Page 1 ITALY INNOVATION CENTER HEWLETT PACKARD ITALIANA SRL DC4Cities and HP Solar Power Moonshot Experiment: Maximizing Renewable Energy Utilization in a Data Centre Datacentres Europe 2014

Category:

Technology


2 download

TRANSCRIPT

Page 1: DC4Cities and HP Solar Experiment

Page 1

ITALY INNOVATION CENTER

HEWLET T PACKARD I TALI ANA SRL

DC4Cities and HP Solar Power Moonshot Experiment:

Maximizing Renewable Energy Utilization in a Data Centre

Datacentres Europe 2014

Page 2: DC4Cities and HP Solar Experiment

Page 2

DC4Cities Origins

Datacentres Europe 2014

Page 3: DC4Cities and HP Solar Experiment

Page 3

DC4Cities Origins

Datacentres Europe 2014

Virtual Machine Dynamic

Consolidation and Turn off Servers

Page 4: DC4Cities and HP Solar Experiment

Page 4

DC4Cities Origins

Datacentres Europe 2014

Virtual Machine Dynamic

Consolidation and Turn off Servers

Green Service Level Agreements

Page 5: DC4Cities and HP Solar Experiment

Page 5

DC4Cities Origins

Datacentres Europe 2014

Virtual Machine Dynamic

Consolidation and Turn off Servers

Green Service Level Agreements

Adapt to Renewable

Energy Availability

Page 6: DC4Cities and HP Solar Experiment

Page 6

DC4Cities Project

Datacentres Europe 2014

DC4Cities: an environmentally sustainable data centre for Smart

Cities

FP7-SMARTCITIES-2013 (ICT Call) Objective ICT-2013.6.2 Data Centres in an energy-efficient and environmentally friendly Internet

The goal of DC4Cities is to make existing and new data centres energy adaptive. DC4Cities will find the adequate actions to run a data centre so as to adapt to external energy constraints such as renewable energy availability and consume the minimal energy, without requiring any modification to the logistics, and without impacting the quality of the services provided to their users. In addition new energy metrics, benchmarks, and measurement methodologies will be developed and proposed for the definition of new related standards.

Abstract http://www.dc4cities.eu

Page 7: DC4Cities and HP Solar Experiment

Page 7

DC4Cities Web Site and Partners

Datacentres Europe 2014

http://www.dc4cities.eu

Page 8: DC4Cities and HP Solar Experiment

Page 8

DC4Cities Rationale

Running a data centre on 100% renewable energy is not a problem if its energy provider is only using hydro and geothermal sources. But if not...

running a data centre at high levels of renewable energy sources is the great challenge

Datacentres Europe 2014

Page 9: DC4Cities and HP Solar Experiment

Page 9

DC4Cities Rationale

Running a data centre on 100% renewable energy is not a problem if its energy provider is only using hydro and geothermal sources. But if not...

running a data centre at high levels of renewable energy sources is the great challenge

Datacentres Europe 2014

Certain Services

require DCs to be close

to users

Smart Cities require

Services, hosted by

DCs

Smart Cities need Eco-

friendly DCs

Europe needs new metrics for DC energy efficiency

Page 10: DC4Cities and HP Solar Experiment

Page 10

DC4Cities Rationale

Running a data centre on 100% renewable energy is not a problem if its energy provider is only using hydro and geothermal sources. But if not...

running a data centre at high levels of renewable energy sources is the great challenge

DC4Cities will find the adequate actions to run a DC so as to adapt to external energy constraints and consume the

minimal energy, targeting the 80% usage of renewable energy sources

Datacentres Europe 2014

Certain Services

require DCs to be close

to users

Smart Cities require

Services, hosted by

DCs

Smart Cities need Eco-

friendly DCs

Europe needs new metrics for DC energy efficiency

Page 11: DC4Cities and HP Solar Experiment

Page 11

DC4Cities Main Goal

Datacentres Europe 2014

Enforce DCs to run in an energy adaptive mode

all data centre components, including applicationsmatching the renewable energy availability;following the Smart City Energy authority

directives on energy usage and plans

Page 12: DC4Cities and HP Solar Experiment

Page 12

DC4Cities Concept

Datacentres Europe 2014

DC4Cities: let DCs become energy adaptive

Eco-friendly DC energy policies needs to be capable of

adapting the power consumption to the

availability of renewable energy

being adapted to the requests received by the Smart City Energy Management authority

Page 13: DC4Cities and HP Solar Experiment

Page 13

DC4Cities Concept

Datacentres Europe 2014

DC4Cities: let DCs become energy adaptive

Eco-friendly DC energy policies needs to be capable of

adapting the power consumption to the

availability of renewable energy

being adapted to the requests received by the Smart City Energy Management authority

Software Execution

Load

HardwarePower

Consumption

Data Centre Total Power

ConsumptionDC4Cities

controls generates PUE*

controls

* approximate factor

Page 14: DC4Cities and HP Solar Experiment

Page 14

DC4Cities Impact on Renewable

Energy Utilization

Trad.DC

PowerRenewablePower

Time

DC4Cities

PowerRenewablePower

Time

50%

50%

20%

80%

DC not using Renewable Power

DC using Renewable Power

DC not using Renewable Power

DC using Renewable Power

Datacentres Europe 2014

Page 15: DC4Cities and HP Solar Experiment

Page 15

Energy Sourcing and Control Options

Datacentres Europe 2014

Option A: Grid Option B: Ren Option C: Mixed

Page 16: DC4Cities and HP Solar Experiment

Page 16

Energy Sourcing and Control Options

Datacentres Europe 2014

Option A: Grid Option B: Ren Option C: Mixed

Option D:Smart [vision]

Page 17: DC4Cities and HP Solar Experiment

Page 17

Data CentreEnergyController

User and Admin Task Scheduling Infrastructure Mgmt Energy Adaptive SW

Renewable Energy Adaptive Interface

Energy Adaptive Data Centre Operation Interface

Grid/Smart Grid Renewable Energy Providers Smart City Control

DC4Cities Overview

Datacentres Europe 2014

Page 18: DC4Cities and HP Solar Experiment

Page 18

Data CentreEnergyController

Renewable Energy Adaptive Interface

Grid/Smart Grid Renewable Energy Providers Smart City Control

DC4Cities Overview (North)

Datacentres Europe 2014

Page 19: DC4Cities and HP Solar Experiment

Page 19

Data CentreEnergyController

Renewable Energy Adaptive Interface

Grid/Smart Grid Renewable Energy Providers Smart City Control

DC4Cities Overview (North)

Datacentres Europe 2014

0:00

4:00

8:00

12:0

0

16:0

0

20:0

00:

000

20406080

100120140160

SunWindGasCoal

Energy Availability Forecast 0:

003:

006:

009:

00

12:0

0

15:0

0

18:0

0

21:0

00:

000

20

40

60

RenPct

Page 20: DC4Cities and HP Solar Experiment

Page 20

Data CentreEnergyController

Renewable Energy Adaptive Interface

Grid/Smart Grid Renewable Energy Providers Smart City Control

DC4Cities Overview (North)

Datacentres Europe 2014

0:00

4:00

8:00

12:0

0

16:0

0

20:0

00:

000

20406080

100120140160

SunWindGasCoal

Energy Availability Forecast

Weather Forecast

0:00

3:00

6:00

9:00

12:0

0

15:0

0

18:0

0

21:0

00:

000

20

40

60

RenPct

0:00

3:00

6:00

9:00

12:0

0

15:0

0

18:0

0

21:0

00:

000

10203040

PV power

Page 21: DC4Cities and HP Solar Experiment

Page 21

Data CentreEnergyController

Renewable Energy Adaptive Interface

Grid/Smart Grid Renewable Energy Providers Smart City Control

DC4Cities Overview (North)

Datacentres Europe 2014

0:00

4:00

8:00

12:0

0

16:0

0

20:0

00:

000

20406080

100120140160

SunWindGasCoal

Energy Availability Forecast

Weather Forecast

Power/EnergyGoals

80%

Ren

0:00

3:00

6:00

9:00

12:0

0

15:0

0

18:0

0

21:0

00:

000

20

40

60

RenPct

0:00

3:00

6:00

9:00

12:0

0

15:0

0

18:0

0

21:0

00:

000

10203040

PV power

Page 22: DC4Cities and HP Solar Experiment

Page 22

Data CentreEnergyController

Renewable Energy Adaptive Interface

Energy Adaptive Data Centre Operation Interface

DC4Cities Overview (Control)

Datacentres Europe 2014

Page 23: DC4Cities and HP Solar Experiment

Page 23

Data CentreEnergyController

Renewable Energy Adaptive Interface

Energy Adaptive Data Centre Operation Interface

DC4Cities Overview (Control)

Datacentres Europe 2014

0:00

3:00

6:00

9:00

12:0

0

15:0

0

18:0

0

21:0

00:

000

20406080

DC Ideal power

Page 24: DC4Cities and HP Solar Experiment

Page 24

Data CentreEnergyController

Renewable Energy Adaptive Interface

Energy Adaptive Data Centre Operation Interface

DC4Cities Overview (Control)

Datacentres Europe 2014

0:00

3:00

6:00

9:00

12:0

0

15:0

0

18:0

0

21:0

00:

000

20406080

DC Ideal power

0:00

3:00

6:00

9:00

12:0

0

15:0

0

18:0

0

21:0

00:

000

20

40

60

Serv CServ BServ. A

Service

QuotaSplit

Policies

Page 25: DC4Cities and HP Solar Experiment

Page 25

Data CentreEnergyController

Renewable Energy Adaptive Interface

Energy Adaptive Data Centre Operation Interface

DC4Cities Overview (Control)

Datacentres Europe 2014

0:00

3:00

6:00

9:00

12:0

0

15:0

0

18:0

0

21:0

00:

000

20406080

DC Ideal power

0:00

3:00

6:00

9:00

12:0

0

15:0

0

18:0

0

21:0

00:

000

20

40

60

Serv CServ BServ. A

0:00

3:00

6:00

9:00

12:0

0

15:0

0

18:0

0

21:0

00:

000

20

Quota A

0:00

3:00

6:00

9:00

12:0

0

15:0

0

18:0

0

21:0

00:

000

20

Quota B

0:00

3:00

6:00

9:00

12:0

0

15:0

0

18:0

0

21:0

00:

000

20

Quota C

Service

QuotaSplit

Policies

Page 26: DC4Cities and HP Solar Experiment

Page 26

Green SLAs (All4Green)

Datacentres Europe 2014

User and Admin Task Scheduling Infrastructure Mgmt Energy Adaptive SW

Page 27: DC4Cities and HP Solar Experiment

Page 27

Green SLAs (All4Green)

Datacentres Europe 2014

User and Admin Task Scheduling Infrastructure Mgmt Energy Adaptive SW

Page 28: DC4Cities and HP Solar Experiment

Page 28

Green SLAs (All4Green)

Datacentres Europe 2014

100% ECU

HighPerfW3D2

10000pg/m

User and Admin Task Scheduling Infrastructure Mgmt Energy Adaptive SW

Page 29: DC4Cities and HP Solar Experiment

Page 29

Green SLAs (All4Green)

Datacentres Europe 2014

100% ECU

HighPerfW3D2

10000pg/m

User and Admin Task Scheduling Infrastructure Mgmt Energy Adaptive SW

Page 30: DC4Cities and HP Solar Experiment

Page 30

Green SLAs (All4Green)

Datacentres Europe 2014

100% ECU

HighPerf

MidPerf

75% ECU

W3D2

W2D2

10000pg/m

6000pg/m

User and Admin Task Scheduling Infrastructure Mgmt Energy Adaptive SW

Page 31: DC4Cities and HP Solar Experiment

Page 31

Green SLAs (All4Green)

Datacentres Europe 2014

100% ECU

HighPerf

MidPerf

75% ECU

LowPerf

W3D2

W2D2

W1D1

10000pg/m

6000pg/m

3000pg/m

User and Admin Task Scheduling Infrastructure Mgmt Energy Adaptive SW

Page 32: DC4Cities and HP Solar Experiment

Page 32

Data CentreEnergyAdmin

Renewable Energy Adaptive Interface

Energy Adaptive Data Centre Operation Interface

DC4Cities Overview(Control - South)

Datacentres Europe 2014

Smart CityEnergy Admin

Page 33: DC4Cities and HP Solar Experiment

Page 33

Data CentreEnergyAdmin

Renewable Energy Adaptive Interface

Energy Adaptive Data Centre Operation Interface

DC4Cities Overview(Control - South)

Datacentres Europe 2014

0:00

4:00

8:00

12:0

0

16:0

0

20:0

00:

0005

101520

A1A2

0:00

4:00

8:00

12:0

0

16:0

0

20:0

00:

000

10

20

30

B1B2

0:00

4:00

8:00

12:0

0

16:0

0

20:0

00:

000

10

20

30

C1C2C3

Smart CityEnergy Admin

Page 34: DC4Cities and HP Solar Experiment

Page 34

Data CentreEnergyAdmin

Renewable Energy Adaptive Interface

Energy Adaptive Data Centre Operation Interface

DC4Cities Overview(Control - South)

Datacentres Europe 2014

0:00

4:00

8:00

12:0

0

16:0

0

20:0

00:

0005

101520

A1A2

0:00

4:00

8:00

12:0

0

16:0

0

20:0

00:

000

10

20

30

B1B2

0:00

4:00

8:00

12:0

0

16:0

0

20:0

00:

000

10

20

30

C1C2C3

0:00

3:00

6:00

9:00

12:0

0

15:0

0

18:0

0

21:0

00:

000

102030405060

C2B2A1

81%

Smart CityEnergy Admin

Page 35: DC4Cities and HP Solar Experiment

Page 35

Data CentreEnergyAdmin

Renewable Energy Adaptive Interface

Energy Adaptive Data Centre Operation Interface

DC4Cities Overview(Control - South)

Datacentres Europe 2014

0:00

4:00

8:00

12:0

0

16:0

0

20:0

00:

0005

101520

A1A2

0:00

4:00

8:00

12:0

0

16:0

0

20:0

00:

000

10

20

30

B1B2

0:00

4:00

8:00

12:0

0

16:0

0

20:0

00:

000

10

20

30

C1C2C3

0:00

3:00

6:00

9:00

12:0

0

15:0

0

18:0

0

21:0

00:

000

102030405060

C2B2A1

81%

B2 A1 C2

Smart CityEnergy Admin

Page 36: DC4Cities and HP Solar Experiment

Page 36

DC4Cities IaaS CTRL and VM Placement Optimizer (FIT4Green)

FIT4Green VM

placement optimizatio

n

Energy Adaptive Software Control Interface

EndUsers

CreateUseDeleteVMs

Assign/Migrate VMs to/between servers

Clo

ud

Fro

nt

En

d

Datacentres Europe 2014

Infrastructure Mgmt

Page 37: DC4Cities and HP Solar Experiment

Page 37

DC4Cities IaaS CTRL and VM Placement Optimizer (FIT4Green)

EA SWCTRLIaaS

FIT4Green VM

placement optimizatio

n

Energy Adaptive Software Control Interface

EndUsers

CreateUseDeleteVMs

Assign/Migrate VMs to/between servers

Change SLA value(s):VM consolidation factor

Monitoring&Forecast

Clo

ud

Fro

nt

En

d

Datacentres Europe 2014

Infrastructure Mgmt

EA SW Profile:• Deploy options

• Actions• Elasticity

Green SLA:• Time/Calendar• Power Status Deploy option

Page 38: DC4Cities and HP Solar Experiment

Page 38

DC4Cities Historical DB and Forecasting Tool

Datacentres Europe 2014

HistoricalData Base

Actual Energy/Weather Data

Actual IT/Power Data

Page 39: DC4Cities and HP Solar Experiment

Page 39

DC4Cities Historical DB and Forecasting Tool

Datacentres Europe 2014

HistoricalData Base

 

Actual Energy/Weather Data

Actual IT/Power Data

Page 40: DC4Cities and HP Solar Experiment

Page 40

DC4Cities Historical DB and Forecasting Tool

Datacentres Europe 2014

HistoricalData Base

 

Actual Energy/Weather Data

Actual IT/Power Data

EnergyAvailability ForecastData

IT/PowerForecastData

Page 41: DC4Cities and HP Solar Experiment

Page 41

Metrics and Benchmarks

Datacentres Europe 2014

Page 42: DC4Cities and HP Solar Experiment

Page 42Brussels AirportNovember 2012Datacentres Europe 2014

Page 43: DC4Cities and HP Solar Experiment

Page 43

Cars vs. Computers and DCs

Datacentres Europe 2014

202020102000199019801970

SPEEDKm/h

Miles/h

POWERHPs

AERODYNAMICSCd

Cx

FUEL CONSUMPTI

ONKm/Litre

Miles/Gallon

Hybrid

Power

EMISSIONSgCO2/KmgCO2/Mile

Page 44: DC4Cities and HP Solar Experiment

Page 44

Cars vs. Computers and DCs

Datacentres Europe 2014

202020102000199019801970

SPEEDKm/h

Miles/h

POWERHPs

AERODYNAMICSCd

Cx

FUEL CONSUMPTI

ONKm/Litre

Miles/Gallon

Hybrid

Power

EMISSIONSgCO2/KmgCO2/Mile

CPU SPEEDMipsMHz

DC LOGISTICSPUE, CUE,

WUE ENERGY/EMISSIONS

CONSUMPTIONOperations/Wh

gCO2/Operation

Page 45: DC4Cities and HP Solar Experiment

Page 45

Proposal for New Metrics

Real Workloadsor Benchmarks

Output = Work Done

Total Work DoneTotal Energy

Renewable EnergyTotal Energy

Software ExecutionEnergy Efficiency

Renewable Energy Utilization Efficiency

Trigger =WorkRequests

Input = Non-RenewableEnergy

Input =Renewable Energy

Datacentres Europe 2014

Page 46: DC4Cities and HP Solar Experiment

Page 46

Proposal for New Metrics

Real Workloadsor Benchmarks

Output = Work Done

Total Work DoneTotal Energy

Renewable EnergyTotal Energy

Software ExecutionEnergy Efficiency

Renewable Energy Utilization Efficiency

Trigger =WorkRequests

Input = Non-RenewableEnergy

Input =Renewable Energy

Datacentres Europe 2014

Collaboration inside EU Project Cluster for common standardization proposal to CEN-CENELEC-ETSI Coordination Group on Green Data Centres

(CG GDC)

Page 47: DC4Cities and HP Solar Experiment

Page 47

PCTREN – Percent of Renewables (from the Grid)

Large variations, unpredictable, uncontrollable

Renewable Energy Sources: “when” matters!

Datacentres Europe 2014

Low Windenergy quota

High Windenergy quota

PCTREN ~50%

PCTREN ~10%

@REE (Spanish Energy Grid) graph: Wind production vs. Total Demand

Page 48: DC4Cities and HP Solar Experiment

Page 48

PCTREN – Percent of Renewables (from the Grid)

Large variations, unpredictable, uncontrollable

Renewable Energy Sources: “when” matters!

Datacentres Europe 2014

Low Windenergy quota

High Windenergy quota

PCTREN ~50%

PCTREN ~10%

@REE (Spanish Energy Grid) graph: Wind production vs. Total Demand

ECREN-GRID = t ECGRID(t) * PCTREN(t)

ECREN-GRID ECGRID * AVG(PCTREN(t))

Page 49: DC4Cities and HP Solar Experiment

Page 49

DC4Cities Trials

Datacentres Europe 2014

Page 50: DC4Cities and HP Solar Experiment

Page 50

HP “Solar” Experiment

~2KW PV ArrayHP Italy HQMilan (Italy)

DC/AC InverterMeters &

Data Loggers HP InternalPower Grid

Moonshotat HP Italy TechnologyShow Room

ExternalEnergyProvider

Datacentres Europe 2014

Workdone

Page 51: DC4Cities and HP Solar Experiment

Page 51

DC4Cities Trials

Datacentres Europe 2014

DC4Cities First Trial will run during Summer 2014

• HP, Milan IT• CSUC/IMI Barcelona

ES• Create-Net, Trento IT

Page 52: DC4Cities and HP Solar Experiment

Page 52

QUESTIONS?

Datacentres Europe 2014

Thank you!

http://www.dc4cities.eu