems connected with the design of external insulation under normal and polluted conditions.
Impulse Current Generator 100 kV, 150 kJ
Types of Tests :
All type tests on Zno arrester blocks upto 11 kV As per National and International
Standards
Necessity Of Testing Arrester Blocks :
Lightning arresters, often called Surge Diverters, play a vital role in protecting expensive substation equipment from high voltage surges. These surge voltages originate from either switching operations of substation equipment or lightning strikes. In either case these over voltages have to be
limited well below the insulation levels of the equipment. By R&D, new designs of lightning arresters have emerged, by which, it has become possible to bring down the insulation levels of the equipment resulting in significant savings to the power systems. Till recently gap type arresters were in use in the power system. Even in this type, new concepts were introduced in the design by which one to two step reduction of basic insulation level (BIL) of 145 and 220 kV systems were possible. These arresters are being now replaced by Zinc Oxide (ZnO) Gap-less arresters, (also known as Metal Oxide Surge Arresters). As reported in the literature, these were first developed in Japan and came into use from 1970. The replacement of conventional arresters by ZnO type initially started from system voltages above 145 kV class owing to their high initial cost. But now even distribution systems use ZnO arresters due to the present affordable cost. Considering the importance of tests on ZnO arresters which are being increasingly used by Powergrid, NTPC, State Electricity Boards and other power utilities. CPRI has established comprehensive test facility for undertaking tests on Zinc Oxide arresters as per IEC-60099-4 and other relevant standards. All tests prescribed by International/Indian Standards (IEC 60099-4) for Metal oxide arresters without gaps for AC systems can be undertaken. Following tests can be taken up with the newly commissioned Computer controlled Impulse Current Generator supplied by M/s. Haefely Trench, Switzerland with a capacity of 100 kV and 150 kJ
Residual Voltage Tests:
This test can be carried out for the following exponential waveforms:
a) Steep Current Impulse 1/<20 micro second.
Front time : 1 micro second ± 0.1 micro second.
Time to half value : <20 micro second.
Max. Current : 20 kA
Residual Voltage : Upto 40 kV
b) Lightning Current Impulse 8/20 micro second.
Front time : 8 micro second ± 1.0 micro second.
Time to half value : 20 micro second ±2.0 micro second.
Max. Current : 50 kA
Residual Voltage : Upto 50 kV
c) Switching Current Impulse 36/90 micro second.
Front time : > 30 micro second.
Time to half value : approx 2.5 T1.
Max. Current : 2 kA
Residual Voltage : Upto 30 kV
d) High Current Impulse 4/10 micro second
Front time : 4 micro second ± 0.5 micro second.
Time to half value : 10 micro second ± 1.0 micro second.
Max. Current : 120 kA
Residual Voltage : Upto 60 kV
Long duration rectangular Current Impulses : Transmission line class tests class I to V can be carried out as per IEC 60099-4. Operating Duty Tests : Operating duty tests as per IEC 60099-4 can be carried out Power frequency voltage V/S Time curve
HV Home
The Pollution Laboratory has dimensions of 12M x 12M x 12M. An array of nozzles confirming to IEC specifications combined with a salt water pumping and air compressor provide the required salt fog. The power supply to the chamber is from one of the outdoor 600 kV, 2,000 kVA Cascade Transformers setup.
Pollution Test on InsulatorEquipment available :
600 kV, 3 Amperes AC source 100 kV, 6 Amperes AC source 150 kV, 1 Ampere DC source
With these equipment/facilities the Pollution Laboratory can carry out tests on insulators and insulator assemblies for systems upto and including 400 kV.
Types of Tests :
Pollution test on insulators by salt fog/solid layer method upto 400 kV AC & 150 kV DC
SF6 Puncture withstand test facility for DC insulators Thermal runaway tests on insulators
This Laboratory can undertake these tests as per National & International Standards
Necessity Of Pollution Testing:
With the ever increasing demand for electrical power, there has been a steady growth in high voltage transmission lines required for optimum and economic transfer of large blocks of power over long distances. As the level of transmission voltage is increased, switching and dynamic over voltages and withstand ability of the insulator under polluted conditions are important factors which determine the insulation level of the system. The reliability of the system mainly depends on the environmental and weather conditions which cause flashover on polluted insulators leading to system outages. It is generally recognized that the main events leading to flashover of polluted insulators under service voltage are the formation of a conductive layer on the insulator surface, leakage current surging with associated dry band formation and partial arc development and arc propagation along the insulator surface eventually spanning the whole insulator. The problem is more complex in case of DC systems because of large contamination due to electrostatic forces and longer duration of partial arc. Therefore the design of external insulation under polluted conditions is very critical and lot of investigations are under way to arrive at safe creepage distances for systems operating in different environments.
The pollution can be broadly classified into two types:
1. Marine pollution found in the immediate neighborhood of the sea and also at considerable distances from coast. 2. Industrial pollution caused by dust, smoke etcObjectives Pollution Investigation :
Collection of pollution flashover data under natural conditions Suitable artificial pollution test under conditions representing natural
pollution Design of insulation for pollution conditions. Pollution ageing tests and investigation of causes of failures to arrive at
suitable remedies. Pollution performance of composite insulators
Pollution Testing And Research At High Voltage Division : The High Voltage Division of CPRI has established a pollution chamber of size 12m x 12m x 12 m where pollution tests as per IEC BIS can be conducted on all types of external insulation for systems upto 400kV. The power source consists of testing transformers of 600kV, 3.3Amp & a 100kV, 6Amp rating. A DC source of 150kV, 1Amp with thyristorized feed back control system.
Two methods namely salt fog and solid layer are employed to test the insulators under pollution conditions.
In the case of salt fog method, the insulator is energised at the service
voltage, which is kept throughout the test and the insulator is continuously subjected to the salt fog whose salinity (expressed in kg of Nacl per cubic meter of water) defines the severity of the test. The series of successive tests, each lasting for one hour, is carried out at the same applied voltage and for various salinities. This is carried out until highest salinity which the insulator withstands is achieved for atleast three tests out of four. The maximum degree of salinity is termed the withstand salinity of the test object.
In the case of solid layer method, the insulator is coated/dipped/sprayed/flowed on with a slurry containing Kaolin and sodium chloride.
1. Wetting before and during energisation, 2. Wetting after energisation
The object of the test is to confirm whether the specified withstand layer conductivity or the specified salt deposit density is withstood at the specified voltage. The insulator complies with this specification if three withstand tests out of four are obtained under the condition examined.
CPRI has been conducting research exhaustively on different aspects of pollution for the last ten years. Pollution level measurements have been carried out along the proposed route of a ± 500 kV DC transmission line of M/S. MSEB
Many research activities have been carried out in collaboration with CESI, Italy and the following are some of the important ones.
1. Effect of pollution flashover with respect to diameter of the porcelain shell 2. Pollution performance of composite insulators 3. Ageing studies on insulator of ceramic & non-ceramic material 4. Pollution test on lightning arrester
Mathematical models for pollution flashover of insulators are widely recognized as efficient tools, which could help in arriving at optimum insulator profiles for polluted areas. A mathematical model of arc under dynamic conditions has been formulated which can predict the safe withstand voltage for a given degree of pollution. Thus CPRI has the capability to study theoretically the pollution performance of insulators.Products Wise Testing :
Protocol Test:
Energy Meter Data Concentrator IED Relay Protocol Convertor RTU
(The above Equipments are tested at ITID-Bangalore)
Cable Test :
Paper/PVC/XLPE/EPR Power cables of Voltage rating up to 220 kV Cable accessories, etc
(The above Equipments are tested at DCCD- Bangalore, STDS-Bhopal, and
RTL-Noida)
Capacitor Test:
HV Shunt capacitors
HV Series capacitors
HV Capacitors for surge
LV Motor capacitors
LV fan motor Capacitors
LV Capacitors for Lighting
LV Power capacitors of self-healing type.
LV Shunt capacitors of non self - healing type.
(The above Equipments are tested at DCCD- Bangalore, STDS-Bhopal, and RTL-Noida)
Flame Retardant Low Smoke Test :
Electric cables
Cable sheath materials
FRP composite materials
Cable trays
Channels
Feeder pillar boxes
Energy meter covers
Terminal blocks
Bushings
Supporting insulators
PVC conduit pipes
Flooring materials
Fabrics/curtain
Materials used in aerospace/navy
Any other plastic material
(The above Equipments are tested at DCCD- Bangalore)
Temperature Rise Test :
Distribution, Transmission & Power equipment and accessories
Diagnostics Test on,
Power Transformer
Generators / Large motors
Power cables
EHV CTs, / CVTs
Resin Cast CTs
(The above Equipments are tested at DCCD- Bangalore)
High Power Test :
High voltage circuit breakers
High Voltage Switches
High Voltage Fuses
High Voltage Switch Boards
Terminal Boxes
MV Metal enclosed Switchgear
Power Transformers
Distribution Transformers
Traction Transformers
Potential Transformers
Current Transformers
Lightning Arresters
Insulator Strings
AC metal enclosed switch gear & control gear.
AC Disconnectors & Earth switches
Reactors
Line traps
Bus ducts, Bus bars, Generator Neutral Bus bar Compartment
Power connectors, ACSR conductors
LV Circuit Breaker
(The above Equipments are tested at HPL- Bangalore, STDS-Bhopal, and SCL-Bangalore)
Insulation / Impulse voltage Withstand Test :
Insulator ( Disc, Pin, Solid Core, Hollow)
Insulator Strings (all types)
Lightning Arrestor Housing & similar Insulating Materials
Battery Container
Rubber Mats
Insulating Tubes etc. Insulating Rod Isolator, Circuit Breaker Bus duct Cables Bushing AB Switch Panel P T /C V T / Coupling Capacitor/ Grading Capacitor / R.V.T.S / CT-PT Units Tap changer Voltage / Current / Power / Distribution Transformers Reactors HT Capacitors Thyristor Valves
(The above Equipments are tested at HV- Bangalore, STDS-Bhopal, UHVRL-Hyderabad and RTL-Noida)
Short Circuit / High Voltage / Synthetic Test :
Circuit Breakers (LV, HV)
Fuses
Switches
Starters
Control Switches
MCB / RCCB Switch Fuse units
Power Connectors
Spacers
Bus bars
Bus ducts
CT's conductors
Transformer
P T /C V T / Coupling /Tap Changers
Capacitors
Grading Capacitors
R.V.T.S
C.T – PT UNITS
Series & Shunt Reactors
Line Traps
Damping Reactors Tuning Reactors
Neutral Earthing Reactors
THYRISTOR VALVES
H.V. Circuit Breaker & Switchgear Panel with Circuit Breaker
HT switches/ Line sectionalizer
Isolators
Power & Distribution transformers & Traction transformers
HT fuses
Surge arresters
Reactors
Auto-reclosures
DC Breakers
HT switchgear panel
Motor terminal box
Spacers for Bundled conductor
HV Contactors
LT Air circuit breakers, MCCBs for voltage not exeeding 1000V
Circuit Breakers for Over current protection for household & similar
installations
Miniature circuit breakers (MCB)
Low voltage fuses for voltage not exceeding 1000V
Low voltage fuse bases for voltage not exceeding 1000V
Air break switches, Air break disconnectors, air break switch disconnectors,
fuse combinations for voltage not exceeding 1000V
Carrier & Bases for Rewirable type fuses
Composite unit of air break switches for rewirable type switches for voltage
not exceeding 650V, AC21, 100A
AC Miniature circuit breaker boards 1000V
Residual current operated circuit breaker
Factory build assemblies of switchgear & controlgears for 1000V
For enclosed distribution board & cutouts 1000V
Contactors & motor starters for voltages at exceeding 1000V
Electric power connectors above 200A
(The above Equipments are tested at HPL- Bangalore, STDS-Bhopal, and SCL-Bangalore)
Dielectric Materials Test :
Lubricating Oil
Transformer Oil
Polymers etc.
(The above Tests are Conducted at DMD- Bangalore)
Materials Test :
Coal
Analysis of coal, ash and water for thermal power stations
Lubrication oil and all other materials.
(The above Tests are Conducted at MTL- Bangalore)
Structural / Mechanical strength/ Vibration Test :
Transmission line towers
Line material
Transmission Line Conductors upto and including 800kV rating
Compression Clamps
Mid Span Joints
I&V Suspension Tension Strings upto and including 800kV rating
Structural Steel
Steel Wire ropes
Electrically Operated/ Hand Operated Winches
Chain Pulley Block upto 20 Tonnes
Load Cell
Line Material
Terminal Clamp
Structural Steel
Connecting Links for Brake Parachute/ Nylon Purchase Tape
Insulators & Insulator Strings of Single/ Twin/ Triple/ Quad-Tension or
Suspension type upto and including 800kV rating
Vibration Dampers upto and including 800kV
Spacer/ Spacer Dampers upto and including 800kV.
Transmission Line Conductors upto and including 800kV rating
Vibration Dampers upto and including 800kV
Spacer/ Spacer Dampers upto and including 800kV.
Transmission Line Conductors upto and including 800kV rating
Conductors
(These Products are tested at MED- Bangalore)
Seismic Qualification / Vibrations Test :
Energy Meter
Switchgear, Control Panel
All Equipments up to 10 Tons.
(The above Tests are Conducted at EVRC- Bangalore)
Calibration Tests :
Digital & Analog Voltmeters
Digital & Analog Ammeters
Multimeters
Digital & Analog Wattmeters
Digital Temperature indicators
Digital & Analog Panel meters
Electronic Thermometers
Data Loggers
Strip chart recorders
Power harmonic analysers
Process calibrators
Hot & Cold temperature baths
Current Clamps
Thermometers
Impulse measuring system
(The above Equipments calibration tests are conducted at ID- Bangalore, STDS-
Bhopal)
Test :
Relay
UPS (Uninterrupted Power Supply) (1 KVA - 10 KVA & above)
Single Phase Electromechanical / kWh / Static / Electronic Energy Meters
Three Phase Four Wire / Three Phase Three Wire Electromechanical / kWh /
TVM Static / Electronic Energy Meters
Single phase / Three phase Static watt-hour meters
Electronic Trivector meters
Static protective relays
Smaller size UPS, SMPS, Inverters, Converters, Contactors etc
All Electronic equipments, like Static Relays, Breakers, contactors, starters,
Electronic ballast, Medical equipments
(The above Equipments are tested at ID- Bangalore, STDS-Bhopal)
Battery Testing :
Lead acid storage Batteries, VRLA, LMLA, NICAD Batteries, Tubular Batteries
(The above Tests are Conducted at EATD-Bangalore)
Flame Proof Testing :
All flame proof electrical equipment
(The above Tests are Conducted at EATD-Bangalore)
Ingress Protection Test:
All types of electrical equipment enclosures such as- Outdoor distribution boards Relay units/Panels Control Cubicles for PCVCB Switching & Control System enclosures RMV panels HT Metering & Switching Panel AC Distribution Board EWM Enclosures Platform Power Supply LT Panel Disconnecting Switch Assembly Junction Boxes LV switch Board AD/DC Panel weatherproof Switch Enclosures Dry type Transformer enclosures PCC Panel, MCC Panel, Bus Ducts DOL Starters Integral Starter Control Panel Electricity Metering Equipment Enclosures Actuators Telecommunication Equipment Enclosures Antennas Cable Connector Assembly GPRS Equipment Enclosures Battery Charger Panels Medical Health Monitoring Equipment Enclosures Drive Mechanism Box Marshalling Kiosks Surge Monitors MOM's Belt sway Switch Enclosures Reactor assembly Enclosures Starter Motors Sot Starter Panels
RAPCONS BAPCONS
Rotating Electrical Machinery Equipment Enclosures such as :
Enclosures of Induction Motors Valve Actuators DC Machines AC Machines Alternators Generators Vibratory Electric Motors Large Motors Automobile Electrical Motors Traction Motors Power Tool Motors Pumps (motors) Etc.
Luminaries and Light Fitting Equipment Enclosures such as :
Street light Fitting Enclosures Aviation Light Fitting Enclosures Domestic Industrial Light Fitting Enclosures Corridor/ Office Light Fitting Enclosures
Solar Operated Light Fitting Enclosures Etc.
(The above Tests are Conducted at EATD-Bangalore, STDS-Bhopal)
Luminaries :
Tubular fluorescent lamps with Starter
Self Ballasted Lamps for General Lighting Service (CFL)
Safety requirements and Performance requirements
Lamp Ballast
(The above Tests are Conducted at EATD-Bangalore)
Fan Testing :
Electrical Ceiling Fans and Regulator
Electrical Table Type Fans and Regulator
Electrical Pedestal Type Fans and Regulators
Propeller Type AC Ventilating Fans
(The above Tests are Conducted at EATD-Bangalore)
Refrigerators :
Direct cool and frost free refrigerators up to 600 lts. capacity.
(The above Tests are Conducted at EATD-Bangalore)
DCCD - DIAGNOSTICS LABORATORY
DCCD Home
The Laboratory has facilities for conducting condition assessment / life
evaluation of HV Power Equipment like Power Transformers, Hydro & Turbo
Generators, Power Cables, Large AC Motors, Current Transformers (CTs), Capacitance
Voltage Transformers (CVTs) etc. in service. The Laboratory has adequate experience
& expertise in conducting Residual Life Assessment (RLA) Studies on High Voltage
Substation and Power Plant Electrical Equipment in service. Diagnostic Laboratory is
an accredited laboratory as per ISO 9001-2000 quality management system for
undertaking field engineering services and consultancy for various utilities.
CPRI Mobile Field testing laboratory Partial Dis charge Test on 110MW Turbo Generator
TEST / EQUIPMENT FACILITIES :-
o Recovery Voltage meter
o Electromagnetic Core Imperfection detector (ELCID)
o HV Dielectric Spectroscopy
o VLF Cable Diagnosis system
o Transformer ratio arm bridge
o Standard Capacitor, 80kV
o Precision microprocessor based Insulation tester, up to 5 kV
o Automatic Capacitance & tan delta test system
o Surge comparison tester – 12 kV
o DC Test kit – 70kV
o Partial Discharge Detection system
o Electronic Wedge mapping equipment
o Rotor Reflectometer
o Testing Transformers
CONSULTANCY :-
1. Consultancy through Field Testing.
a. Test facilities for undertaking condition monitoring & diagnostic tests
on HV Power Equipment in order to assess the state & condition of
their insulation systems.
b. Mobile Field Testing Laboratory with diagnostic test facilities for
conducting diagnostic tests on HV Power Equipment at site
c. Failure analysis of HV Power equipment
2. Involved in Renovation & Modernization (R & M) & Residual Life
Assessment (RLA) / Life Extension (LE) studies on Thermal / Hydro Power
Plant Electrical Equipment.
DIAGNOSTIC TESTS :-
Product / Apparatus Type of Tests conducted
§ Power Transformer
Frequency Domain Analysis
Dielectric loss angle at 50 Hz
Polarization Index Test
Capacitance at 50 Hz
Recovery Voltage Test
Surge Comparison Test
Partial Discharge Test
§ Generators / Large
motors
Stator
Rotor
Dielectric loss angle at 50 Hz
Capacitance at 50 Hz
ELCID Test
Partial Discharge Test
DC Leakage current Test
Polarization Index Test
Conductor resistance Test
Surge Comparison Test
Wedge mapping Test
Polarization Index Test
Recurring Surge Oscillogram (RSO
Test)
Conductor Resistance Test
Field Impedance test
Power cables
Frequency domain analysis
Dielectric loss angle at 50 Hz
Capacitance at 50 Hz
VLF tan delta test
DC Leakage current test
EHV CTs, / CVTs Dielectric loss angle at 50 Hz
Polarization Index Test
Capacitance at 50 Hz
Resin Cast CTs
(Up to 33kV)
Insulation Resistance / Polarization
Index
Tan-delta & Capacitance
Partial Discharge Test
Resin Cast PTs
(Up to 33kV)
Partial Discharge Test
NATIONAL / INTERNATIONAL STANDARDS / GUIDELINES :-
Apparatus /
Equipment
Standards / Guidelines
Power Transformer IEEE 62-1995 - IEEE Guide for Diagnostic Filed
Testing of Electrical Power Apparatus-Part 1: Oil
filled Power transformers, Regulators and Reactors
Generator / Motors
Stator
Rotor
IEEE 43-2000 – IEEE Recommended practice for
Testing IR of Rotating Machinery
IEEE 95-2002 – IEEE recommended practice for
Insulation testing of AC Electric machinery with High
Direct Voltage
IEEE 1434-2000 – IEEE Trial use guide to the
measurement of partial discharges in rotating
machinery.
Power Cables As per National/International practices and as per
Clients requirement
CTs & CVTs As per National/International practices and as per
Clients requirement
RESEARCH :-
Infrastructure to undertake R&D, in the areas of Functional evaluation of
a) Paper – oil insulation system
b) Power Cable insulation system
c) Rotating Machine insulation system
RLA Studies on Hydro Generator ELCID Test on 110 MW Turbo Generator
Stator winding
RVM Test on 15.75kV/220kV, Winding Resistance test on 15.75kV/220kV, 250MVA Generator Transformer 250MVA Generator Transformer
Partial Discharge Test on HV Motor Tan delta Test on Transformer
Tan delta Test on sub-station equipment ELCID test on Hydro Generator Stator Winding
Dielectric Spectroscopy Test on Tan-Delta Test on Generator Transformer
Distribution Cables (MV)
CLIENTELE :-
SOLID DIELECTRIC LABORATORY
DCCD Home
The Dielectric laboratory has comprehensive testing and evaluation facilities on
insulating materials and systems. Insulating materials are evaluated and test for
electrical, mechanical, physical and electro chemical properties. The Dielectric
laboratory has undertaken consultancy work and sponsored projects for different
power utilities and industries. Evaluation of class “H” insulation for traction motors
and compatibility studies on enameled winding wires and varnished were two
projects completed for RDSO, Ministry of Railways. Assistance has been rendered to
BIS in formulation of various standards on insulating materials and systems and on
enameled winding wires.
Facilities available:
- Micro processor based UTM 50KN capacity (-700C to2000C).
- High resistance meter upto 10-16
- SIGMA Tester.
- Automatic tracking comparator upto 1000VAC.
- Arc resistance tester.
- Rubber glove tester
- Complete equipment for evaluation of enameled winding wires as per relevant
parts of IS/IEC standards.
- Power frequency capacitance and dissipation factor measuring bridges, NBS smoke
box
- High frequency capacitance and dissipation factor measuring bridges.
- Electrometer
- High pressure chamber for conducting investigation on gaseous dielectrics upto 5
bars
- Static Decay meter
- Tear Tester
- Surface Roughness Meter
- Gas Chromatography/Mass Spectrometer
- Impact Tester
- Stress Cracking Equipment
- Compression Molding machine (4000C)
- Micro - OHM Meter.
- Liquid contaminant tracking and erosion test equipment
AREAS OF WORK :
- Electrical and mechanical tests on conductors, electrical, mechanical and chemical
tests on various solid insulating materials like paper, press board, polymeric molding
materials. B stage epoxy mica and epoxy glass materials etc.
- All tests on enameled/winding wires including endurance tests.
- Studies on gaseous dielectrics.
- Electrical tests on cable filling compound, capacitor fluids etc.
- Tests on Teflon, polypropylene, polyester, kapton films.
- Electrical tests on antistatic materials.