Eclipse Tube FiringBurnerModel TFB075
Datasheet 310-211/14/2014
All inputs based on gross calorific values.
Eclipse reserves the right to change the construction and/or configuration of our products at any time without being obliged to adjust earlier supplies accordingly.
Plumbing of air and gas will affect accuracy of orifice readings. All information is based on generally acceptable air and gas piping practices.
1 The low firing rate represents the capability of the burner. Achievement of this rate will be affected by the control method and ratio-regulator used in the system design.
2 Total static air pressure required will be the sum of the differential pressures and the static air pressure, as indicated on pages 3 and 4.
3 Gas pressures shown are for system sizing only. Provisions must be made to supply fuel pressure at the burner fuel input port at least 3" w.c. higher than the differential pressure shown in the tables.
4 Flame rod not available with preheated combustion air (PCA). Contact Eclipse if PCA and propane/butane will be used in combination.
5 All weights are approximate.
ParameterBurner Input 1000’s Btu/h (kW)
400 (117) 500 (146) 600 (176) 750 (220)Low Firing Rate x 1000 Btu/h (kW)1
At 100% excess airWithout Flame Safety 5 (1.5) 5 (1.5) 5 (1.5) 5 (1.5)
With Flame Safety 10 (2.9) 10 (2.9) 10 (2.9) 10 (2.9)
Air Inlet Pressure, "w.c. (mbar)2
Measured between Taps A and B (see pages 3 and 4)8.4 (20.9) 8.3 (20.7) 5.7 (14.2) 6.2 (15.4)
Air Flow, SCFH (Nm3/h)At 15% excess air
4600 (130.3)
5750 (162.8)
6900 (195.4)
8625 (244.2)
Differential Gas Pressure, "w.c. (mbar)3
Measured between Taps C and D(see pages 3 and 4)
Natural Gas 4.3 (10.7) 3.2 (8.0) 2.8 (7.0) 4.4 (11.0)Propane 3.5 (8.7) 2.7 (6.7) 3.9 (9.7) 2.9 (7.2)
Butane 2.6 (6.5) 4.3 (10.7) 3.0 (7.5) 4.8 (12.0)Piping NPT or BSP burner piping is available
Flame Detection4 Flame rod, UV Scanner
Ignition Direct spark ignition (6 kVAC)Fuels For any other mixed gas, contact Eclipse, Inc. Natural gas, propane, butaneMaximum PCA Temperature, °F (°C) 1000 (540)
Weight 5, lbs (kg) 20 to 29 (9 to 13)Approvals
Version 2
Performance Graphs
0
100
200
300
400
500
600
0 150 300 450 600 750
% E
xces
s A
ir
Input (x 1000 BTU/h)
Ignition & Operation Zone
0 45 90 130 175 220Input (kW)
Ignition & Operational Zone
CO emissions are less than 10ppm (corrected to 3% O2)for furnace temperatures between 1400°F and 1800°FEmissions from the burner are influenced by: • fuel type • combustion air temperature • chamber conditions • percent of excess airFor estimates of other emissions, contact Eclipse Inc.
430
380
330
280
230
180
130
801400 1500 1600 1700 1800
NO
x p
pm (C
orre
cted
to 3
% O
2)
Furnace Temperature °F
700°F PCA500°F PCA300°F PCANo PCA
NOx Emission (On ratio)(Natural Gas Fuel, 300,000 Btu/h Input)
Furnace Temperature °C850 950900800
2 Eclipse Tube Firing BurnerTFB075 V2, Datasheet 310-2, 11/14/2014
Performance Graphs (Continued)
0 0
1
3
5
7
Air Orifice ∆p vs. Input (∆p Measured Between Taps A and B)
Natural Gas Orifice ∆p vs. Input(∆p Measured Between Taps C and D)
Propane Orifice ∆p vs. Input(∆p Measured Between Taps C and D)
Butane Orifice ∆p vs. Input(∆p Measured Between Taps C and D)
2
4
6
8
0
1
3
5
7
2
4
6
8
0
1
3
5
7
2
4
6
8
37m
m
34m
m
44mm
42m
m 12.7
mm
14 m
m
10.8
mm
12.7 mm
10.8
mm
9.1
mm
10.8
mm
9.1
mm
0 50 150 250 350 450 550 650 750
0 15 44 73 103 132 161 190 220
Input x 1000 Btu/h
Input kW
0 100 200 300 400 500 600 700 800
0 29 59 88 117 146 176 205 234
Input x 1000 Btu/h
Input kW
0 100 200 300 400 500 600 700 800
0 29 59 88 117 146 176 205 234
Input x 1000 Btu/h
Input kW
0 50 150 250 350 450 550 650 750
0 15 44 73 103 132 161 190 220
Input x 1000 Btu/h
Input kW
1
2
3
4
5
6
7
∆p ("
w.c
. ±10
%)
8
9
5
10
15
20
∆p (m
bar ±
10%
)
5
10
15
20
∆p (m
bar ±
10%
)
5
10
15
20
∆p (m
bar ±
10%
)
5
10
15
20
∆p (m
bar ±
10%
)
∆p ("
w.c
. ±10
%)
∆p ("
w.c
. ±10
%)
∆p ("
w.c
. ±10
%)
Datasheet 310-2, 11/14/2014
Dimensions and SpecificationsDimensions in mm (inches)
0
5
10
15
20
25
0 200 300 400 500 600Input (x 1,000 Btu/h)
800700
Pres
sure
("w
.c.)
Static Pressure at the Air Inlet (no air orifice)
70°F
400°F
800°F
100
0 50 100 150 200Input (kW)
0
10
20
30
40
50
60Pr
essu
re (m
bar)
Tap A
Tap B
70(2.8)
97.5(3.8)
Peepsight orUV Scanner Adapter
B
B
219.8(8.7)
85(3.3)
176.6(7.0)
Ø88.9(3.5)
Spark Rod orFlame Rod
Tap DTap C
Air Tube Length76-609 mm (3-24 in.)
in 25 mm (1 in. increments)
45º
4x 90º
Ø136(5.4)
4x Ø12(4x Ø0.5)Peepsight or
Spark RodSection B-B
100(3.9)
Tap D
Tap C
118(4.6)
Tap B
277(10.9)
Air Inlet2” NPT / Rc 2
Fuel Inlet3/4” NPT /Rc 0.75
Non-PCA Option
PCA Option(includes tap extensions)
Available air tube lengths are the same as Non-PCA Option.
© Eclipse, Inc. All Rights Reserved