DATA SHEET FOR POWER AND MOTOR CONTROL CENTRE Mangala Field Development Project Enchance Oil Recovery Pilot (EORP)Project B 12.02.2010 NAK BPR ADS - A 08.02.2010 NAK BPR ADS - REV DATE BY CHK'D APPR CLIENT TOTAL OR PARTIAL REPRODUCTION AND / OR UTILISATION OF THIS DOCUMENTATION ARE FORBIDDEN WITHOUT PRIOR WRITTEN AUTHORIZATION OF THE OWNER DESCRIPTION Issued for Review / Comments Issued for DIC/IDR Document No: EORP-EL-J-001

Upload: vaithy2011

Post on 12-Apr-2015

97 views

Category:

Documents


16 download

DESCRIPTION

For Panel

TRANSCRIPT

Page 1: Data Sheet & SLD

DATA SHEET

FOR

POWER AND MOTOR CONTROL CENTRE

Mangala Field Development Project

Enchance Oil Recovery Pilot (EORP)Project

B 12.02.2010 NAK BPR ADS -

A 08.02.2010 NAK BPR ADS -

REV DATE BY CHK'D APPR CLIENT

TOTAL OR PARTIAL REPRODUCTION AND / OR UTILISATION OF THIS DOCUMENTATION ARE FORBIDDEN WITHOUT PRIOR WRITTEN AUTHORIZATION OF THE OWNER

DESCRIPTION

Issued for Review / Comments

Issued for DIC/IDR

Document No:

EORP-EL-J-001

Page 2: Data Sheet & SLD

DOC. NO: EORP-EL-J-001 2 of 4

SERVICE: Power & Motor Control Centre TAG NO : EORP-PMCC NO OF UNITS: 1

1. GENERAL DATA

Installation : Onshore

Ref. Specification No. : EORP-EL-S-001 Altitude : Less than 1000 m m

Codes and Standard : Location Indoor

IS IEC Outdoor

Ambient temp. : Max/Min : Outdoor

Design ambient temp. : Seismic Zone : Zone - III

Relative Humidity :

Atmosphere : Desert area, Humid and Corrosive

2. RATING 4.ACCESSORIES

Supply Voltage & Variation : 415V (+/-) 10% Panel Space Heater Name Plate as per specification

Frequency & Variation : 50HZ (+/-) 5% Grounding Stud Lifting Lugs

Number of Phases : 3Ph + Netrual FloorFrame Internal Receptacle

System Earthing : Reistance Earthed, 750mA Limit Internal Lighting Breaker Trolley

Bus Bar Rating : 1200A Anchor Bolts Colour mark for Buses

Supply system fault level (MVA/KA): 50 kA for 1 sec Fuse Pullers Closing Rectifier

Control Voltage : 240V, AC

Heater Circuit : 240V, AC 5.ADDITIONAL TEST

3. TYPE According to Specification EORP-EL-001

Applied Standard

Enclosure Metal Enclosed 1

DATA SHEET

FOR POWER AND MOTOR CONTROL CENTRE

PAGE NO:

23 TO 74 %

50 / -2 deg. C.

42/10.6 deg C

Metal Clad 2

3

Degree of Protection IP 42

6.OTHER

Circuit Breaker MCCB (Outgoing)

Air Circuit Breaker (Incomers) Painting Colour Manufacture's Standard

Unit Mounting Single Front As per Spec. (SUPP-ST-S-001)

Double Front Painting Method Manufacture's Standard

LV Switchboard (Incoming, Outgoing) Draw Out Type (Incomers) As per Spec. (SUPP-ST-S-001)

Fixed Type (Outgoing)

Form of Construction Form 4

Configuration / Feeder Arrangement

Feeder List

(EORP-EL-K-001) 1. All status signals from PMCC to Instrument PLC will be through potential

Key Single Line Diagram free contacts.

(EORP-EL-D-001) 2. ON / OFF commands from instrument PLC to individual motor starters shall

be through potential free contacts.

Protective Relay 3. ESD Trip commands from Instrument PLC to air circuit breakers shall be

Microprocessor based through 24 VDC powered signal.

Incoming feeder connection point Top

Bottom

Cable

Bus Duct

Main Busbar Location

Bottom

Bottom

Cable

7. NOTES

Electromechanical /

Top

Outgoing feeder connection point

12.02.2010 ADS08.02.2010 ADS

Rev Date ApprovedPrepared Description Checked

AB

NAK Issued for DIC/IDR BPRNAK Issued for Review / Comments BPR

Page 3: Data Sheet & SLD

DOC. NO: EORP-EL-J-001 3 of 4

SERVICE: Power & Motor Control Centre TAG NO : EORP-PMCC NO OF UNITS: 1

1 Equipment Tag No. : 18.7 Mechanical life :

2 Make : 19 CONTACTOR

3 Type / Designation : 19.1 Rated Current

4 Overall dimensions of PMCC - AC-3 Duty : A

- Width : mm - AC-4 Duty : A

- Depth : mm 19.2 Making Capacity :

- Height : mm 19.3 Breaking Capacity :

5 Total Weight of PMCC : Kg 19.4 Coil consumption - Pick up : VA at pf

6 Weight and Dimensions of largest 19.5 Coil consumption - Hold on : VA at pf

shipping section 19.6 No. of auxiliary contacts : NO + NC

- Weight : Kg 20 THERMAL OVERLOAD RELAY

- Width : mm 20.1 Setting range :

- Depth : mm 20.2 Single phasing preventor :

- Height : mm 20.3 Temperature compensation :

7 Recommended clearances for PMCC feature

- Front : mm 21 Heat Load of PMCC : Watts

- Rear : mm 22 AIR CIRCUIT BREAKERS

- Top : mm 22.1 Rated current : A

- Sides : mm 22.2 Rated SC making capacity - Icm : kA

8 Clearance in air 22.3 Rated service SC breaking : kA

8.1 Phase to Phase : mm capacity - Ics

8.2 Phase to Earth : mm 22.4 Type of built-in control unit :

9 Main Horizontal Busbars 22.5 Auxiliary contacts :

DATA SHEET

FOR POWER AND MOTOR CONTROL CENTRE

PAGE NO:

DATA TO BE FILLED BY VENDOR

9.1 Main busbar current rating : A 22.6 Closing & Trip Coil

9.2 Main busbar size : sqmm - Voltage :

9.3 Main bas bar material : Cu - Power Consumption :

9.4 : 23 Protective relays provided as : Yes / No

10 Vertical Busbars per SLD

10.1 Busbar current rating : 24 Indications / Alarms provided as : Yes / No

10.2 Busbar size : sqmm per SLD

10.3 : 25 Interlocks and synchronizing : Yes / No

11 Insulating material of busbars : facility privided as per SLD

12 Earth Busbars 26 Total Power Consumption for :

12.1 Earth bus size : mm space heaters in PMCC

12.2 Earth bus material : Cu 27 Mechanical life :

13 1 min. power frequency voltage : kV 28 Cable Glands with check nuts

14 1.2/50 μs Impulse withstand voltage : kV 28.1 Material / Type :

15 1 sec. short circuit withstand : kA 28.2 Provided for all I/C & O/G :

capacity power & control cables

16 Peak dynamic withstand : kA 29 Cable Lugs

capacity 29.1 Material / Type :

17 Safety shutter provided for test : Yes / No 29.2 Provided for all I/C & O/G :

and drawout positions power & control cables

18 MCCB

18.1 Rated current : A

18.2 Rated SC making capacity - Icm : kA

18.3 Rated service SC breaking :

capacity - Ics

18.4 Thermal release setting range :

18.5 Short circuit release :

setting range Note:

18.6 Accessories Typical control schematic drawings for each type of feeder (motor feeder

- Auxiliary contacts : as well as power feeder) shall be prepared by vendor and submitted for

- Shunt release : Purchaser’s review and approval.

- Undervoltage release :

- Trip alarm contacts :

- Rotary operating mechanism :

Busbar material

Top

A

kA

Main bus bar location

Cu

12.02.2010 ADS08.02.2010 ADS

Rev Date Approved

BPR

Prepared CheckedChecked

NAKIssued for DIC/IDR

Description

A NAK BPRBPRB Issued for Review / Comments

Page 4: Data Sheet & SLD

DOC. NO: EORP-EL-J-001 4 of 4

SERVICE: Power & Motor Control Centre TAG NO :EORP-PMCC NO OF UNITS: 1

S.No

1 Electromechanical Relays Alstom / ABB / Siemens / Easun Reyrolle

2 Auxiliary relays Alstom / ABB / Siemens / Easun Reyrolle

3 Breaker control switch Alstom / RECOM

4 Power switches Alstom / L&T / Siemens / Stromberg / Control & switchgear

5 Control switches Alstom / L&T / Siemens / Kaycee

6 DC Switches Kaycee or equivalent

7 CTs / PTs AEP / Precise Electrical / Prayog / Silkans / Pragati

8 Meters AEP / Simco / IMP / MECO

9 PB & indicating lights Siemens / L&T / Tecknic / BCH

10 Air circuit breakers L&T / Siemens / Alstom / Control & switchgear

11 Contactors L&T / Siemens / BCH / Telemechanique

12 Bimetallic relay L&T / Siemens / BCH / Telemechanique

13 Heavy duty switches / fuse switches / motor duty switches Siemens / L&T / Alstom

14 MCB MDS / HAVELL / Indo-Asian

15 Timer for re-acceleration BCH / Concord

16 Power fuse & base Siemens / L&T / Alstom

17 Control fuse & base Siemens / L&T / Alstom

18 MCCB Siemens / L&T / Alstom

19 Terminals ELMEX / TOSHA / Connectwell

20 Control transformer INDCOIL / AEP / Kappa / Precise Electrical

21 Battary (Ni-Cd) AMCO / HBL-NIFE

22 Battery charger HBL-NIFE / Chhabi / Universal Industrial Products

VendorItem

MAKE OF EQUIPMENT / COMPONENTS

DATA SHEET

FOR POWER AND MOTOR CONTROL CENTRE

PAGE NO:

23 Cable glands Comet / Baliga / Flexpro

24 Cable lugs Dowell or equivalent

12.02.2010 ADS08.02.2010 ADS

Rev Date ApprovedPrepared Description Checked

B NAK Issued for Review / Comments BPRA NAK Issued for DIC/IDR BPR

Page 5: Data Sheet & SLD

DATA SHEET

FOR

DISTRIBUTION BOARDS

Mangala Field Development Project

Enchance Oil Recovery Pilot (EORP)Project

B 12.02.2010 NAK BPR ADS -

A 08.02.2010 NAK BPR ADS -

REV DATE BY CHK'D APPR CLIENT

TOTAL OR PARTIAL REPRODUCTION AND / OR UTILISATION OF THIS DOCUMENTATION ARE FORBIDDEN WITHOUT PRIOR WRITTEN AUTHORIZATION OF THE OWNER

DESCRIPTION

Issued for Review / Comments

Issued For DIC/IDR

Document No:

EORP-EL-J-002

Page 6: Data Sheet & SLD

DOC. NO: EORP-EL-J-002 2 of 3

SERVICE: Power DB TAG NO : EORP-PDB NO OF UNITS: 1

Heat Tracing DB EORP-HTDB 1

Lighting DB EORP-LDB 1

1. GENERAL DATA

Installation : Onshore

Ref. Specification No. : EORP-EL-S-002 Altitude : Less than 1000 m m

Codes and Standard : Location Indoor

IS IEC Outdoor

Ambient temp. : Max/Min : Outdoor

Design ambient temp. : Seismic Zone : Zone - III

Relative Humidity :

Atmosphere : Desert area, Humid and Corrosive

2. RATING 4.ACCESSORIES

Supply Voltage & Variation : 415V (+/-) 10% Panel Space Heater Name Plate as per specification

Frequency & Variation : 50HZ (+/-) 5% Grounding Stud Lifting Lugs

Number of Phases : 3Ph + Netrual Wall mouting Internal Receptacle

System Earthing : Reistance Earthed, 750mA Limit Internal Lighting Breaker Trolley

Bus Bar Rating : As per SLD Anchor Bolts Colour mark for Buses

Supply system fault level (MVA/KA): 10 kA for 1 sec Fuse Pullers Closing Rectifier

Control Voltage : 240V, AC

Space Heater Circuit : 240V, AC 5. TESTS

3. TYPE According to Specification EORP-EL-S-002

DATA SHEET

FOR DISTRIBUTION BOARDS

PAGE NO:

23 TO 74 %

50 / -2 deg. C.

42/10.6 deg C

Applied Standard

Enclosure Metal Enclosed 1

Metal Clad 2

3

Degree of Protection IP 42

6.OTHER

Circuit Breaker ELCB / MCB (Outgoing)

MCCB/ MCB (Incomers) Painting Colour Manufacture's Standard

Unit Mounting Single Front As per Spec. (SUPP-ST-S-001)

Double Front Painting Method Manufacture's Standard

LV Switchboard (I/C, O/G) Draw Out Type As per Spec. (SUPP-ST-S-001)

Fixed Type

Form of Construction Form 2b

Configuration / Feeder Arrangement

Single Line Diagram

(EORP-EL-D-002,003 & 004)

Protective Relay

Incoming feeder connection point Top

Bottom

Cable

Bus Duct

Main Busbar Location

Bottom

Top

Outgoing feeder connection point

Cable

Bottom

12.02.2010 ADS08.02.2010 ADS

Rev Date ApprovedPrepared Description Checked

AB

NAK Issued For DIC/IDR BPRNAK Issued for Review / Comments BPR

Page 7: Data Sheet & SLD

DOC. NO: EORP-EL-J-002 3 of 3

SERVICE: Power DB TAG NO : EORP-PDB NO OF UNITS: 1

Heat Tracing DB EORP-HTDB 1

Lighting DB EORP-LDB 1

1 Make : 14 MCCB

2 Type / Designation : 14.1 Rated current : A

3 Overall dimensions 14.2 Rated SC making capacity - Icm : kA

3.1 PDB : mm 14.3 Rated service SC breaking : kA

3.2 HTDB : mm capacity - Ics

3.3 LDB : mm 14.4 Thermal release setting range :

4 Total Weight 14.5 Short circuit release :

4.1 PDB : Kg setting range

4.2 HTDB : Kg 14.6 Accessories

4.3 LDB : Kg - Auxiliary contacts :

5 Clearance in air - Shunt release :

5.1 Phase to Phase : mm - Undervoltage release :

5.2 Phase to Earth : mm - Trip alarm contacts :

6 Busbars - Rotary operating mechanism :

6.1 Busbar current rating : A 14.7 Mechanical life :

6.2 Busbar size : sqmm 15 MCB

6.3 Bus bar material : Cu. 15.1 Rated current : A

6.4 Bus bar location : Top 15.2 Rated service SC breaking : kA

7 Insulating material of busbars : capacity - Ics

8 Earth Busbars 16 ELCB

8.1 Earth bus size : 16.1 Rated current : A

DATA TO BE FILLED BY VENDOR

DATA SHEET

FOR DISTRIBUTION BOARDS

PAGE NO:

mm

8.2 Earth bus material : Cu. 16.2 Rated service SC breaking : kA

9 1 min. power frequency voltage : kV capacity - Ics

10 1 sec. short circuit withstand : kA 16.3 Earth Leakagetrip current : mA

capacity

11 Indications provided as per SLD : Yes / No

12 Cable Glands with check nuts

12.1 Material / Type :

12.2 Provided for all I/C & O/G cables : Yes / No

13 Cable Lugs

13.1 Material / Type :

13.2 Provided for all I/C & O/G cables :

1 Meters AEP / Simco / IMP / MECO

2 Indicating lights Siemens / L&T / Tecknic / BCH

3 MCB MDS / HAVELL / Indo-Asian

4 MCCB Siemens / L&T / Alstom

5 Terminals ELMEX / TOSHA / Connectwell

6 Cable glands Comet / Baliga / Flexpro

7 Cable lugs Dowell or equivalent

8 ELCB MDS / HAVELL / Indo-Asian

Yes / No

MAKE OF EQUIPMENT / COMPONENTS

12.02.2010 ADS08.02.2010 ADS

Rev Date Approved

B NAKA NAK Issued For DIC/IDR

Prepared CheckedCheckedDescription

BPRIssued for Review / CommentsBPRBPR

Page 8: Data Sheet & SLD

Mangala Field Development Project

Enchance Oil Recovery Pilot (EORP)Project

DATA SHEET

FOR

LV MOTOR

B 09.02.2010 KA BPR ADS -

A 05.02.2010 KA BPR ADS -

REV DATE BY CHK'D APPR CLIENT

TOTAL OR PARTIAL REPRODUCTION AND / OR UTILISATION OF THIS DOCUMENTATION ARE FORBIDDEN WITHOUT PRIOR WRITTEN AUTHORIZATION OF THE OWNER

Issued For DIC/IDR

DESCRIPTION

Issued for Review / Comments

Document No:

EORP-EL-J-003

Page 9: Data Sheet & SLD

DOC. NO: EORP-EL-J-003 2 of 2

SERVICE: TAG NO : NO OF UNITS: 2

1. GENERAL DATA

Installation : Onshore

Ref. Specification No. : EORP-EL-S-003 Altitude : Less than 1000 m m

Codes and Standard Location Indoor

IS IEC Outdoor

Ambient temp. : Max/Min :

Design ambient temp. : Seismic Zone : Zone - III

Relative Humidity :

Atmosphere : Desert area, Humid and Corrosive

2. RATING 3.VENDOR DATA

KW rating : * kW @ °C Name of motor Manufacturer : * *

KW rating at design ambient : * kW @ °C Country of Manufacturer : *

Number of Phases : 3Ph Service Centre (at delivery Location): *

Conform to International Std : * Full load current (Amps) : *

Conform to project Standard : * Starting time at full load (sec.) : *

Supply Voltage & Variation : 415V (+/-) 10% Starting current at 100% of voltage (%): *

Frequency & Variation : 50HZ (+/-) 5% : *

Combined Voltage & frequency Variation: (+/-) 10% Starting torque (as % of FLT) : *

System Earthing : Resistance Earthed Locked rotor current at Un(Amps) : *

Supply system fault level (MVA/KA): 50 kA for 1 sec Locked rotor withstand time in sec.-cold/ Hot: *

Motor Ternimal box fault rating : * kA for * s Powe factor at 100% /75% /50% load: *

Motor full load speed : * rpm Efficiency at 100% /75% /50% load: *

23 TO 74 %

Full load Torque ( kgm)

50 / -2 deg. C.

42/10.6 deg C

DATA SHEET

FOR LV MOTOR

PAGE NO:

Variable speed drive operation : yes No Motor Cooling method / Code : TEFC / IC *

Motor speed range for VSD : No.of consecutive starts in one hour: *

Method of motor starting : DOL : *

Duty : Continuous

Direction of rotation (facing drive end (DE)) * *

Mouting type per (IS -2253) : * * * *

Motor Frame Size : * * *

Insulation Class : Class F /B * *

Temperature rise : Limited to Class B * Hours * Hours

Area Classification of installation : Zone 2 □ yes □ No □ yes □ No

Gas Group / Temperature Class : Group IIA / T3 * * EEx Protection type : EEx'd ' or EEx' e'

Atex certificate : *

Enclosure IP Protection (IEC 60034-5): IP55

Position of Power terminal Box : * Driven Equipment description :

Vibration probes : * Type of driven equipment :

RTDs for Winding (6nos.) : Coupling type :

RTD cable size & type : Moment of intertia of the load : * * kg.m2

Space heater Rating : * Absorbed power : * * kW

Space heater cable size & type : * Speed (Synchronous) : * * rpm

: Stainless Steel

Grounding stud : Required 5. NOTES:

Lifting Eyes : Required

: 2. " * * " To be furnished by Driven Equuipment Manufacturer

:

:

Routine Test as per IS : Required

Not Required

* *

1. " * " To be furnished by Motor Manufacturer

3. Motors rated above 30KW shall be provided with anti-condensation heaters.Tropical treatment required

631/632 as per IS:5/ * microns

Yes

Power Cable size

Name Plate

Lubricant type

Final Paint shade / thickness

Bearings:

4.DRIVEN EQUIPMENT DATA

Bearing type

Reacceleration

Not Required

Model no.

Bearing life

* *

* *

Insulated

DE Bearing NDE Bearing

Make

* * % to * * % □ N.A.

09.02.2010 ADS05.02.2010 ADS

Rev Date Approved

Issued For DIC/IDR BPRKA Issued for Review / Comments BPR

Prepared Description Checked

AB

KA

Page 10: Data Sheet & SLD

MANGALA FIELD DEVELOPMENT PROJECT

Enhance Oil Recovery Pilot (EORP) Project

ELECTRICAL CABLE SCHEDULE

B 01.03.2010 NAK BPR ADS -

A 12.02.2010 NAK BPR ADS -

REV DATE BY CHK'D APPR CLIENT

TOTAL OR PARTIAL REPRODUCTION AND / OR UTILISATION OF THIS DOCUMENTATION ARE FORBIDDEN WITHOUT PRIOR WRITTEN AUTHORIZATION OF THE OWNER

Issued for Review / Comments

Issued For DIC/IDR

DESCRIPTION

Document No:

EORP-EL-K-002

Page 11: Data Sheet & SLD

Cairn Energy India Pty Ltd

Project : MANGALA FIELD DEVELOPMENT PROJECT - ENHANCE OIL RECOVERY PILOT (EORP) PROJECT

Document Title : ELECTRICAL CABLE SCHEDULE - INDEX, GLAND DESCRIPTION, CABLE DESCRIPTION, NOTES

Document No : EORP-EL-K-002

Revision No : B

INDEX GLAND DESCRIPTION

PAGE No.

1 COVER SHEET

2 INDEX , DESCRIPTION, NOTES Flameproof (EEX'd'), double compression cable glands suitable for use in Zone 2, gas group-II A, T3 area,

3 CABLE NUMBERING made of nickel plated brass, with soft sealing nylon washer, locknut, weatherproof, outdoor heat shrinkable hood,

4, 5 CABLE SCHEDULE-POWER & MOTOR CONTROL CENTRE suitable for installation in sandy desert environment

6,7,8 CABLE SCHEDULE-LIGHTING DISTRIBUTION BOARD Double compression cable glands, made of nickel plated brass, with soft sealing nylon washer, locknut,

9 CABLE SCHEDULE- POWER DISTRIBUTION BOARD weatherproof IP55, outdoor heat shrinkable hood, suitable for installation in sandy desert environment

VP Petro6 Engineers and Consultants Pvt Ltd

TITLE TYPES OF GLAND

DESCRIPTION

G1

G29 CABLE SCHEDULE POWER DISTRIBUTION BOARD weatherproof IP55, outdoor heat shrinkable hood, suitable for installation in sandy desert environment

Indoor type Double compression cable glands, made of nickel plated brass, with soft sealing nylon washer, locknut,

IP55.

CABLE DESCRIPTION

TYPE OF CABLE

600/1100 V Grade, Plain Annealed Copper - Stranded Conductor, XLPE Insulation, Extruded & Low Smoke Inner Sheath,

Galvanized Steel Wire Armored , LSLH PVC & Flame Retardant Outer Sheath , Outer Color - Black, halogen free, heat & oil resistant,

UV resistant, power, control, and lighting FRLS cables conforming to IEC-60332-3 Cat A.

1. This Cable Schedule lists all Electrical power, control, and lighting cables which are to be installed on the MPT off spec tank-tie in mangala train-1 .

2. Cable lengths indicated are estimated route lengths only.

3. Cables data selection is based on PRIMECAB KABELS catalogue

4. Cable glands data selection is based on HAWKE cable gland catalogue.

G3

NOTES:

DESCRIPTION

A

Page 2 of 9

Page 12: Data Sheet & SLD

Cairn Energy India Pty Ltd

Project : MANGALA FIELD DEVELOPMENT PROJECT - ENHANCE OIL RECOVERY PILOT (EORP) PROJECT

Document Title : ELECTRICAL CABLE SCHEDULE - CABLE NUMBERING

Document No : EORP-EL-K-002

Revision No : B

CABLE NUMBERING :

Generator & Synchronising Panel cable Power & motor control cable

Cable Serial number reference

Cable Serial number reference Circuit reference

Distribution board/Equipemnt reference Distribution board/Equipemnt reference

VP Petro6 Engineers and Consultants Pvt Ltd

P - EORP- XX- YY-01 P - EORP- XX- 01

Enhance Oil Recovery Pilot (EORP) Project Enhance Oil Recovery Pilot (EORP) Project

Cable type : Cable type :

P - 415VAC, Power cable P - 415VAC, Power cable

C - 230VAC, Control cable C - 230VAC, Control cable

H- Anti Condensation Heater H- Anti Condensation Heater

Lighting & small power cable

Circuit reference

Distribution board reference

Enhance Oil Recovery Pilot (EORP) Project

Cable type :

L - Lighting cable

L -EORP-XX- 01

P- Power cable

Page 3 of 9

Page 13: Data Sheet & SLD

Project : MANGALA FIELD DEVELOPMENT PROJECT - ENHANCE OIL RECOVERY PILOT (EORP) PROJECT

Document Title : ELECTRICAL CABLE SCHEDULE- GENERATOR, POWER & MOTOR CONTROL CENTRE

Document No : EORP-EL-K-002

Revision No : B

NO OF CORES

COND. SIZE (Sq.mm)

TYPE OF CABLE

APPROX. OD (mm)

TOTAL LENGTH

(M)SIZE TYPE SIZE TYPE

1 P-EORP-X-809A-01 3.5 185 A 50 40 X-809A Diesel Generator M63 G3 EORP-PMCC Power & motor control centre M63 G3

2 P-EORP-X-809A-02 3.5 185 A 50 40 X-809A Diesel Generator M63 G3 EORP-PMCC Power & motor control centre M63 G3

3 P-EORP-X-809A-03 3.5 185 A 50 40 X-809A Diesel Generator M63 G3 EORP-PMCC Power & motor control centre M63 G3

4 P-EORP-X-809A-04 1 300 A 31 40 X-809A Diesel Generator (Neutral) M40 G3 EORP-PMCC NGR Cubicle (Resistor) M40 G3

5 P-EORP-X-809A-05 1 6 A 11 40 X-809A NGR Cubicle (Resistor) M20 G3 - Earth Pit -

6 C-EORP-X-809A-01 3 2.5 A 15 40 X-809A Diesel Generator (Neutral CT) M20 G3 EORP-PMCC Power & motor control centre (for 64 Relay) M20 G3

7 C-EORP-X-809A-02 7 2.5 A 15 150 EORP-PMCC Power & motor control centre (Incomer-1) M20 G3 - IRP for Control Status M20 G3ON, OFF &

Indication Status

EQUIPMENT TAG NO.

GLAND

VP Petro6 Engineers and Consultants Pvt Ltd

REMARKSSL.NO. CABLE TAG NO.

Cairn Energy India Pty Ltd

TO

EQUIPMENT TAG NO.

EQUIPMENT DESCRIPTION

GLANDDESCRIPTION OF CABLE

EQUIPMENT DESCRIPTION

FROM

7 H-EORP-X-809A-01 2 2.5 A 14 40 EORP-PMCC Power & motor control centre M20 G3 X-809A Diesel Generator (Space heater) M20 G3

8 P-EORP-X-809B-01 3.5 185 A 50 40 X-809B Diesel Generator M63 G3 EORP-PMCC Power & motor control centre M63 G3

9 P-EORP-X-809B-02 3.5 185 A 50 40 X-809B Diesel Generator M63 G3 EORP-PMCC Power & motor control centre M63 G3

10 P-EORP-X-809B-03 3.5 185 A 50 40 X-809B Diesel Generator M63 G3 EORP-PMCC Power & motor control centre M63 G3

11 P-EORP-X-809B-04 1 300 A 31 40 X-809B Diesel Generator (Neutral) M40 G3 EORP-PMCC NGR Cubicle (Resistor) M40 G3

12 P-EORP-X-809B-05 1 6 A 11 40 X-809B NGR Cubicle (Resistor) M20 G3 - Earth Pit -

13 C-EORP-X-809B-01 3 2.5 A 15 40 X-809B Diesel Generator (Neutral CT) M20 G3 EORP-PMCC Power & motor control centre (for 64 Relay) M20 G3

14 C-EORP-X-809B-02 7 2.5 A 15 150 EORP-PMCC Power & motor control centre (Incomer-2) M20 G3 - IRP for Control Status M20 G3ON, OFF &

Indication Status

14 H-EORP-X-809B-01 2 2.5 A 14 40 EORP-PMCC Power & motor control centre M20 G3 X-809B Diesel Generator (Space heater) M20 G3

15 P-EORP-PMCC-01-01 3 6 A 17 100 EORP-PMCC Power & motor control centre M25 G3 EORP-P-203A Fluid Transfer Pump A M25 G1

16 C-EORP-PMCC-01-01 3 2.5 A 15 100 EORP-PMCC Power & motor control centre M20 G3 - LCS for Fluid Transfer Pump A M20 G1

17 C-EORP-PMCC-01-02 7 2.5 A 19 150 EORP-PMCC Power & motor control centre M20 G3 - IRP for Control Status M20 G3Start, Stop &

Indication Status

18 P-EORP-PMCC-02-01 3 6 A 17 100 EORP-PMCC Power & motor control centre M25 G3 EORP-P-203B Fluid Transfer Pump B M25 G1

19 C-EORP-PMCC-02-01 3 2.5 A 15 100 EORP-PMCC Power & motor control centre M20 G3 - LCS for Fluid Transfer Pump B M20 G1

20 C-EORP-PMCC-02-02 7 2.5 A 19 150 EORP-PMCC Power & motor control centre M20 G3 - IRP for Control Status M20 G3Start, Stop &

Indication Status

21 P-EORP-PMCC-03-01 3 4 A 16 70 EORP-PMCC Power & motor control centre M25 G3 EORP-P-805A Chemical Injection Pump A M25 G1

22 C-EORP-PMCC-03-01 3 2.5 A 15 70 EORP-PMCC Power & motor control centre M20 G3 - LCS for Chemical Injection Pump A M20 G1

Page 4 of 9

Page 14: Data Sheet & SLD

Project : MANGALA FIELD DEVELOPMENT PROJECT - ENHANCE OIL RECOVERY PILOT (EORP) PROJECT

Document Title : ELECTRICAL CABLE SCHEDULE- GENERATOR, POWER & MOTOR CONTROL CENTRE

Document No : EORP-EL-K-002

Revision No : B

NO OF CORES

COND. SIZE (Sq.mm)

TYPE OF CABLE

APPROX. OD (mm)

TOTAL LENGTH

(M)SIZE TYPE SIZE TYPE

EQUIPMENT TAG NO.

GLAND

VP Petro6 Engineers and Consultants Pvt Ltd

REMARKSSL.NO. CABLE TAG NO.

Cairn Energy India Pty Ltd

TO

EQUIPMENT TAG NO.

EQUIPMENT DESCRIPTION

GLANDDESCRIPTION OF CABLE

EQUIPMENT DESCRIPTION

FROM

23 P-EORP-PMCC-04-01 3 4 A 16 70 EORP-PMCC Power & motor control centre M25 G3 EORP-P-805B Chemical Injection Pump B M25 G1

24 C-EORP-PMCC-04-01 3 2.5 A 15 70 EORP-PMCC Power & motor control centre M20 G3 - LCS for Chemical Injection Pump B M20 G1

25 P-EORP-PMCC-05-01 3 4 A 16 65 EORP-PMCC Power & motor control centre M25 G3 EORP-P-806A Chemical Injection Pump A M25 G1

26 C-EORP-PMCC-05-01 3 2.5 A 15 65 EORP-PMCC Power & motor control centre M20 G3 - LCS for Chemical Injection Pump A M20 G1

27 P-EORP-PMCC-06-01 3 4 A 16 65 EORP-PMCC Power & motor control centre M25 G3 EORP-P-806B Chemical Injection Pump B M25 G1

28 C-EORP-PMCC-06-01 3 2.5 A 15 65 EORP-PMCC Power & motor control centre M20 G3 - LCS for Chemical Injection Pump B M20 G1

29 P-EORP-PMCC-07-01 3 4 A 16 60 EORP-PMCC Power & motor control centre M25 G3 EORP-P-807A Chemical Injection Pump A M25 G1

30 C-EORP-PMCC-07-01 3 2.5 A 15 60 EORP-PMCC Power & motor control centre M20 G3 - LCS for Chemical Injection Pump A M20 G1

31 P-EORP-PMCC-08-01 3 4 A 16 60 EORP-PMCC Power & motor control centre M25 G3 EORP-P-807B Chemical Injection Pump B M25 G1

32 C-EORP-PMCC-08-01 3 2.5 A 15 60 EORP-PMCC Power & motor control centre M20 G3 - LCS for Chemical Injection Pump B M20 G1

33 P-EORP-PMCC-09-01 3 4 A 16 55 EORP-PMCC Power & motor control centre M25 G3 EORP-P-808A Chemical Injection Pump A M25 G1

34 C-EORP-PMCC-09-01 3 2.5 A 15 55 EORP-PMCC Power & motor control centre M20 G3 - LCS for Chemical Injection Pump A M20 G1

35 P-EORP-PMCC-10-01 3 4 A 16 55 EORP-PMCC Power & motor control centre M25 G3 EORP-P-808B Chemical Injection Pump B M25 G1

36 C-EORP-PMCC-10-01 3 2.5 A 15 55 EORP-PMCC Power & motor control centre M20 G3 - LCS for Chemical Injection Pump B M20 G1

37 P-EORP-PMCC-11-01 3 95 A 33 225 EORP-PMCC Power & motor control centre M40 G3 - ESP Motor VFD Panel M40 G3

38 C-EORP-PMCC-11-01 3 2.5 A 15 225 EORP-PMCC Power & motor control centre M20 G3 - LCS for ESP Motor A M20 G1

39 C-EORP-PMCC-11-02 10 2.5 A 20 15 EORP-PMCC Power & motor control centre M20 G3 - ESP Motor VFD Panel M20 G3

40 C-EORP-PMCC-11-03 7 2.5 A 14 150 EORP-PMCC ESP Motor VFD Panel M20 G3 - IRP for Control Status M20 G3Start, Stop &

Indication Status

41 P-EORP-PMCC-12-01 4 16 A 22 25 EORP-PMCC Power & motor control centre M25 G3 EORP-LDB-001 Lighting distribution board M25 G3

42 P-EORP-PMCC-13-01 4 16 A 22 25 EORP-PMCC Power & motor control centre M25 G3 EORP-PDB-001 Power distribution board M25 G3

43 P-EORP-PMCC-14-01 4 150 A 45 25 EORP-PMCC Power & motor control centre M40 G3 EORP-HTDB-001 Heat Tracing Panel M40 G3

Page 5 of 9

Page 15: Data Sheet & SLD

Project : MANGALA FIELD DEVELOPMENT PROJECT - ENHANCE OIL RECOVERY PILOT (EORP) PROJECT

Document Title : ELECTRICAL CABLE SCHEDULE- LIGHTING DISTRIBUTION BOARD

Document No : EORP-EL-K-002

Revision No : B

NO OF CORES

COND. SIZE (Sq.mm)

TYPE OF CABLE

CABLE OD (mm)

TOTAL LENGTH

(M)SIZE TYPE SIZE TYPE

1 L-EORP-LDB-01-01 2 4 A 15 250 EORP-LDB-001 Lighting distribution board at ckt - 1 M20 G3 - Junction box-1 M20 G1

2 L-EORP-LDB-01-02 2 2.5 A 14 8 - Junction box-1 M20 G1 - Light fitting-1 M20 G1

3 L-EORP-LDB-01-03 2 2.5 A 14 20 - Junction box-1 M20 G1 - Junction box-2 M20 G1

4 L-EORP-LDB-01-04 2 2.5 A 14 8 - Junction box -2 M20 G1 - Light fitting-2 M20 G1

5 L-EORP-LDB-01-05 2 2.5 A 14 20 - Junction box-2 M20 G1 - Junction box-3 M20 G1

6 L-EORP-LDB-01-06 2 2.5 A 14 8 - Junction box-3 M20 G1 - Light fitting-3 M20 G1

REMARKSEQUIPMENT TAG NO.

EQUIPMENT DESCRIPTION

GLAND

EQUIPMENT TAG NO.

GLAND

EQUIPMENT DESCRIPTION

Cairn Energy India Pty Ltd VP Petro6 Engineers and Consultants Pvt Ltd

SL.NO. CABLE TAG NO.

DESCRIPTION OF CABLE FROM TO

7 L-EORP-LDB-01-07 2 2.5 A 14 20 - Junction box-3 M20 G1 - Junction box-4 M20 G1

8 L-EORP-LDB-01-08 2 2.5 A 14 8 - Junction box-4 M20 G1 - Light fitting-4 M20 G1

9 L-EORP-LDB-01-09 2 2.5 A 14 20 - Junction box-4 M20 G1 - Junction box-5 M20 G1

10 L-EORP-LDB-01-10 2 2.5 A 14 8 - Junction box-5 M20 G1 - Light fitting-5 M20 G1

11 L-EORP-LDB-01-11 2 2.5 A 14 20 - Junction box-5 M20 G1 - Junction box-6 M20 G1

12 L-EORP-LDB-01-12 2 2.5 A 14 8 - Junction box-6 M20 G1 - Light fitting-6 M20 G1

13 L-EORP-LDB-01-13 2 2.5 A 14 20 - Junction box-6 M20 G1 - Junction box-7 M20 G1

14 L-EORP-LDB-01-14 2 2.5 A 14 8 - Junction box-7 M20 G1 - Light fitting-7 M20 G1

15 L-EORP-LDB-02-01 2 4 A 15 250 EORP-LDB-001 Lighting distribution board at ckt- 2 M20 G3 - Junction box-8 M20 G1

16 L-EORP-LDB-02-02 2 2.5 A 14 8 - Junction box-8 M20 G1 - Light fitting-8 M20 G1

17 L-EORP-LDB-02-03 2 2.5 A 14 20 - Junction box-8 M20 G1 - Junction box-9 M20 G1

18 L-EORP-LDB-02-04 2 2.5 A 14 8 - Junction box -9 M20 G1 - Light fitting-9 M20 G1

19 L-EORP-LDB-02-05 2 2.5 A 14 20 - Junction box-9 M20 G1 - Junction box-10 M20 G1

20 L-EORP-LDB-02-06 2 2.5 A 14 8 - Junction box-10 M20 G1 - Light fitting-10 M20 G1

21 L-EORP-LDB-02-07 2 2.5 A 14 20 - Junction box-10 M20 G1 - Junction box-11 M20 G1

22 L-EORP-LDB-02-08 2 2.5 A 14 8 - Junction box-11 M20 G1 - Light fitting-11 M20 G1

23 L-EORP-LDB-02-09 2 2.5 A 14 20 - Junction box-11 M20 G1 - Junction box-12 M20 G1

Page 6 of 9

Page 16: Data Sheet & SLD

24 L-EORP-LDB-02-10 2 2.5 A 14 8 - Junction box-12 M20 G1 - Light fitting-12 M20 G1

25 L-EORP-LDB-02-11 2 2.5 A 14 20 - Junction box-12 M20 G1 - Junction box-13 M20 G1

26 L-EORP-LDB-02-12 2 2.5 A 14 8 - Junction box-13 M20 G1 - Light fitting-13 M20 G1

27 L-EORP-LDB-02-13 2 2.5 A 14 20 - Junction box-13 M20 G1 - Junction box-14 M20 G1

28 L-EORP-LDB-02-14 2 2.5 A 14 8 - Junction box-14 M20 G1 - Light fitting-14 M20 G1

29 L-EORP-LDB-03-01 2 2.5 A 14 80 EORP-LDB-001 Lighting distribution board at ckt- 3 M20 G3 - Junction box-15 M20 G1

30 L-EORP-LDB-03-02 2 2.5 A 14 6 - Junction box-15 M20 G1 - Light fitting-15 M20 G1

31 L-EORP-LDB-03-03 2 2.5 A 14 12 - Junction box-15 M20 G1 - Junction box-16 M20 G1

32 L-EORP-LDB-03-04 2 2.5 A 14 6 - Junction box -16 M20 G1 - Light fitting-16 M20 G1

33 L-EORP-LDB-03-05 2 2.5 A 14 12 - Junction box-16 M20 G1 - Junction box-17 M20 G1

34 L-EORP-LDB-03-06 2 2.5 A 14 6 - Junction box-17 M20 G1 - Light fitting-17 M20 G1

35 L-EORP-LDB-03-07 2 2.5 A 14 12 - Junction box-17 M20 G1 - Junction box-18 M20 G1

36 L-EORP-LDB-03-08 2 2.5 A 14 6 - Junction box-18 M20 G1 - Light fitting-18 M20 G1

37 L-EORP-LDB-03-09 2 2.5 A 14 12 - Junction box-18 M20 G1 - Junction box-19 M20 G1

38 L-EORP-LDB-03-10 2 2.5 A 14 6 - Junction box-19 M20 G1 - Light fitting-19 M20 G1

39 L-EORP-LDB-03-11 2 2.5 A 14 12 - Junction box-19 M20 G1 - Junction box-20 M20 G1

40 L-EORP-LDB-03-12 2 2.5 A 14 6 - Junction box-20 M20 G1 - Light fitting-20 M20 G1

41 L-EORP-LDB-04-01 2 2.5 A 14 60 EORP-LDB-001 Lighting distribution board at ckt- 4 M20 G3 - Junction box-21 M20 G1

42 L-EORP-LDB-04-02 2 2.5 A 14 6 - Junction box-21 M20 G1 - Light fitting-21 M20 G1

43 L-EORP-LDB-04-03 2 2.5 A 14 12 - Junction box-21 M20 G1 - Junction box-22 M20 G1

44 L-EORP-LDB-04-04 2 2.5 A 14 6 - Junction box -22 M20 G1 - Light fitting-22 M20 G1

45 L-EORP-LDB-04-05 2 2.5 A 14 12 - Junction box-22 M20 G1 - Junction box-17 M20 G1

46 L-EORP-LDB-05-01 2 2.5 A 14 40 EORP-LDB-001 Lighting distribution board at ckt- 5 M20 G3 - Junction box-23 M20 G1

47 L-EORP-LDB-05-02 2 2.5 A 14 6 - Junction box-23 M20 G1 - Light fitting-23 M20 G1

48 L-EORP-LDB-05-03 2 2.5 A 14 10 - Junction box-23 M20 G1 - Junction box-24 M20 G1

49 L-EORP-LDB-05-04 2 2.5 A 14 6 - Junction box -24 M20 G1 - Light fitting-24 M20 G1

50 L-EORP-LDB-05-05 2 2.5 A 14 10 - Junction box-24 M20 G1 - Junction box-25 M20 G1

51 L-EORP-LDB-05-06 2 2.5 A 14 6 - Junction box-25 M20 G1 - Light fitting-25 M20 G1

52 L-EORP-LDB-05-07 2 2.5 A 14 10 - Junction box-25 M20 G1 - Junction box-26 M20 G1

53 L-EORP-LDB-05-08 2 2.5 A 14 6 - Junction box-26 M20 G1 - Light fitting-26 M20 G1

54 L-EORP-LDB-05-09 2 2.5 A 14 10 - Junction box-26 M20 G1 - Junction box-27 M20 G1

55 L-EORP-LDB-05-10 2 2.5 A 14 6 - Junction box-27 M20 G1 - Light fitting-27 M20 G1

Page 7 of 9

Page 17: Data Sheet & SLD

56 L-EORP-LDB-05-11 2 2.5 A 14 10 - Junction box-27 M20 G1 - Junction box-28 M20 G1

57 L-EORP-LDB-05-12 2 2.5 A 14 6 - Junction box-28 M20 G1 - Light fitting-28 M20 G1

58 L-EORP-LDB-05-13 2 2.5 A 14 10 - Junction box-28 M20 G1 - Junction box-29 M20 G1

59 L-EORP-LDB-05-14 2 2.5 A 14 6 - Junction box-29 M20 G1 - Light fitting-29 M20 G1

60 L-EORP-LDB-05-15 2 2.5 A 14 10 - Junction box-29 M20 G1 - Junction box-30 M20 G1

61 L-EORP-LDB-05-16 2 2.5 A 14 6 - Junction box-30 M20 G1 - Light fitting-30 M20 G1

62 L-EORP-LDB-06-01 2 2.5 A 14 15 - Lighting distribution board at ckt- 6 M20 G3 - Operator cabin lighting M20 G3

Page 8 of 9

Page 18: Data Sheet & SLD

Project : MANGALA FIELD DEVELOPMENT PROJECT - ENHANCE OIL RECOVERY PILOT (EORP) PROJECT

Document Title : ELECTRICAL CABLE SCHEDULE-POWER DISTRIBUTION BOARD

Document No : EORP-EL-K-002

Revision No : B

NO OF CORES

COND. SIZE (Sq.mm)

TYPE OF CABLE

CABLE OD (mm)

TOTAL LENGTH

(M)SIZE TYPE SIZE TYPE

1 P-EORP-PDB-01 2 2.5 A 14 20 EORP-PDB-001 Power distribution board M20 G3 - 24V DC Charger for Instrumention M20 G3

2 P-EORP-PDB-02 2 2.5 A 14 40 EORP-PDB-001 Power distribution board M20 G3 - X-809A EDG Auxiliaries M20 G3

3 P-EORP-PDB-03 2 2.5 A 14 30 EORP-PDB-001 Power distribution board M20 G3 - X-809B EDG Auxiliaries M20 G3

4 P-EORP-PDB-04 2 2.5 A 14 20 EORP-PDB-001 Power distribution board M20 G3 - Operator Cabin A/C Unit -1 M20 G3

5 P-EORP-PDB-05 2 2.5 A 14 20 EORP-PDB-001 Power distribution board M20 G3 - Operator Cabin A/C Unit -2 M20 G3

EQUIPMENT DESCRIPTION

Cairn Energy India Pty Ltd VP Petro6 Engineers and Consultants Pvt Ltd

SL.NO. CABLE TAG NO.

DESCRIPTION OF CABLE FROM TO

REMARKSEQUIPMENT TAG NO.

EQUIPMENT DESCRIPTION

GLAND

EQUIPMENT TAG NO.

GLAND

6 P-EORP-PDB-06 2 2.5 A 14 20 EORP-PDB-001 Power distribution board M20 G3 - Operator Cabin A/C Unit -3 M20 G3

7 P-EORP-PDB-07 2 2.5 A 14 20 EORP-PDB-001 Power distribution board M20 G3 - Operator Cabin A/C Unit -4 M20 G3

8 P-EORP-PDB-08 2 2.5 A 14 20 EORP-PDB-001 Power distribution board M20 G3 - 24V Charger for operation of CB & Synchronizing M20 G3

Page 9 of 9