STANDARDS FOR HOUSING STANDARDS FOR HOUSING DESIGNAND CONSTRUCTION DESIGNAND CONSTRUCTION Relevance/Applicability in View of “New Normal” A presentation by Ar. Maria Benita O. Regala. fuap Manager, Housing Technology Development Office (HTDO), NHA to the Technical Workshop on Holistic Solutions for Resilient Low-Cost Housing at The Oracle Hotel, Quezon City on 03 April 2014

Upload: co-kho-martin

Post on 06-Nov-2015

47 views

Category:

Documents


17 download

DESCRIPTION

NHA STANDARDS FOR HOUSING GUIDELINES/GUIDELINES FOR HOUSING/NHA

TRANSCRIPT

  • STANDARDS FOR HOUSINGSTANDARDS FOR HOUSINGDESIGNAND CONSTRUCTIONDESIGNAND CONSTRUCTIONRelevance/Applicability in View of New Normal

    A presentationby Ar. Maria Benita O. Regala. fuap

    Manager, Housing Technology Development Office (HTDO), NHAto the Technical Workshop on Holistic Solutions for Resilient Low-Cost Housing

    at The Oracle Hotel, Quezon Cityon 03 April 2014

  • OUTLINE OF PRESENTATION

    Standards from BP 220 Site Selection Criteria and Planning Principlesbeing applied for NHA Projects

    22 m Row House Model with 11 m Loftdeveloped as a disaster-resilient housing

    Standards from BP 220 Site Selection Criteria and Planning Principlesbeing applied for NHA Projects

    22 m Row House Model with 11 m Loftdeveloped as a disaster-resilient housing

    2

  • BP 220 Standards

    A. Site Criteria (Sec. 5, BP 220)1. Availability of Basic Needs (Water, Movement

    and Circulation, Storm Drainage, Solid and LiquidWaste Disposal, Parks/Playground, Power)

    2. Conformity with Zoning Ordinances/ City orMunicipality Land Use Plan

    3. Physical Suitability4. Accessibility

    A. Site Criteria (Sec. 5, BP 220)1. Availability of Basic Needs (Water, Movement

    and Circulation, Storm Drainage, Solid and LiquidWaste Disposal, Parks/Playground, Power)

    2. Conformity with Zoning Ordinances/ City orMunicipality Land Use Plan

    3. Physical Suitability4. Accessibility

    3

  • BP 220 Standards

    B. Planning Considerations (Sec. 5, BP 220)1. Area Planning2. Site Preservation/ Alteration

    a. Slopeb. Preservation of Site Assetsc. Ground Cover

    3. Easements4. Circulation

    B. Planning Considerations (Sec. 5, BP 220)1. Area Planning2. Site Preservation/ Alteration

    a. Slopeb. Preservation of Site Assetsc. Ground Cover

    3. Easements4. Circulation

    4

  • BP 220 Standards

    B. Design Parameters (Sec. 5, BP 220)1. Land Allocation2. Lot Requirement3. Length of Block4. Shelter Component5. Setback/ Yard6. Water Supply7. Electrical Power Supply

    B. Design Parameters (Sec. 5, BP 220)1. Land Allocation2. Lot Requirement3. Length of Block4. Shelter Component5. Setback/ Yard6. Water Supply7. Electrical Power Supply

    5

    8.Sewage Disposal System9. Drainage Disposal System10. Garbage Disposal System11. Firefighting

  • SITE SELECTION CRITERIA LOCATION

    With consideration of both the regional and localcontext Housing projects shall be within suitable sites forhousing and outside potential hazard prone andprotection areas

    ACCESSIBILITY FROM MAJOR TRANSPORTATIONFACILITIES Site shall have an existing legal road right of way froma major thoroughfare

    6

    LOCATION With consideration of both the regional and localcontext Housing projects shall be within suitable sites forhousing and outside potential hazard prone andprotection areas

    ACCESSIBILITY FROM MAJOR TRANSPORTATIONFACILITIES Site shall have an existing legal road right of way froma major thoroughfare

  • SITE SELECTION CRITERIA ZONING AND LAND USE CLASSIFICATION

    Classification shall be Residential as defined underapproved CLUP

    TOPOGRAPHY AND SOIL CHARACTERISTICS Must be relatively flat (or filling requirement forrolling terrain shall not exceed max cost) Slopes should not exceed 15% max gradient. For highdensity, slope should be below 5%. Soil characteristics must conform to the suitabilitystandards for construction by DENR through itsBureau of Mines and Geo-Sciences

    7

    ZONING AND LAND USE CLASSIFICATION Classification shall be Residential as defined underapproved CLUP

    TOPOGRAPHY AND SOIL CHARACTERISTICS Must be relatively flat (or filling requirement forrolling terrain shall not exceed max cost) Slopes should not exceed 15% max gradient. For highdensity, slope should be below 5%. Soil characteristics must conform to the suitabilitystandards for construction by DENR through itsBureau of Mines and Geo-Sciences

  • SITE SELECTION CRITERIA WATER SUPPLY FACILITIES

    Source of potable water should be establishedwhether from local water company, from the ground,or other alternative source

    POWER SUPPLY FACILITIES Presence of power utility company that will serve theneeds of new community

    DRAINAGE Natural waterways and outfalls shall be established onground

    8

    WATER SUPPLY FACILITIES Source of potable water should be establishedwhether from local water company, from the ground,or other alternative source

    POWER SUPPLY FACILITIES Presence of power utility company that will serve theneeds of new community

    DRAINAGE Natural waterways and outfalls shall be established onground

  • SITE PLANNING PRINCIPLES Compliance to all existing laws, rules andregulations on housing (local or national)

    Adoption of the green infrastructure andpreservation of existing natural assets of the land(e.g., trees, ground cover, vegetation, naturalwaterways)

    Promotion of walkable communities

    9

    Compliance to all existing laws, rules andregulations on housing (local or national)

    Adoption of the green infrastructure andpreservation of existing natural assets of the land(e.g., trees, ground cover, vegetation, naturalwaterways)

    Promotion of walkable communities

  • SITE PLANNING PRINCIPLES Promotion of appropriate community facilitiesand infrastructure To serve the socio-economic needs and culturalactivities of the beneficiaries as well as encouragethe implementation of environmentalmanagement programs in the housing sites

    NHA shall provide the minimum requirements forcommunity facilities

    10

    Promotion of appropriate community facilitiesand infrastructure To serve the socio-economic needs and culturalactivities of the beneficiaries as well as encouragethe implementation of environmentalmanagement programs in the housing sites

    NHA shall provide the minimum requirements forcommunity facilities

  • SITE PLANNING PRINCIPLES LAND USE ALLOCATION PER SITE

    66% Saleable Residential housing development

    34% Non-Saleable Circulation/ Road Network Parks and Playgrounds Community Facilities

    11

    LAND USE ALLOCATION PER SITE66% Saleable

    Residential housing development

    34% Non-Saleable Circulation/ Road Network Parks and Playgrounds Community Facilities

  • SITE PLANNING PRINCIPLES LAND USE ALLOCATION PER SITE

    66% Saleable Residential housing development

    34% Non-Saleable Circulation/ Road Network Parks and Playgrounds Community Facilities

    12

    LAND USE ALLOCATION PER SITE66% Saleable

    Residential housing development

    34% Non-Saleable Circulation/ Road Network Parks and Playgrounds Community Facilities

  • SITE PLANNING PRINCIPLES MAXIMUM ALLOWABLE DENSITY PER HECTARE

    Horizontal Development 1-Storey Row House (Loftable) : 160 units/ha. 1-Storey Row House (with loft) : 160 units/ha. 2-Storey Row House : 160 units/ha.

    Vertical Development (Low Rise Buildings) 2-Storey LRB : 225 units/ha. 3-Storey LRB : 245 units/ha. 4-Storey LRB : 325 units/ha. 5-Storey LRB : 405 units/ha.

    13

    MAXIMUM ALLOWABLE DENSITY PER HECTARE Horizontal Development

    1-Storey Row House (Loftable) : 160 units/ha. 1-Storey Row House (with loft) : 160 units/ha. 2-Storey Row House : 160 units/ha.

    Vertical Development (Low Rise Buildings) 2-Storey LRB : 225 units/ha. 3-Storey LRB : 245 units/ha. 4-Storey LRB : 325 units/ha. 5-Storey LRB : 405 units/ha.

  • HOUSING UNIT DESIGN GUIDELINES MINIMUM FLOOR AREA

    22.0 square meters loftable 22.0 square meters with 11 sq.m loft 24.0 square meters (for LRBs) Models for lots along major roads may be modified toinclude provision of a space for home-based economicactivity, but should not exceed cost parameters If new technology or material substitute: must havepassed AITECH (Accreditation of InnovativeTechnologies for Housing)

    HIGHER THANBP 220 MINIMUMHIGHER THAN

    BP 220 MINIMUM

    14

    MINIMUM FLOOR AREA 22.0 square meters loftable 22.0 square meters with 11 sq.m loft 24.0 square meters (for LRBs) Models for lots along major roads may be modified toinclude provision of a space for home-based economicactivity, but should not exceed cost parameters If new technology or material substitute: must havepassed AITECH (Accreditation of InnovativeTechnologies for Housing)

  • STANDARDS FOR COMMUNITY FACILITIES Provision of community facilities shall bedetermined based on the needs of targetbeneficiaries

    Based on existence of public infrastructure within the5-km radius of the site

    For horizontal development: 1 covered basketball court/ multi-purpose center 1 day care center w/ 2 classrooms 1 MRF 1 tricycle terminal

    15

    Provision of community facilities shall bedetermined based on the needs of targetbeneficiaries Based on existence of public infrastructure within the5-km radius of the site

    For horizontal development: 1 covered basketball court/ multi-purpose center 1 day care center w/ 2 classrooms 1 MRF 1 tricycle terminal

  • OTHER FACTORS IN PROJECT PLANNINGFactors that Help Ensure Effective Project Planningand Management for Disaster Resilient Homes:

    Local Inter-Agency Committeewith POs and NGOs organized atthe start of the projectLocal Inter-Agency Committeewith POs and NGOs organized atthe start of the project

    A Planning Team and a ProjectManagement Composite Team wereset up by NHAA Planning Team and a ProjectManagement Composite Team wereset up by NHA

    16

    Local Inter-Agency Committeewith POs and NGOs organized atthe start of the projectLocal Inter-Agency Committeewith POs and NGOs organized atthe start of the project

    Securing of all EnvironmentalClearances and Permits prior toconstruction:*ECC from DENR*Clearance from PHIVOLCS*Devt/ Building Permit from LGUs

    Securing of all EnvironmentalClearances and Permits prior toconstruction:*ECC from DENR*Clearance from PHIVOLCS*Devt/ Building Permit from LGUs

    A Planning Team and a ProjectManagement Composite Team wereset up by NHA

    Community Representatives weremade part of project monitoringduring and after constructionCommunity Representatives weremade part of project monitoringduring and after construction

    Individual beneficiaries accepttheir housing units prior topayment to ContractorsIndividual beneficiaries accepttheir housing units prior topayment to Contractors

  • 22 SQ. M. ROW HOUSE MODEL FOR TYPHOON22 SQ. M. ROW HOUSE MODEL FOR TYPHOONYOLANDA VICTIMSYOLANDA VICTIMS (WITH 11 SQ. M. LOFT)(WITH 11 SQ. M. LOFT)

    LOT SIZE:40 sq. m.

    (10.00m x 4.00m)BUILDING

    FOOTPRINT:22 sq. m.

    (5.50m x 4.00m)TOTAL FLOOR AREA: 33 sq. m.(GROUND FLOOR AND LOFT)

    17

    REVISED 06 MAR 2014

    LOT SIZE:40 sq. m.

    (10.00m x 4.00m)BUILDING

    FOOTPRINT:22 sq. m.

    (5.50m x 4.00m)TOTAL FLOOR AREA: 33 sq. m.(GROUND FLOOR AND LOFT)

  • DISASTER RESILIENT HOUSING STRUCTURAL DESIGN STANDARDSDESIGN PARAMETER ONE-STOREY TWO- STOREY 3-STOREYS OR

    MOREWIND LOAD 250 KPH 250 KPH 250 KPHSTRENGTH OF WALLANDSUPERSTRUCTURE

    3,000 PSI 3,000 PSI 3,000 PSI

    22 SQ. M. ROW HOUSE MODEL FOR TYPHOON22 SQ. M. ROW HOUSE MODEL FOR TYPHOONYOLANDA VICTIMSYOLANDA VICTIMS (WITH 11 SQ. M. LOFT)(WITH 11 SQ. M. LOFT)

    STRENGTH OF WALLANDSUPERSTRUCTURESOIL BEARINGCAPACITY

    95 KPA 95 KPA 95 KPA

    SEISMIC LOAD ZONE 4 ZONE 4 ZONE 4LOADINGS 50 PSF 50 PSF 50 PSFFIRE RESISTANCE 2 HOURS 2 HOURS 2 HOURSThis is one of the outputs generated from the consultation meetings of theNHA TWG on Disaster-Resilient Housing in November to December 2013.

  • PROPOSED LOT SIZE:40 sq. m. (10.00m x 4.00m)

    22 SQ. M. ROW HOUSE MODEL FOR TYPHOON22 SQ. M. ROW HOUSE MODEL FOR TYPHOONYOLANDA VICTIMSYOLANDA VICTIMS (WITH 11 SQ. M. LOFT)(WITH 11 SQ. M. LOFT)

    SITE DEVELOPMENT PLAN

  • GROUND FLOOR AREA22 sq. m. (5.50m x 4.00m)

    22 SQ. M. ROW HOUSE MODEL FOR TYPHOON22 SQ. M. ROW HOUSE MODEL FOR TYPHOONYOLANDA VICTIMSYOLANDA VICTIMS (WITH 11 SQ. M. LOFT)(WITH 11 SQ. M. LOFT)

    GROUND FLOOR PLAN

  • LOFT FLOOR AREA11 sq. m. (2.75m x 4.00m)

    22 SQ. M. ROW HOUSE MODEL FOR TYPHOON22 SQ. M. ROW HOUSE MODEL FOR TYPHOONYOLANDA VICTIMSYOLANDA VICTIMS (WITH 11 SQ. M. LOFT)(WITH 11 SQ. M. LOFT)

    LOFT FLOOR PLAN

  • 22 SQ. M. ROW HOUSE MODEL FOR TYPHOON22 SQ. M. ROW HOUSE MODEL FOR TYPHOONYOLANDA VICTIMSYOLANDA VICTIMS (WITH 11 SQ. M. LOFT)(WITH 11 SQ. M. LOFT)

    CROSS SECTION

  • 22 SQ. M. ROW HOUSE MODEL FOR TYPHOON22 SQ. M. ROW HOUSE MODEL FOR TYPHOONYOLANDA VICTIMSYOLANDA VICTIMS (WITH 11 SQ. M. LOFT)(WITH 11 SQ. M. LOFT)

    LONGITUDINAL SECTION

  • 22 SQ. M. ROW HOUSE MODEL FOR TYPHOON22 SQ. M. ROW HOUSE MODEL FOR TYPHOONYOLANDA VICTIMSYOLANDA VICTIMS (WITH 11 SQ. M. LOFT)(WITH 11 SQ. M. LOFT)

    FRONT ELEVATION

  • 22 SQ. M. ROW HOUSE MODEL FOR TYPHOON22 SQ. M. ROW HOUSE MODEL FOR TYPHOONYOLANDA VICTIMSYOLANDA VICTIMS (WITH 11 SQ. M. LOFT)(WITH 11 SQ. M. LOFT)

    REARELEVATION

  • 22 SQ. M. ROW HOUSE MODEL FOR TYPHOON22 SQ. M. ROW HOUSE MODEL FOR TYPHOONYOLANDA VICTIMSYOLANDA VICTIMS (WITH 11 SQ. M. LOFT)(WITH 11 SQ. M. LOFT)

    TYPHOON SHUTTER DETAILSFRONT ELEVATION

  • 22 SQ. M. ROW HOUSE MODEL FOR TYPHOON22 SQ. M. ROW HOUSE MODEL FOR TYPHOONYOLANDA VICTIMSYOLANDA VICTIMS (WITH 11 SQ. M. LOFT)(WITH 11 SQ. M. LOFT)

    TYPHOON SHUTTER DETAILSSECTIONSIDE

    ELEVATION

  • 22 SQ. M. ROW HOUSE MODEL FOR TYPHOON22 SQ. M. ROW HOUSE MODEL FOR TYPHOONYOLANDA VICTIMSYOLANDA VICTIMS (WITH 11 SQ. M. LOFT)(WITH 11 SQ. M. LOFT)

    TYPHOON SHUTTER DETAILSWINDOW SILL DETAILS

  • 22 SQ. M. ROW HOUSE MODEL FOR TYPHOON22 SQ. M. ROW HOUSE MODEL FOR TYPHOONYOLANDA VICTIMSYOLANDA VICTIMS (WITH 11 SQ. M. LOFT)(WITH 11 SQ. M. LOFT)

    CONCRETE GUTTER DETAIL

  • 22 SQ. M. ROW HOUSE MODEL FOR TYPHOON22 SQ. M. ROW HOUSE MODEL FOR TYPHOONYOLANDA VICTIMSYOLANDA VICTIMS (WITH 11 SQ. M. LOFT)(WITH 11 SQ. M. LOFT)

    INCLINED ROOF BEAM DETAILS

  • 22 SQ. M. ROW HOUSE MODEL FOR TYPHOON22 SQ. M. ROW HOUSE MODEL FOR TYPHOONYOLANDA VICTIMSYOLANDA VICTIMS (WITH 11 SQ. M. LOFT)(WITH 11 SQ. M. LOFT)

    PURLIN EMBEDMENT DETAILS

  • 22 SQ. M. ROW HOUSE MODEL FOR TYPHOON22 SQ. M. ROW HOUSE MODEL FOR TYPHOONYOLANDA VICTIMSYOLANDA VICTIMS (WITH 11 SQ. M. LOFT)(WITH 11 SQ. M. LOFT)

    ROOFING SHEETSOVERLAP DETAIL

  • OUTLINE SPECIFICATIONSSTRUCTURAL : RC BEAM, COLUMN & FOOTINGRC WALL FOOTINGRC FLOOR SLAB, 100MM thk. WITH 10mmRSB @ 400mm BOTHWAYSWALLS : 150mm thk. CHB (FIREWALL)

    100mm thk. CHB, PLASTER FINISH (EXTERIOR)100mm thk. CHB, TOOL JOINT FINISH (INTERIOR)

    ROOFING : 0.404mm thk CORR. G.I. ROOFING SHEETS at 82.0mm X 50mm X 150mm C-PURLINS WITH12mm SAGROD @ MIDPOINT

    DOORS(OPTIONAL) : 1 FLUSH DOOR TYPE1 PANEL DOOR TYPE1 PVC DOOR TYPEWINDOWS (OPTIONAL) : ALUMINUM JALOUSIE TYPE with TYPHOON SHUTTERS

    : 4 x 8 x 8 CONCRETE LOUVER BLOCKSFINISHES : EXTERIOR WALL PLASTERED AND PAINTED FINISH

    T & B FLOOR 200mm X 200mm FLOOR TILESPLUMBING : WATER LINE uPVC PIPES

    SANITARY & DRAINAGE LINES PVC PIPESTOILET BOWL PAIL FLUSH TYPE LAVATORY

    SEPTIC TANK : PURIFYING POLYTHYLENE SEPTIC TANK

    22 SQ. M. ROW HOUSE MODEL FOR TYPHOON22 SQ. M. ROW HOUSE MODEL FOR TYPHOONYOLANDA VICTIMSYOLANDA VICTIMS (WITH 11 SQ. M. LOFT)(WITH 11 SQ. M. LOFT)

    OUTLINE SPECIFICATIONSSTRUCTURAL : RC BEAM, COLUMN & FOOTINGRC WALL FOOTINGRC FLOOR SLAB, 100MM thk. WITH 10mmRSB @ 400mm BOTHWAYSWALLS : 150mm thk. CHB (FIREWALL)

    100mm thk. CHB, PLASTER FINISH (EXTERIOR)100mm thk. CHB, TOOL JOINT FINISH (INTERIOR)

    ROOFING : 0.404mm thk CORR. G.I. ROOFING SHEETS at 82.0mm X 50mm X 150mm C-PURLINS WITH12mm SAGROD @ MIDPOINT

    DOORS(OPTIONAL) : 1 FLUSH DOOR TYPE1 PANEL DOOR TYPE1 PVC DOOR TYPEWINDOWS (OPTIONAL) : ALUMINUM JALOUSIE TYPE with TYPHOON SHUTTERS

    : 4 x 8 x 8 CONCRETE LOUVER BLOCKSFINISHES : EXTERIOR WALL PLASTERED AND PAINTED FINISH

    T & B FLOOR 200mm X 200mm FLOOR TILESPLUMBING : WATER LINE uPVC PIPES

    SANITARY & DRAINAGE LINES PVC PIPESTOILET BOWL PAIL FLUSH TYPE LAVATORY

    SEPTIC TANK : PURIFYING POLYTHYLENE SEPTIC TANK

  • 22 SQ. M. ROW HOUSE MODEL FOR TYPHOON22 SQ. M. ROW HOUSE MODEL FOR TYPHOONYOLANDA VICTIMSYOLANDA VICTIMS (WITH 11 SQ. M. LOFT)(WITH 11 SQ. M. LOFT)

    STRUCTURAL DRAWINGS

    INCREASE BEAM WIDTH FROM150mmto175mm

    INCREASE SIZE OF REINFORCING STEELBARS FROM12 mm

    TO16 mm DIAMETER

  • DPWH COMMENTS AND RECOMMENDATIONS

    22 SQ. M. ROW HOUSE MODEL FOR TYPHOON22 SQ. M. ROW HOUSE MODEL FOR TYPHOONYOLANDA VICTIMSYOLANDA VICTIMS (WITH 11 SQ. M. LOFT)(WITH 11 SQ. M. LOFT)

    STRUCTURAL DRAWINGS

    INCREASE COLUMN WIDTH FROM150mmto175mmINCREASE SIZE OF LOFT WOODEN FLOORJOISTS FROM2 x 3 to2 x 6

  • DPWH COMMENTS AND RECOMMENDATIONS

    22 SQ. M. ROW HOUSE MODEL FOR TYPHOON22 SQ. M. ROW HOUSE MODEL FOR TYPHOONYOLANDA VICTIMSYOLANDA VICTIMS (WITH 11 SQ. M. LOFT)(WITH 11 SQ. M. LOFT)

    STRUCTURAL DRAWINGSCHANGE ROOFING SCREWS FROM

    TEKSCREW TO J-BOLT

  • DPWH COMMENTS AND RECOMMENDATIONS

    22 SQ. M. ROW HOUSE MODEL FOR TYPHOON22 SQ. M. ROW HOUSE MODEL FOR TYPHOONYOLANDA VICTIMSYOLANDA VICTIMS (WITH 11 SQ. M. LOFT)(WITH 11 SQ. M. LOFT)

    ARCHITECTURAL DRAWINGS

    REVISED STAIR RISER HEIGHT TOACCOMMODATE LARGER FLOOR JOIST

    AND BEAMINCREASE FLOOR TO FLOOR HEIGHT TOACCOMMODATE LARGER FLOOR JOISTAND BEAM (FROM 5.30M TO 5.50M)

  • COMPARATIVE ANALYSIS22 sq.m.LOFTABLEROWHOUSE

    22 sq.m.ROWHOUSEWITH LOFT

    COST Php 125,000.00 Php 219,723.63TOTAL FLOOR AREA 22sq.m. 33 sq.m.

    (22 sq.m. G/F AREAand 11 sq.m. LOFT)

    22 SQ. M. ROW HOUSE MODEL FOR TYPHOON22 SQ. M. ROW HOUSE MODEL FOR TYPHOONYOLANDA VICTIMSYOLANDA VICTIMS (WITH 11 SQ. M. LOFT)(WITH 11 SQ. M. LOFT)

    COST Php 125,000.00 Php 219,723.63TOTAL FLOOR AREA 22sq.m. 33 sq.m.

    (22 sq.m. G/F AREAand 11 sq.m. LOFT)

    COST PER SQ. M. Php 5,681.81 Php 6,658.29

  • 22 sq.m. LOFTABLEROWHOUSE

    22 sq.m. ROWHOUSEWITH LOFT

    ARCHITECTURALArchitectural Features Structural Provision

    for Loft and StairsLoft, Stairs, WoodenTyphoon Shutters

    COMPARATIVE ANALYSIS

    22 SQ. M. ROW HOUSE MODEL FOR TYPHOON22 SQ. M. ROW HOUSE MODEL FOR TYPHOONYOLANDA VICTIMSYOLANDA VICTIMS (WITH 11 SQ. M. LOFT)(WITH 11 SQ. M. LOFT)

    Structural Provisionfor Loft and Stairs

    Loft, Stairs, WoodenTyphoon Shutters

    G/F Floor to LoftFloor Finish Height

    2.40meters 2.60meters

    Gutter No Gutter andDownspout

    Concrete Gutter(3 inches thick) andDownspout

    Height of Firewall 4.80meters 5.80metersRoof Thickness 0.30millimetersthk.

    Corrugated GI Sheet0.40millimetersthk.Corrugated GI Sheet

    Roof Purlins 1.2 x 100 x 50mm 2.0 x 150 x 65mm

  • 22 sq.m. LOFTABLEROWHOUSE

    22 sq.m. ROWHOUSEWITH LOFT

    STRUCTURALColumn Size 200 x 150 mm, with

    4-12 mm reinforcingbar

    250 x 175 mm, with4-16 mm reinforcingbar

    COMPARATIVE ANALYSIS

    22 SQ. M. ROW HOUSE MODEL FOR TYPHOON22 SQ. M. ROW HOUSE MODEL FOR TYPHOONYOLANDA VICTIMSYOLANDA VICTIMS (WITH 11 SQ. M. LOFT)(WITH 11 SQ. M. LOFT)

    200 x 150 mm, with4-12 mm reinforcingbar

    250 x 175 mm, with4-16 mm reinforcingbar

    Beam Size B-1: 250 x 150 mm,with 4-12 mm reinforcing bar

    B-1 and B-3:300 x 175 mm andB-2: 250 x 175 mm,with4-16 mm reinforcingbar

    Footing Size 400 x 400mm 800 x 800mmWall Footing Size 300mm 400mm

  • 22 sq.m. LOFTABLEROWHOUSE

    22 sq.m. ROWHOUSEWITH LOFT

    ELECTRICALNumber of LightingOutlets

    3 4

    COMPARATIVE ANALYSIS

    22 SQ. M. ROW HOUSE MODEL FOR TYPHOON22 SQ. M. ROW HOUSE MODEL FOR TYPHOONYOLANDA VICTIMSYOLANDA VICTIMS (WITH 11 SQ. M. LOFT)(WITH 11 SQ. M. LOFT)

    Number of LightingOutletsNumber ofConvenience Outlets

    3 4

    Number of Switches 2 2Service Entrance 2-5.5 mm THW +

    1-3.5 mm TW in 20mm PVC CONDUIT

    2-5.5 mm THHN +1-5.5 mm THHN(G) in 20 mm RSCCONDUIT

  • DESCRIPTION MATERIALCOST LABOR COSTESTIMATED

    DIRECT COSTTOTAL INDIRECT

    COST TOTAL COST

    I. EARTHWORKSSUB-TOTAL 2,418.00 1,943.63 4,361.63 610.63 4,972.25

    II. CONCRETE/STRUCTURAL WORKSSUB-TOTAL 65,420.75 19,135.65 84,556.41 11,837.90 96,394.30

    III. FORMWORKSSUB-TOTAL 3,460.00 720.78 4,180.78 585.31 4,766.09

    IV. ROOFING WORKSSUB-TOTAL 16,105.00 3,952.28 20,057.28 2,808.02 22,865.30

    22 SQ. M. ROW HOUSE MODEL FOR TYPHOON22 SQ. M. ROW HOUSE MODEL FOR TYPHOONYOLANDA VICTIMSYOLANDA VICTIMS (WITH 11 SQ. M. LOFT)(WITH 11 SQ. M. LOFT)

    SUB-TOTAL 16,105.00 3,952.28 20,057.28 2,808.02 22,865.30V. DOORS AND JAMBS

    SUB-TOTAL 13,000.00 1,741.89 14,741.89 2,063.86 16,805.75VI. WINDOWS

    SUB-TOTAL 7,008.00 1,321.43 8,329.43 1,166.12 9,495.55VII. PLUMBING WORKS

    SUB-TOTAL 14,557.32 4,805.39 19,362.70 2,710.78 22,073.48VIII. ELECTRICAL WORKS

    SUB-TOTAL 12,881.00 4,127.43 17,008.43 2,381.18 19,389.61IX. ARCHITECTURAL WORKS

    SUB-TOTAL 17,880.74 2,260.76 20,141.49 2,819.81 22,961.30

    TOTAL 152,730.81 40,009.22 192,740.02 26,983.60 219,723.63

  • THE DPWH APPROVAL OF THE PLAN IS BASED ONTHE REVIEW OF DESIGN CONCEPT AND DESIGNANALYSIS SUBMITTED BY NHA.

    CLOSE SUPERVISION DURING CONSTRUCTIONSHOULD BE UNDERTAKEN BY NHA TO ENSURECOMPLIANCE TO THE APPROVED PLANS.

    SUFFICIENT TESTING OF MATERIALS SHOULD BECONDUCTED TO VERIFY COMPLIANCE TO STANDARDDPWH STANDARDS.

    DPWH NOTES

    22 SQ. M. ROW HOUSE MODEL FOR TYPHOON22 SQ. M. ROW HOUSE MODEL FOR TYPHOONYOLANDA VICTIMSYOLANDA VICTIMS (WITH 11 SQ. M. LOFT)(WITH 11 SQ. M. LOFT)

    THE DPWH APPROVAL OF THE PLAN IS BASED ONTHE REVIEW OF DESIGN CONCEPT AND DESIGNANALYSIS SUBMITTED BY NHA.

    CLOSE SUPERVISION DURING CONSTRUCTIONSHOULD BE UNDERTAKEN BY NHA TO ENSURECOMPLIANCE TO THE APPROVED PLANS.

    SUFFICIENT TESTING OF MATERIALS SHOULD BECONDUCTED TO VERIFY COMPLIANCE TO STANDARDDPWH STANDARDS.