Page 1: Date MY HOME LIGHT AND AUTOMATION. 2 Division Appareillage et Système Résidentiels Apartment Villa My home SCS bus system was designed with:  system

Date

MY HOME LIGHT AND AUTOMATION

Page 2: Date MY HOME LIGHT AND AUTOMATION. 2 Division Appareillage et Système Résidentiels Apartment Villa My home SCS bus system was designed with:  system

2Division Appareillage et Système Résidentiels

ApartmentVilla

My home SCS bus system was designed with:system dimension and features for houses (residential)installation method close to the traditional installationaesthetic integrated with wd and des offer

Introduction

Page 3: Date MY HOME LIGHT AND AUTOMATION. 2 Division Appareillage et Système Résidentiels Apartment Villa My home SCS bus system was designed with:  system

3Division Appareillage et Système Résidentiels

L

System compositionNOT ONE GENERAL CENTRAL UNIT

NO CENTRALIZED CONFIGURATION

Power supplyControls

N

Actuators

Loads

27V BUS

Page 4: Date MY HOME LIGHT AND AUTOMATION. 2 Division Appareillage et Système Résidentiels Apartment Villa My home SCS bus system was designed with:  system

4Division Appareillage et Système Résidentiels

SCS bus characteristics27V D.C. NOT POLARIZED POWER SUPPLY AND DIGITAL DATA

Sender

Receiver

Information0 1 0 1 0 1 0 1 0 1 0 1

L230V

N

System composition

Page 5: Date MY HOME LIGHT AND AUTOMATION. 2 Division Appareillage et Système Résidentiels Apartment Villa My home SCS bus system was designed with:  system

5Division Appareillage et Système Résidentiels

Catalogue

USER INTERFACES

ACTUATORS(ON/OFF)

DIMMERS

INTERFACES

ACCESSORIES

Page 6: Date MY HOME LIGHT AND AUTOMATION. 2 Division Appareillage et Système Résidentiels Apartment Villa My home SCS bus system was designed with:  system

6Division Appareillage et Système Résidentiels

SOME MH DEVICE ARE IN COMMON WITH LM SYSTEM.

FOR THIS REASON YOU CAN USE THE LM CONFIGURATION RULES AND SYSTEM LIMITS.

Catalogue

Page 7: Date MY HOME LIGHT AND AUTOMATION. 2 Division Appareillage et Système Résidentiels Apartment Villa My home SCS bus system was designed with:  system

7Division Appareillage et Système Résidentiels

Incandescent

Discharge

Halogen

Fluorescent

LED

Motors ON/OFF

Motors up/downright/left

Loads typology driven: most of the typology

Catalogue

Page 8: Date MY HOME LIGHT AND AUTOMATION. 2 Division Appareillage et Système Résidentiels Apartment Villa My home SCS bus system was designed with:  system

8Division Appareillage et Système Résidentiels

Configuration

Page 9: Date MY HOME LIGHT AND AUTOMATION. 2 Division Appareillage et Système Résidentiels Apartment Villa My home SCS bus system was designed with:  system

9Division Appareillage et Système Résidentiels

Relating to different products or different choices there are 2 main types of configuration:

PHYSICAL CONFIGURATION USING JUMPERSGreen for the address and the blue ones are for functioning mode.

VIRTUAL CONFIGURATIONAvailable ONLY for automation and temperature control system. It is a

SW able to configure the devices through the gateway (MH200N, F454).

Configuration

Page 10: Date MY HOME LIGHT AND AUTOMATION. 2 Division Appareillage et Système Résidentiels Apartment Villa My home SCS bus system was designed with:  system

10Division Appareillage et Système Résidentiels

3° Level

Project & Download:ONLY for Lighting Management.

1° Level

PhysicalUsing jumpers.

81 addresses

A=0-9PL=1-9

Configuration

2° Level

175 addresses

A=0-10PL=0-15

Virtual

Page 11: Date MY HOME LIGHT AND AUTOMATION. 2 Division Appareillage et Système Résidentiels Apartment Villa My home SCS bus system was designed with:  system

11Division Appareillage et Système Résidentiels

Actuator addressing mode

The addresses of the actuator depending by the configuration of the site A and PL.

For each area it is possible to set a max of 9 PL for each Area (max 9).In order to link an actuator to a group, it is necessary to add a jumper in the site G (group).

Socket Jumpers Notes

[A] AreaActuator address

From11 to 99Numeric jumpers 1÷9

[PL] Light point

[M] Mode From 1÷4 Numeric and blue jumpers 1÷9 [G] Group Group address Numeric Jumpers from 1 to 9

Physical configuration

Page 12: Date MY HOME LIGHT AND AUTOMATION. 2 Division Appareillage et Système Résidentiels Apartment Villa My home SCS bus system was designed with:  system

12Division Appareillage et Système Résidentiels

Addressing and control type

Also the control devices have the configuration sockets A and PL in order to set the receiver of the messages (actuators).

Physical configuration

Page 13: Date MY HOME LIGHT AND AUTOMATION. 2 Division Appareillage et Système Résidentiels Apartment Villa My home SCS bus system was designed with:  system

13Division Appareillage et Système Résidentiels

Physical configuration

POINT -POINT CONTROLDirect control to one actuator identified by a “room number” and a “light point number”.

ROOM CONTROLDirect control to all the actuatorsidentified by the same room number (site A).

Page 14: Date MY HOME LIGHT AND AUTOMATION. 2 Division Appareillage et Système Résidentiels Apartment Villa My home SCS bus system was designed with:  system

14Division Appareillage et Système Résidentiels

Physical configuration

GROUP CONTROLDirect control to all the actuatorswhich perform particular functionseven if they belong to differentrooms and are identified by the same“group number”.

Page 15: Date MY HOME LIGHT AND AUTOMATION. 2 Division Appareillage et Système Résidentiels Apartment Villa My home SCS bus system was designed with:  system

15Division Appareillage et Système Résidentiels

Physical configuration

GENERAL CONTROLDirect control to all the system actuators

Page 16: Date MY HOME LIGHT AND AUTOMATION. 2 Division Appareillage et Système Résidentiels Apartment Villa My home SCS bus system was designed with:  system

16Division Appareillage et Système Résidentiels

CONFIGURATION EXAMPLE

Physical configuration

Page 17: Date MY HOME LIGHT AND AUTOMATION. 2 Division Appareillage et Système Résidentiels Apartment Villa My home SCS bus system was designed with:  system

17Division Appareillage et Système Résidentiels

The functioning mode

Physical configuration

Page 18: Date MY HOME LIGHT AND AUTOMATION. 2 Division Appareillage et Système Résidentiels Apartment Villa My home SCS bus system was designed with:  system

18Division Appareillage et Système Résidentiels

The blue jumpers (including also some numbers) are used for the mode of work.

Physical configuration

Page 19: Date MY HOME LIGHT AND AUTOMATION. 2 Division Appareillage et Système Résidentiels Apartment Villa My home SCS bus system was designed with:  system

19Division Appareillage et Système Résidentiels

Controls operation modes

Light functioning modes:

ON timed command

ON command

OFF command

Pushbutton command

ON / OFF command

Automatism functioning modes:

UP / DOWN bistable command

UP / DOWN monostable command

Jumpers

PUL

ON

OFF

O/I

M

1-8

Physical configuration

Page 20: Date MY HOME LIGHT AND AUTOMATION. 2 Division Appareillage et Système Résidentiels Apartment Villa My home SCS bus system was designed with:  system

20Division Appareillage et Système Résidentiels

Physical configuration

CONTROLS for Scheduler

Page 21: Date MY HOME LIGHT AND AUTOMATION. 2 Division Appareillage et Système Résidentiels Apartment Villa My home SCS bus system was designed with:  system

21Division Appareillage et Système Résidentiels

Enable

Disable

Enable/disable

Timed ON 2 sec - 10 min

Blinking (from 0,5 to 5 sec)

Set the adjustment level (dimmer) (from 10 to 90 %)

Scenario recall (from 1 to 9)

SOFT START and SOFT STOP

Recall and program of the scenario module (from 1 to 16)

Door lock control

Sound diffusion control

Timed ON (from 5 sec to 99 min 45 sec)

Auxiliary input management

The “SPEcial” functioning modality

Physical configuration

Page 22: Date MY HOME LIGHT AND AUTOMATION. 2 Division Appareillage et Système Résidentiels Apartment Villa My home SCS bus system was designed with:  system

22Division Appareillage et Système Résidentiels

Using the Virtual Configuration , there are the same configuration rules of the physical one, but there are also some improvement:

Example: F411/4

Physical configuration Virtual configuration

APL1PL2PL3PL4M

A1PL1M1

A2PL2M2

A3PL3M3

A4PL4M4

One area for all the PL.Also the mode of work is

in commonEach PL can became independent from the

others

Virtual configuration

Page 23: Date MY HOME LIGHT AND AUTOMATION. 2 Division Appareillage et Système Résidentiels Apartment Villa My home SCS bus system was designed with:  system

23Division Appareillage et Système Résidentiels

PC Connections Gateway Systems

Web Server - F454

Scheduler- MH200N

Suitcase 3504 o 3503N

Ethe

rnet

cab

le

Virtual configuration

Page 24: Date MY HOME LIGHT AND AUTOMATION. 2 Division Appareillage et Système Résidentiels Apartment Villa My home SCS bus system was designed with:  system

24Division Appareillage et Système Résidentiels

With devices with ID and VIRT labels

Virtual configuration

Devices description

Reference number

Configuration

Page 25: Date MY HOME LIGHT AND AUTOMATION. 2 Division Appareillage et Système Résidentiels Apartment Villa My home SCS bus system was designed with:  system

25Division Appareillage et Système Résidentiels

Basic scenarios configuration

EASY SCENARIOS WITH LIGHTS AND MOTORS

4 scenarios per Unit (command)16 scenarios per DIN module (memory)Configure the device (physical-virtual)Customizable by the end-user (push & learn)

Easy to set-upPush & Learn

Modulo scenari.wmv

Scenario module

4 scenarios command

Page 26: Date MY HOME LIGHT AND AUTOMATION. 2 Division Appareillage et Système Résidentiels Apartment Villa My home SCS bus system was designed with:  system

26Division Appareillage et Système Résidentiels

Memory module

SAVE THE SYSTEM STATE IN BLACK-OUT SITUATION

• It needs an A/PL address• To save address it can be used in area 0

A=PL=

• 1 module for every system

(phisical extension included)

PL

A

1 to 9

0

Memory module

Easy to set-upPush & Learn

Modulo memoria.wmv

Page 27: Date MY HOME LIGHT AND AUTOMATION. 2 Division Appareillage et Système Résidentiels Apartment Villa My home SCS bus system was designed with:  system

27Division Appareillage et Système Résidentiels

INSTALLATION RULES AND

LIMITS

Page 28: Date MY HOME LIGHT AND AUTOMATION. 2 Division Appareillage et Système Résidentiels Apartment Villa My home SCS bus system was designed with:  system

28Division Appareillage et Système Résidentiels

System limits

DISTANCE

ABSORPTION

ADDRESSES LOGICAL LIMITS

PHYSICAL LIMITS

Installation rules and limits

Page 29: Date MY HOME LIGHT AND AUTOMATION. 2 Division Appareillage et Système Résidentiels Apartment Villa My home SCS bus system was designed with:  system

29Division Appareillage et Système Résidentiels

Free BUS cabling topology

Star connections Free connection

Just one rule: no closed ring!

Installation rules and limits

PHYSICAL LIMITS

Page 30: Date MY HOME LIGHT AND AUTOMATION. 2 Division Appareillage et Système Résidentiels Apartment Villa My home SCS bus system was designed with:  system

30Division Appareillage et Système Résidentiels

Power supply Actuator Control

250m MAX 500m MAX

Installation rules and limits

PHYSICAL LIMITS

Page 31: Date MY HOME LIGHT AND AUTOMATION. 2 Division Appareillage et Système Résidentiels Apartment Villa My home SCS bus system was designed with:  system

31Division Appareillage et Système Résidentiels

9 Areas

9 PL for every area

9 x 9 = 81 addresses

LOGICAL LIMITS

Installation rules and limits

Using physical configuration

9 Groups

Page 32: Date MY HOME LIGHT AND AUTOMATION. 2 Division Appareillage et Système Résidentiels Apartment Villa My home SCS bus system was designed with:  system

32Division Appareillage et Système Résidentiels

11 Areas

16 PL for every area

(16 x 11)- 1 = 175 addresses

LOGICAL LIMITS

Installation rules and limits

The address 00 doesn’t exist

Using virtual configuration

255 Groups