Data sheet GRCpump.1 V_1.0
Data sheet GRCpump.1Controller GHM pump
ERP no.: 5206763
http://www.guentner.de
-
page 2 / 15
Data sheet GRCpump.1 V_1.0 © Güntner GmbH & Co. KG
Contents
1 GRCpump.1...................................................................................31.1 Functional description.......................................................................31.2 Configuration table............................................................................51.3 Function table.................................................................................... 71.4 Connections........................................................................................ 91.5 Electrical properties........................................................................121.6 Installation / Operating conditions...............................................141.7 Dimensions and weight..................................................................15
-
page 3 / 15
Data sheet GRCpump.1 V_1.0 © Güntner GmbH & Co. KG
1 GRCpump.1
1.1 Functional description
The GRCpump.1 provides hydro management for hybrid dry coolers and evaporative coolingsystems and is used together with a GMM EC speed controller with bus communication.
The GRCpump.1 needs to be combined with a GIOD.1 expansion module, ERP no. 5204183.
GHM pump with GMM
In order to ensure controlled operation, the controller must have a power supply and must beenabled via digital input DI1. If the input DI1 is configured with an alternate function, then theexternal release is considered as implicitly granted. If it is not enabled the heat exchanger coilwill not be wetted at all.
The unit has an internal power control whose parameters (fan control value, setpoint devi-ation) can be configured either from the menu or via an external bus module. The controlmode for wetting can be pre-set from the internal menu.
The controller can control one or two wetting pumps. The relay outputs that control the wet-ting pumps are operated as directed by the control parameters and the operating mode. Theswitch-on threshold for each pump can be configured individually.
A humidity sensor displaces the setpoint in response to the wet bulb temperature.
The hydro management uses a conductivity sensor to monitor the quality of the wetting water,where necessary initiating a reduction in its conductivity as specified in the pre-set values. TheGHM also uses a sensor to regulate the water level in the tray, taking into account the currentoperating state.
The digital inputs are designed as potential-free contacts that must be connected to +24V.Wetting is enabled only if the external enable is issued and the criteria for the start of thepump are met (controlled value of the fans and/or setpoint deviation).
In addition to this external enable, other digital inputs are also used to monitor various exter-nal status notifications, fault messages, and measured values.
Digital inputs or the external bus communication can be used to activate system functions(such as blowdown, pump on/off, etc.) via a higher-level controller.
Impulse water meters can be connected to digital inputs DI2 and DI3 of the GRCpump.1 torecord the volumes of water for inlet and outlet.
NOTICE
Please note that connecting the wrong voltage (e.g. 230V) may seriously damage the controller.
-
page 4 / 15
Data sheet GRCpump.1 V_1.0 © Güntner GmbH & Co. KG
The relay outputs on the GRCpump.1 are used to control valves (DO1-DO3) and a generalfault message (DO4).
The expansion module GIOD.1 can be used to control the disinfection unit, the tray and ancil-lary heating systems and to signal readiness for wetting.
The CAN interface of the GRCpump.1 is an internal interface for communication with otherGüntner units (e.g. the expansion module GIOD.1).
There are communication modules available for external bus communications: for ModbusRTU (GCM MOD GHMpump Rail.2, ERP no. 5206759) and for Modbus TCP/IP and BACnet(GCM (W)LAN Rail.1, ERP no. 5206123).
-
page 5 / 15
Data sheet GRCpump.1 V_1.0 © Güntner GmbH & Co. KG
1.2 Configuration table
NOTICE
The inputs and outputs on the GRCpump.1 and the GIOD.1 can be configured flexibly.
The table below shows a “standard configuration” with corresponding options for the GHMpump after startup.
I/O Signal Function
DI1 24V External release
DI2 24V Free
DI3 24V Free
AI1 4..20mA Water level sensor
AI2 4..20mA/KTY Conductivity sensor (4..20 mA) *1
AI3 KTY Basin water temperature
AI4 0..10V Free
AO1 0..10V Control value for regulated pump *1
AO2 0..10V Water level symbolic
DO1 Relay Feed water valve (on site) *1
DO2 Relay Make-up water valve (at the unit)
DO3 Relay Blowdown valve (at the unit)
GRCpump.1
DO4 Relay Fault report for alarms of PRIO 1 and 2
CAN BUS Data from GMM: Pressure or return temperature / ambient temperature / setpoint / units
system
Data to GMM:
Wet-bulb temperature / limitation of fans’ control value / control of fans’
inverse operation
DO1 Relay Pump 1 *1
DO2 Relay Pump 2 *1
DO3 Relay Free
DO4 Relay Free
DO5 Relay Free
DO6 Relay Free
DO7 Relay Free
DO8 Relay Free
DI1 24V Feed water valve open (on site) *1
DI2 24V Feed water valve closed (on site) *1
GIOD.1
DI3 24V Make-up water valve open (at the unit) *1
Configuration table GRCpump.1 with GIOD.1
-
page 6 / 15
Data sheet GRCpump.1 V_1.0 © Güntner GmbH & Co. KG
I/O Signal Function
DI4 24V Make-up water valve closed (at the unit) *1
DI5 24V Blowdown valve open (at the unit) *1
DI6 24V Blowdown valve closed (at the unit) *1
DI7 24V Free
DI8 24V Free
DI9 24V Free
DI10 24V Free
DI11 24V Free
DI12 24V Free
DI13 24V Free
DI14 24V Free
DI15 24V Free
DI16 24V Free
Configuration table GRCpump.1 with GIOD.1
*1 Function is dependent upon the startup settings
-
page 7 / 15
Data sheet GRCpump.1 V_1.0 © Güntner GmbH & Co. KG
1.3 Function table
The following table shows possible functions of GHM pump. Depending on the wiring of thecontroller, these functions can be selected individually in the service menu or the I/O con-figu-ration.
I/O-Type Function Possible I/Os Reference *1
DO (Relay) Feed water valve (on site) GRCpump DO1 GRCpump DO1
DO (Relay) Make-up water valve (at the unit) GRCpump DO2 GRCpump DO2
DO (Relay) Blowdown valve (at the unit) GRCpump DO3 GRCpump DO3
DO (Relay) Fault report for alarms of PRIO 1 and 2 GRCpump DO4 GRCpump DO4
DO (Relay) Fault report for alarms of PRIO 1 GRCpump DO4
DO (Relay) Fault report for alarms of PRIO 2 DO freely selectable *2
DO (Relay) Pump 1 DO freely selectable *2 GIOD DO1
DO (Relay) Pump 2 DO freely selectable *2 GIOD DO2
DO (Relay) Biocide unit DO freely selectable *2 GIOD DO3
DO (Relay) UV lamps DO freely selectable *2 GIOD DO4
DO (Relay) Ready for wetting DO freely selectable *2 GIOD DO5
DO (Relay) Basin heater DO freely selectable *2 GIOD DO6
DO (Relay) Trace heater DO freely selectable *2 GIOD DO7
DO (Relay) Make-up water request DO freely selectable *2 GIOD DO8
DI (24 V) External release GRCpump DI1 GRCpump DI1
DI (24 V) Water meter for make-up water GRCpump DI2 GRCpump DI2
DI (24 V) Water meter for blowdown water GRCpump DI3 GRCpump DI3
DI (24 V) Feed water valve open (on site) DI freely selectable *3 GIOD DI1
DI (24 V) Feed water valve closed (on site) DI freely selectable *3 GIOD DI2
DI (24 V) Make-up water valve open (at the unit) DI freely selectable *3 GIOD DI3
DI (24 V) Make-up water valve closed (at the unit) DI freely selectabler *3 GIOD DI4
DI (24 V) Blowdown valve open (at the unit) DI freely selectable *3 GIOD DI5
DI (24 V) Blowdown valve closed (at the unit) DI freely selectable *3 GIOD DI6
DI (24 V) Biocide unit OK DI freely selectable *3 GIOD DI7
DI (24 V) UV lamps OK DI freely selectable *3 GIOD DI8
DI (24 V) Basin heater OK DI freely selectable *3 GIOD DI9
DI (24 V) All Pumps OK DI freely selectable *3 GIOD DI10
DI (24 V) Pump 1 OK DI freely selectable *3 GIOD DI11
DI (24 V) Pump 2 OK DI freely selectable *3 GIOD DI12
DI (24 V) Circuit breaker OK DI freely selectable *3 GIOD DI13
DI (24 V) External feed water request DI freely selectable *3
DI (24 V) External request: activate all pumps DI freely selectable *3
DI (24 V) External request: start filling up DI freely selectable *3
-
page 8 / 15
Data sheet GRCpump.1 V_1.0 © Güntner GmbH & Co. KG
I/O-Type Function Possible I/Os Reference *1
DI (24 V) External request: start blowdown DI freely selectable *3
DI (24 V) External request: start draining DI freely selectable *3
DI (24 V) External request: start biocide process DI freely selectable *3
DI (24 V) External request: start defrost DI freely selectable *3
AI (4…20 mA) Water level sensor GRCpump AI1, AI2 GRCpump AI1
AI (4…20 mA) Conductivity sensor GRCpump AI1, AI2 GRCpump AI2
AI (4…20 mA) Humidity sensor GRCpump AI1, AI2
AI (KTY) Basin water temperature GRCpump AI3 GRCpump AI3
AI (0…10 V) Humidity sensor GRCpump AI4 GRCpump AI4
AI (0…10 V) Pressure sensor after pump GRCpump AI4
AO (0…10 V) Control value for regulated pump GRCpump AO1, AO2 GRCpump AO1
AO (0…10 V) Water level symbolic GRCpump AO1, AO2 GRCpump AO2
AO (0…10 V) Water level continuous GRCpump AO1, AO2
AO (0…10 V) Conductivity of wetting water GRCpump AO1, AO2
*1 The reference represents a recommendation for a consistent system configuration.
*2 This function can be configured on any free DO of GRCpump (DO1-DO4) or GIOD (DO1-DO8). This DO function can be simultaneously configured on several free DOs.
*3 This function can only be configured on one single free DI of GRCpump (DI1-DI3) or GIOD(DI1-DI16).
-
page 9 / 15
Data sheet GRCpump.1 V_1.0 © Güntner GmbH & Co. KG
1.4 Connections
Upper row of connections
Name Description
Service Service plug only for use by service personnel
Firm Pushbutton only for use by service personnel
+24V
+24VExternal feed for power supply
GND
GND
GND
Contact ground for external power feed
Terminal not connected
11
12
TB1
14
Relay DO1
21
22
24
Relay DO2
31
32
34
Relay DO3
41
42
TB2
44
Relay DO4
-
page 10 / 15
Data sheet GRCpump.1 V_1.0 © Güntner GmbH & Co. KG
Lower row of connections
Name Description
AO1 Analogue output 1, 0-10V
GND Ground
AO2 Analogue output 2, 0-10V
GND Ground
+24V Voltage +24V
DI1 Digital input +24V
DI2 Digital input +24V
DI3 Digital input +24V
TB3
+24V Voltage +24V
+24V Voltage +24V
GND Ground
AI1 Analogue output 4-20mA
AI2Analogue input 4-20mA or for temperature sensor GTF must be configured in the soft-
ware
AI3 Analogue input for temperature sensor GTF
AI4 Analogue input 0-10V
GND Ground
+24V
TB4
+24VVoltage +24V
Term DIP switch for CAN bus termination (120Ω) / ON = termination activated
+24V Voltage +24V
GND Ground
CH CAN high signalTB5
CL CAN low signal
-
page 11 / 15
Data sheet GRCpump.1 V_1.0 © Güntner GmbH & Co. KG
Lower row of connections
GND Ground
+24V Voltage +24V
CAN CAN bus plug including power supply
*TB: Terminal block
-
page 12 / 15
Data sheet GRCpump.1 V_1.0 © Güntner GmbH & Co. KG
1.5 Electrical properties
Min Type Max Unit
Voltage supply 21 24 30 V
Current consumption 80 2501 mA
Digital inputs
High level 15 24 30 V
Low level -3 0 5 V
Relay outputs
Voltage DC 24 30 V
Voltage AC 250 V
Current resistive load 24V DC/250VAC
1 A
Current inductive load 24VDC/250V AC
1 A
Switch cycles, mechanical 1*106 Switching cycles
Switch cycles, electrical 1*105 Switching cycles
Voltage input
Dielectric strength -24 30 V
Measuring range 0 12 V
Resolution 10 bit
Fault 1 %2
Input resistor: 230 kΩ
Current input
Dielectric strength -24 30 V
Measuring range 0 21 mA
Resolution 10 bit
Fault 1 %2
Input resistance(without protective circuit)
130Ω
Voltage output
-
page 13 / 15
Data sheet GRCpump.1 V_1.0 © Güntner GmbH & Co. KG
Min Type Max Unit
Voltage range 0 10 V
Load resistance >=100 kΩ
Resolution 10 bit
Fault 2.5 %2
Short protection Yes
Potential separation No
Temperature input
Dielectric strength -24 30 V
Measuring range -30 100 °C
Resolution 10 bit
Precision 3 %2
CAN bus
Dielectric strength -24 24 V
Transmission rate 125 kbit/s
Galvanic separation No
1. The maximum current consumption includes supplying two attached pressure transpon-ders and one attached temperature sensor.
2. Of the appropriate range
-
page 14 / 15
Data sheet GRCpump.1 V_1.0 © Güntner GmbH & Co. KG
1.6 Installation / Operating conditions
• The module is designed for mounting on a top-hat rail.
• All measurement and signalling lines must be connected via shielded cables.
• The shielding of measuring, signal and bus lines must be earthed at one end only.
• Suitable shielding and routing measures must be taken to ensure that mains cables andmotor cables do not give rise to any interference in signal and control lines.
• Temperature:Storage Transport:Operation:
-20°C ... +70°C-20°C ... +65°C
• Protection rating: IP 20
• Recommended cables: Belden 9841, Lapp 2170203, Lapp 2170803, Helukabel 81910
-
page 15 / 15
Data sheet GRCpump.1 V_1.0 © Güntner GmbH & Co. KG
1.7 Dimensions and weight
You will find the casing dimensions below. All dimensions are given in millimetres.
Dimensions of casing GRCpump.1
Weight:approx. 340g