data sheet: tempower 2 acb for 800v dc - terasaki · ar650-ndh drawout type outline dimensions c p:...

3
0.08 10 10000 5000 500 460 380 60 AGR over-current release cannot be used for DC. Please prepare DC over-current relay and connect with shunt trip device. The time constant (L/R) of the circuit should be: less than 2.0ms nearby rated current less than 15ms for short circuit Vertical terminals only. Available Accessories: Page 1 of 3 - Auxiliary switch (4AB, 7AB, 10AB) - Position switch (2C, 4C) - Motor Operator (AC 100-240V, DC 24V, DC 48V, DC 100-200V) - Shunt (AC 100-240V, DC 24V, DC 48V, DC 100-200V) - UVT (AC 100-240V, DC 24V, DC 48V, DC 100-200V) - Mechanical Interlock - Horizontal and Vertical - Key Locking - Shutter Padlock (additional unit) - Fixing Bolt - Lifting Plates - Spring Charge Switch - Trip Indication Switch - Operation Counter - IP Cover - Door Flange - Door Interlock Type AR650-NDH DC 5000 5000 1000 3 800 30/30 - - - 12 30 120 125 75 200 799 DATA SHEET: TEMPOWER 2 ACB FOR 800V DC Types: AR650-NDH

Upload: others

Post on 23-Oct-2020

10 views

Category:

Documents


0 download

TRANSCRIPT

  • 0.08

    10

    100005000

    500

    46038060

    AGR over-current release cannot be used for DC. Please prepare DC over-current relay and connect with shunt trip device.

    The time constant (L/R) of the circuit should be:less than 2.0ms nearby rated currentless than 15ms for short circuit

    Vertical terminals only.

    Available Accessories:

    Page 1 of 3

    - Auxiliary switch (4AB, 7AB, 10AB)- Position switch (2C, 4C)- Motor Operator (AC 100-240V, DC 24V, DC 48V, DC 100-200V)- Shunt (AC 100-240V, DC 24V, DC 48V, DC 100-200V)- UVT (AC 100-240V, DC 24V, DC 48V, DC 100-200V)- Mechanical Interlock - Horizontal and Vertical- Key Locking- Shutter Padlock (additional unit)

    - Fixing Bolt- Lifting Plates- Spring Charge Switch- Trip Indication Switch- Operation Counter- IP Cover- Door Flange- Door Interlock

    Type AR650-NDHDC

    5000

    5000

    1000

    3

    800

    30/30---

    12

    30

    120

    125

    75

    200

    799

    DATA SHEET: TEMPOWER 2 ACB FOR 800V DC Types: AR650-NDH

  • ¶2: Panel cut should be 339 mm not 335 mm when the doorflange is used.

    • N represents the neutral pole of 4-pole ACBs.

    555(4P)

    N

    50

    R116

    335

    ¶2

    PC PC

    PC

    30

    6546

    0

    235 235

    57.5 18 1880

    235

    2

    540.5(4P)305.5(3P)

    555(4P)320(3P)

    577(4P)342(3P)

    640(4P)405(3P)

    512.5(4P)277.5(3P)

    520

    392.5

    166

    94

    457

    320(3P)435

    238

    4-ø14

    60

    435

    250

    N

    27

    Rear panel cut

    Front panel cut

    Front panel

    Maintenance space

    Panel cutout

    draw-out handleM8 screwearth terminal

    Mounting hole

    DATA SHEET: TEMPOWER 2 ACB FOR 800V DC Types: AR650-NDH

    Drawout Type Outline Dimensions CP: ACB Front cover center line

    AR650-NDH only available in 3 Pole

    Page 2 of 3

    Page 3 of 5

  • 2

    23

    1530

    3030

    15

    120

    1530

    3030

    15

    165

    8012

    0

    4-φ 11

    15

    1221

    17

    380 30

    21255

    308

    440

    95

    33

    14

    500

    490

    460

    329

    35 (conductor overlap max.)

    Rear panel

    Rear panel

    Front panel

    Maintenance space

    Control circuit terminal cover (optional)

    TEST position

    CONNECTED position

    ISOLATED positionON-OFF button cover

    M8 screwearth terminal

    2X2-ø20Lifting hole

    Details

    DATA SHEET: TEMPOWER 2 ACB FOR 800V DC Types: AR650-NDH

    Drawout Type Outline Dimensions

    Page 3 of 5Page 3 of 5

    Page 3 of 3